Professional Documents
Culture Documents
Aim of the work: 1. To get acquainted with the work and characteristics of single-phase transformer.
2. To master the methods of measuring the main transformer operating parameters.
Task: 1. Examine the connection circuits of measuring devices and the values that
they measure.
2. Experimentally obtain a single-phase transformer operating
characteristics.
3. To study the variation of the primary current curve shape under load change
from no load to nominal power.
Theoretical part
Transformer tests
The short-circuit test is performed by short-circuiting the secondary winding and connecting
the primary winding to a lowered primary voltage source that the current ind both windings would be
same as rated (Figure 2).
The short-circuit test measures the voltage U1k, current I1v and power P1k for the primary
winding and current I2k= I2v for the secondary.
The measurement data shall provide:
U1k
1. Relative short-circuit voltage uk 100 %.
*
U1v
2. Electrical (Copper) Loss Pel= Pcu = P1k..
Performance characteristics
The external characteristic shows the dependence of the secondary voltage and the load, i.e. secondary
current. This is one of the most important performance characteristics of the transformer. The
secondary voltage of power transformers has little to no affect while load is changing. However, there
are receivers that are very sensitive to voltage changes. For example, when the mains voltage is 1%
different from the rated voltage, the luminous flux of the incandescent lamp is 3.5% compared to their
rated values. For most other industrial receivers the allowed voltage drop is 5% and for some 10%.
T
U 1v 220 V
Ra
Methodology of work
1. Familiarize yourself with the working scheme (Fig. 4), the devices used in it and their purpose.
1.1. Check that the power switch QF1 is in the off position.
1.2. Set the slider of the load rheostat Ra to the maximum resistance position.
1.3. Check that the measuring range of the secondary circuit devices corresponds to the measured
values: voltage 40 V, current 5 A.
1.4. After completing p. 1.1-1.3. requirements, connect the test circuit to the supply voltage.
1.5. Switch on the mains voltage with the automatic switch QF1.
2. No-load test.
2.1. Disconnect one load rheostat wire so that secondary current is zero.
2.2. Write the following data in the data table: U1v, I10, P10 and U20.
2.3. Draw the voltage and current curves from the meter METREL or computer screen and record the
percentage of the 3rd harmonic in the primary current curve.
2.4. Calculate the voltage transformation coefficient from the test data and determine the magnetic
losses.
3. Short circuit test.
3.1. Adjust the slider of the autotransformer AT so that the supply voltage is zero. Check that the
meter METREL shows a primary voltage U1=0.
3.2. Connect the rheostat wires to transformer and set the slider so that the resistance of load rheostat
is zero.
3.3. With the autotransformer AT, slowly increase the primary voltage until the secondary current
reaches the nominal (rated) current, i.e. 5 A.
3.4. Write the following data in the data table: U1k, I1k, P1k and I2k.
3.5. Draw the voltage and current curves from the meter METREL or computer screen and record the
percentage of the 3rd harmonic in the primary current curve.
3.6. After finishing the short circuit test reset test scheme: Set the load rheostat slider to the maximum
impedance position and the autotransformer to a rated supply voltage of 220 V.
4. Performance characteristics.
4.1. The performance characteristics is obtained by changing the load (secondary) current from 0 to
5A with a load rheostat every 1 A. Measure and record the following data during the test:
in the primary winding U1, I1, P1 and in the secondary winding U2, I2, P2.
4.2. Calculate the power and efficiency ratios of the primary circuit for each load value and write the
data in a table.
4.3. To observe the change of the primary current curve shape and harmonic composition while the
transformer is under load.
4.4. Switch off the power supply at the end of the test with the QF circuit breaker.
Control questions
1. What changes when the transformer is loaded compared to the no-load conditions?
2. Why does the secondary voltage decrease when the transformer is loaded?
3. Draw the equivalent diagram of the transformer and explain the physical meaning of its elements.
4. Explain what would change in a transformer if its magneto core had a small air gap.
5. Explain what would change in a transformer if its magneto conductor were made of a solid
ferromagnetic material.
6. Why is the power factor cos not equal to zero when the load current is zero?
7. What are the causes of primary current distortion during idle mode?
8. What power describes transformers?
9. What are the losses in transformers?
10. What does steel loss on transformers depend on?