The length of connections between a structural element and the bonding network
does not exceed 50 centimetres and an additional connection should be installed
LQSDUDOOHODWDFHUWDLQGLVWDQFHIURPWKH¿UVW7KHLQGXFWDQFHRIWKHFRQQHFWLRQ
between the earthing bar of the electrical enclosure for a set of equipment and
the bonding network (see below) should be less than one μHenry (0.5 μH, if
possible). For example, it is possible to use a single 50 cm conductor or two parallel
conductors one meter long, installed at a minimum distance from one another (at
least 50 cm) to reduce the mutual inductance between the two conductors.
Where possible, connection to the bonding network should be at an intersection to
GLYLGHWKH+)FXUUHQWVE\IRXUZLWKRXWOHQJWKHQLQJWKHFRQQHFWLRQ7KHSUR¿OHRIWKH
ERQGLQJFRQGXFWRUVLVQRWLPSRUWDQWEXWDÀDWSUR¿OHLVSUHIHUDEOH7KHFRQGXFWRU
should also be as short as possible.