You are on page 1of 1

TEST REPORT

Standard as per : IEC 60502-2 Date : 02.1.2020


Size of cable : 1x400 Rm (mm²) Colour : Black
Type of cable : 2xHSYRaY (CWS) Length : 500 Meter

Voltage Grade :18/30 (36) kV Party :


Ref No. :
Sl Required Observed
Description of test Unit
No Value Value
2
01 Physical Nom.Cross-sectional Area of Conductor mm 400 400
Test No. of cores No. 1 1
Conductor
Material Copper Copper
Stranded Circular Stranded Circular
Shape of conductor
Compacted Compacted
Minimum number of wire no. 30 37
Minimum & Maximum Diameter mm 15.3-16.8 16.21
Insulation
Material - XLPE XLPE
Nom. Thickness mm 3.4 3.46
Min. Thickness mm 2.96 3.40
Metalic Sceen
Material - Copper Tape Copper Tape
Diameter of wire mm 0.06
Inner Covering
Material - PVC PVC
Approx. Thickness mm 1.6 1.86
Armour
Material - Round Aluminium Wire Round Aluminium Wire
Diameter of Armour mm 2.5
Sheath
Material - PVC PVC
Nom. Thickness mm 3.0 3.24
Min. Thickness mm 2.20 3.07
Approximate overall diameter mm 72.5 ± 3 74.28
Surface Finishing - Smooth Smooth
0
02 Electrical Max. D.C. Resistance of Conductor at 20 C Ohm/km 0.0991 0.0978
Test
Min. Insulation resistance at ambient temp.
G.Ohm - 105
(Voltage level of Megger is 5000 V)
A.C. Voltage test for 05 minutes kV 21 (withstand) Withstood

You might also like