You are on page 1of 9

PART B Chapter 7 Contents

Movement 7.1 basis of design

This chapter provides the design requirements for 7.2 design requirements
movement joints in masonry to control cracking due
to shrinkage of the wall, concrete slab shrinkage, 7.3 standard designs
foundation movement and thermal expansion or
contraction. 7.4 worked example

PART B:CHAPTER 7
Movement QUIT
7.1 BASIS OF DESIGN
Unreinforced concrete masonry is a brittle 7.1.1 factors influencing the Coefficient of Drying Contraction is the Temperature Differential
material which will crack if long walls formation of cracks in shrinkage which takes place in concrete Walls that are exposed to large temperature
are constructed without a break or if its masonry units when dried from a saturated condition differentials (including those on the
supports move. The following factors to a stable dry condition. It is an indication northern or western facades of buildings
Shrinkage of Masonry Units
influence the formation of cracks in masonry of the likelihood of shrinkage-related in temperate areas) will be more likely to
Concrete masonry units shrink as the
which may be controlled by the methods cracking as a result of expelling all of the suffer cracking than similar walls in benign
concrete cures. To avoid this, units should
set out in clause 7.1.2. moisture from the units. When combined environments.
be properly cured before delivery to the
with the shrinkage caused by the mortar, it
site. Saturated units should not be laid Footing Movement
gives an indication of the upper bound of
as they could be subject to subsequent Footing movement is a major source of
the possible shrinkage in the wall.
drying shrinkage. AS/NZS 4456.12 provides cracking in unreinforced masonry and is
two tests, Coefficient of Residual Curing For example: discussed fully in Part B:Chapter 10.
Contraction and Coefficient of Drying 0.6 mm/m represents at least 4.8 mm in
an 8 m length of wall. Support Movement
Contraction, for contraction of concrete
Differential movements of supports can
masonry units. These tests are not routinely 0.8 mm/m represents at least 6.4 mm in
lead to cracking. For example, if a masonry
performed, and are specified only when an 8 m length of wall.
wall is fixed to large steel portal frames it
dealing with specific problems related to
No limits are set in AS/NZS 4455 or will move sympathetically with the frames
shrinkage and cracking.
AS/NZS 4456. A value over 0.6 mm/m would as they deflect under the action of lateral
Coefficient of Residual Curing Contraction normally be considered to be quite high. loads. A crack will develop in the bottom
is the shrinkage which takes place in bed joint but this would not normally be
Shrinkage of the Mortar
newly-manufactured concrete units (at noticed. However, if the masonry wall is also
If mortars with a particularly high cement
constant saturated moisture content). It is bonded to a masonry shear wall (parallel to
content are used, their shrinkage could
an indication of the likelihood of shrinkage the frames) which is much stiffer than the
provide sufficient tensile force to crack the
related cracking as a result of cement frames, there is potential for diagonal cracks
masonry.
hydration in the units. It is indicative of the to develop in the masonry.
lower bound of shrinkage in the wall. Shrinkage in applied renders and
coatings Mixing Clay and Concrete Masonry
For example: Clay units expand while concrete units
0.1 mm/m represents at least 0.8 mm in Renders are prone to cracking if a high
cement content is used, if excessively fine contract. It is permissible to construct cavity
an 8 m length of wall. walls with one leaf of clay units and the
sands are used (requiring additional water)
0.3 mm/m represents at least 2.4 mm in other leaf of concrete units, provided they
or if the render is too thick.
an 8 m length of wall. are separated by cavities with flexible ties.
Although no limits are set in AS/NZS 4455 or While little harm is done by incorporating
AS/NZS 4456, a value over 0.1 mm/m would the odd clay unit into a concrete masonry
normally be regarded as relatively high. leaf or the odd concrete unit into a clay
masonry leaf, large area of each should not
be mixed in the same leaf since this will lead
to differential movement and cracking.

PART B:CHAPTER 7
Movement QUIT
7.1.2 Methods of controlling Supports Expansion joints are closing joints. They
cracking in masonry The potential for diagonal cracks to are usually built into clay masonry to cater
develop where masonry walls are bonded for brick growth and find application in
Mortar
to masonry shear walls (parallel to and in concrete masonry only when there is the
To avoid potential cracking from mortar
conjunction with portal frames) which are possibility of high thermal movement.
shrinkage, the mortars recommended in the
much stiffer than the frames, can best be Expansion joints incorporate a compressible
Standard Specification, provided in Part C:
avoided by the incorporation of reinforced material of sufficient thickness to cater for
Chapter 2 should be used, viz:
bond beams. the expansion in the walls
M3 applications – 1:0:5 + water thickener
adjacent to the joint.
or Reinforcement
M4 applications – 1:0:4 + water thickener. The inclusion of reinforcement within the Articulation joints are both opening and
masonry will greatly enhance its ability to closing joints that cater for movement
Applied Renders and Coatings
spread the cracks and thus restrict their of the footings or supports. The strategic
To minimise the risk of cracking, the
width. Reinforced masonry will tolerate positioning of articulation joints at points
specified render mix should be suitable for
larger deflections than unreinforced of weakness (such as door or window
the type of masonry and the thickness of
masonry before collapse occurs. Therefore, openings) will minimise cracking as
any coat not more than 12 mm. If necessary,
design for strength will not necessarily the supports move due to foundation
wire or expanded metal reinforcement can
provide a guarantee of adequate movement and similar actions. In some
be used to control cracking. Control joints
serviceability performance. In particular, cases, contraction and expansion joints will
in renders and coating should be included
centrally- reinforced masonry walls may function as articulation joints.
wherever control joints are provided in the
exhibit larger than expected lateral
masonry. Control joints result in free ends of the
deflections and crack widths due to their
masonry which may increase slenderness
Footings small effective depth.
and decrease support conditions of walls.
To limit cracking from footing movement,
Control Joints Therefore, the location of joints should be
suitable precautions include:
The strategic placement of control joints will determined as part of the structural design.
■ Adequate drainage for the removal of limit the position and width of cracks.
water from the foundations Control joints should be detailed so as to
Contraction joints are opening joints to maintain resistance to moisture penetration,
■ Ensuring that large trees are not placed
cater for shrinkage of the wall. In a wall fire, heat and sound.
adjacent to the footings
exposed to the weather, contraction joints
■ Correctly sized footings must be weather-proof with a flexible
■ Inclusion of reinforcement in the wall. sealant at the surface. They may also be
filled with a compressible material if required
to serve also as expansion joints (for thermal
movement) or as articulation joints (for
footing or support movement).

PART B:CHAPTER 7
Movement QUIT
7.2 DESIGN REQUIREMENTS
AS 3700 Clause 2.5.2 places an upper limit
on crack width of 1 mm for “masonry which
is not subject to aesthetic limitations”. Because
it is often difficult to assess the crack widths
which result from particular load actions
(eg wind, earthquake and foundation
movement), the 1 mm limit is not intended
to cover all situations. However, it does
define a quantifiable limit for use in design,
construction and post-construction
assessment.
The performance requirement for residential
dwellings is set out in AS 2870 Appendix C
which states that the footing systems used
to support the masonry walls shall be such
that there is “usually no damage, a low
incidence of damage Category 1 (fine cracks
which do not need repair, crack < 1 mm)
and occasional incidence of damage
Category 2” (cracks noticeable but easily
filled, doors and windows stick slightly, crack
< 5 mm). Refer to Part B:Chapter 10.
AS 3700 Clause 4.8 requires that the opening
movement shall not exceed 10 mm. The
closing movement (if any) shall not exceed
15 mm and the width of the joint after
closure shall not be less than 5 mm.
The strategic positioning of control joints
will limit the formation of cracks, and those
which do form will be kept small.

PART B:CHAPTER 7
Movement QUIT
7.3 STANDARD DESIGNS
n Incorporating N16 horizontal
7.3.1 General n at not more than 5 metre centres in a wall Minimum characteristic compressive
with openings more than 900 mm x 900 reinforcement at not greater than strength,
Design and detailing
mm, and positioned in line with one edge 400 mm centres f’uc = 10 MPa
All design and detailing shall comply with
of the opening n On a soil of type A or S Site Classifications
the requirements of AS 3700. It is the Minimum characteristic lateral modulus of
designer’s responsibility to allow for the n at the position where a wall changes in accordance with AS 2870, and rupture,
effects of control joints, chases, openings, height by more than 20% n With a reinforced concrete footing of f’ut = 0.8 MPa
strength and stiffness of ties and connectors, n at a change in thickness of a wall adequate stiffness.
Mortar joints
and strength and stiffness of supports, in n at control joints or construction joints in No control joints are required for single-leaf, Mortar type M3 (or M4)
addition to normal considerations of loads supporting slabs partially-reinforced masonry for houses as
and masonry properties. Control joints and Joint thickness 10 mm
n at the junctions of walls constructed of defined in AS 3700 Section 12.
openings must be treated as free ends.
different masonry materials Concrete grout
Hollow concrete blocks
Masonry properties n at deep rebates Minimum characteristic compressive
Width 90 mm, 110 mm, 140 mm and 190 mm
The standard designs in this chapter are strength,
AS 4773.1 also places the following Height 190 mm
based on masonry properties complying f’c = 20 MPa
restrictions for residential building:
with the Standard Specification set out in Length 390 mm
n at a distance from all corners not less Minimum cement content 300 kg/m3
Part C:Chapter 2, modified as noted on the
standard design. The Standard Specification than 470 mm for cavity walls or 230 mm Face-shell bedded Steel reinforcement
includes the following requirements: for veneer walls and not greater than N12, N16 or N20 as noted.
Minimum face-shell thickness,
4500 mm.
Unreinforced Masonry Construction ts = 25 mm for 90 mm, 110 mm and
Reinforced Masonry Construction 7.3.2 index to design details
Vertical control joints or articulation joints 140 mm units
at least 10 mm wide shall be built into Control joints shall be built into reinforced ts = 30 mm for 190 mm units The following diagrams show the
unreinforced masonry at the following concrete masonry at all points of potential suggested positions of control joints in
Minimum characteristic compressive
locations: cracking and at the locations shown on concrete masonry houses and industrial or
strength,
the drawings. The spacing of control joints commercial buildings.
n centres not exceeding the following f’uc = 15 MPa
should not exceed 16 metre.
in straight continuous walls without CONTROL JOINTS –
Minimum characteristic lateral modulus of
openings: The spacing of control joints may be Concrete Masonry Houses
rupture,
For Class A and S sites – increased in reinforced masonry walls
f’ut = 0.8 MPa CONTROL JOINTS –
Articulation is not required meeting the following criteria:
Industrial or Commercial Buildings
For Class M, H, M-D and H-D sites – n Consisting of at least 190 mm hollow Solid or cored concrete bricks
External masonry face finish, concrete units, and Width 110 mm
rendered or painted 7.0 m
n Built less than 3 metres high, and Height 76 mm
Internal masonry sheeted
n Incorporating a top reinforced bond Length 230 mm
and/or face finished 6.0 m
Internal masonry rendered beam, and
Fully bedded
and/or painted 5.0 m

PART B:CHAPTER 7
Movement QUIT
CONTROL JOINTS – Concrete Masonry Houses

NOTE:
In addition, control joints are required in the following situations.
Window* Door* • At the position where a wall changes height by more than 20%
• At a change in thickness of a wall
• At junctions of walls constructed of different masonry materials
• At deep rebates
• At control joints or construction joints in supporting slabs.

CJ indicates control joint


CJ CJ CJ

Min. 500 5000 max. when openings > 900 x 900 5000 min. to 7000 max. depending on finishes
max. 3000
from corner * Carry window and door openings to top of wall and use timber or similar infill panel
UNREINFORCED MASONRY VENEER CONSTRUCTION (Class M, H, M-D and H-D sites)

Window Door

NOTE: No control joints required


Reinforced masonry shown hatched

REINFORCED SINGLE-LEAF MASONRY CONSTRUCTION (As defined in AS 3700 Section 12)

PART B:CHAPTER 7
Movement QUIT
CONTROL JOINTS – Industrial or Commercial Buildings
Reinforced masonry shown hatched
CJ CJ CJ

Door Door

CJ CJ indicates control joint CJ indicates control joint


8.0 m maximum 16.0 m maximum in reinforced wall and bond beam
UNREINFORCED MASONRY CONSTRUCTION VERTICALLY-REINFORCED MASONRY CONSTRUCTION

16.0 m maximum in bond beam

CJ CJ

> 3.0 m
Door

CJ CJ indicates control joint


8.0 m maximum in wall
HORIZONTALLY-REINFORCED MASONRY CONSTRUCTION

PART B:CHAPTER 7
Movement QUIT
7.4 WORKED EXAMPLE
7.4.1 general Hollow concrete blocks Mortar joints
Width 90 mm, 110 mm, 140 mm and 190 mm Mortar type M3 (or M4)
Purpose of the worked example
The purpose of the following worked Height 190 mm Joint thickness 10 mm
example is to demonstrate the steps to
Length 390 mm Concrete grout
be followed when performing manual
Minimum characteristic compressive
calculations or when preparing computer Face-shell bedded
strength,
software for the analysis and design of
Minimum face-shell thickness, f’c = 20 MPa
masonry. The worked example also serves
ts = 25 mm for 90 mm, 110 mm and
the purpose of demonstrating the origin of Minimum cement content 300 kg/m3
40 mm units
the Standard Designs which are based on
Steel reinforcement
similar masonry capacity considerations. ts = 30 mm for 190 mm units
N12, N16 or N20 as noted.
Although comprehensive in its treatment Minimum characteristic compressive
of AS 3700, the worked example is not strength,
intended to analyze or design all parts of f’uc =15 MPa
the particular structure. It deals only with
enough to demonstrate the design method. Minimum characteristic lateral modulus of
rupture,
Design and detailing f’ut = 0.8 MPa
All design and detailing shall comply with
the requirements of AS 3700. It is the Solid or cored concrete bricks
designer’s responsibility to allow for the Width 110 mm
effects of control joints, chases, openings, Height 76 mm
strength and stiffness of ties and connectors,
and strength and stiffness of supports, in Length 230 mm
addition to normal considerations of loads Fully bedded
and masonry properties. Control joints and
openings must be treated as free ends as Minimum characteristic compressive
specified by AS 3700. strength,
f’uc =10 MPa
Masonry properties
The worked examples in this chapter are Minimum characteristic lateral modulus of
based on masonry properties complying rupture,
with the General Specification set out in f’ut = 0.8 MPa
Part C:Chapter 2, modified as noted in the
calculations and as noted below.

GO TO WORKED EXAMPLE

PART B:CHAPTER 7
Movement QUIT
Worked Example [Page 1 of 1]

DESIGN BRIEF
Design control joints in the walls of an industrial building at the locations indicated.
sr = spacing of control joints in reinforced masonry
15 000
= 15.0 m
190-mm unreinforced blockwork Reinforced bond beams
CJ < 16 m OK
B B
su = spacing of control joints in unreinforced masonry
= 7.5 m
<8m OK
6000

A A Door
opening Cc = coefficient of drying contraction
= 0.6 mm/m

δo = maximum possible opening movement under the condition of


repeated wetting and drying of the unreinforced masonry
CJ
CJ indicates control joint = Cc su
7500 = 0.0006 x 8000
LAYOUT OF CONTROL JOINTS 20 dia dowel with = 4.8 mm
bond-breaker and Bitumen-impregnated < 10.0 mm OK 4.8
plastic cap one end filler board between
NOTE: Actual opening movement under normal environmental
situations will be much lower than the calculated maximum
190
Detail at control joints provides for weather-proofing OK
20-MPa grout in
Sealant with backing rod bond beam Sealant Detail at control joints provides for the horizontal out-of-plane support of all
SECTION A-A SECTION B-B reinforced and unreinforced masonry OK

H = height of wall Relative in-plane movement between the reinforced bond beam and the
= 6.0 m unreinforced masonry panel may lead to a little localized bed joint cracking,
> 3.0 m Provide articulation of both reinforced and unreinforced masonry but this is considered to be minor OK

PART B:CHAPTER 7
Movement QUIT

You might also like