CONVERSION
N O Z Z L E K I T
NOZZLE SELECTION
REFRIGERANT HCFC-22
Evaporator Temperature (°F)
Evaporator
–20°F 0°F 10°F 20°F 30°F
Capacity
Liquid Temperature (°F)
(BTU/HR)
80 60 40 20 80 60 40 20 80 60 40 80 60 40 80 60 40
2000 1/4 1/6 1/9 1/9 1/4 1/6 1/9 1/9 1/6 1/9 1/9 1/6 1/9 1/9 1/6 1/9 1/9
4000 1/2 1/3 1/6 1/6 1/3 1/4 1/6 1/6 1/3 1/4 1/6 1/3 1/6 1/6 1/4 1/6 1/6
6000 3/4 1/2 1/4 1/4 3/4 1/3 1/4 1/4 1/2 1/3 1/4 1/2 1/4 1/4 1/3 1/4 1/4
8000 1 3/4 1/3 1/4 3/4 1/2 1/4 1/4 3/4 1/2 1/4 3/4 1/3 1/4 1/2 1/4 1/4
10000 1-1/2 3/4 1/2 1/3 1 3/4 1/3 1/3 1 3/4 1/3 3/4 1/2 1/3 3/4 1/3 1/3
12000 1-1/2 1 3/4 1/2 1-1/2 3/4 1/2 1/2 1-1/2 3/4 1/2 1 1/2 1/2 1 1/2 1/2
14000 2 1-1/2 3/4 1/2 1-1/2 1 1/2 1/2 1-1/2 1 1/2 1-1/2 3/4 1/2 1 1/2 1/2
16000 2 1-1/2 3/4 1/2 2 1-1/2 3/4 1/2 1-1/2 1 3/4 1-1/2 3/4 3/4 1-1/2 3/4 3/4
18000 2-1/2 2 1 3/4 2 1-1/2 3/4 3/4 2 1 3/4 1-1/2 3/4 3/4 1-1/2 3/4 3/4
REFRIGERANT HFC-134a
Evaporator Temperature (°F)
Evaporator
–20°F 0°F 10°F 20°F 30°F
Capacity
Liquid Temperature (°F)
(BTU/HR)
80 60 40 20 80 60 40 20 80 60 40 80 60 40 80 60 40
2000 1/2 1/3 1/6 1/9 1/2 1/4 1/9 1/9 1/3 1/4 1/9 1/3 1/6 1/9 1/4 1/9 1/9
4000 1 3/4 1/3 1/6 3/4 1/2 1/4 1/6 3/4 1/2 1/4 3/4 1/3 1/6 1/2 1/4 1/6
6000 1-1/2 1 1/2 1/4 1-1/2 3/4 1/4 1/4 1 3/4 1/4 1 1/2 1/4 3/4 1/3 1/4
8000 2 1-1/2 3/4 1/3 1-1/2 1 1/3 1/3 1-1/2 1 1/3 1-1/2 3/4 1/3 1 1/2 1/3
10000 2-1/2 2 1 1/2 2 1-1/2 1/2 1/2 2 1 1/2 1-1/2 3/4 1/2 1-1/2 1/2 1/2
12000 3 2 1 3/4 2-1/2 1-1/2 3/4 1/2 2 1-1/2 3/4 2 1 3/4 1-1/2 3/4 3/4
14000 3 2-1/2 1 3/4 2-1/2 2 3/4 3/4 2-1/2 1-1/2 3/4 2 1-1/2 3/4 2 3/4 3/4
16000 4* 2-1/2 1-1/2 3/4 3 2 3/4 3/4 2-1/2 2 3/4 2-1/2 1-1/2 3/4 2 3/4 3/4
18000 4* 2-1/2 1-1/2 1 4* 2 1 3/4 3 2 1 2-1/2 1-1/2 1 2-1/2 1 1
*#4 nozzle not available in kit.
Nozzle selections assume a pulldown load equivalent to twice the evaporator rating. For nozzle selections with other
refrigerants, please contact your local Sporlan Sales Office, or Sporlan Valve Company, Washington, Missouri.
SELECTION
Distributor Conversion Nozzle Type Nozzle Size Bolt
To correctly select a conversion
Type (Specify Orifice Size) Available (Not Supplied)
nozzle the following requirements
must be known: 1603
1. Refrigerant in the system 1606
T
2. Evaporator Capacity (BTU/HR) 1650 1/9 1/4
1650R Through 20 Thread
3. Evaporator Temperature (°F)
D115 3
4. Liquid Temperature (°F) V
D116
5. Distributor Type
1652
1652R
EXAMPLE 1654
W
1/6 3/8
Refrigerant in the system is R-22 1654R Through 16 Thread
Evaporator Capacity = 1656 3
1656R
10000 BTU/HR
Evaporator Temperature = 10°F
Liquid Temperature = 80°F
Non-Replaceable Nozzle
Distributor Type is 1650
Conversion Nozzle
Bolt
From the selection chart based on (Not Supplied)
above information choose a T-1
conversion nozzle. Note: If
capacities fall between values on
the selection chart, select the lower
"O" Ring (2 places)
conversion nozzle.