You are on page 1of 4



1- 9ESES01 (Q2,Q3)

1-1 I fl = S/(sqrt(3)*V) = 2500/(sqrt(3)*6.6) =219 A

1-2 I max = 219 * 1.25 = 273.75 A

1-3 CT : 250 / 1 A 15 VA 5P20

1-4 I max.sec = 273.75 / 250 = 1.095

1-5 Relay :

1-5-1 Manufacturer : Square D

1-5-2 Model : Sepam Series 40

1-5-3 Function :

1-5-3-1 51P :

1-5-3-1-1 Curve : Extremely Inverse Time

1-5-3-1-2 PU : 1.1 ( Pick up value)

1-5-3-1-3 TM : 2.69 (Time Dial Multiplier)

2- 9ESES01 (Q5)

2-1 I lf = I fl (9ESES01-Q3) – I lf (9ESES01-Q9) = 219 – 38.4 = 180.6 A

Or

I lf = I fl (9ESES01-Q2) – I lf (9ESES01-Q7) = 219 – 12.4 = 206.6 A

So , We take

I lf = 206.6 A

2-2 I max = 206.6 * 1.25 = 258.25 A

2-3 CT : 1000 / 1 A 30 VA 5P20

2-4 I max.sec = 258.25 / 1000 = 0.25825 A

2-5 Relay :

2-5-1 Manufacturer : Square D

2-5-2 Model : Sepam Series 40

;ϭͿ



2-5-3 Function :

2-5-3-1 51P :

2-5-3-1-1 Curve : Extremely Inverse Time

2-5-3-1-2 PU : 0.3 ( Pick up value)

1-5-3-1-3 TM : 1.59 (Time Dial Multiplier)

3- 9ESES01 (Q1,Q4)

3-1 I lf = I lf (motor) + I (starting) + 3 * I (Safe Shutdown)

= 98.4 + 1023/(sqrt(3)*6.6) + 3 * 523/(sqrt(3)*6.6)

= 325 A

3-2 I max = 325 * 1.25 = 406.25 A

3-3 CT : 1000 / 1 A 30 VA 5P20

3-4 I max.sec = 406.25 / 1000 = 0.40625 A

3-5 Relay :

3-5-1 Manufacturer : Square D

3-5-2 Model : Sepam Series 40

3-5-3 Function :

3-5-3-1 51P :

3-5-3-1-1 Curve : Extremely Inverse Time

3-5-3-1-2 PU : 0.4 ( Pick up value)

3-5-3-1-3 TM : 0.44 (Time Dial Multiplier)

3-5-3-2 50P : (If Applicable)

I fmax (Maximum Fault Current at Far End) = 5.16 KA

I (instantaneous.) = 1.75* I fmax = 1.75*5160 = 9030 A (To avoid overreach due to DC


component)

I (inst,sec.) = 9030/1000 = 9.03 A

;ϮͿ



So we set (50P) as follows

3-5-3-2-1 I set = 9.1

3-5-3-2-2 With Zero Time Delay

4- 1ESES01 (Q4)

4-1 I lf = I lf (motor) + I (starting) + 3 * I (Safe Shutdown)

= 98.4 + 1023/(sqrt(3)*6.6) + 3 * 523/(sqrt(3)*6.6)

= 325 A

4-2 I max = 325 * 1.25 = 406.25 A

4-3 CT : 1000 / 1 A 30 VA 5P20

4-4 I max.sec = 406.25 / 1000 = 0.40625 A

4-5 Relay :

4-5-1 Manufacturer : Square D

4-5-2 Model : Sepam Series 40

4-5-3 Function :

4-5-3-1 51P :

4-5-3-1-1 Curve : Extremely Inverse Time

4-5-3-1-2 PU : 0.4 ( Pick up value)

4-5-3-1-3 TM : 0.1 (Time Dial Multiplier)

5- 2ESES01 (Q12)

5-1 I lf = I lf (motor) + I (starting) + 3 * I (Safe Shutdown)

= 98.4 + 1023/(sqrt(3)*6.6) + 3 * 523/(sqrt(3)*6.6)

= 325 A

5-2 I max = 325 * 1.25 = 406.25 A

5-3 CT : 1000 / 1 A 30 VA 5P20

5-4 I max.sec = 406.25 / 1000 = 0.40625 A

;ϯͿ



5-5 Relay :

5-5-1 Manufacturer : Square D

5-5-2 Model : Sepam Series 40

5-5-3 Function :

5-5-3-1 51P :

5-5-3-1-1 Curve : Extremely Inverse Time

5-5-3-1-2 PU : 0.4 ( Pick up value)

5-5-3-1-3 TM : 0.1 (Time Dial Multiplier)

‘…Ž—•‹‘ǣ 
”‘—”˜‡•ƒ†•‡––‹‰˜ƒŽ—•ǡƒ†–ƒ‹‰‹–‘ƒ……‘—––Š‡Š‡”ƒŽƒƒ‰‡—”˜‡‘ˆ
ȋͿ
ͶͷǡͿ
Ͷ͸Ȍ™‡…‘…Ž—†‡–Šƒ–ǣ
•’‹–‡‘ˆ–Š‡ˆƒ…––Šƒ–™‡ƒ†Œ—•––Š‡•‡––‹‰‘ˆͷͶͷȋͺȌƒ†͸Ͷͷȋͷ͸Ȍ–‘„‡ƒ•ˆƒ•–ƒ•’‘••‹„Ž‡ǡ
–‹ŽŽ™‡†‹†ǯ–’”‘˜‹†‡„ƒ…—’‘˜‡”…—””‡–’”‘–‡…–‹‘–‘–Š‡‰‡‡”ƒ–‘”•ȋͿ
ͶͷǡͿ
Ͷ͸ȌǤ
‡…‘‡†ƒ–‹‘•ǣ
‡”‡…‘‡†–Š‡—•‡‘ˆ‘–Š‡”–›’‡•‘ˆ…—”˜‡•–Šƒš–”‡‡Ž› ˜‡”•‡‹‡Ǥ
           