You are on page 1of 13

BUILD SIMUL (2016) 9: 429–441

DOI 10.1007/s12273-016-0280-9

Influence of household air-conditioning use modes on the energy


performance of residential district cooling systems

Research Article
Xin Zhou1 (), Da Yan2, Xiaohang Feng2, Guangwei Deng3, Yiwen Jian4, Yi Jiang2

1. School of Architecture, Southeast University, Nanjing 210096, China


2. School of Architecture, Tsinghua University, Beijing 100084, China
3. Shanghai Research Institute of Building Sciences Group, Shanghai 610041, China
4. Beijing University of Technology, Beijing 100084, China

Abstract Keywords
During technical evaluations of cooling systems in residential buildings, it is necessary to consider AC usage model,
the influence of the household air-conditioning (AC) use modes. In other words, how the load distribution,
occupants control the AC, for instance, when it is turned on, what the temperature setting is, and residential district cooling system,
how long it is used. Field measurements and spot interviews indicate that AC usage by residents uncertainty analysis,
should be environmental, event and random related. A reduced-order AC conditional probability energy performance
(CP) model was developed in this study to describe AC usage. The AC CP model was integrated
with a building energy modeling program (BEMP) to reflect the interaction of the AC operation
Article History
Received: 22 November 2015
and the indoor environment. With consideration of stochastic AC use modes, the uncertainty of
Revised: 19 January 2016
user compositions was studied. Additionally, simulation results revealed that AC use modes and
Accepted: 22 January 2016
user compositions can cause up to a 4.5-fold difference in the system efficiency of district cooling
systems. The Lorenz curve and Gini coefficient were applied in this study to describe the load
© Tsinghua University Press and
distribution in a quantitative manner. Through a comparison with the constant schedule definition
Springer-Verlag Berlin Heidelberg
model, the study also identified inclusion of the stochastic feature of AC use modes and their
2016
compositions in simulations as being important to the technical evaluation of district cooling
systems.

1 Introduction part of the total energy consumption and the associated


greenhouse gas emissions (Tanimoto et al. 2008). In China,
There is a growing concern regarding energy consumption it is estimated that buildings stocks will account for about

Building Systems and


in buildings, due to the rapidly increasing trend of energy 35% of total energy consumption in 2020, 65% of this being
use worldwide. Energy consumption of residential and com- consumed by the heating, ventilation, and air-conditioning Components
mercial buildings has increased between 20% and 40% in (HVAC) system (Lam et al. 2008). The cooling consumption
developed countries (Pérez-Lombard et al. 2008). Energy of residential buildings is influenced by many factors,
use in residential buildings of different countries ranges including building envelope, building equipment, climate,
between 16% and 50%, and the worldwide average energy and so on. Amongst these factors, the type of air-conditioning
consumption of the residential sector accounts for about (AC) system plays an important role in the building con-
30% of the total energy usage (Meyers et al. 2003; Morelli sumption and system efficiency (Peng et al. 2012). Therefore,
2001; Boardman 2004; Ueno et al. 2006; Araujo et al. 2001; increasing attention is directed towards reducing energy
Kamal 1997; Lenzena et al. 2006). Therefore, energy require- consumption in residential buildings, resulting in the
ments for residential buildings have drawn a great deal of development and implementation of new technologies.
attention. In particular, great attention has been directed Integrated application of energy-saving technologies
towards the cooling consumption, which is an important in residential communities can improve energy utilization
E-mail: zhou-x06@seu.edu.cn
430 Zhou et al. / Building Simulation / Vol. 9, No. 4

and allocation of regional energy resources. District cooling for differences in the energy consumption of the two types
systems are one such system that has become increasingly of the AC systems.
popular in recent years (Zhang et al. 2009). District cooling Theoretical analyses of district cooling systems often
systems can provide cooling for many buildings at the same differ greatly from actual operating experiences, especially
time (Chow et al. 2004b). These cooling systems use large, when important factors that influence the district cooling
efficient refrigeration equipment, so less installed capacity system are ignored. Many studies have focused on the
is required compared to split AC systems (Chow et al. physical modeling of the district cooling system, including
2004c; Shimoda et al. 2008; Soederman 2007; Ortiga et al. the cooling plants, pumps, and fans (Nagota et al. 2008; Chow
2013). In addition, they are capable of using renewable et al. 2004a). Some researchers have acknowledged that the
energy sources, such as underground water or seawater, as building thermal load has an important effect on the district
the cooling source. From the perspective of energy use cooling system performance (Chow et al. 2004b; Nagota et
and urban landscape, district cooling systems have great al. 2008; Shimoda et al. 2008). Many studies have shown that
potential value (Rezaie and Rosen 2012; Chow et al. 2004a). occupant behavior is one of the most important factors (Hoes
Most of the studies listed above have assumed that district et al. 2009) influencing the building thermal load, energy
cooling systems would improve system performance and consumption, and technical suitability (Yan et al. 2015).
consume less energy in practical applications. Many models with consideration for occupant behavior have
The application of district cooling systems in residential been developed, such as the occupant movement model
buildings is in its early stages of deployment, with a very (Richardson et al. 2008; Page et al. 2008; Wang et al. 2011;
limited number of projects implemented (Pardo et al. 2013). Zhao et al. 2014; Feng et al. 2015; D’Oca and Hong 2015),
Some studies have investigated the applicability of district the window opening model, and the appliance usage models
cooling systems in residential buildings theoretically, and (Nicol 2001; O’Doherty et al. 2008; Reinhart 2004; Rijal et
its broad application prospect has been considered (Jing et al. 2007; Wei et al. 2014). In China, AC is usually manually
al. 2014; Chen et al. 2001; Al-Qattan et al. 2014). However, controlled. Therefore, the AC use mode is an important
in China, most of the district cooling systems have not part of occupant behavior, and has a significant impact on
performed at their optimal efficiencies. Several researchers the building thermal load. AC use modes refer to how the
(Long et al. 2003; Chen et al. 2008; Building Energy Research occupants control the AC, e.g. when the AC is turned on,
Center in Tsinghua University 2013) have conducted energy what the temperature setpoint is, and how long the AC is
consumption surveys in residential buildings located in used (Peng et al. 2012).
different districts of China (Fig. 1). Therefore, it is necessary to consider the influence of
The residents of these surveys are typical of each city, so AC use modes during the technical evaluation of cooling
occupant behavior of the same city should not differ much systems. Few studies have focused on the influence of AC
(Building Energy Research Center in Tsinghua University use modes on the energy savings of district cooling systems.
2013). Regardless of the building location, the energy Moreover, besides AC use modes, uncertainty of user
consumption of district cooling systems in residential compositions has been largely neglected in the existing
buildings is larger than that of split AC systems by as much studies, a factor found by this study to be important in the
as ten times. Despite this fact, most of these studies exclusively performance of the district cooling system.
focus on the energy consumption of one AC system type. This paper discusses the influence of AC use modes
Few investigations have been conducted regarding the reason and user compositions on the energy consumption and

Fig. 1 Electricity consumption of district cooling systems and split AC systems in residential buildings
Zhou et al. / Building Simulation / Vol. 9, No. 4 431

system performance of district cooling systems in residential 12 buildings was built. The uncertainty of user compositions
communities. A reduced-order AC conditional probability was studied, and typical cases were analyzed to figure out
(CP) model was developed to describe AC usage. Meanwhile, the influence of AC use modes and user compositions on
the AC CP model is integrated with a building energy the load feature and system performance of the district
modeling program (BEMP) to reflect the interaction of AC cooling system.
operation and the indoor environment. The uncertainty of
user compositions is studied to investigate the influence 2.1 AC usage CP model
of AC use modes and user compositions on the energy
consumption and system performance of the district The field investigation was conducted in a residential
cooling system. The applicability of district cooling systems community in Henan Province, China. The climate was
in residential buildings was analyzed with consideration characteristic of monsoon season, with warm temperate
for the influence of stochastic AC use modes and user conditions. The residential community included 12
compositions. multifamily buildings with 294 households. The residential
community was equipped with ceiling cassette units, which
2 Methodology are a common type of fan coil unit (FCU). An AC unit
metering system was installed, which recorded the on–off
Field measurements and computer simulations were used state and run time of the FCU each day. Five households
to analyze the influence of AC use modes on energy with typical FCU run times were chosen due to their
performance of district cooling systems. The research representative FCU run times (maximum, upper quartile,
methodology is shown in Fig. 2. First, a reduced-order AC medium, lower quartile and minimum values in the
CP model was developed based on field measurements. community). Field measurements were conducted in these
Second, an AC usage survey was conducted in a residential households from Jul. 15 to Sep. 15, a two-month span in
community to figure out the typical parameters of the AC the cooling season during which AC is most frequently
CP model. Five typical AC use modes were summarized. used in Chinese residential buildings. The indoor dry bulb
Then using the BEMP, a residential community model with temperatures were measured every five minutes in the living
rooms and bedrooms of these five households, and spot
interviews about AC usage patterns were also conducted. A
more detailed description about the measurement acquisition
can be found in Ren’s study (Ren et al. 2014).
Based on data analysis and previous research (Ren et al.
2014), an AC CP model was developed to describe the AC
usage quantitatively. The model was composed of three parts:
the AC turning on model, the AC turning off model, and the
Fig. 2 Research methodology AC setting temperature model. The curve fitting results of

Fig. 3 Curve fitting result in a typical family (Ren et al. 2014)


432 Zhou et al. / Building Simulation / Vol. 9, No. 4

a typical family are shown in Fig. 3. A detailed application during the interview, in which few residents expressed
and verification of this AC CP model was previously dissatisfaction with the indoor thermal environment. Some
conducted (Ren et al. 2014). standards such as ASHRAE Standard 55 (ASHRAE 2010) and
The AC turning on model is an environmental trigger ISO 7730 (ISO 2005) set indoor comfort classes depending
model, and is related to the indoor temperature. The on comfort indicators (PMV and PPD). These were mainly
measurement results show the environment trigger model developed from steady state (Fanger 1970) environments;
to be single valued, with y∈[0,1] and an S shaped growth however, in residential buildings the domestic scene is
pattern that satisfies the probability transformation far from steady state, and nearly all forms of adaptations
relationship: 1−y(n)=(1−y(1))n , where n is the time step. applied to residential buildings. Additionally, the price for
Therefore, a reduced-order discrete Weibull cumulative consumed energy increases the acceptable temperature
function (Weibull 1951) was chosen for its probabilistic range (Peeters 2009). Therefore, adaptive approaches have
characteristic. The statistical model is assumed to have the revealed that residents are able to feel comfortable in a wider
form: range of conditions than those prescribed by applying the
PMV index (Frontczak and Wargock 2011; Jones 2000; de
ìï1 - e-( x-u) , x ³ u
k
Dear and Brager 2002).
Pon = ïí (when occupied) (1) Five typical AC use modes are summarized in Table 1.
ïïî 0, x <u
Use mode A corresponds to residents who use AC units in
the most thrifty way; for example, turning on AC units when
in which, Pon is the probability of turning on the AC, x is the indoor temperature is above 29 °C, turning off AC units
the indoor temperature measured in °C, and u and k are before bed (about 11:00 p.m.), and keeping the AC setpoint
parameters of the equation. at a higher value (around 28 oC). The AC setpoint of use
Based on the survey, most residents were office workers, mode B is lower than that of use mode A (around 26 °C).
and turning off the AC was mainly related to the occupancy. For use modes C through E, residents tend to use the AC
Therefore, it was assumed that the AC turning off model units more frequently, and keep indoor temperatures at
was an event-triggered model related to the time of the day lower values (about 27 °C, 26 °C, and 24 °C for use modes C
(Ren et al. 2014). Similarly, this can be described by the model: through E, respectively). Use mode E corresponds to residents
who use the AC units in the least thrifty way, often keeping
ìï1 - e-(t-m)n , t ³ m
Poff = ïí
the AC units running all the day long and setting the indoor
(2)
ïïî 0, t <m temperature to a low value about 24 °C.

in which, Poff is the probability of turning off the AC, t is Table 1 Typical AC use modes
the time of the day (t∈[0,24]), and m and n are parameters AC use Room
of the equation. mode type Pon Poff Pt
The AC setting temperature model is a normal Living ì
ï
ï 1- e -( x -29 )2.5
, x ³ 29 ì
ï
ï 1- e-( t -23 )10
, t ³ 23 1 -
( T-28 ) 2

í í e 0.5
room ï 0,
ï x < 29 ï 0,
ï t < 23 0.5 2π
distribution model, and is described below: A
î î

ïì1 - e-( x-29 )2.5 , x ³ 29


ï ì
ï
ï 1 - e-( t-23 ) , t ³ 23
10

1 -
( T-27 ) 2

Bedroom íï 0, x < 29
í
ï t < 23
e 0.5
(T -μ )
2 ï
î î 0,
ï 0.5 2π
1 -
Pt = 2σ 2 (3) ì
ï 1 - e-( x-30 ) , x ³ 30 ì
ï 1 - e-( t-23 ) , t ³ 23
10 10
e Living ï ï 1 -
( T-26 )2

σ 2π í í e 0.5
room ï
î 0,
ï x < 30 ï
î 0,
ï t < 23 0.5 2π
B
ïì1 - e-( x-29 )2.5 , x ³ 29
ï ì
ï
ï 1 - e-( t-23 ) , t ³ 23
10

1 -
( T-26 ) 2

in which, Pt is the probability of setting the indoor tem- Bedroom íï 0, x < 29


í
ï 0, t < 23
e 0.5
ï
î ï
î 0.5 2π
perature to temperature T, T is the temperature setpoint ì
ï 1 - e-( x-29 ) , x ³ 29
2.5
ì
ï 1 - e-( t-23 ) , t ³ 23
10
( T-27 ) 2
Living ï
í ï
í
1 -
measured in °C, and μ and σ are parameters of the equation. e 0.5
room ï
ï
î 0, x < 29 ï
ï
î 0, t < 23 0.5 2π
C
( T-27 ) 2
1 -
Bedroom Pon=1 Poff=0 e 0.5
0.5 2π
2.2 Typical AC use modes
Living 1 -
( T-26 )2
Pon=1 Poff=0 e 0.5
room 0.5 2π
Surveys about AC use modes were conducted in all 294 D
( T-27 ) 2
1 -
households of which 210 effective questionnaires were Bedroom Pon=1 Poff=0
0.5 2π
e 0.5
received. The residents were asked when at home, what Living 1 -
( T-24 )2
Pon=1 Poff=0 e 0.5
ambient conditions would cause them to turn on the AC, room 0.5 2π
E
and what temperatures make them feel comfortable. Bedroom Pon=1 Poff=0 1 -
( T-24 )

e 0.5
2

In addition, the thermal comfort issue was considered 0.5 2π


Zhou et al. / Building Simulation / Vol. 9, No. 4 433

Based on the results of the questionnaire survey and an indoor environment and energy consumption simulation.
field measurements, only about 5% of the residents used Then indoor environment parameters and occupancy in-
the AC units in the dining room, kitchen and other spaces. formation from DeST would be passed to the AC usage CP
Simultaneously, more than 60% of the households had AC model to determine the AC states for the next time step.
units only in the bedroom and living room. Therefore, only
the AC usage in the living rooms and bedrooms were con- 2.4 Modeling and validation
sidered in our study. This phenomenon was also detected
in Yoshino’s study (Yoshino 2006). A residential community model with 294 households in 12
buildings was built with the DeST software. This community
2.3 Combined model was based on the investigated residential community in
Henan Province, China. All the buildings in the community
The DeST (Designer’s Simulation Toolkits) software was had a similar architectural design, and key characteristics
used for the simulations. DeST is a BEMP (building energy of buildings are shown in Table 2. This data comes from
modeling program) developed at Tsinghua University in the design document of the community, which includes the
the late 1980s, aimed at aiding teaching, research, and the architectural design and structural design. The layout and
practical use of building energy analyses and simulations in orientation of the buildings is shown in Fig. 5.
China (Yan et al. 2008; Zhang et al. 2008). DeST has been The validation data was measured from Jul. 1 to Sep. 30,
widely used in China, with some applications in Europe 2011. The outdoor dry bulb temperatures are shown in
and Japan. It has been applied in around 25 million square Fig. 6, with the lowest outdoor dry bulb temperature being
meters of building design and commissioning applications. 13.7 °C, the highest being 36.3 °C, and the average being
More than 4000 users currently use DeST as a building 24.8 °C.
simulation tool (Yan et al. 2008). The results from compara-
tive tests on building loads and HVAC system calculations Table 2 Key characteristics of buildings in the communities
show small differences from those of DeST, EnergyPlus and Characteristics Community A
DOE-2 (Zhu et al. 2013; Zhou et al. 2014).
Number of floors of each building 5
The AC usage CP model was integrated with the DeST
Number of households 294
software to reflect the interaction of the AC operation and
Net site area (m2) 28000
the indoor environment, as shown in Fig. 4. At each time-
2
Habitable floor area (m ) 41200
step, three uniform-distribution random numbers between
0 and 1 were generated (a, b, and c). These were used as Average window–wall ratio 0.5

inputs to the AC usage CP model. If the random number Average external wall area (m2/building) 1971
−1
a/b was larger than Pon /Poff, then the AC units were turned Air change rate (h ) 0.5
on/off. The random number c was used as an input to the Thermal transmittance of building envelope U (W/(m2·K))
inverse function of the cumulative probability distribution External wall 1.84
of Pt, in order to find the corresponding value of the AC Windows 2.5
setpoint temperature. Therefore, based on the random Attic floor 0.6
number, environmental parameters, and occupancy, the
AC usage CP model was used to calculate the on–off states
and the setpoint temperatures of the AC units in each
household. DeST took this AC information and performed

Fig. 4 Combined model Fig. 5 Layout of the residential community


434 Zhou et al. / Building Simulation / Vol. 9, No. 4

was no central ventilation system, and the ventilation rates


through the window changed between 0.5 (Yoshino 2006)
and 10, according to the load requirements and the weather
conditions (Yan et al. 2008).
A district cooling system was applied to the residential
community model. Three chillers with the same capacity were
chosen for the peak load, and their rated COP (coefficient
of performance) was set to 5. The operating units of the
chillers were adjusted to keep the equipment working at a
maximum load ratio. The supply chilled water temperature
was set to 7 °C. In addition, several important control
measures were used on the waterside. The water pumps
Fig. 6 Outdoor dry bulb temperatures had variable speeds with the frequency ranging from 30 Hz
to 50 Hz. The operating units and speed were adjusted to
The FCU metering data for the 5 typical households keep the temperature differences between the supply and
(see Section 2.1 for details) was used to calculate the daily return water as close to the design value (5 °C) as possible.
AC usage hours for each household. Then, this number was Meanwhile, the pump heads were used to satisfy the water
used to divide all the households of the community into the flow rate requirement of each AC unit. To emphasize the
5 typical AC use modes. The AC use mode assignments are operation of chillers and pumps, the heat gain by heat
summarized in Table 3. As previously mentioned, AC use conduction and pump works was ignored. The part-load
mode A corresponds to the most thrifty AC usage, and AC performance curves of the chiller and pump in DeST can
use mode E corresponds to the least thrifty AC usage (see be found in (Zhou et al. 2013).
Table 1). Based on the information above, the cooling activity of the
During the simulation, the cooling capacity of these residential community from Jul. 1 to Sep. 30 was simulated.
FCUs was auto-sized according to the cooling load in each Meanwhile, the actual cooling consumption was obtained
zone. For each FCU unit, a constant volume fan and an from the property management company of the residential
on–off valve were used to supply air and chilled water. The community. Figure 7(a) shows that the total measured
fan pressure rise was set to 600 Pa (Korolija et al. 2011). The cooling consumption for the residential community had
indoor temperature was controlled by a local thermostat an error of 9% with respect to the simulated results. The
which influenced the state of the on–off valve, and in this hourly cooling consumption of three typical days is shown
in Fig. 7(b), where it is depicted that the simulation results
way, the water flow rate through the cooling coil was
and measured data have similar trends.
adjusted to respond to the zone demand. When there was
no need for cooling, the fan coil was switched off. There
2.5 Case study
Table 3 Proportions of different AC use modes
The validated model was used to analyze the district cooling
Use mode Not used A B C, D, E
systems with different combinations of AC use modes during
Proportion 60% 10% 10% 20% the cooling season (July to September). The uncertainty of

Fig. 7 Comparison between simulation result and measured data


Zhou et al. / Building Simulation / Vol. 9, No. 4 435

user compositions was analyzed in this study. Each household 3 Results and discussion
was represented by one typical AC use mode. The ratios of
the five typical AC use modes change at a 10% interval, and 3.1 Uncertainty analysis of user composition
the sum of the total ratio of the five AC use modes cannot
be larger than 100%. For example, the ratios of the five AC With different user compositions shown in Fig. 8, the system
use modes of the first case were (0, 0, 0, 0, 10%), and the energy efficiency ratio (EER) was calculated, as described
ratios of the five AC use modes of the second case were (0, by Eq. (4):
0, 0, 0, 20%). A total number of 3003 cases were simulated
Qc
in this study, as shown in Fig. 8. This figure shows a total of EER= (4)
Echiller + Epumps
3003 columns, each corresponding to a case in which a
certain user composition is applied with different ratios of in which, Qc is the cooling consumption in kWh, Echiller is
AC use modes A (most thrifty AC usage) through E (least the electricity consumption of chillers, and Epumps is the
thrifty AC usage) in the five subgraphs. With different user electricity consumption of pumps.
compositions, the load profiles had different characteristics, The 3003 results were classified into 5 groups, shown
leading to different influences on energy consumption and in Fig. 9. In Series 1, most households used AC use mode A
performance of the district cooling system. (the most thrifty AC usage), and similarly, Series 2 to 5 were
Five user compositions (shown in Table 4) were taken households primarily using AC use modes B through E,
as typical cases and analyzed in this study. In each case, a respectively.
certain AC use mode was taken by most of the residents. From the comparison of system EERs of different series
Therefore, Case 1 corresponds to the most thrifty AC usage in Fig. 9, it can be concluded that when most people use
case, and Case 5 corresponds to the least thrifty AC usage AC use modes A or B, namely the more thrifty AC usage,
case. Through analysis of the five cases, the influence of AC the uncertainty of system performance was more obvious.
use modes on the load feature and the performance of the With different kinds of user compositions, the system EERs
district cooling system was revealed in detail. changed from 1 to 4.5 in Series 1 and 2. When most people
used AC use modes C or D, the uncertainty of system
performance decreased, and the change range of the system
EER was limited between 2 to 4.5. Meanwhile, when most
households used AC use mode E, namely the least thrifty
AC usage, the system performance was quite steady, and
the system EER was around 4.5.
The results above demonstrate that AC use modes and
user compositions have a significant influence on the system
performance of district cooling systems. When different AC
use modes are dominant, the uncertainty range of the system
performance was substantially different.

3.2 Influence of AC use modes on load features

In order to investigate the influence of AC use modes and


Fig. 8 Study cases user compositions on the load feature, the cases described
in Table 4 were simulated and analyzed as follows. The
Table 4 Typical cases Lorenz curve and Gini coefficient (Corrado 1921) were
Household composition applied to evaluate the unevenly distributed load feature in
AC use mode a quantitative way. The uneven distribution of the load
Simulation cases A B C D E feature had two aspects.
Case 1 90% 2.5% 2.5% 2.5% 2.5%
1. Load distribution among different households at a given time
Case 2 2.5% 90% 2.5% 2.5% 2.5%
Case 3 2.5% 2.5% 90% 2.5% 2.5% Taking a typical hour (12:00, July 9) as an example, the
Case 4 2.5% 2.5% 2.5% 90% 2.5%
Lorenz curve and the corresponding Gini coefficient are
shown in Fig. 10. The x-axis represents the cumulative share
Case 5 2.5% 2.5% 2.5% 2.5% 90%
of the number of households in the order of lowest to highest
436 Zhou et al. / Building Simulation / Vol. 9, No. 4

Fig. 9 Uncertainty analysis of the influence of user compositions on system EER

load requirement, and the y-axis represents the cumulative The uneven cooling load distributions influenced the opera-
share of load requirements. The load requirement is expressed tion of water pumps greatly. Taking Case 1 as an example,
as a dimensionless number equal to the load needed at the the different AC usages amongst different households led
designated moment divided by the rated load. When the to uneven cooling load distributions. Therefore, only a few
Lorenz curve deviates from the 45° line, the load distribution AC units were in operation. To satisfy the users’ thermal
significantly differs between different households. In addition, comfort, the pumps had to work at a relatively high speed
if the Lorenz curve lies along the 45° line, it means that all to provide enough water head, causing them to significantly
the users have the same load requirement. The Gini coefficient deviate from their rated working point. With the user com-
can be thought as the ratio of the area that lies between the position in Case 1, the efficiency of the chilled water pumps
line of equality and the Lorenz curve over the total area under at this moment was only 0.67 (rated value 0.75), and the
the line of equality. So larger Gini coefficients correspond transport factor of chilled water pumps (equal to the cooling
to more uneven load distributions. consumption divided by the electricity consumption of the
From Fig. 10, it can be seen that, at this typical hour, chilled water pumps) was only 16. At the same moment,
with different user compositions, the uneven degree of the the efficiency of the chilled water pumps in Case 5 was 0.72,
load distributions is different. From Case 1 (the most thrifty and the water transport factor was 42.
case) to Case 5 (the least thrifty case), the differences in The distribution of Gini coefficients at different times
load requirements amongst different households decreases. during the whole cooling season is shown in Fig. 11.

Fig. 10 Load distributions among air units at a typical moment


Zhou et al. / Building Simulation / Vol. 9, No. 4 437

case) to Case 5 (the least thrifty case), the Lorenz curve


deviates from the line of equality, and the Gini coefficient
becomes smaller. This results means that for the user
composition of Case 1, the load distribution across different
times is uneven and deviates more from the rated condition,
which causes the actual operation of the chillers to differ
greatly from the design intention. The chillers worked at
low load ratios more than in the other four cases, which led
Fig. 11 Distribution of Gini coefficients in the cooling season
to poor system performance.

In Fig. 11, the line in the box represents the mean value 3.3 The applicability of district cooling systems
of the Gini coefficients during the cooling season. The edges
of the boxes are placed at the 25% and the 75% quartiles. The five simulation cases in Table 4 are analyzed in detail
The vertical lines show the 95% and 5% quartiles. From to compare the energy consumption and system efficiencies
Case 1 to Case 5, the Gini coefficient becomes increasingly for different user compositions during the cooling season.
smaller, therefore showing that the load requirements As Fig. 13 shows, there were large differences between the
become more evenly distributed amongst households, a cooling rates of the five user compositions. The cooling
trend that is beneficial for the operation of water pumps. consumption rate of Case 5 (the least thrifty case) was nine
times that of Case 1 (the most thrifty case). These differences
2. Load change amongst different times
were also reflected in the amount of electricity consumed by
The Lorenz curves and the Gini coefficients are also used to the district cooling system. As Fig. 14 shows, the maximum
reflect load changes amongst different times, as shown in electricity consumption was four times that of the minimum
Fig. 12. In Fig. 12, the x-axis represents the cumulative share electricity consumption. Since AC use modes differed
of the number of time-steps in the order of lowest to highest amongst different households, the traditional design method
load requirement, and the y-axis is the cumulative share of that assumes AC use modes of different households are
load requirements. This load requirement is equal to the the same yields results that differ greatly from reality. The
total load requirement of the system divided by the maximum differences in AC usage mean that the cooling requirements
load supplied by the cooling equipment operating at the are different for different households during the same time
corresponding time-step. From Case 1 (the most thrifty of day, and this uneven distribution of cooling loads creates

Fig. 12 Load distribution amongst different times


438 Zhou et al. / Building Simulation / Vol. 9, No. 4

Fig. 13 Influence of AC use modes on the cooling consumption Fig. 15 Influence of AC use modes on the AC efficiency

Fig. 14 Influence of AC use modes on the AC electricity Fig. 16 Influence of AC use modes on the chiller and pump
consumption efficiencies

difficulties in operating the district cooling systems. Therefore, AC usage has an important effect on district cooling
the huge influence of the AC use modes on cooling and system evaluations. The use of split AC systems in the same
electricity consumption should be considered when evaluating residential community was also simulated. The average
the suitability of district cooling systems. COP (coefficient of performance) of the split AC system
Comparing the electricity consumption (Fig. 14) with the was assumed to be 2.3 during the cooling season (Devotta
system efficiency (Fig. 15) provides a better understanding et al. 2005; Building Energy Research Center in Tsinghua
of the district cooling system operation. As Fig. 14 and Fig. 15 University 2013). Figure 17 compares the electricity con-
show, the district cooling system electricity consumption is sumption of the district cooling system and a split AC system
the highest with the user composition of Case 5 (the least for the various user compositions. When most residents
thrifty case), but the efficiency is also the highest. Similarly, use AC use mode A (Case 1, the most thrifty case), the split
the system efficiency decreases as the electricity consump- AC system consumes less electricity. However, when most
tion decreases. As Fig. 16 shows, the chiller and pump users use AC use mode E (Case 5, the least thrifty case), the
efficiencies gradually increase from Case 1 to Case 5, which
leads to the system efficiency trend shown in Fig. 16. This
result reveals that for district cooling systems, high system
efficiency corresponds to high electricity consumption.
Thus, the district cooling system needs suitable conditions
for high system efficiencies. When the load ratios are larger
and more centralized, the district cooling system is more
efficient. Under low load ratios and decentralized load
distributions, the operation of the district cooling system
should be limited, and advanced technologies, such as an
economizer, should be employed to improve the performance
of the district cooling system. Without this, the system would Fig. 17 Electricity consumption rates under different user
be inefficient and wasteful of energy. compositions
Zhou et al. / Building Simulation / Vol. 9, No. 4 439

district cooling system is better. The simulation results in modes and user compositions are involved, a shift from
this case also indicate that the results would differ for positive to negative occurs.
different AC usage trends. Thus, reasonable evaluations of These results show that it is the unevenly distributed
these systems require consideration of the influence of AC cooling load feature that causes the actual operation situation
usage. Without this, the evaluation results could potentially of the district cooling system to differ from that of the
lead to energy waste and investment losses. design intent. Both stochastic AC use modes and their
compositions are highly influential elements of the system
3.4 Influence of the stochastic feature of AC usage design. In order to achieve a better and more reasonable
performance of district cooling systems, it is necessary
Another interesting finding is that for a single AC use mode to take the uncertainty analysis of AC use modes into
simulated with the constant schedule definition model, the consideration during the design phase.
performance of the district cooling system is always better
than that of the split AC system, as shown in Fig. 18. The 4 Conclusions
schedule definition model is one of the most general models
used to describe occupant behavior (Peng et al. 2012), This study investigates the influence of AC use modes on
which uses constant schedules to describe the on–off states the energy consumption and system efficiency of district
of AC units and the corresponding setpoint temperatures. cooling systems in residential buildings through use of
The influence of stochastic AC use modes and user com- simulations and field measurements in a residential com-
positions on consumption differences of the two AC systems munity. A reduced-order AC CP model was developed to
is compared in Fig. 19. Without consideration of stochastic describe the AC usage in the residential community, and 5
AC use modes and user compositions, the ΔElectricity distinct AC use modes, namely AC use mode A (the most
consumption is always negative. When stochastic AC use thrifty AC usage) through mode E (the least thrifty AC
usage), were categorized. Using this organizational approach,
the uncertainty of user compositions was analyzed. The
main conclusions of this paper are summarized below.
(1) The influence of different combinations of AC use
modes on energy savings, and the practicality of district
cooling systems were thoroughly analyzed. The uncertainty
of user compositions was analyzed, and the simulation
results revealed that AC use modes and user com-
positions can lead to a 4.5-fold difference in the system
efficiencies of the district cooling system. When different
AC use modes are dominant, the uncertainty range of
the system performance changes drastically.
Fig. 18 Electricity consumption rates without consideration of (2) The distributed characteristic of the cooling load
stochastic AC use modes and user compositions requirements among different households and different
times plays an important role in the performance of the
district cooling system. The Lorenz curve and Gini
coefficient can effectively describe the distributed load
feature in an quantitative way. The unevenly distributed
load feature had a high Gini coefficient and resulted in
vastly different operational activity of the chillers and
water pumps than that of the original design.
(3) Higher cooling load ratios and centralized load distri-
butions result in reduced energy usage of district
cooling systems. Conversely, low cooling load ratios
and decentralized load distributions result in inefficient
operation and advanced technologies should be employed
Fig. 19 The influence of stochastic AC use modes and user com- to save energy.
positions (Note: ΔElectricity consumption=2 × (District cooling − (4) When only one AC use mode is considered and the
Split AC)/ (District cooling + Split AC) × 100%)
stochastic feature of AC use modes is ignored, then the
440 Zhou et al. / Building Simulation / Vol. 9, No. 4

simulated performance of the split AC system yields Devotta S, Padalkar AS, Sane NK (2005). Performance assessment of
better results than the district cooling system, which HC-290 as a drop-in substitute to HCFC-22 in a window air
may not be true in reality. Therefore, consideration of conditioner. International Journal of Refrigeration, 28: 594–604.
the influence of both the stochastic AC use modes and Fanger PO (1970). Thermal Comfort: Analysis and Applications in
Environmental Engineering. New York: McGraw-Hill.
their compositions in the simulation process is critical
Feng X, Yan D, Hong T (2015). Simulation of occupancy in buildings.
for better system design and more effective equipment
Energy and Buildings, 87: 348–359.
investments.
Frontczak M, Wargocki P (2011). Literature survey on how different
factors influence human comfort in indoor environments. Building
Acknowledgements and Environment, 46: 922–937.
Hoes P, Hensen JLM, Loomans MGLC, de Vries B, Bourgeois D
This research is supported by the Natural Science Foundation (2009). User behavior in whole building simulation. Energy and
of Beijing, China (No. 8142022). Buildings, 41: 295 – 302.
ISO (2005). ISO 7730, Ergonomics of the Thermal Environment—
References Analytical Determination and Interpretation of Thermal Comfort
Using Calculation of the PMV and PPD Indices and Local
Al-Qattan A, ElSherbini A, Al-Ajmi K (2014). Solid oxide fuel cell Thermal Comfort Criteria.
application in district cooling. Journal of Power Sources, 257: Jing ZX, Jiang XS, Wu QH, Tang WH, Hua B (2014). Modelling and
21–26. optimal operation of a small-scale integrated energy based district
Araujo AM, Roberto S, La Rovere EL (2001). The potential for electricity heating and cooling system. Energy, 73: 399–415.
conservation and peak load reduction in the residential sector of Jones B (2000). Capabilities and limitations of thermal models, Smart
Brazil. Energy, 26: 413–429. Controls and Thermal Comfort Project. Final Report (Confidential).
ASHRAE (2010). ASHRAE Standard 55-2010, Thermal Environmental Oxford Brookes University, pp. 112–121.
Conditions for Human Occupancy. Atlanta, GA, USA: American Kamal WA (1997). Improving energy efficiency—The cost-effective way
Society of Heating, Refrigerating and Air-Conditioning Engineers. to mitigate global warming. Energy Conversion and Management,
Boardman B (2004). Achieving energy efficiency through product 38: 39–59.
policy: The UK experience. Environmental Science & Policy, 7: Korolija I, Marjanovic-Halburd L, Zhang Y, Hanby VI (2011). Influence
165–176. of building parameters and HVAC systems coupling on building
Building Energy Research Center in Tsinghua University (2013). 2013 energy performance. Energy and Buildings, 43: 1247–1253.
Lam JC, Wan KKW, Tsang CL, Yang L (2008). Building energy
Annual Report on China Building Energy Efficiency. Beijing:
efficiency in different climates. Energy Conversion and Management,
China Architecture & Building Press. (in Chinese)
49: 2354–2366.
Chen SQ, Li N, Guan J, Xie Y, Sun F, Ni J (2008). A statistical method
Lenzena M, Wier, M, Cohen C, Hayami H, Pachauri S, Schaeffer R
to investigate national energy consumption in the residential
(2006). A comparative multivariate analysis of household energy
building sector of China. Energy and Buildings, 40: 654–665.
requirements in Australia, Brazil, Denmark, India and Japan.
Chen X, Zhang GQ, Yu LK (2001). Life-cycle cost analysis applied
Energy, 31: 181–207.
to comparison among different air conditioning schemes for
Long WD, Zhong T, Zhang BH (2003). Situation and trends of residential
residential district. In: Proceedings of 4th International Conference
building environment services in Shanghai. In: Proceedings of
on Indoor Air Quality, Ventilation and Energy Conservation in
4th International Symposium on Heating, Ventilating and Air
Buildings, Changsha, China, pp. 1863–1869.
Conditioning. Beijing: Tsinghua University Press, pp. 493–498.
Chow TT, Au WH, Yau R, Cheng V, Chan, A, Fong KF (2004a).
Meyers S, McMahon JE, McNeil M, Liu X (2003). Impacts of US
Applying district-cooling technology in Hong Kong. Applied federal energy efficiency standards for residential appliances.
Energy, 79: 275–289. Energy, 28: 755–767.
Chow TT, Chan ALS, Song CL (2004b). Building-mix optimization in Morelli N (2001). Technical innovation and resource efficiency. A
district-cooling system implementation. Applied Energy, 77: 1–13. model for Australian household appliances. The Journal of
Chow TT, Fong KF, Chan ALS, Yau R, Au WH, Cheng V (2004c). Sustainable Product Design, 1: 3–17.
Energy modeling of district cooling system for new urban Nagota T, Shimoda Y, Mizuno M (2008). Verification of the energy-
development. Energy and Buildings, 36: 1153–1162. saving effect of the district heating and cooling system—Simulation
Corrado G (1921). Measurement of Inequality of Incomes. The of an electric-driven heat pump. Building and Environment, 40:
Economic Journal, 31: 124–126. 732–741.
D’Oca S, Hong T (2015). Occupancy schedules learning process through Nicol JF (2001). Characterising occupant behaviour in buildings:
a data mining framework. Energy and Buildings, 88: 395–408. Towards a stochastic model of occupant use of windows, lights,
de Dear RJ, Brager GS (2002). Thermal comfort in naturally ventilated blinds, heaters and fans. In: Proceedings of International IBPSA
buildings: Revision to ASHRAE standard 55. Energy and Buildings, Building Simulation Conference, Rio de Janeiro, Brazil, pp.
34: 549–561. 493–498.
Zhou et al. / Building Simulation / Vol. 9, No. 4 441

O’Doherty J, Lyons S, Tol RSJ (2008). Energy-using appliances and Ueno T, Sano F, Saeki O, Tsuji K (2006). Effectiveness of an energy-
energy-saving features: Determinants of ownership in Ireland. consumption information system on energy savings in residential
Applied Energy, 85: 650–662. houses based on monitored data. Applied Energy, 83: 166–183.
Ortiga J, Bruno JC, Coronas A (2013). Operational optimisation of a Wang C, Yan D, Jiang Y (2011). A novel approach for building
complex trigeneration system connected to a district heating and occupancy simulation. Building Simulation, 4:149–167.
cooling network. Applied Thermal Engineering, 50: 1536–1542. Wei S, Jones R, de Wilde P (2014). Driving factors for occupant-
Page J, Robinson D, Morel N, Scartezzini J-L (2008). A generalised controlled space heating in residential buildings. Energy and
stochastic model for the simulation of occupant presence. Energy Buildings, 70: 36–44.
and Buildings, 40, 2: 83–98. Weibull W (1951). A statistical distribution function of wide applicability.
Pardo N, Vatopoulos K, Riekkola AK, Perez A (2013). Methodology ASME Journal of Applied Mechanics, 18, 3: 293–297.
to estimate the energy flows of the European Union heating and Yan D, Xia J, Tang W, Fangting Song F, Zhang X, Jiang Y (2008).
cooling market. Energy, 52: 339–352. DeST—An integrated building simulation toolkit, Part Ⅰ:
Peeters L, de Dear R, Hensen J, D’haeseleer W (2009). Thermal Fundamentals. Building Simulation, 1: 95–110.
comfort in residential buildings: Comfort values and scales for Yan D, O’Brien W, Hong T, Feng X, Gunay HB, Tahmasebi F,
building energy simulation. Applied Energy, 86: 772–780. Mahdavi A (2015). Occupant behavior modeling for building
Peng C, Yan D, Wu R, Wang C, Zhou X, Jiang Y (2012). Quantitative performance simulation: Current state and future challenges.
description and simulation of human behavior in residential Energy and Buildings, 107: 264–278.
buildings. Building Simulation, 5: 85–94. Yoshino H, Yoshino Y, Zhang Q, Mochida A, Li N, Li Z, Miyasaka H
Pérez-Lombard L, Ortiz J, Pout C (2008). A review on buildings energy (2006). Indoor thermal environment and energy saving for
consumption information. Energy and Buildings, 40: 394–398. urban residential buildings in China. Energy and Buildings, 38:
Reinhart CF (2004). Lightswitch-2002: A model for manual and 1308–1319.
automated control of electric lighting and blinds. Solar Energy, Zhang X, Xia J, Jiang Z, Huang J, Qin R, Zhang Y, Liu Y, Jiang Y
77: 15–28. (2008). DeST—An integrated building simulation toolkit, Part Ⅱ:
Ren X, Da Y, Wang C (2014). Air-conditioning usage conditional pro- Applications. Building Simulation, 1: 193–209.
bability model for residential buildings. Building and Environment, Zhang WJ, Huai LL, Liu JL (2009). Comparison analysis of energy
81: 172–182. consumption characteristics between decentralized and centralized
Rezaie B, Rosen MA (2012). District heating and cooling: Review of AC systems in residential buildings by commissioning. In:
technology and potential enhancements. Applied Energy, 93: 2–10. Proceedings of 5th International Workshop on Energy and
Richardson I, Thomson M, Infield D (2008). A high-resolution domestic Environment of Residential Buildings and 3rd International
building occupancy model for energy demand simulations. Energy Conference on Built Environment and Public Health, Guilin,
and Buildings, 40, 8: 1560–1566. China, pp. 1768–1775.
Rijal HB, Tuohy P, Humphreys MA, Nicol JF, Samuel A, Clarke J Zhao J, Lasternas B, Lam KP, Yun R, Loftness V (2014). Occupant
(2007). Using results from field surveys to predict the effect of behavior and schedule modeling for building energy simulation
open windows on thermal comfort and energy use in buildings. through office appliance power consumption data mining.
Energy and Buildings, 39: 823 – 836. Energy and Buildings, 82: 341–355.
Shimoda Y, Nagota T, Isayama N, Mizuno M (2008). Verification Zhou X, Hong T, Yan D (2013). Comparison of building energy
of energy efficiency of district heating and cooling system by modeling programs: HVAC systems. Available at http://www.osti.gov/
simulation considering design and operation parameters. Building scitech/biblio/1165199. Accessed May 2015.
and Environment, 43: 569–577. Zhou X, Hong T, Yan D (2014). Comparison of HVAC system
Soederman J (2007). Optimisation of structure and operation of modelling in EnergyPlus, DeST and DOE-2.1E. Building Simulation,
district cooling networks in urban regions. Applied Thermal 7: 21–33.
Engineering, 27: 2665–2676. Zhu D, Yan D, Wang C, Hong T (2013). A detailed loads comparison
Tanimoto J, Hagishima A, Sagara H (2008). A methodology for peak of three building energy modeling programs: EnergyPlus, DeST
energy requirement considering actual variation of occupants’ and DOE-2.1E. Building Simulation, 6: 323–335.
behavior schedules. Building and Environment, 43: 610–619.

You might also like