Professional Documents
Culture Documents
CALCULATIONS
1)QE = [( 0.827 x AE x (PE)½ ] 2) QE = A x V x 3600
QE= IS THE AIR SUPPLY TO THE PRESSURIZED SPACE (CMH) QE= IS THE AIR SUPPLY TO THE PRESSURIZED SPACE (CMH)
AE = IS THE TOTAL LEAKAGE AREA OUT OF THE SPACE ( SQ.MT.) A = IS THE TOTAL AREA OF OPEN DOORS ( SQ.MT.)
PE = IS THE PRESSURIZATION LEVEL IN THE PRESSURIZED SPACE (Pa) V = IS THE EGRESS VELOCITY (M/S) (NOT LESS THAN 1 M/S)
TO CALCULATE LEAKAGE AREA OF LIFT DOOR 3 MM GAP ALL AROUND THE DOOR AND BETWEEN TWO LEAF'S HAS BEEN CONSIDERED.
ANNEXURE-IV
S.N. JOSHI CONSULTANTS P. LTD.
PROJECT: VRINDAVAN, NEPEANSEA ROAD
PROJECT NO. 3450
SELECTION OF - LIFT LOBBY PRESSURIZATION FAN
LIFT LOBBY NO DESIGN CRITERIA DOOR SIZE (MTRS) QTY OF DOORS QTY OF DOORS QTY OF DOORS TOTAL NO VELOCITY "K" LEAKAGE PASCAL
SR.
NO. PER FLOOR FULLY OPEN FULLY OPEN ON OF FLOOR (M/S) FACTOR AREA √(30)
HEIGHT WIDTH
(N0) REFUGE FLOOR SQMT
S.N. JOSHI CONSULTANTS P. LTD.
PROJECT: VRINDAVAN, NEPEANSEA ROAD
PROJECT NO. 3450
SELECTION OF - LIFTWELL PRESSURIZATION FAN
STAIR NO DESIGN CRITERIA DOOR SIZE (MTRS) QTY OF DOORS QTY OF DOORS PERMENENT VENT TOTAL NO VELOCITY "K" LEAKAGE PASCAL AIR QTY TOTAL ADDITIONAL 10% AIR QTY SELECTION
SR. IN CMH AIR QTY SAFETY FACTOR IN CFM OF CFM
PER FLOOR FULLY OPEN AT THE TOP OF FLOOR (M/S) FACTOR AREA √(50)
NO. HEIGHT WIDTH IN CMH FOR LEAKAGES "Q"
(N0) (N0) (SQM) SQMT
1 LIFT WELL PRESSURE DIFF.(50 Pa) 16 ------- 0.827 0.025 7.071 12610
2.10 1.00 1 0 0.2 12610 13871 8159 8500
EGRESS VELO.(.75 M/S) 16 0.75 0
CALCULATIONS
1)QE = [( 0.827 x AE x (PE)½ ] 2) QE = A x V x 3600
QE= IS THE AIR SUPPLY TO THE PRESSURIZED SPACE (CMH) QE= IS THE AIR SUPPLY TO THE PRESSURIZED SPACE (CMH)
AE = IS THE TOTAL LEAKAGE AREA OUT OF THE SPACE ( SQ.MT.) A = IS THE TOTAL AREA OF OPEN DOORS ( SQ.MT.)
PE = IS THE PRESSURIZATION LEVEL IN THE PRESSURIZED SPACE (Pa) V = IS THE EGRESS VELOCITY (M/S) (NOT LESS THAN 1 M/S)
TO CALCULATE LEAKAGE AREA OF LIFT DOOR 3 MM GAP ALL AROUND THE DOOR AND BETWEEN TWO LEAF'S HAS BEEN CONSIDERED.