149 - Functional Testing - R10093.FT-Air Handling Unit AHU-1 - Submitted - 2014 01 27 PDF
149 - Functional Testing - R10093.FT-Air Handling Unit AHU-1 - Submitted - 2014 01 27 PDF
PC: 237313
ITEM: Air Handling Unit
ID: AHU-1
AREA SERVED: Office and Support Areas
The above equipment and systems integral to them are complete and ready for functional testing per
Mechanical and Controls Contractors. The prefunctional checklist items are complete and have been
checked off only by parties having direct knowledge of the event. This construction checklist is
submitted for approval, subject to an attached list of outstanding items yet to be completed (See Notes
and Associated Project Issues Log). None of the outstanding items preclude safe and reliable
functional tests being performed.
This Checklist does not take the place of the manufacturer’s recommended checkout and startup
procedures or report. Construction checklist items are to be completed as part of startup and initial
checkout.
Approvals. This filled-out checklist has been reviewed. Its completion is approved with the exceptions
noted below.
Components Included
Comments:
Mode ID Pass
Test Procedure Response Note #
(including special conditions) Y/N
AHU Scheduling Verify scheduling of unit on BMS.
In Occupied Mode:
Verify supply and return fans are on, Y
outside air damper is open.
Put fan(s) in off manually; verify alarm at
BMS upon fan failure. Fan alarm generated to the BMS.
Unoccupied Record heating and cooling set points in
unoccupied mode:
Unocc HTG:
Unocc CLG:
Schedule unit in unoccupied mode. Y
Verify supply and return fans are off, the
heating and cooling coil valves are
closed, the outdoor air damper is closed,
the return air damper is open, and the
exhaust air damper is closed.
Mode ID Pass
Test Procedure Response Note #
(including special conditions) Y/N
Record static pressure setpoint BMS space pressure and Y
adjustments made for testing: setpoints are not in
Record airflow variation: the BMS graphics.
Mode ID Pass
Test Procedure Response Note #
(including special conditions) Y/N
Verify when outdoor air temperature is
above 55 degrees and return air enthalpy
is lower than the outdoor air enthalpy, the Y
return air damper and outdoor air damper
are at minimum position, relief damper is
closed, and return damper is open.
1. Safety/Smoke detection alarm shut down not commissioned, devices verified by Fire Marshall testing.
2. SA and RA “Photohelic” pressure gauges need to be labeled.
3. Interior unit segment casings are dirty and need vacuum cleaning.
4. OA CO2 detector device and value are missing from the AHU-1 graphic at BMS.
5. View Window inside frame for RA fan section is loose.
6. Ruskin dampers (ALL) to be replaced with Tamco.
7. .136” w.c. ER wheel delta P
8. 42% E.A. Rel. humidity.
9. 40% O.A. Rel. humidity.
10. 58% R.A. Rel. humidity.
11. 57% S.A. Rel. humidity.
12. Loose heating coil circulator support corrected at time of Functional Testing by MCM.