KENTZ ENGINEERS & CONSTRUCTORS Page:2

TEMPORARY STRUCTURE DESIGN Rev. : B2

INDEX

SHEET NO. DESCRIPTION PAGE NO.

1 Cover Sheet 1

2 Index 2

3 Reference and Design criteria  3

4 Design Data and Load calculation 4

5 Rafter Calculation 5‐8

6 Design of Vertical column 9

7 Design of Girder 10‐11

VELATH 
KENTZ ENGINEERS & CONSTRUCTORS Page: 3
TEMPORARY STRUCTURE DESIGN Rev. : B2

Design criteria and References

DESIGN CODES

a) Standard Engineering Practice
b) ASME‐Sec.II Div.D for material stress
c) API 650

REFERENCES
a. Data given by client
b. Strength of Material Text Book
c. Tank's drawing
d. Velath drawing no. VE‐835‐DM‐SKT‐001

LOADING CONSIDERED
a. Roof plate weight
b. Platform weight
c. Roof structure weight
d. Live load

DESIGN CRITERIA
This temporary structure is designed for erection of Roof plate and Out side structure
of Dome roof tank 
Live load is considered as working people's own weight (50% of code specified load)

 As per API 650 ,Wind load acting on the roof is taken to be 1.44 kPa (146.835 Kg/m )
B2
MATERIAL OF CONSTRUCTION
Rafter SA 36
Girder  SA 36
Gusset SA 36
Base plate SA 36
Column SA 106 Gr.B
3
Density of Material 7850 Kg/m

VELATH 
KENTZ ENGINEERS & CONSTRUCTORS Page: 4
TEMPORARY STRUCTURE DESIGN Rev. : B2

DESIGN DATA
Diameter of Tank D 15000 mm
Height of Tank H 19000 mm
Shape of Roof Dome 
Ratio of Radius to Diameter 1.0
Radius of Dome R 15.00 mtr
Live Load 102 Kg/m2
LOAD CALCULATION
As this is an temporary structure used for Roof plate erection, need not to consider additional  live load
However for conservative design, we have considered 50% of code live load as a std. engineering practice.
As per API‐650 5.2.2, Gravity Load shall be greater of  load‐1 and load 2  ignoring internal pressure
Load ‐1 DL+ (Lr or Su or Sb) + 0.4 Pe
Load ‐2 DL+  Pe + 0.4x(Lr or Su or Sb)
Where DL Dead Load 58.88 Kg/m2
Lr Live Load 51.00 Kg/m2
Su Snow Load 0.00 Kg/m2
Sb Snow Load 0.00 Kg/m2
Pe Internal Pressure 0.00 Kg/m2
tr Roof Thickness 7.50 mm
Is  Insulation Thickness 0.00 mm
Dins Density of Insulation 0.00 Kg/m3
Insulation supports 0.00 Kg/m2
Structural loading 21.00 Kg/m2
Platform loading 28.00 Kg/m2
Hence  Load‐1 109.88 Kg/m2
Load‐2 79.28 Kg/m2
Hence  Load to be considered P 158.88 Kg/m2
WIND LOAD
Shell height considered 5.000 mtr B2
Wind velocity 41 m/sec
Wind pressure Pz = 0.6xVz 2
1008.6 N/m2
102.81 Kg/m2
 As per API 650 ,Wind load acting on the roof is taken to be 1.44 kPa as uplift pressure. 
‐146.84 Kg/m2
SEISMIC LOAD
Design horizontal seismic coefficient  Ai  0.155 from seismic design
As per API‐650 clause E.5.1 Seismic shear = A h *  Wo Fa 24.626 Kg/m2
As per API‐650 clause E.6.1.3 Seismic force = Av  *  Weff Fv 21.766 Kg/m2
Where  Av  0.137 from seismic design
Hence Resultant force P+ Fv 180.641 Kg/m2

B2

VELATH 
KENTZ ENGINEERS & CONSTRUCTORS Page: 5
TEMPORARY STRUCTURE DESIGN Rev. : B2

RAFTER CALCULATION WITH BASIC ENGINEERING METHOD
LOAD INCREASING UNIFORM FROM CENTRE TO END
Diameter of Tank D 15.000 mtr
Radius of Roof R 15.000 mtr
Total Number of  Rafter  N 20 Nos
Dead load of Roof Plate L1 12418.07 Kgs
Wt. Of Roof Structue & Roof platform L2 8659.01 Kgs
Design Under Pressure  L3 0.00 Kgs
Live load L4 9012.44 Kgs
Wind Load (Vertical) L5 ‐25947.89 Kgs B2
Seismic Load (Vertical) L6 3846.35 Kgs
MOC of Rafter SA 36
Min. Tensile strength of MOC 58000 psi 4078.76 Kg/Cm2
Min. Yield strength of MOC 36000 psi 2531.65 Kg/Cm2
Selected Rafter section Built up T section 60 x 60 x 8 thk
Width of horizontal member 60 mm
Height of vertical member 60 mm
Thickness 8.0 mm
Crossectional area  horizontal member a1 480.0 mm2
Crossectional area  of vertical member a2 480.0 mm2
Total area A (a1+a2) 960.0 mm2
Distance of CG y1 64.0 mm
Distance of CG y2 30.0 mm
CG of composite section Y 47.0 mm
Moment of Inertia Ixx 424000.0 mm4
Section Modulus Z 9021.28 mm3
Dome Radius 15.000 mtr
Unit Weight (self) 8.00 Kg/mtr
Approximate length of Main Rafteter  7.854 mtr
Rafter length considered 7.100 mtr
Total Weight 1136.00 Kgs
Total load W on one arc
Roof plate L1 121821.28 N
Structure  L2 84944.93 N
Under pressure L3 0.00 N
Live load L4 88412.07 N
Wind Load (Vertical) L5 332910.96 N
Seismic Load (Vertical) L6 16645.55 N
Total Wt. W 332910.96 N
Weight per rafter w 16645.55 N
B2
OR L1 12182.13 daN
L2 8494.49 daN
L3 0.00 daN
L4 8841.21 daN
Not taken into consideration as over pressure L5 ‐25454.88 daN
L6 3773.27 daN
W 33291.10 daN
Weight per rafter w 1664.55 daN
VELATH 
KENTZ ENGINEERS & CONSTRUCTORS Page: 6
TEMPORARY STRUCTURE DESIGN Rev. : B2

Bending Moment  for Beam :
2 3 2L 2
Md = (W/6L )x (4x ‐6x +3xL )
Ordinate, Y =[(R ‐{L/2‐x} )^  ‐ {R 2 ‐ L2/4}^1/2
2 2 1/2

Ordinate  X = (Numbetr of Point ‐ 0.25)

Point X in (mtr) Md in daN Y in (mtr) Md x Y Y 2 8.5 W


0.00 0.00 0.0 0.0000 0.0 0.00 8.00 1664.6
0.50 0.25 201.21 0.1412 28.40 0.02 7.50 1664.6
1.00 0.75 563.87 0.4050 228.39 0.16 7.00 1664.6
1.50 1.25 876.59 0.6455 565.85 0.42 6.50 1664.6
2.00 1.75 1143.07 0.8638 987.35 0.75 6.00 1664.6
2.50 2.25 1367.02 1.0609 1450.22 1.13 5.50 1664.6
3.00 2.75 1552.12 1.2377 1921.02 1.53 5.00 1664.6
3.50 3.25 1702.08 1.3949 2374.31 1.95 4.50 1664.6
4.00 3.75 1820.61 1.5333 2791.55 2.35 4.00 1664.6
4.50 4.25 1911.39 1.6533 3160.10 2.73 3.50 1664.6
5.00 4.75 1560.83 1.7554 2739.85 3.08 3.00 1664.6
5.50 5.25 1446.78 1.8399 2661.94 3.39 2.50 1664.6
6.00 5.75 1279.70 1.9072 2440.63 3.64 2.00 1664.6
6.50 6.25 1059.61 1.9574 2074.13 3.83 1.50 1664.6
7.00 6.75 786.50 1.9909 1565.81 3.96 1.00 1664.6
7.50 7.25 460.37 2.0075 924.21 4.03 0.50 1664.6
8.00 7.75 81.22 2.0075 163.06 4.03 0.00 1664.6
0.00 0.00 0.00 0.00 0.00 0.00 ‐0.50 1664.6
0.00 0.00 0.00 0.00 0.00 0.00 ‐1.00 1664.6
0.00 0.00 0.00 0.00 0.00 0.00 ‐1.50 1664.6
0.00 0.00 0.00 0.00 0.00 0.00 ‐2.00 1664.6
0.00 0.00 0.00 0.00 0.00 0.00 ‐2.50 1664.6
0.00 0.00 0.00 0.00 0.00 0.00 ‐3.00 1664.6
0 0.00 0.00 0.00 0.00 0.00 ‐3.50 1664.6
0 0.00 0.00 0.00 0.00 0.00 ‐4.00 1664.6
0 0.00 0.00 0.00 0.00 0.00 ‐4.50 1664.6
0 0.00 0.00 0.00 0.00 0.00 ‐5.00 1664.6
0 0.00 0.00 0.00 0.00 0.00 ‐5.50 1664.6
0 0.00 0.00 0.00 0.00 0.00 ‐6.00 1664.6
0 0.00 0.00 0.00 0.00 0.00 ‐6.50 1664.6
0 0.00 0.00 0.00 0.00 0.00 ‐7.00 1664.6
0 0.00 0.00 0.00 0.00 0.00 ‐7.50 1664.6
0 0.00 0.00 0.00 0.00 0.00 ‐8.00 1664.6
0 0.00 0.00 0.00 0.00 0.00 ‐8.50 1664.6
0 0.00 0.00 0.00 0.00 0.00 ‐9.00 1664.6
0 0.00 0.00 0.00 0.00 0.00 ‐9.50 1664.6
0 0.00 0.00 0.00 0.00 0.00 ‐10.00 1664.6
0 0.00 0.00 0.00 0.00 0.00 ‐10.50 1664.6
TOTAL 26077 36.99

VELATH 
KENTZ ENGINEERS & CONSTRUCTORS Page: 7
TEMPORARY STRUCTURE DESIGN Rev. : B2

H = Md * y /y 2 = 704.90 daN


V = W/2 = 832.28 daN
w = (W/2)/(L/2)*2 = 2* W/L = 221.9
2
wt = w*x/(L/2) = (2*W/L)*(x/(L/2)) = 4*W*x/L
Uniformly distributed load,wvd  = w‐wt = (2*W/L)‐(4*W*x/L 2)
Angle b =sin ‐1((l/2‐x)/R
Bending Moment curved arch =  Mx =‐H*y + V*x ‐(wt*x 2/3) ‐(wvd*x 2/2)
Cpompressive strength Sc = H cos b +V sin b ‐(wt*(x/2)sin b) ‐(wvd*x*sin b)

Point X in (mtr) b in Deg y in (mtr) Mx in daN‐m Sc in daN 8.50 L


0.00 0.00 30.0000 0.0000 0.0000 1026.60 8.00 15.00
0.50 0.25 28.9033 0.1412 101.7041 992.99 7.50 15.00
1.00 0.75 26.7437 0.4050 278.3515 932.86 7.00 15.00
1.50 1.25 24.6243 0.6455 421.5713 881.61 6.50 15.00
2.00 1.75 22.5403 0.8638 534.2028 838.57 6.00 15.00
2.50 2.25 20.4873 1.0609 619.2158 803.05 5.50 15.00
3.00 2.75 18.4615 1.2377 679.6893 774.34 5.00 15.00
3.50 3.25 16.4592 1.3949 718.7949 751.73 4.50 15.00
4.00 3.75 14.4775 1.5333 739.7842 734.53 4.00 15.00
4.50 4.25 12.5133 1.6533 745.9785 722.01 3.50 15.00
5.00 4.75 10.5640 1.7554 740.7608 713.46 3.00 15.00
5.50 5.25 8.6269 1.8399 727.5691 708.16 2.50 15.00
6.00 5.75 6.6998 1.9072 709.8920 705.37 2.00 15.00
6.50 6.25 4.7802 1.9574 691.2643 704.37 1.50 15.00
7.00 6.75 2.8660 1.9909 675.2642 704.43 1.00 15.00
7.50 7.25 0.9550 2.0075 665.5114 704.81 0.50 15.00
8.00 7.75 ‐0.9550 2.0075 665.6655 704.78 0.00 15.00
0.00 0.00 0.0000 0.0000 704.90 ‐0.50 15.00
0.00 0.00 0.0000 0.0000 704.90 ‐1.00 15.00
0.00 0.00 0.0000 0.0000 704.90 ‐1.50 15.00
0.00 0.00 0.0000 0.0000 704.90 ‐2.00 15.00
0.00 0.00 0.0000 0.0000 704.90 ‐2.50 15.00
0.00 0.00 0.0000 0.0000 704.90 ‐3.00 15.00
0.00 0.00 0.0000 0.0000 704.90 ‐3.50 15.00
0.00 0.00 0.0000 0.0000 704.90 ‐4.00 15.00
0.00 0.00 0.0000 0.0000 704.90 ‐4.50 15.00
0.00 0.00 0.0000 0.0000 704.90 ‐5.00 15.00
0.00 0.00 0.0000 0.0000 704.90 ‐5.50 15.00
0.00 0.00 0.0000 0.0000 704.90 ‐6.00 15.00
Now Max Mx 745.9785 daN
Max Sc 722.0137 daN
Rafter size considered T 60 x 60 x 8 thk
Yield Stres 24.83 daN /mm 2
Safety Factor 1.0
Allowable stress in bending and compression 24.83 daN /mm 2
Crossectional area provided 960.00 mm2
Section Modulus 9021.28 mm3
Hence induced stress 83.443 daN /mm 2
B2
Allowable stress in bending and compression < Induced Stress, Hence Provide column 
VELATH 
KENTZ ENGINEERS & CONSTRUCTORS Page: 8
TEMPORARY STRUCTURE DESIGN Rev. : B2

Bending Moment  for Beam :
Md = (W/6L 2)x (4x 3‐6x2L+3xL2)
Ordinate, Y =[(R 2‐{L/2‐x}2)^1/2  ‐ {R 2 ‐ L2/4}^1/2
Ordinate  X = (Numbetr of Point ‐ 0.05)
Point X in (mtr) Md in daN Y in (mtr) Md x Y Y 2 4.75 W
0 0.0 0.0 0.000 0.0 0.00 4.25 832
0.50 0.25 97.25 0.138 13.43 0.02 3.75 832
1.00 0.75 253.84 0.379 96.12 0.14 3.25 832
1.50 1.25 366.05 0.576 210.80 0.33 2.75 832
2.00 1.75 441.26 0.733 323.54 0.54 2.25 832
2.50 2.25 486.88 0.853 415.45 0.73 1.75 832
3.00 2.75 510.31 0.938 478.59 0.88 1.25 832
3.50 3.25 518.94 0.988 512.78 0.98 0.75 832
4.00 3.75 520.17 1.005 522.68 1.01 0.25 832
4.00 3.75 520.17 1.005 522.68 1.01 ‐0.25 832
TOTAL 3096 5.64
2
H = Md * y /y = 549.43 daN
V = W/2 = 416.14 daN
w = (W/2)/(L/2)*2 = 2* W/L = 221.9
2
wt = w*x/(L/2) = (2*W/L)*(x/(L/2)) = 4*W*x/L
Uniformly distributed load,wvd  = w‐wt = (2*W/L)‐(4*W*x/L 2)
Angle b =sin ‐1((l/2‐x)/R
Bending Moment curved arch =  Mx =‐H*y + V*x ‐(wt*x 2/3) ‐(wvd*x 2/2)
Cpompressive strength Sc = H cos b +V sin b ‐(wt*(x/2)sin b) ‐(wvd*x*sin b)
Point X in (mtr) b in Deg y in (mtr) Mx in daN‐m Sc in daN 4.75 L
0.00 0.00 14.4775 0.000 0.0000 636.02 4.25 7.50
0.50 0.25 13.4934 0.138 21.3991 618.85 3.75 7.50
1.00 0.75 11.5370 0.379 45.7896 591.60 3.25 7.50
1.50 1.25 9.5941 0.576 49.6426 572.57 2.75 7.50
2.00 1.75 7.6623 0.733 38.4036 560.31 2.25 7.50
2.50 2.25 5.7392 0.853 18.0638 553.34 1.75 7.50
3.00 2.75 3.8226 0.938 ‐4.9719 550.18 1.25 7.50
3.50 3.25 1.9102 0.988 ‐23.9666 549.37 0.75 7.50
4.00 3.75 0.0000 1.005 ‐31.9010 549.43 0.25 7.50
4.00 3.75 0.0000 1.005 ‐31.9010 549.43 ‐0.25 7.50
Now Max Mx 49.6426 daN
Max Sc 572.5722 daN
Rafter size considered T 60 x 60 x 8 thk
Section Modulus provided 9021.28 mm3
Hence induced stress Rafter selected is safe 6.09927 daN /mm 2
VELATH 
KENTZ ENGINEERS & CONSTRUCTORS Page: 9
TEMPORARY STRUCTURE DESIGN Rev. : B2

COLUMN COMPRESSION
Column support is considered as a cylindrical vertical section  and are designed  primarily as compression
members but have a factor introduced to cater for bending, which can occur from a number of causes.
The Cylindrical section  is unlikely to be absolutely vertical under load and it may also have a slight initial
 curvature. The bottom should sit properly on the Foundation due to normal tolerances or uneven bottom 
settlement and there is  always a possibility of the whole roof moving as it settles onto the foundation.
Any of the above conditions will add a bending momentIn the limiting case, the design is based on the formula,
As this a temporary structure, effective length is considered actual length
P = K*F/A
Where, P = permissible compressive stress (N/mm²)
F = Total Roof Load  (N)
A = Cross sectional area (mm²)
K = A factor to allow for bending.

Design Load Ddes 16.65 kN


Size of column 2 " NB x SCH.40
Outer diameter  od 60.30 mm
Thickness t 3.91 mm
Corossion Allowance ca 0.000 mm
Inside diameter ld 52.48 mm
Young's Modulus E 209000 N/mm²
Yield Stress  Fy 250.0 N/mm²
Height considered H 6000 mm
Effective length le 6000 mm
Moment of Innertia I 276646.98 4
mm
Crosectional Area  A 692.67 mm²
Radius of gyration r 19.98 mm
Total vertical Load  Ddes 16646 N
Factor K Refer BS 449 Part B K 1.10
Compressive stress P 26.43 N/mm²
K * Ddes
P =
A
2 0.5 Cc 128.46
Cc = (2 π  E / Fy)

As le/r > Cc Hence Allowable Compressive Stress le/r 300.23

[
⎡ 12 π 2 E ]⎤ Fa 120.78 N/mm²
⎢ ⎥
⎣ 23 (l r )
2

Fa = ⎦
⎡ l ⎤
⎢1 . 6 − 200 r ⎥
⎣ ⎦

Column size is OK 

VELATH 
KENTZ ENGINEERS & CONSTRUCTORS Page :10
TEMPORARY STRUCTURE DESIGN Rev. : B2

Design of Girder
Nos of Row of Girder Gn 1.0 nos
Radius of Tank R1 7500.0 mm
Angle between the main rafter q 18.0 degree
No. of cross girders N 20.0 nos
Length of girders  L 1.178 mtr
Actual length of girders L 1.273 mtr
Loading area , A(ABCD) A 8.836 m2
Size of Girder width D 60 mm
Thickness B 8 mm
Moment of Innertia Ixx 14.400 cm4
Distance of CG y 3.0 Cm
Section Modudulus Ixx/y Z 4.800 cm3
Radius of gyration r 1.732 cm
Self Wt  w 3.768 Kg/mtr
Crossectional Area a 4.80 Cm2
Loading on G‐G , wg :
a) Load on roof plate through rafters L1 8.0 kg/m
b) Self wt of sec.& tertiary rafters shared by girder L2 5.0 kg/m
wg 13.0 kg/m
A(ABCD)  Area 8.836 m2
Total load on G3‐G3, 8.836 *wg/ 2#  + 1.178 * self wt.
Wg 61.87 kg
Roof plate thickness tr 7.5 mm
 Half will be shared by G‐G & remaining half will be shared independently by truss.
Girder G‐G is conservatively considered as simply supported at ends.
Max Bending Moment , Mmax = W*L/4 18.22 Kg/m

Section Modulus provided  4.80 cm3


Min specified yeild strength 36000 psi.
2531.6 Kgf/cm2
Allowable bending compressive stress ,fbc :
Max unsupported lg  L 1.273 mtr
A 480.0 mm2
LB/A 21.22 < 600

Allowable bending compressive stress

VELATH 
KENTZ ENGINEERS & CONSTRUCTORS Page : 11
TEMPORARY STRUCTURE DESIGN Rev. : B2

Radius of gyration  r 1.732 cm
Lmax 127.30 cm
Hence  L/r 73.50
Now,  Cc =[2*p^2*E/Fy]^0.5 Cc 127.8482
Fy  36000 psi
Modulus of Elasticity E 29810000 psi
In ousr case L/r is less than Cc

Hence As per API ‐650 Cl. No 3.10.3.4, 

Fa 12082.80 psi

Allowable bending compressive stress , Sbc 849.53 Kg/cm2


Section Modulus required, Zcgr= Mmax/Sbg Zcgr 2.15 cm3
Section Modulus provided Zcpr 4.80 cm3
As section Modulus required is less than that provided ,size   Girder selected is OK.

VELATH 