Will Edwards
(SEL Engineering Services Division)
65
64
Simulation
Frequency (Hz)
63
62 Field
61
60
59
0 10 20 30 40
Time (s)
Control Cost, Quality, and Features
Hardware-in-the-Loop Testing
Frequency Governor Frequency
Controller (pu) Set Point
Status
Steady-State
Droop Line
Inputs
Dynamic 1.0
Controller Simulation 0.96
System
Outputs
Transient Governor
Behavior
Power
Controls
(pu)
1.0
Both Mechanical and Electrical Systems Must Be Modeled Accurately
Inverter-Based Generation Has
Limited Overload Capacity
Q Long-Term
Capacity Limit
Q
P P
Inverter-Based
Rotating Generators Short-Term
Generation
Capacity Limit
Load Balancing Must Happen FASTER
With Inverter-Based Generation
Power
Rotating Generation Power
Frequency
Load
Power, Frequency
Inverter-Based Power
Inverter-Based Frequency
Time
FAST Load Shedding Prevents Blackouts
Grid-Tied Controller
Operation
Automatic
Decoupling
Synchronization
Systems
Load
Shedding Relay
Islanded Subcycle
Operation FAST!
Status Trip
SEL Controllers Take Action FASTER
Process Control Systems
PLC Solutions
Protection, Automation, Controls, and Security
Layer 4
Outside Visualization, Economic Business
Security Gateway
Networks Optimization, Engineering Tools Systems
Layer 3
Control
Central Controllers
Systems
Layer 2
Communications Equipment
Communications
Layer 1
Protective Metering and Protection
Remote I/O
Relays Power Quality and Metering
Layer 0
Microgrid or
Current and Power Generation
Circuit Breakers Macrogrid
Voltage Transformers Controllers
Security for Critical Infrastructure
• Avoid OS and software
• Made in the USA
• Mature processes
• Vertical integration
• Cybersecurity
Generation Runback Philosophy
Runback Reference Valve
Speed Valve
Speed Control
Reference Control
Runback
Speed Feedback Selector
MW
60 MW Contingency Detected (breaker trips)
(actual load) Signal Sent by
Maximum Runback Generation-Shedding
MW Set Point System
t
Seamless Islanding and Decoupling Systems
DFDT (Hz/s)
+81RFRP
Trip Region 1
0.2
–81RFDFP –0.1
DF (Hz)
0.1 +81RFDFP
–0.2
Trip Region 2
–81RFRP
System Synchronization
Safely Reconnecting Islanded Grids
Inertia-Compensated Load Shedding MW Load to Shed
F
Do It Right! DFDT
59 58
F < 0.5 2
4 4
8
Normal Operation
60 0.5 to
4
8 8
12
1.0
Inertia-Compensated
> 1.0 8
12 12
16
Success
59 Macrogrid
Load
Shed
58 F1 F2
57 T Complex Grid
Blackout
L1 L2 L3
Load Shed ~ H • DFDT = 8 • 1 = 8 MW
F1 F1 F2
Load Shed ~ H • DFDT = 4 • 2 = 8 MW
Load Tracking – Add Your H’s
Discriminate Islands With Time
F
Macrogrid
60
T = 0.1 s
F1 F2 T = 0.3 s
59
Complex Grid 58
L1 L2 L3 57 T
F1 F1 F2
Protection Must ADAPT
To Changing Fault Conditions
t
• Fault levels DER
• Grounding
I
• Directions 2,000 20,000
• Impedances Relay
20,000
2,000
Physics Are the Same – Big or Small
Import: 471 GWh
Sokhumi
Export: 931 GWh
Large
Enguri
Hydro
Generation
Menji Zestafoni Load Center
Ksani
T’BILISI
Akhaltsikhe
Batumi
Thermal
Gardabani
Generation
Physics Are the Same – Simple or Complex
Borrego Microgrid
SEL-351
Relay SEL-351
Relay
69 kV
SEL-351
Relay SEL-351
Relay
G1 G2
Automation V Relay
SEL-351 V Relay
SEL-351
1 MW SEL-3530-4
SEL-351
Relay Battery Controller
System
12 kV
SEL-351
Relay 1 2 3 4 5 Relay
SEL-351 SEL-351 Relay Relay
SEL-351 Relay
SEL-351
V V V V
Navy Seabees, U.S. Navy
Portable Microgrid Controls, Protection, and Security
WAN
Security HMI
Gateway
Utility PCC Diesel Photovoltaic Wind Turbines
Generators Solar Cells
Computer
Computer
Serial HMI
Data Portable Control Center
Diode Microgrid
Clamp-On SEL-849
Relay SEL-3530-4
RTAC
CTs for Controls Portable Control Center
Monitoring
Key Points
of Grid Relay
SEL-849
Protection SEL-849
Relay
Meter and I/O
SEL-849
Relay
Monitoring
and
Synchronous Condenser Monitoring Communication
Dispatch
and Flywheel and Tesla Three-Phase Power
Dispatch Battery
CT and PT
Rugged and Economical for Restricted Budgets
• Load shedding
• Voltage / VAR optimization
• Frequency / power dispatch
• Autosynchronization
Saint Paul • Decoupling
Island
• Comprehensive HIL testing
Detroit
Vacaville
Denver King of
St. Louis Columbus Prussia
Irvine
Charlotte
Phoenix
Atlanta
Tampa
Houston
Distribution Chattanooga Electric Power Board
Automation
NO
Closed
Open
NO NO Normally Open
NO NO
AEP Ohio
Mississippi
DAC System
Questions?