Zio® Lite Wall Modules™

TR40 AND TR42 MODELS WITH SYLK

SPECIFICATION DATA

FEATURES
The TR40 and TR42 wall modules include:
• Two wire, polarity insensitive Sylk provides both power
and communication to the device.
• Models available with display (TR42) or without display
(TR40).
• Models available with or without built in humidity or
CO2 sensors.

All TR42 display wall modules include:


• Override option
• Ability for tenant to change between °F and °C
• Ability to provide tenant either a relative "warmer-
cooler" setpoint adjustment or absolute temperature
setpoint adjustment
• Fan speed options: Auto-On, Auto-Off-On, Auto-Off-
Low-Med-High (Not available on ComfortPoint Open
VAV applications)
• For Spyder/Niagara users, an installer mode with
optional password protection that allows:
• Switching between °F and °C
• Temperature calibration
PRODUCT DESCRIPTION • Humidity calibration
The TR40 and TR42 are 2-wire, non-polarity sensitive, Sylk • Numerical or Graphical setpoint adjustment
communicating wall modules, which communicate with all • Adjustment of the Setpoint Range Limits
Spyder® programmable controllers and ComfortPoint™ Open
controllers that are enabled with Sylk. Not compatible with • Adjustment of override time (Choose Network
Stryker® controllers. Time or 1-24 hours)
The TR40 and TR42 are simple temperature wall modules • Choosing the sensor or setpoint value to be
with basic setpoint, override, and fan options, and are shown in the Home Screen, or choose to scroll
designed for a broad range of applications. Models are through sensor and setpoint values
available that include humidity and CO2 sensing. • Choosing between English and International
icon display
NOTE: Refer to the forms listed below for more details.
— 62-0467 Installation Instructions • For ComfortPoint Open users, installer mode is
— 63-2741 Operating Guide removed from configurations. All configuration is via
— 38-00003 Engineering Guide Spec studio tool

63-1389-04
ZIO® LITE WALL MODULES

SPECIFICATIONS Approvals: CE; UL94-V0 plastic enclosure; FCC Part 15,


Class B
Models: See Table 1 for a list of models with description. Accuracy:
Environmental Ratings: • Temperature: ± 0.2 °C at 25 °C (± 0.36 ºF at 77 ºF)
• Operating Temperature: • Humidity: ±3% RH from 20-80%RH
• Operating Range: 32 to 125 °F (0 to 52 °C) • CO2: ±(30ppm +3% of measured value).
• Setpoint Limit: 50 to 149 °F (10 to 65 °C) (Spyder/ • Calibrated at the factory.
Niagara users only) • Uses automatic background calibration. No
• Shipping Temperature: -40 to 150 °F (-40 to 65.5 °C) calibration required for the life of the product.
• Relative Humidity: 5% to 95% non-condensing • Meets CEC Title 24 requirement of ±75ppm
accuracy at 600ppm and 1000ppm ambient levels.
Accessories: • For proper CO2 operation, install only in spaces that
50007298-001 (pack of 12) medium, cover plate; see at least 4 hours of continuous unoccupied time
6-7/8 x 5 in. (175 x 127 mm). per week.

Table 1. Part Descriptions.


Part Description Sensors Communication Interface
TR40 Wall Module, Temp only, Sylk Temperature Sylk None
TR40-H Wall Module, Temp and Humidity, Sylk Temp, Humidity Sylk None
TR40-CO2 Wall Module, Temp and CO2, Sylk Temp, CO2 Sylk None
TR40-H-CO2 Wall Module, Temp, Humdity, CO2, Sylk Temp, Hum, CO2 Sylk None
TR42 LCD Wall Module, Temp only, Sylk Temperature Sylk Configurable:
Temp Setpoint Adjust,
Override, Fan (if FCU app)
TR42-H LCD Wall Module, Temp and Humidity, Sylk Temp, Humidity Sylk Configurable:
Temp Setpoint Adjust,
Override, Fan (if FCU app)
TR42-CO2 LCD Wall Module, Temp and CO2, Sylk Temp, CO2 Sylk Configurable:
Temp Setpoint Adjust,
Override, Fan (if FCU app)
TR42-H-CO2 LCD Wall Module, Temp, Humidity, CO2, Sylk Temp, Hum, CO2 Sylk Configurable:
Temp Setpoint Adjust,
Override, Fan (if FCU app)

Communications Setting the Wall Module Address Dial


The wall modules use the two wire polarity insensitive Sylk for Every Sylk device wired to a single controller must have a
communication with the programmable controller. unique address. The address on the wall module must match
the address in the control logic.

Compatibility Sylk Device Capacity


For Spyder/Niagara users, the TR40/42 models work with For ComfortPoint Open controllers, a maximum of three (3)
Spyders manufactured after date code 1220, and work with TR40/42s can be supported by a single controller.
any Spyder Micro BACnet. Be sure to use an updated Spyder
tool to get the TR40/42 functional support. For Spyder controllers, to determine the maximum number of
Sylk devices, including Zio Lites, please refer to the Sylk
Also compatible with the ComfortPoint™ Open CPO-VAV2A Device Capacity Calculation Tool on the Buildings Forum. Sylk
direct coupled, VAV box controller-actuator. Capacity can also be determined, and should always be
verified, using the Resouce Usage view in the Spyder Tool
itself. Total Sylk proxy file memory, total Sylk power
consumption, and total Sylk bandwidth must all fall below
maximum limits.

By using this Honeywell literature, you agree that Honeywell will have no liability for any damages arising out of your use or
modification to, the literature. You will defend and indemnify Honeywell, its affiliates and subsidiaries, from and against any
liability, cost, or damages, including attorneys’ fees, arising out of, or resulting from, any modification to the literature by you.
Automation and Control Solutions
Honeywell International Inc.
1985 Douglas Drive North
® U.S. Registered Trademark
Golden Valley, MN 55422 © 2015 Honeywell International Inc.
63-1389—04 M.S. Rev. 12-15