LEVCON CONTROLS PVT. LTD.

“Rajkamal”, 6th floor, 13, Camac Street, Kolkata-700017.


Ph: 033 2283 2766/3022 5767 Fax: 033 22832719 Email: info@levcongroup.com Web: www.levcongroup.com

RF Capacitance type Level Transmitter


Capacitance type Radio Frequency level transmitters are suitably used for monitoring and
controlling of liquid / slurry / solid (free flowing) levels in tanks or vessels. No moving parts ensure
any wear and tear. These level transmitters are suitable for a wide variety of applications having a
fixed dielectric constant

Features:

• Simple and low cost


• Continuous 4-20 mA DC o/p
• Set points option available (Remote Unit)
• Set points adjustable
• Wide range of Probe designs
• Integral and Non Integral models

Applications:

• Liquids
• Slurries
• Free flowing granules

Principle of Operation:

With the rise or fall of liquid/solid level, the capacitance between the active electrode and
reference electrode (still well) increases or decreases. The change in capacitance is converted by
the probe head electronics into a current signal, 4 – 20 mA proportional to level. In Non Integral
models, the preamplifier inside the probe head converts the change in capacitance into a
proportional current for onward transmission to the remote Control Unit. The Control Unit
processes the input signal to generate a 4 – 20 mA output.
Specifications:

Active Electrode: SS 304 / SS 316


Still Well: CS / GI / SS 304 / SS 316 concentric tube
Mounting: Vertical
Process Connection: Flanged, 2” ANSI #150 RF as standard
Threaded, ¾” NPT (M) as standard
Enclosure: DMC / Aluminium
Protection: IP 66
Range: 3 Mtrs. (Rigid probe)
25 Mtrs. (Flexible probe)
Temperature: 250ºC max, please consult factory for higher values
Pressure: 20 Kg/cm² max, please consult factory for higher values
Power Supply: 110 V AC / 230 V AC ± 10%, 50 Hz / 24 V DC
Output: 4 – 20 mA, 2 wire (24 V DC) / 4 wire (110 V AC or 230 V AC)
Cable Entry: ½” NPT (F)

Model Number decoding system:

Probe Unit -

LRF/ Enclosure Design Process Supply Output Special


LRFI Conn. Features, S

1. Standard 1. Integral 1. Threaded 1. Flexible 1. Dedicated Cooling fins,


3. IP:66 3. Remote 3. Flanged 3. Rigid Current Ext. pipe etc.
5. WP+FLP 3. 4-20 mA,
2 wire
5. 4-20 mA,
4 wire

Control Unit (Remote) –

LC Enclosure Mounting Indication Set points Output Switch Special


Features,
type
S

1. Standard 1. Panel 1. No 1. one 1. 4–20 mA 1. SPDT Intrinsic Safety


3. IP:66 2. Wall 3. Other 3. two 3. DPDT Etc.
5. Universal 5. three
7. four

Note:
All combinations are not possible
Since improvements are made from time to time, specifications are liable to change without notice

Tech. Pub.: LC/RF/002 dt. 01/09/2007