Controlling and monitoring system
for the
ROLLER PRESS
Plant/Client:
El Brocal
Peru
Contract No.:
B.03.0731.3.001
486051418.doc
ROLCOX 20.03.2012
486051418.doc
page: 2 of 20
List of content
1 SCADA OUTPUT...................................................................................................................................... 3
2 SCADA INPUT.......................................................................................................................................... 6
6 SCADA: CRT: Status indication field for groups and input field "Switches".................................19
7 Limit values............................................................................................................................................. 20
ROLCOX 20.03.2012
486051418.doc
page: 3 of 20
1 SCADA OUTPUT
1.1 SCADA to PLC ROLCOX: PARAMETER Roller Press
PARAMETER
PLC ROLCOX input
DB 41 Description Range PWL
DBW2 Op.pressure 30 - 150 bar
DBW4 Op.pressure increase max 10 - 99 bar
DBW6 Pressure ratio (10*) 0.0 - 8.0 bar/mm
DBW8 Pressure tolerance +/- 5 - 25 bar
DBW14 Pressure difference max (x) 20 - 70 bar
DBW16 Bearing distance Lmin (x) (10*) 1.0 - 12.0 mm
DBW18 Press.corr. Factor K3 0 - 100 %
DBW20 Gap setpoint ( L2 ) (x) (10*) 15.0 - 35.0 mm
DBW22 Gap difference permit (x) (10*) 2.0 - 7.0 mm
DBW24 Roller distance L/R min (x) (10*) 0.0 - 30.0 mm
DBW26 Grease distrib. pulsrate (x) 10 - 200 pulses/h
DBW28 Pressure incr. delay time (x) 0 - 180 sec
DBW30 Prop. Valves, P-highpoint 0 - 100 %
DBW32 Prop. Valves, P-low, lowpoint 0 - 100 %
DBW34 Prop. Valves, P-low, highpoint 0 - 100 %
DBW46 Bear.distance L2increase (x) (10*) 5.0 - 20.0 mm
DBW48 Excess current, drives (x) 900 - 1150 A
DBW50 Operation current, drives (x) 700 - 900 A
DBW52 Current difference, drives (x) 50 - 200 A
DBW54 Setpoint pre-bin level max 20 - 95 %
DBW56 Setpoint pre-bin level min 2 - 50 %
DBW58 Setpoint feed regulating gate (10*) 0 - 100 %
DBW60 Hysteresis for feed regulating gate (10*) 1-5 %
DBW62 Heater off, tank oil lubrication 30 - 50 °C
DBW64 Heater on, tank oil lubrication 25 - 40 °C
DBW66 5312MD1.J01 Power fixed roll 0 - 1000 kW
DBW68 5312MD2.J01 Power move roll 0 - 1000 KW
DBW70 5312MD1.I01 Current fixed roll 0 - 1000 A
DBW72 5312MD2.I01 Current move roll 0 - 1000 A
DBW74 Temperature recycle material 0
DBW76 Humidity fresh feed 0
DBW78 Fresh feed total 0
DBW80 Signal from metal detector 0
DBW82 Siganl flap to metal container 0
DBW84 Recycle feed total 0
Definition (10*): value will be transferred with factor 10; for example value 10.0 = 100
CONTROL SIGNAL 1
PLC ROLCOX input
DB 41 Bit Description
DBX1 0 DI=Pl > Manual pressure increase left 1)
(F44.0)
1 DI=Pl < Manual pressure decrease left 1)
(F44.1)
2 DI=Pr > Manual pressure increase right 1)
(F44.2)
3 DI=Pr < Manual pressure decrease right 1)
(F44.3)
4 DI=Pl+r > Manual pressure increase left + right 1)
(F44.4)
5 DI=Pl+r < Manual pressure decrease left + right 1)
(F44.5)
6 DI=PCON Pressure controller automatic /manual 1)
(F44.6)
7 DI=BLC Shut-off gate, controller on 1)
(F44.7)
DBX0 0 DI=ALR Alarm acknowledgement 1)
(F45.0)
1 Spare
2 Spare
3 Spare
4 Spare
5 Spare
6 DI=WATCHDOG Ind. Ethernet Watchdog SCADA (F45.6)
7 Spare (F45.7)
1)
Definition of signals: The command will be executed, when the signal is 1.
The execution stops, when the signal is 0.
2)
The command will be executed, when the signal is 1.
The reverse action will be executed, when the signal
is 0.
3)
Upon receive of this signal (1) from SCADA the
corresponding watchdog signal from ROLCOX will
be set (1) and provided for SCADA. This signal shall
then be inverted (0) in SCADA. Consequently, the
watchdog signal from ROLCOX will also be inverted
(0).
ROLCOX 20.03.2012
486051418.doc
page: 5 of 20
RETURN SIGNALS 1
PLC ROLCOX input
DB 41 type Description
DBX 100.0 BOOL Lubr_comm Command for Lubrication system group – start/stop
DBX 100.1 BOOL RP_comm Command for Roller press group – start/stop
DBX 100.2 BOOL Loc_oper Permission for local operation ( Roller press group )
DBX 100.3 BOOL GAP_ALR Alarm reset local
DBX10 0.4 BOOL R_5312MD1.M01 Return signal, main motor fixed roll
DBX 100.5 BOOL R_5312MD2.M01 Return signal, main motor move. roll
DBX 100.6 BOOL R_5312LQ1.M01 Return signal, motor gear oil pump fixed roll
DBX 100.7 BOOL R_5312LQ2.M01 Return signal, motor gear oil pump move. roll
DBX 101.0 BOOL R_5312LQ3.M01 Return signal, motor grease pump
DBX 101.1 BOOL R_5312HD1.M01 Return signal, motor hydraulic pump
DBX 101.2 BOOL Loc_oper_oil Permission for local operation (Oil lubrication group)
DBX 101.3 BOOL R_5312HD1.H01 Return signal, tank heater, hydraulic oil tank
DBX 101.4 BOOL R_5312LQ4.H01 Return signal, tank heater, oil lubr. system
DBX 101.5 BOOL TRANSP_R Material discharge on – return signal
DBX 101.6 BOOL R_5312SG2.M01_cl_on1 Return signal, feed regulating gate, closing on
DBX 101.7 BOOL R_5312SG2.M01_opn_on1 Return signal, feed regulating gate, opening on
DBX 102.0 BOOL R_5312LQ4.M01 Return signal, motor for circulation pump
DBX 102.1 BOOL R_5312LQ5.M01 Return signal, motor for feed pump
DBX 102.2 BOOL R_5312MX1.M01 Return signal, motor for stirrer
DBX 102.3 BOOL R_5312FN01.M01 Return signal, lube oil cooler FR
DBX10 2.4 BOOL R_5312FN02.M01 Return signal, lube oil cooler MR
DBX 102.5 BOOL R_5312FN03.M01 Return signal, oil to air cooler
DBX 102.6 BOOL Spare
DBX 102.7 BOOL Spare
2 SCADA INPUT
2.1 PLC ROLCOX to SCADA: MEASURING DATA
MEASURING DATA
PLC ROLCOX output
DB 40 Description Range
DBW28 5312RP1.G01 Bearing distance left (10*) 0.0 - 100.0 mm
DBW30 5312RP1.G02 Bearing distance right (10*) 0.0 - 100.0 mm
DBW32 5312HD1.P02 Hydraulic pressure left 0 - 400 bar
DBW34 5312HD1.P03 Hydraulic pressure right 0 - 400 bar
DBW36 5312MD1.J01 Power FR drive 0 - 1000 KW
DBW38 5312MD2.J01 Power MR drive 0 - 1000 KW
DBW40 5312FB1.W01 Level pre-bin roller press 0 - 100 %
DBW42 5312RP1.T11 Bearing temp. MR drive site (10*) -20.0 ..+100.0 °C
DBW44 5312RP1.T12 Bearing temp. MR non drive site (10*) -20.0 ..+100.0 °C
DBW46 5312RP1.T01 Bearing temp. FR non drive site (10*) -20.0 ..+100.0 °C
DBW48 5312RP1.T02 Bearing temp. FR drive site (10*) -20.0 ..+100.0 °C
DBW50 5312LQ2.T01 Gear box bearing temp. MR (10*) -20.0 ..+100.0 °C
DBW52 5312LQ1.T01 Gear box bearing temp. FR (10*) -20.0 ..+100.0 °C
DBW54 Spare
DBW56 Spare
DBW58 Spare
DBW60 5312SG2.G01 Feed regulating gate (10*) 0.0 - 100.0 %
DBW62 Spare
DBW62 5312LQ4.T02 Temp. Oil lubrication tank (10*) -20.0 ..+100.0 °C
DBW66 5312LQ5.T04 Temp. in front of bearings- left (10*) -20.0 ..+100.0 °C
DBW68 Spare
DBW70 Spare
DBW72 5312LQ5.T06 Oil temp behind oil to air cooler -20.0 ..+100.0 °C
(10*)
DBW74 Spare
DBW76 5312MD1.I01 Current FR drive 0 - 1000 A
DBW78 5312MD2.I01 Current MR drive 0 - 1000 A
DBW80 5312HD1.T01 Temp. Hydraulic oil tank (10*) 0.0 ..+100.0 °C
DBW82 5312LQ5.T05 Temp. in front of bearings- right (10*) -20.0 ..+100.0 °C
DBW84 5312LQ4.T03 Temp. return line to tank (10*) -20.0 ..+100.0 °C
DBW86 5312RP1.S11 Speed movable roll (10*) 0.0 ... 21.0 1/min
DBW88 5312RP1.S01 Speed fixed roll (10*) 0.0 ... 21.0 1/min
Definition (10*): value will be transferred with factor 10; for example value 10.0 = 100
ROLCOX 20.03.2012
486051418.doc
page: 7 of 20
Definition (10*): value will be transferred with factor 10; for example value 10.0 = 100
ROLCOX 20.03.2012
486051418.doc
page: 8 of 20
STATUS SIGNAL 1
PLC ROLCOX output
DB 40 Bit Description
DBX127 0 DO=PCON Pressure controller automatic on (F46.0)
1 DO=PACT Pressure controller active (F46.1)
2 DO=BIN Shut-off gate, controller on (F46.2)
3 DO=WD Ind. Ethernet Watchdog ROLCOX 1) (F46.3)
4 DO=ALARM General alarm (F46.4)
5 RP_NSTOP RP Normal stop (F46.5)
6 RP_FASTSTOP RP Fast stop (F46.6)
7 RP_Emergency stop ROLCOX local panel ( +V4 ) (F46.7)
DBX126 0 DO=GAP_ALARM GAP_ALARM ( +V4 ) (F47.0)
1 DO=RP RUN Release Material transport (RP run) (F47.1)
2 DO=RP AVAIL Roller Press available (F47.2)
3 Spare (F47.3)
4 Spare (F47.4)
5 Spare (F47.5)
6 Spare (F47.6)
7 Spare (F47.7)
These signals are provided for indication on client’s operator’s station and interlocking.
3)
Definition of signals: Upon receive of this signal (1) from SCADA the
corresponding watchdog signal from ROLCOX will
be set (1) and provided for SCADA. This signal shall
then be inverted (0) in SACDA. Consequently, the
watchdog signal from ROLCOX will also be inverted
(0).
ROLCOX 20.03.2012
486051418.doc
page: 9 of 20
PICTURE SIGNAL 1
PLC ROLCOX output
DB 40 Bit Description
DBX19 0 DO=PCON Pressure Controller automatic on
1 DO=PCACT Pressure Controller active
2 DO=BIN Shut off gate automatic on
3 Spare
4 DO=ALARM General alarm
5 Spare
6 GRO/OFF Group Roller press off
7 F 109.4 Group Roller press runs
DBX18 0 GRO/ONAC Group Roller press on active
1 GRO/ONRO Group Roller press delay off
2 GRO/LOC Group Roller press local
3 GR1/OFF Group Aux. heater off
4 F 57.4 Group Aux. heater runs
5 GR1/ONAC Group Aux. heater on active
6 GR1/ONRO Group Aux. heater delay off
7 GR1/LOC Group Aux. heater local
ROLCOX 20.03.2012
486051418.doc
page: 14 of 20
PICTURE SIGNAL 2
PLC ROLCOX output
DB 40 Bit description
DBX21 0 5312MD1.M01_R Main motor FR on
1 5312MD1.M01_FLT Trouble Main drive FR
2 5312MD2.M01_R Main motor MR on
3 5312MD2.M01_FLT Trouble Main drive MR
4 5312LQ1.M01_R Gear oil pump FR on
5 5312LQ1.M01_FLT Trouble Gear oil pump FR
6 5312LQ2.M01_R Gear oil pump MR on
7 5312LQ2.M01_FLT Trouble Gear oil pump MR
DBX20 0 5312LQ3.M01_R Grease barrel pump labyrinth sealing on
1 5312LQ3.M01_FLT Trouble Grease barrel pump labyrinth sealing
2 5312HD1.M01_R Hydraulic pump on
3 5312HD1.M01_FLT Trouble Hydraulic pump
4 5312LQ4.H01_R Heater oil lubrication system – tank on
5 5312LQ4.H01_FLT Trouble Heater oil lubrication system - tank
6 5312LQ4.M01_R Circulation pump, oil lubrication system on
7 5312LQ4.M01_FLT Trouble Circulation pump, oil lubrication system
ROLCOX 20.03.2012
486051418.doc
page: 15 of 20
PICTURE SIGNAL 3
PLC ROLCOX output
DB 40 Bit description
DBX23 0 5312LQ5.M1_R Feed pump, oil lubrication system on
1 5312LQ5.M1_FLT Trouble Feed pump, oil lubrication system
2 5312MX1.M1_R Stirrer, oil lubrication system on
3 5312MX1.M1_FLT Trouble stirrer, oil lubric. system
4 5312HD1.H1_R Hydraulic oil tank heater on
5 5312HD1.H1_FLT Trouble, hydraulic oil tank heater
6 5312SG2.V1_STAT Shut off gate opened
7 5312SG2.V1_FLT Trouble shut off gate
DBX22 0 5312HD1.V05 Solen. valve pressure decrease left
1 5312HD1.V06 Solen. valve pressure decrease right
2 5312HD1.V07 Solen. valve retraction cylinder
3 5312HD1.V09 Bypass valves hydraulic system - left
4 5312HD1.V10 Bypass valves hydraulic system - right
5 5312LQ5.V2 Valve bypass bearing right
6 5312LQ5.V3 Valve bypass bearing left
7 5312LQ5.V1 Solen. valve bypass behind feed pump
1)
Valve type is "fail open" (closed when energized).
ROLCOX 20.03.2012
486051418.doc
page: 16 of 20
PICTURE SIGNAL 4
PLC ROLCOX output
DB 40 Bit description
DBX25 0 5312HD1.V8 Emergency-off valve
1 F 53.0 SCADA: Grease flow at pump
2 F 53.1 SCADA: Grease flow progressive distributor left
3 F 53.2 SCADA: Grease flow progressive distributor right
4 5312HD1.V11 Bypass valves hydraulic system – left – 2. set -
5 5312HD1.V12 Bypass valves hydraulic system – right – 2. Set -
6 5312SG2.M1_LL Feed regulating gate
7 5312SG2.M1_HH Feed regulating gate
DBX24 0 5312LQ3.H1/2_C Aux. trace oil heater on
1 5312LQ5.H1/3_C Aux. trace grease heater on
2 F 36.0 Prop. valve, flow control left, close
3 P_DECR_L Flag: pressure decrease left
4 P_INCR_L Flag: pressure increase left
5 F 35.7 Prop. valve, flow control right, close
6 P_DECR_R Flag: pressure decrease right
7 P_INCR_R Flag: pressure increase right
PICTURE SIGNAL 5
PLC ROLCOX output
DB 40 Bit description
DBX27 0 5312FN01.M01_R Fan gear lubrication FR on
1 5312FN01.M01_FL Trouble, fan gear lubrication FR
T
2 5312FN02.M01_R Fan gear lubrication MR on
3 5312FN02.M01_FL Trouble, fan gear lubrication MR
T
4 5312FN03.M01_R Fan oil to air cooler on
5 5312FN03.M01_FL Trouble, fan oil to air cooler
T
6 Spare
7 Spare
DBX26 0 Spare
1 Spare
2 Spare
3 Spare
4 Spare
5 Spare
6 Spare
7 Spare
ROLCOX 20.03.2012
486051418.doc
page: 17 of 20
START SIGNALS 1
PLC ROLCOX OUTPUT
DB 40 type Description
DBX 100.0 BOOL C_5312MD1.M01 5312MD1.M01 Start order from
ROLCOX
DBX 100.1 BOOL C_5312MD2.M01 5312MD2.M01 Start order from
ROLCOX
DBX 100.2 BOOL C_5312LQ1.M01 5312LQ1.M01 Start order from
ROLCOX
DBX 100.3 BOOL C_5312LQ2.M01 5312LQ2.M01 Start order from
ROLCOX
DBX 100.4 BOOL C_5312HD1.M01 5312HD1.M01 Start order from ROLCOX
DBX 100.5 BOOL C_5312LQ3.M01 5312LQ3.M01 Start order from
ROLCOX
DBX 100.6 BOOL C_5312LQ3.H01/02 5312LQ3.H01/H02 Start order from ROLCOX
DBX 100.7 BOOL RELMAT Release material transport
DBX 101.0 BOOL RPAVAILA Roller press available
DBX 101.1 BOOL GENFAULT General fault
DBX 101.2 BOOL GAP_ALARM GAP alarm
DBX 101.3 BOOL C_5312SG2.M01_close Feed regulating gate, end limit – close -
DBX 101.4 BOOL C_5312SG2.M01_open Feed regulating gate, end limit – open -
DBX 101.5 BOOL C_5312MX1.M01 5312MX1.M01 Start order from
ROLCOX
DBX 101.6 BOOL C_5312LQ5.M01 5312LQ5.M01 Start order from
ROLCOX
DBX 101.7 BOOL C_5312LQ4.M01 5312LQ4.M01 Start order from
ROLCOX
DBX 102.0 BOOL C_5312LQ5H01/02/03 5312LQ5.H01/02/H03 Start order from ROLCOX
DBX 102.1 BOOL C_5312LQ4.H01 5312LQ4.H01 Start order from ROLCOX
DBX 102.2 BOOL C_5312HD1.H01 5312HD1.H01 Start order from
ROLCOX
DBX 102.3 BOOL C_5312FN01.M01 5312FN01.M01 Start order from
ROLCOX
DBX 102.4 BOOL C_5312FN02.M01 5312FN02.M01 Start order from
ROLCOX
DBX 102.5 BOOL C_5312FN03.M01 5312FN03.M01 Start order from
ROLCOX
DBX 102.6 BOOL Spare
DBX 102.7 BOOL Spare
Output definition:
manual / off / stop flag = 0
automatic / on / start flag = 1
The function shall be executed (output flag = 1) as long as the template at the
display is selected with the mouse curser and the mouse button is pressed.
6 SCADA: CRT: Status indication field for groups and input field "Switches"
The status text shall be indicated in the respective area at the display.
ROLCOX 20.03.2012
486051418.doc
page: 20 of 20
7 Limit values
LIMIT VALUES
PLC ROLCOX output
description value
PLC Gap difference max. (10*) 14,0 mm
PLC Bearing temp. move./fixed roll H 55 °C
PLC Bearing temp. move./fixed roll HH 60 °C
PLC Gear box bearing temp. move./fixed roll H 85 °C
PLC Gear box bearing temp. move./fixed roll HH 100 °C
PLC Hydraulic oil temp. H 60 °C
PLC Hydraulic oil temp. HH 70 °C
PLC Lube oil temp. ( tank ) LL 10 °C
PLC Lube oil temp. ( tank ) L 30 °C
PLC Lube oil temp. ( tank ) H 55 °C
PLC Lube oil temp. ( tank ) HH 60 °C
PLC Lube oil temp. roller bear. left/right L 25 °C
PLC Lube oil temp. roller bear. left/right H 30 °C
PLC Hydraulic pressure min. left/right 30 bar
Limits are included within the ROLCOC program, and will not be transferred