You are on page 1of 22

Expansion Tank Sizing and

Location For

Chilled Water & Hot Water Systems


In Multistory Building

Prepared By
Engineer. Mostafa Al Wakeel

https://www.facebook.com/groups/mepprofessionals/

The source is ASHRAE journal March 2003 (attached)


By: Steven T. Taylor, P.E.
Example 1: Chilled Water System:

Assume the system is a chilled water system with a design chilled water
temperature of 40°F (4.4 C) and system volume of 1000 gallons (3785 L).

The layout is as shown in Figure 1 with the pump at the bottom of a


multistory building. Pump head is 80 ft (240 kPa)

First calculate the initial precharge pressure Pi.

Since the system is chilled water, there is no concern about net positive
suction head.

The Lpp (Lowest Pressure Point) in the system is the highest point on the
return line just as it drops down to the pump (Point A in Figure 1).

Pmin is 4 psig (28 kPa) as shown in Figure 2.

The tank will be the smallest and least expensive if located near the Lpp.
However, for this example, assume the tank is located near Point B at the
pump suction, which is often the most convenient location since space is
usually available as shown in fig (1-1).
Fig (1-1)

The static pressure rises DPs, Lpp to tank from the Lpp to the tank is 100 ft
(or 100/2.31= 43 psi [296 kPa]) (1ft = 0.43 psi).

DPs = 43 psi (from the Lpp (point A) to the tank)

The frictional pressure drops DPf, tank to Lpp from tank to the Lpp is taken
as zero (0) since the tank is downstream of the Lpp.

DPf = 0 (from tank to the Lpp (point A))

The minimum tank initial or precharge gauge pressure Pi is:

Pi = (static pressure) + (frictional pressure drop)

Pi = (Pmin) + (DPs, Lpp to tank) + (DPf, tank to Lpp) = 4 + 43+ 0

Pi = 47 psig (324 kPa)


Now find the maximum pressure (Pmax):

The standard pressure rating of all components in the system will be 125 psig
(862 kPa) or higher. Hence Pmax is taken as 125 psi (862 kPa) and the Cpp
(critical pressure point) is the lowest point in the system on the discharge side
of the pump, Point C in fig (1).

Assume the pressure relief valve will be located near the chiller and the
expansion tank, Point B (at pump suction).

The static pressure difference DPs, Cpp to Prv from the Cpp to the pressure
relief valve is zero since they are at the same elevation.

DPs = 0 (from the Cpp to the pressure relief valve)

The relief valve (Point B) is downstream of the Cpp (critical pressure Point
C). DPf, Cpp to Prv is the roughly equal to pump head (80 ft or 35 psi [241
kPa]).

The frictional pressure drop is DPf = 35 psi (from Cpp to Prv)

The pressure relief valve setpoint Prv is then:

Prv = Pmax + (static pressure difference DPs) - (frictional pressure drop DPf)
Prv = Pmax + (DPs, Cpp to Prv) – (DPf, Cpp to Prv)

Prv =125+ (0) – (35) = 90 psi

This setting assures that the pressure at the discharge side of the pump will
Not exceed 125 psi (862 kPa).

If the relief valve setpoint were 125 psi (862 kPa), the pressure downstream
of the pump could be as high as 160 psi (1100 kPa), possibly above the
equipment rating.

The static pressure difference DPs, Prv to tank from the relief valve to the
tank is zero (0) since they are at the same location.

DPs = 0 (from the relief valve to the tank)


The frictional pressure drops DPf, Prv to tank from the relief valve to the
tank is zero (0) since they are at the same location.

DPf = 0 (from the relief valve to the tank)

The tank maximum gauge pressure Pmax is:

Pmax = Prv + (DPs, Prv to tank) – (DPf, Prv to tank) = 90 + (0) – (0)

Pmax = 90 psi.

The minimum tank volume:

The tank minimum volume (assuming a maximum temperature of 80°F


(27°C) with specific volume values taken from Table 1) is then calculated as:

Vs = The total volume of water in the system, including all piping, Heat
Exchangers and vessels = 1000 gallons).

Va = acceptance volume, this is the capacity of the bladder (for bladder


tanks) or the volume of the waterside of the tank not the air side when the
diaphragm is fully extended (for diaphragm tanks). With so-called “full
acceptance” tanks, the bladder can open to the full shape of the tank.

So, the tank’s acceptance volume (Va) and total tank volume (Vt) are equal to
(Ve)= the increase in volume of water as it expands from its minimum
temperature to its maximum temperature.

Ve = Vt + Va
Ve = expanded water volume.
Vt = the total tank volume (water and air).
Pa = atmospheric pressure = 14.7 psi

Pi = precharge pressure = 47 psi

Then Va = acceptance volume = 3.75 gallons

Vt >= (Va) / 1- ((Pa + Pi) / (Pa + Pmax))

Vt = 9.1 gallons (tank total volume).

Hence, the expansion tank must have an acceptance volume greater than 3.75
gallons (14 L) and an overall volume greater than 9.1 gallons (34 L) then 10
gallons or 15 gallons is preferred as a total tank volume = 0.01 of the system
water volume.

***
Example 2: Chilled Water System:

Assume the system is as in Example 1, but instead of locating the tank at the
pump suction, assume it is located at the Lpp (Point A) as shown in fig (2-2).

The precharge pressure would then be calculated as:


The static pressure rise Ps, Lpp tank from the Lpp to the tank is zero (0)
since the tank is located at this point.

Ps = 0 (from the Lpp (POINT A) to the tank)

Fig (2-2)

The frictional pressure drop Pf, tank Lpp from the tank to the Lpp is zero
(0) since the tank is located at this point.

Pf = 0 (from the tank to the Lpp (point A))


The minimum tank initial or precharge gauge pressure Pi is:

Pi Pmin) Ps, Lpp tank) Pf, tank Lpp) =4 0 0

Pi4 psi

Now find the maximum pressure:

The static pressure difference Ps, Prv tank from the relief valve to the
tank is (-100 ft) (or (-100/2.31= - 43 psi) [- 296kPa]). It is negative since the
Prv is below the tank.

Ps = - 43 psi (from the relief valve to the tank)

The frictional pressure drop Pf, Prv tank from the relief valve to the tank
is taken as zero (0) since the tank is upstream of the relief valve.

Pf = 0 (from the relief valve to the tank)

The tank maximum gauge pressure Pmax is:

Pmax Prv Ps, Prv tank) Pf, Prv tank) 90 430

Pmax = 47 psi

The tank volume is then calculated as:

As in Example 1, the expansion tank must have an acceptance volume greater


than 3.75 gpm (0.24 L/s) (the volume of expanded water is unchanged), but
the total volume required falls to 5.4 gallons (20 L).
This demonstrates that a tank located at the Lpp in a multi-story system is
smaller and therefore less expensive than a tank located at the pump suction
(as in Example 1).

***
Example 3: High Temperature Hot Water System

Assume the system is a high temperature hot water system with a design hot
water temperature of 300°F (149°C) and system volume of 1000 gallons
(3785 L).

The pumps’ required NPSH (net positive suction head) r is 5 ft (15 kPa) and
its head is 50 ft (150 kPa). The layout is horizontal as shown in Figure 3.

First calculate the initial precharge pressure Pi, which will be the larger of
that required to prevent boiling and that required to maintain adequate net
positive suction head at the pump.

The pressure required to prevent boiling is determined as:

The Lpp (lowest pressure point) in the system is the highest point on the
return line just after it drops down to the pump (Point A in Figure 3).

Pmin is recommended to be 70 psi (482 kPa) as shown in Figure 2 at 300F.

Pmin = 70 psi

If there are control valves located near the Lpp, the minimum pressure may
need to be higher (to avoid cavitation in control valves).
For this example, assume the tank is located near Point B at the pump suction
as shown in fig (3-2).

The static pressure rise Ps, Lpp tank from the Lpp to the tank is 15 ft (or
15/2.31= 6.5 psi [45 kPa]).

Ps = 6.5 psi (from the Lpp to the tank)

The frictional pressure drop Pf, tank Lpp from the tank to the Lpp is
taken as zero (0) since the tank is downstream of the Lpp.

Pf = 0 (from the tank to the Lpp)

The minimum tank initial or precharge gauge pressure Pi is:

Pi = 76.5 psi

The initial pressure must also be sufficient to maintain the required net
positive suction head (NPSHr) at the pump inlet:
The required net positive suction head

(NPSHr) is 5 ft (or 5/2.31 = 2 psi = [15 kPa]).

The frictional pressure drop Pf, tank suction from the tank to the pump
suction is zero (0) since the tank is located at the pump suction.

Pf = 0 (from the tank to the pump suction)

The gauge vapor pressure of the fluid Pv is 53 psi (365 kPa) per Figure 2.

Pv = 53 psi

The static pressure difference Ps, tank suction from the tank to the pump
suction is zero (0) since the tank is located at this point.

Ps = 0 (from the tank to the pump suction)

Assume velocity pressure difference pv, tank suction is negligible = 0

pv = 0
Calculate the minimum tank initial or precharge gauge pressure Pi as:

This pressure is lower than that required to prevent boiling at the Lpp, so it
may be ignored. As noted above, this is typically the case unless the pump is
a long distance from the expansion tank or located well above the tank.

Now find the maximum pressure (Pmax):

The standard pressure rating of all components in the system will be 125 psi
(862 kPa) or higher. Hence Pmax is taken as 125 psig and the Cpp (critical
pressure point) in this case it is the lowest point in the system on the
discharge side of the pump, Point C.

Pmax = 125 psi

The pressure relief valve will be located at the boiler.


The static pressure difference Ps, Cpp Prv from the Cpp to the pressure
relief valve is zero (0) since they are roughly at the same elevation.

Ps = 0 (from the Cpp to the pressure relief valve)

The relief valve (at the boiler) is downstream of the Cpp (critical pressure
point) (Point C).
Pf, CPP Prv is the then approximately equal to pump head means
(50 ft or 22 psi [152 kPa]).

Pf = 22 psi (from the Cpp to the pressure relief valve)

The pressure relief valve setpoint Prv is then:


The static pressure difference Ps, Prv tank from the relief valve to the
tank is zero (0) since they are roughly at the same elevation.

Ps = 0 (from the relief valve to the tank)

The frictional pressure drop Pf, Prv tank from the relief valve to the tank
may be ignored (0) since they are near the same location.

Pf = 0 (from the relief valve to the tank)


The tank maximum gauge pressure Pmax is:

The tank minimum acceptance volume:

Assuming a minimum temperature of 60°F [16°C] with specific volume


values taken from Table 1) is then calculated as:
Hence, the tank must have an acceptance volume Va = 88 gallons (333 L) or
larger and a total volume Vt = 390 gallons (1476 L) or larger (400 gallons).

Note:
For the chilled water the tank size is about 1/100 of the system water volume
(1000 gallons and the tank maximum are 10 gallons) but in hot water system
the tank is about 40% of the system water volume (1000 gallons and the tank
are 400 gallons) because of the expansion of hot water.

***

Example 4: Redo the above calculations with the tank at the pump
discharge, Point C as shown in fig (3-3).

You will find that the precharge pressure increases (to overcome the head and
losses in the pipes and fitting because it is the source of pressure th the whole
system) while all other variables remain the same, resulting in a somewhat
larger tank. Nevertheless, the tank will still meet all of its intended functions
so this is a perfectly acceptable, if unusual, location. Then it’s better to put
the tank before suction of the pump.
Practical Guide

By Steven T. Taylor, P.E., Member ASHRAE pansion tank remains constant.


Fact: This claim has resulted in unnec-

M
isleading and sometimes incorrect statements regarding how to essary confusion and concern among
select and pipe expansion tanks can be found in design manuals operating engineers when they find sys-
tem operating pressures varying widely.
and manufacturers’ installation guides. Some of the more common The pressure at the expansion tank will
claims follow. Claim: Expansion tanks must be connected to the sys- not change when pumps are started and
tem near the suction of the pump. Fact: Closed expansion tanks (those stopped (other than a brief pulse), but
the pressure will change when the tem-
not vented to the atmosphere) may be connected anywhere in the perature of the fluid in the system
system provided their precharge (initial) pressure and size are cor- changes, causing the water volume to
expand or contract. The amount of pres-
rectly selected. However, maximum pressure ratings of some system
sure change is a function of the size of
components may limit expansion tank connection location. the tank and the change in fluid tempera-
ture. As shown in the examples below,
Claim: The best connection point for est point in the system on the return pip- the designer can select a tank to operate
expansion tanks is near the suction of ing to the pump. But the “best” location over a wide range of pressures, e.g., 10 to
the pump. may not be the one that results in the 1 or more.
Fact: If “best” means the point that will smallest tank size. It may be where the To better understand these facts and to
result in the smallest (lowest cost) expan- tank may be most conveniently located, properly select expansion tanks, we must
sion tank, the best location is at the point such as in a mechanical room where space start with the fundamentals.
in the system that has the lowest gauge is available and the tank is readily ac-
pressure when the pump is on. For a sys- cessible for service. The low-pressure Purpose
tem that is distributed horizontally (e.g., point may, for instance, be located over a Expansion tanks are provided in
a one-story building), the low-pressure hotel guest room that is not a convenient closed hydronic systems to:
point will be at the pump suction. How- location for an expansion tank.
About the Author
ever for a system that is distributed verti- Claim: The connection point of the Steven T. Taylor, P.E., is a principal at Taylor
cally (e.g., a multi-story building), the expansion tank is the “point of no pres- Engineering in Alameda, Calif. He is a member of
low-pressure point will be near the high- sure change,” i.e., the pressure at the ex- TCs 4.3 and 1.4 and former chair of SSPC 62.1.

2 ASHRAE Journal ashrae.org March 2003


Hydronic

• Accept changes in system water volume as water density


changes with temperature to keep system pressures below ‘But the “best” location may not
equipment and piping system component pressure rating lim-
its. be the one that results in the
• Maintain a positive gauge pressure in all parts of the sys- smallest tank size. It may be
tem in order to prevent air from leaking into the system.
• Maintain sufficient pressures in all parts of the system in where the tank may be most
order to prevent boiling, including cavitation at control valves
and similar constrictions.
conveniently located, such as in
• Maintain required net positive suction head (NPSHr) at a mechanical room where space
the suction of pumps.
The latter two points generally apply only to high tempera- is available and the tank is readily
ture hot water systems. For most HVAC applications, only the accessible for service.’
first two points need be considered.

Types
There are basically two types of expansion tanks: static head increase due to elevation as positive. The point
• Tank type or “plain steel” tanks (water in contact with air), with the lowest net pressure is the LPP. The static pressure
which may be atmospheric (vented to atmosphere) or pressur- increase as you move down in elevation from the high point
ized, and increases 1 foot of head for every foot of elevation drop (3 kPa
• Diaphragm or bladder-type tanks (air and water separated for every 0.3 m). In normal practice, the frictional pressure
by a flexible diaphragm or bladder, typically made of heavy- drop rate will be almost two orders of magnitude smaller, so the
duty butyl rubber). The bladders in bladder-type tanks gener- increase in pressure due to a reduction in elevation is always a
ally are field replaceable should they fail while failure of a much larger factor than the pressure decrease due to friction.
diaphragm tank would require complete replacement of the Hence, the LPP will almost always be the highest point of the
tank. return line just after it drops down to the pump.
Both types of expansion tanks work by allowing water to 2. Determine Pmin, the minimum pressurization required at
compress a chamber of air as the water expands with increas- the LPP to maintain a positive gauge pressure (to prevent air
ing temperature. When the system is cold and the water in the from leaking into the system when a vent is opened) and to
tank is at the minimum level (which may be no water at all), prevent boiling. A commonly recommended minimum pres-
the tank pressure is at its initial or precharge pressure Pi. As the surization is 4 psig (28 kPa) plus 25% of the saturation vapor
water in the system expands upon a rise in temperature, water pressure when this pressure exceeds atmospheric pressure (Fig-
flows into the tank and the air pocket is compressed, increas- ure 2). For chilled water, condenser water, and typical hot wa-
ing both the air and water system pressure. ter (<200°F [93°C]) systems, the recommended minimum
When the system is at its highest temperature and the tank pressure is 4 psi (28 kPa).
water volume is at its design capacity, the resulting air and For high temperature hot water, the minimum pressure will
water system pressure will be equal to or less than the design need to be higher as shown in Figure 2. For hot water systems
maximum pressure Pmax. Both Pi and Pmax are predetermined that have high pressure-drop control valves located near the
by the designer as part of the tank selection process outlined LPP, the minimum pressure may need to be even higher to
below. prevent cavitation downstream of the valve.1
3. Locate the tank position. The tank will be the smallest
Initial Pressure and least expensive if located near the LPP. However, space or
The tank initial or precharge gauge pressure Pi must be other considerations (e.g., convenient makeup water source,
greater than or equal to the larger of the following: which should be connected near the same point in the system)
A. The minimum pressure required to prevent boiling and may make another location more desirable.
to maintain a positive gauge pressure at any point in the 4. Calculate the static pressure rise ∆Ps, LPP →tank from the
system. LPP to the point of connection. This is simply the elevation
This pressure can be determined as follows: difference between the two (for pressure in units of feet of
1. Find the low pressure point (LPP) in the system when the water).
pump is on. To do this, start at the highest point in elevation on 5. If the tank is upstream of the LPP, calculate the frictional
the return side closest to the pump suction (Point A in Figure pressure drop ∆Pf ,tank→ LPP from the connection point to the
1). Calculate the net pressure drop from that point to the pump LPP when the pump is on. ∆Pf ,tank→ LPP will be negative if
suction with friction and dynamic head losses as negative and the tank is downstream of the LPP, but if included in the calcu-
March 2003 ASHRAE Journal 3
Point A 160

140

Gauge Pressure, psig


120

100

80 Recommended
100 ft Minimum
(30.5 m) 60 Pressurization, Pmin

40
Saturation
20 Vapor
Point C Pressure
Point B
0
50 100 150 200 250 300 350
Chiller or
Boiler –20
Pump Temperature, °F
Figure 1 (left): Typical system in a multistory building. Figure 2 (right): Recommended minimum pressurization and
saturation vapor pressure of water.

lation of Pi, minimum pressures would only be maintained the minimum pressurization resulting from Step A will result
when the pump is running. Once it stops, the pressure at the in pump suction pressures well above the NPSHr . Hence, for
LPP will drop by ∆Pf ,tank→ LPP below the desired minimum the large majority of common HVAC applications, the calcula-
pressure. Thus if the tank is downstream of the LPP, tions in Step B may be skipped. This step is listed here for
∆Pf ,tank→ LPP should be ignored (assumed to be zero). completeness.
6. Calculate the minimum tank initial or precharge gauge The precharge pressure required to maintain NPSHr is deter-
pressure Pi as: mined as follows:
Pi = Pmin + ∆Ps, LPP →tank + ∆Pf ,tank→LPP 1. Find the required pump net positive suction head (NPSHr)
(1)
from the manufacturer’s pump curve or selection software.
The tank precharge pressure Pi is often selected at a mini- 2. Calculate the frictional pressure drop
mum of 12 psig (83 kPa), which is the industry standard ∆Pf ,tank→ suction from the tank to the pump suction in the di-
precharge for diaphragm and bladder tanks when no other rection of flow.
value is specified. 3. Determine the gauge saturation vapor pressure of the fluid
Tanks typically are precharged to the specified pressure in Pv at its maximum expected temperature. See discussion under
the factory. However, the precharge pressure should be field Selection later for determining the maximum fluid tempera-
verified and adjusted if necessary. First, turn off any heat-pro- ture. See Figure 2 for a curve of Pv in psig versus temperature.
ducing equipment in the system, then close the tank isolation (Pv is more commonly listed in absolute pressure rather than
valve so it is isolated from the system. Fully drain the tank, gauge pressure, but gauge pressure is used here since we are
then check and adjust the tank air pressure to the desired Pi calculating Pi in gauge pressure.)
setpoint using an air compressor. Before opening the tank iso- 4. Calculate the static pressure difference ∆Ps,tank → suction
lation valve, the system must be near its lowest temperature (as from the tank to the pump suction. This is simply the elevation
determined under Selection later). Connecting the tank to a difference between the two (for pressure in units of feet of
system that is warmer than the minimum temperature will re- water).
sult in pressures below Pi when the system temperature drops 5. Calculate the difference in velocity pressure
and water volume decreases. ∆PV ,tank → suction in the piping at the point where the tank is
B. The minimum pressure required to maintain the avail- connected to that at the pump suction. The velocity pressure is
able net positive suction head (NPSHa ) at the pump suction proportional to the square of the velocity in the pipe (equal to
above the pump’s minimum required net positive suction head V 2 64.3 in units of psi with velocity V expressed in ft/s).
(NPSHr ): Typically this term is negligible and may be ignored, particu-
This criterion is only a factor in determining Pi for high larly when the pipe size at the expansion tank connection
temperature (>200°F [93°C]) hot water systems where the pump point is close to the pump suction pipe size, resulting in nearly
is a long distance (hydraulically) from the expansion tank or equal velocity pressures.
located well above the tank. In almost all other applications, 6. Calculate the minimum tank initial or precharge gauge
4 ASHRAE Journal ashrae.org March 2003
Hydronic

°F 40 60 80 100 120 140 160 180 200 220 240 260 280 300
ft3/ lbm 0.01602 0.01604 0.01608 0.01613 0.01620 0.01629 0.01639 0.01651 0.01663 0.01677 0.01692 0.01709 0.01726 0.01745
°C 4 16 27 38 49 60 71 82 93 104 116 127 138 149
cm3/g 1.000 1.001 1.004 1.007 1.011 1.017 1.023 1.031 1.038 1.047 1.056 1.067 1.078 1.089
Table 1: Specific volume of saturated water at various temperatures.

pressure Pi as: valve to that of the expansion tank. This is simply the eleva-
Pi = NPSHr + ∆P f ,tank→suction + Pv − ∆Ps,tank→suction tion difference between the two (for pressure in units of feet of
− ∆PV ,tank → suction (2) water) and may be positive (PRV above tank) or negative (PRV
below tank).
Maximum Pressure 7. If the tank is downstream of the relief valve, calculate the
Tank maximum pressure Pmax is determined as follows: frictional pressure drop ∆Pf , PRV →tank from the relief valve to
1. Determine the maximum allowable system pressure Pma the tank when the pump is on. (This term is ignored if the tank
and critical pressure point, CPP. The CPP is the “weakest link” is upstream of the relief valve because maximum pressure will
in the system. It is a function of the pressure ratings at the need to be maintained even when the pump is off.)
maximum expected operating temperature of components and 8. Calculate the tank maximum gauge pressure Pmax as:
equipment (obtained from the manufacturer) and their loca- Pmax = Prv + ∆Ps, PRV →tank − ∆P f , PRV →tank (4)
tion in the system in elevation and relative to the pump. To
find the CPP, make a list of the components and equipment
with the lowest pressure ratings (often boilers and other pres- Tank Selection
sure vessels) and calculate the difference between their rating Typically, expansion tanks are selected using manufactur-
and their vertical elevation, in consistent units (e.g., convert ers’ software or selection charts based on the following data:
the psig pressure ratings into units of head (feet of water) and • The minimum temperature the system will see, Tc . For heat-
subtract the elevation of the component). The component with ing systems, this would generally be the initial fill tempera-
the smallest difference is the “weakest link.” Its location on ture, e.g., 50°F (10°C). For cooling systems, this would be the
discharge side of the pump is the CPP and the maximum pres- design chilled water temperature, e.g., 40°F (4°C).
sure Pma is the rating pressure of the equipment. • The maximum temperature the system will see, Th. For heat-
2. Locate the pressure relief valve. Typically, the best loca- ing systems, this would be the design hot water temperature,
tion is near the CPP and the component the relief valve is e.g., 180°F (82°C). For cooling systems, this would generally
intended to protect, but a common location is near the expan- be the temperature the system may rise to when it is off, e.g.,
sion tank connection to the system, on the system side of the 80°F (27°C) or so depending on the location of piping (in-
tank isolation valve. doors or outdoors).
3. Calculate the static pressure difference • The total volume of water in the system, Vs , including all
∆Ps,CPP → PRV from the CPP to the connection point of the piping and vessels.
pressure relief valve. This is simply the elevation difference • The precharge pressure Pi and the maximum pressure Pmax
between the two (for pressure in units of feet of water) and may determined previously.
be positive (CPP above PRV) or negative (CPP below PRV). Tank volume also may be selected from fundamental equa-
4. If the relief valve is downstream of the CPP, calculate the tions such as Equations 5 and 6, 2 which apply to
frictional pressure drop ∆Pf ,CPP → PRV from the CPP to the bladder/diaphragm type tanks:
relief valve when the pump is on. (This term is ignored if the Va ≥ Ve
relief valve is upstream of the CPP because maximum pressure
v 
will need to be maintained even when the pump is off.) ≥ Vs  h − 1 (5)
5. Calculate the pressure relief valve setpoint Prv as:  vc 
Prv = Pma + ∆Ps,CPP →PRV − ∆Pf ,CPP →PRV (3) Ve
Vt ≥
For most single-story systems, 30 psig (207 kPa) is com- 1 − (Pa + Pi ) (Pa + Pmax ) (6)
monly used as the relief valve setpoint even when the above where
calculation results in a larger value. This is the standard rating Vt = the tank volume
of many low-pressure boilers, although most boilers are avail- Va = the tank “acceptance” volume. This is the capacity of
able at higher pressure ratings (e.g., 60 psig [414 kPa]) at low the bladder (for bladder tanks) or the volume of the waterside
or no cost. of the tank when the diaphragm is fully extended (for dia-
6. Calculate the static pressure difference phragm tanks). With so-called “full acceptance” tanks, the blad-
∆Ps, PRV →tank from the connection point of the pressure relief der can open to the full shape of the tank, so the tank’s

March 2003 ASHRAE Journal 5


acceptance volume and total volume, Vt , are equal. Point A
Ve = the increase in volume of water as it expands from its
minimum temperature to its maximum temperature.
vc = the specific volume of water at the minimum tempera- 15 ft
ture, Tc. (4.6 m)
Point C
vh = the specific volume of water at the minimum tempera- Point B
ture, Th.
Equation 5 ensures that the acceptance volume Va exceeds Boiler
Pump
the expanded water volume Ve to avoid damage to the bladder
or diaphragm when the system is at its highest temperature and Figure 3: Typical system in a single story building.
pressure. Equation 6 ensures that the tank volume Vt is suffi-
cient for both the expanded water Ve and the air cushion neces- chiller and the expansion tank, Point B.
sary to maintain pressures in the tank between Pi and Pmax . 3. The static pressure difference ∆Ps,CPP → PRV from the CPP
Equation 6 conservatively ignores the expansion of the sys- to the pressure relief valve is zero since they are at the same
tem piping since the resulting increase in volume is relatively elevation.
small and the calculation is complicated in systems with vari- 4. The relief valve (Point B) is downstream of the CPP (Point
ous piping materials, each with different coefficients of ex- C). ∆Pf ,CPP → PRV is the roughly equal to pump head (80 ft or
pansion. 35 psi [241 kPa]).
Specific volume at various temperatures is shown in Table 1. 5. The pressure relief valve setpoint Prv is then:
Prv = Pma + ∆Ps,CPP →PRV − ∆Pf ,CPP →PRV
Examples = 125 + 0 − 35
Example 1: Chilled Water System = 90 psig
Assume the system is a chilled water system with a design This setting assures that the pressure at the discharge side of
chilled water temperature of 40°F and system volume of 1,000 the pump will not exceed 125 psig (862 kPa). If the relief valve
gallons (3785 L). The layout is as shown in Figure 1 with the setpoint were 125 psig (862 kPa), the pressure downstream of
pump at the bottom of a multistory building. Pump head is 80 the pump could be as high as 160 psig (1100 kPa), possibly
ft (240 kPa). above the equipment rating.
First calculate the initial precharge pressure Pi . Since the 6. The static pressure difference ∆Ps, PRV →tank from the re-
system is chilled water, there is no concern about net positive lief valve to the tank is zero since they are at the same location.
suction head, so only Step A needs to be followed: 7. The frictional pressure drop ∆Pf , PRV →tank from the re-
1. The LPP in the system is the highest point on the return lief valve to the tank is zero since they are at the same location.
line just as it drops down to the pump (Point A in Figure 1). 8. The tank maximum gauge pressure Pmax is:
2. Pmin is 4 psig (28 kPa) as shown in Figure 2. Pmax = Prv + ∆Ps, PRV →tank − ∆P f , PRV →tank
3. The tank will be the smallest and least expensive if lo- = 90 + 0 − 0
cated near the LPP. However, for this example, assume the tank = 90 psig
is located near Point B at the pump suction, which is often the The tank minimum volume (assuming a maximum tempera-
most convenient location since space is usually available. ture of 80°F (27°C) with specific volume values taken from
4. The static pressure rise ∆Ps, LPP →tank from the LPP to the Table 1) is then calculated as:
tank is 100 ft (or 100/2.31= 43 psi [296 kPa]). Va ≥ Ve
5. The frictional pressure drop ∆Pf ,tank→ LPP from tank to v 
the LPP is taken as zero since the tank is downstream of the ≥ Vs  h − 1
LPP.  vc 
6. The minimum tank initial or precharge gauge pressure Pi  0.01608 
≥ 1000 − 1
is:  0 .01602 
Pi = Pmin + ∆Ps, LPP →tank + ∆Pf ,tank→LPP ≥ 3 .75 gallons
= 4 + 43 + 0
3.75
= 47 psig (324 kPa) Vt ≥
Now find the maximum pressure: 1 − (Pa + Pi ) Pa + Pmax
1. The standard pressure rating of all components in the 3. 75

system will be 125 psig (862 kPa) or higher. Hence Pma is 1 − (14.7 + 47) (14.7 + 90)
taken as 125 psig (862 kPa) and the CPP is the lowest point in
the system on the discharge side of the pump, Point C. ≥ 9.1 gallons
2. Assume the pressure relief valve will be located near the Hence, the expansion tank must have an acceptance volume
6 ASHRAE Journal ashrae.org March 2003
Hydronic

greater than 3.75 gallons (14 L) and an overall volume greater be the larger of that required to prevent boiling and that re-
than 9.1 gallons (34 L). quired to maintain adequate net positive suction head at the
pump. The pressure required to prevent boiling is determined
Example 2: Chilled Water System as:
Assume the system is as in Example 1, but instead of locat- 1. The LPP in the system is the highest point on the return
ing the tank at the pump, assume it is located at the LPP (Point line just after it drops down to the pump (Point A in Figure 3 ).
A). The precharge pressure would then be calculated as (start- 2. Pmin is recommended to be 70 psig (482 kPa) as shown in
ing at Step 4): Figure 2. If there are control valves located near the LPP, the
4. The static pressure rise ∆Ps, LPP →tank from the LPP to the minimum pressure may need to be higher. 1
tank is zero since the tank is located at this point. 3. For this example, assume the tank is located near Point B
5. The frictional pressure drop ∆Pf ,tank→ LPP from the tank at the pump suction.
to the LPP is zero since the tank is located at this point. 4. The static pressure rise ∆Ps , LPP →tank from the LPP to the
6. The minimum tank initial or precharge gauge pressure Pi is: tank is 15 ft (or 15/2.31= 6.5 psi [45 kPa]).
5. The frictional pressure drop ∆Pf ,tank → LPP from the tank
Pi = Pmin + ∆Ps, LPP →tank + ∆Pf ,tank→LPP
to the LPP is taken as zero since the tank is downstream of the
=4+0+0 LPP.
= 4 psig 6. The minimum tank initial or precharge gauge pressure Pi
is:
Now find the maximum pressure (starting at Step 6): Pi = Pmin + ∆Ps, LPP →tank + ∆Pf ,tank→LPP
6. The static pressure difference ∆ Ps , PRV →tank from the re-
= 70 + 6.5 + 0
lief valve to the tank is –100 ft (or –100/2.31= –43 psi [–296 = 76.5 psig
kPa]). It is negative since the PRV is below the tank.
The initial pressure must also be sufficient to maintain the
7. The frictional pressure drop ∆Pf , PRV →tank from the re-
required net positive suction head (NPSHr) at the pump inlet:
lief valve to the tank is taken as zero since the tank is upstream
1. The required net positive suction head (NPSHr) is 5 ft (or
of the relief valve.
5/2.31 = 2 psi [15 kPa]).
8. The tank maximum gauge pressure Pmax is:
2. The frictional pressure drop ∆Pf ,tank → suction from the
Pmax = Prv + ∆Ps, PRV →tank − ∆P f , PRV →tank tank to the pump suction is zero since the tank is located at the
= 90 − 43 − 0 pump suction.
= 47 psig 3. The gauge vapor pressure of the fluid Pv is 53 psig (365
kPa) per Figure 2.
The tank volume is then calculated as:
4. The static pressure difference ∆Ps,tank → suction from the
3. 75 tank to the pump suction is zero since the tank is located at
Vt ≥
1 − (Pa + Pi ) (Pa + Pmax ) this point.
5. Assume velocity pressure difference ∆PV ,tank → suction is
3.75 negligible.

1 − (14. 7 + 4) (14.7 + 47) 6. Calculate the minimum tank initial or precharge gauge
pressure Pi as:
≥ 5.4 gallons
Pi = NPSHr + ∆P f ,tank→suction + Pv − ∆Ps,tank→ suction
As in Example 1, the expansion tank must have an accep- − ∆PV ,tank → suction
tance volume greater than 3.75 gpm (0.24 L/s) (the volume of = 2 + 0 + 53 − 0 − 0 (2)
expanded water is unchanged), but the total volume required = 55 psig
falls to 5.4 gallons (20 L). This demonstrates that a tank lo- This pressure is lower than that required to prevent boiling
cated at the LPP in a multi-story system is smaller and there- at the LPP, so it may be ignored. As noted above, this is typi-
fore less expensive than a tank located at the pump suction cally the case unless the pump is a long distance from the
(Example 1). expansion tank or located well above the tank.
Now find the maximum pressure:
Example 3: High Temperature Hot Water System
1. The standard pressure rating of all components in the
Assume the system is a high temperature hot water system
system will be 125 psig (862 kPa) or higher. Hence Pma is
with a design hot water temperature of 300°F (149°C) and
taken as 125 psig and the CPP is the lowest point in the system
system volume of 1,000 gallons (3785 L). The pumps’ required
on the discharge side of the pump, Point C.
NPSHr is 5 ft (15 kPa) and its head is 50 ft (150 kPa). The
2. The pressure relief valve will be located at the boiler.
layout is horizontal as shown in Figure 3.
3. The static pressure difference ∆Ps,CPP → PRV from the CPP
First calculate the initial precharge pressure Pi , which will
March 2003 ASHRAE Journal 7
to the pressure relief valve is zero since they are roughly at the
same elevation.
4. The relief valve (at the boiler) is downstream of the CPP
(Point C). ∆Pf ,CPP → PRV is the then approximately equal to
pump head (50 ft or 22 psi [152 kPa]).
5. The pressure relief valve setpoint Prv is then:
Prv = Pma + ∆Ps,CPP →PRV − ∆Pf ,CPP →PRV
= 125 + 0 − 22
= 103 psig
6. The static pressure difference ∆Ps, PRV →tank from the re-
lief valve to the tank is zero since they are roughly at the same
elevation.
7. The frictional pressure drop ∆Pf , PRV →tank from the re-
lief valve to the tank may be ignored since they are near the
same location.
8. The tank maximum gauge pressure Pmax is:
Pmax = Prv + ∆Ps, PRV →tank − ∆P f , PRV →tank
= 103 + 0 − 0
= 103 psig
The tank minimum acceptance volume (assuming a mini-
mum temperature of 60°F [16°C] with specific volume values
taken from Table 1) is then calculated as
Va ≥ Ve
v 
≥ Vs  h − 1
v
 c 
 0.01745 
≥ 1000 − 1
 0 .01604 
≥ 88 gallons
88
Vt ≥
1 − (Pa + Pi ) (Pa + Pmax )
88
Vt ≥
1 − (14.7 + 76.5) (14.7 + 103)

≥ 390 gallons

Hence, the tank must have an acceptance volume 88 gallons


(333 L) or larger and a total volume 390 gallons (1476 L) or
larger.
As a home exercise, redo the above calculations with the
tank at the pump discharge, Point C. You will find that the
precharge pressure increases while all other variables remain
the same, resulting in a somewhat larger tank. Nevertheless,
the tank will still meet all of its intended functions so this is a
perfectly acceptable, if unusual, location.

References
1. Carlson, B. 2001. “Avoiding cavitation in control valves.”
ASHRAE Journal 43(6):58–63.
2. 2000 ASHRAE Handbook—HVAC Systems and Equip-
ment.
8 ASHRAE Journal ashrae.org March 2003

You might also like