Professional Documents
Culture Documents
FEATURES
• Operates from thermostat and DCV (CO2) sensor to
provide a totally integrated control system.
• Solid state control package provides accurate, reliable
and stable control.
• Mounts on M7215 Motor or ductwork.
• Control can be tempered by DCV and fan cycling.
• Used with Honeywell actuators.
• Combines minimum and DCV maximum damper
position potentiometers with compressor staging.
• Solid state enthalpy or dry bulb changeover control.
• Terminals included for switching between Occupied
and Unoccupied operation.
• Terminals included for connecting optional S963B1128
Remote Potentiometer for remote minimum damper
position control.
• LED indicates when free cooling is available.
• LED indicates when module is in DCV mode.
APPLICATION • LED indicates when exhaust fan contact is closed.
• On CO2 sensor failure defaults to DCV maximum
W7212, W7213, and W7214 Economizer Logic Modules are damper position for minimum position.
used with C7232 (CO2) Demand Control Ventilation (DCV) This feature was added with the series 2 version of the
Sensors, and solid state C7400 Enthalpy Sensors or C7660 product. See Table 1.
Dry Bulb Temperature Sensors. All models proportion outdoor
and return air dampers for control of free cooling in • W7213 is used with heat pump B terminal.
commercial HVAC equipment. • W7214 is used with heat pump O terminal.
• W7212C is used for applications requiring low
temperature and humidity and has the “E” enthalpy
curve.
Contents
Application ........................................................................ 1
Features ........................................................................... 1
Specifications ................................................................... 2
Ordering Information ........................................................ 2
Installation ........................................................................ 3
Settings and Adjustments ................................................. 8
Checkout and Troubleshooting ......................................... 20
63-2596-09
W7212, W7213, W7214 ECONOMIZER LOGIC MODULES
SPECIFICATIONS
Models: W7212A, W7213A, W7214A Logic Modules: for use Nominal Power Consumption (at 24 Vac, 60 Hz): 11.5 VA.
with any Honeywell 2-10 Vdc actuator; includes DCV Relay Contact Rating at 30 Vac (maximum power from class 2
(CO2) input; adjustable exhaust fan setpoint. input only): 1.5A run, 3.5A inrush.
NOTES: IMPORTANT
— All models include a minimum damper position All inputs and outputs must be 24 Vac Class 2.
potentiometer, and setpoints for: enthalpy or
dry-bulb, occupied/unoccupied control, DCV Ambient Ratings:
(CO2) operation, CO2 sensor failure mode and Temperature: -40°F to +149°F (-40°C to +65°C).
DCV maximum (DCV MAX). Humidity: 5 to 95 percent RH (noncondensing).
— Occupied/Unoccupied overrides minimum
damper position setting when building is Inputs:
unoccupied. Enthalpy (C7400): 2-wire (18,20,22 AWG) connection.
— On CO2 sensor failure the damper outdoor Dry Bulb Temperature (C7660): 2-wire (18,20,22 AWG)
damper defaults to DCV maximum position. See connection.
table 1 for economizer functions based on occu- Discharge Air (C7046): 2-wire (18,20,22 AWG) connection.
pancy, CO2 input and damper positions for Mixed Air (C7150): 2-wire (18,20,22 AWG) connection.
adjustments of potentiometers for MIN POS and DCV (CO2) Sensor (C7232): 0/2-10 Vdc control signal;
DCV MAX. This feature was added with series 2 100K ohm input impedance.
version of the product; series 1 does NOT default
to DCV MAX, series 1 defaults to MIN POS on Outputs:
failure of CO2 sensor. Actuator Signal: 2-10 Vdc.
Minimum Actuator Impedance: 1K ohm.
Dimensions: See Fig. 1. Exhaust Fan: Contact closure.
24 Vac Out: 25 VA maximum.
Electrical Ratings:
Input Voltage: 24 Vac ±20%; 50/60 Hz (Class 2).
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada—Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Toronto, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France,
Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
63-2596—09 2
W7212, W7213, W7214 ECONOMIZER LOGIC MODULES
4-1/8
(104)
ECONOMIZER
LOGIC MODULE
1/8 (4)
2-5/8 (66) M20578A
3 63-2596—09
W7212, W7213, W7214 ECONOMIZER LOGIC MODULES
OUTDOOR AIR SENSING mizer will spring return damper closed, if fan is on and no
1. Mount sensor in any orientation exposing it to freely occupancy damper will drive to DCV MAX position.
circulating air while protecting it from rain, snow, and
direct sunlight.
2. Connect it to the SO and SO+ terminals of the device.
63-2596—09 4
W7212, W7213, W7214 ECONOMIZER LOGIC MODULES
Mount the CO2 sensor according to the manufacturer 3. Adjust the DCV potentiometer setpoint to correspond to
specifications. If not available, use the following guidelines: DCV voltage output at the threshold.
1. Mount sensor in an area with unobstructed air
circulation.
2. Connect it to the AQ and AQ1 terminals of the W7212
(see Wiring section for details).
DISCHARGE COMMERCIAL
AIR SENSOR THERMOSTAT
DIRECT DCV
C7046A 2 C7232
EXPANSION SENSOR
COIL
2
W7212, C7150B
W7213, ENTHALPY
1 C7400
W7214 MIXED AIR SENSOR
SENSOR
INDOOR
FAN
HONEYWELL
DISCHARGE ACTUATOR
AIR
OUTDOOR
AIR
1
ENTHALPY
C7400 SENSOR
5 63-2596—09
W7212, W7213, W7214 ECONOMIZER LOGIC MODULES
OPERATION When wired as shown in Fig. 9 through 15, the logic module
responds to the cooling thermostat signal. The system uses
C7400 Solid State Enthalpy Changeover Sensor(s) or C7660
The purpose of the economizer is to use outdoor air for Dry Bulb Temperature Sensor(s). The C7400 responds to both
cooling, whenever possible, to reduce compressor operation. dry bulb temperature and humidity, allowing use of outdoor air
at higher temperatures for free cooling when humidity is low.
Power at the N terminal determines the Occupied/Unoccupied The C7660 responds only to dry bulb temperature; use only in
setting: dry, arid climates and only in single dry bulb changeover. Do
— W7212: not use the C7660 in differential dry bulb applications.
• 24 Vac (Occupied).
• No power (Unoccupied). The logic module functions as a true first stage of cooling
— See Fig. 9 through 15 for controller hookup. providing maximum energy economy during the cooling cycle.
It automatically locks out free cooling during heating; holding
NOTE: When module is operating in Occupied mode, the the outdoor air damper at the minimum position setting (or if
minimum position is defined by the potentiometers. using Demand Control Ventilation and the space CO2 level is
When the module is operating in Unoccupied mode, above the set point, the damper will be between the MIN POS
and there is no call for cooling, the damper drives fully and DCV MAX position).
closed.
63-2596—09 6
W7212, W7213, W7214 ECONOMIZER LOGIC MODULES
7 63-2596—09
W7212, W7213, W7214 ECONOMIZER LOGIC MODULES
SETTINGS AND ADJUSTMENTS established by ASHRAE standard 62.1. When used with a
CO2 occupancy sensor the minimum position will modulate
between the MIN POS pot setting and the DCV MAX pot
setting based on the CO2 input to the AQ-AQ1 terminals from
CAUTION the CO2 sensor located in the space. When a CO2 sensor is
NOT USED with the unit, the OA dampers will modulate based
Equipment Damage Hazard.
on the actions in Table 1. Setting the DCV maximum position of
Excessive force can damage potentiometer
the damper prevents the introduction of large amounts of hot or
controls.
cold air into the space by preventing the dampers from opening
Use a small screwdriver or the plastic tool provided
100% during a call for additional ventilation. On a call for
with the economizer when adjusting all potentiometers
cooling AND the OA is good for economizing, the unit will
located on the unit.
override the DCV MAX setting and allow the dampers to drive
full open.
Potentiometers with screwdriver adjustment slots, located on
device face, provide adjustments for several parameters
IMPORTANT
(see Fig. 5 for locations on device):
With the DCV maximum position set below the
— DCV setpoint.
minimum position, the minimum position overrides the
— Minimum damper position.
maximum position with the series 2 units.
— DCV maximum damper position.
— Enthalpy changeover.
— Exhaust setpoint. NOTES:
— When the mixed air sensor takes control based on
EXHAUST an increased requirement for cooling, it overrides
FAN SETPOINT the DCV maximum position potentiometer and can
LED LIGHTS
N1 EXH
Set
drive the damper full-open.
WHEN EXHAUST N 2V 10V
— If the mixed air temperature drops to 45°F, the
CONTACT IS MADE
P1 EXH mixed air sensor overrides the DCV and closes the
MINIMUM DAMPER
POSITION SETTING P Min damper to protect from freezing the hot or chilled
Pos
MAXIMUM DAMPER
T1
Open
water coils. Control returns to normal once the
DEMAND CONTROL
T
mixed air temperature rises to 48°F. Some models
VENTILATION SETPOINT DCV
Max
of the W7212 close the damper fully and others
LED LIGHTS WHEN 2V 10V
close the damper to minimum position. Check the
DEMAND CONTROL AQ1
VENTILATION INPUT DCV label on the box for position of damper on freeze
AQ
IS ABOVE SETPOINT DCV
protection. If the CO2 sensor should fail, the
SO+ Set
SO
2V 10V
W7212 defaults to DCV maximum, providing mini-
DEMAND CONTROL
VENTILATION SETPOINT SR+
Free
Cool mum ventilation for the maximum design occu-
SR B C
pancy.
LED LIGHTS WHEN A D
OUTDOOR AIR IS
SUITABLE FOR
FREE COOLING B
C
D W7212C modules have Minimum Position Adjustment
ENTHALPY the "E" enthalpy curve
CHANGEOVER SETPOINT
A E
For detailed assistance in minimum position selection
M20604B
reference the Economizer Application Guide (form 63-8594)
Ventilation section. The following provides basic guidelines for
Fig. 5. Potentiometer and LED locations (W7212 shown). minimum position selection and adjustment:
IMPORTANT
Demand Control Ventilation Setpoint • Adjust the minimum position potentiometer to allow
The logic module modulates the outdoor damper to provide the minimum amount of outdoor air for building efflu-
ventilation based on the 2-10 Vdc DCV input (AQ-AQ1 ents, as required by local codes, to enter the building.
terminals). With no cooling signal, the DCV overrides the • This procedure requires use of a quality thermometer
outdoor air damper when ventilation requires additional capable of reading to 0.5°F [0.25°C].
outdoor air.
NOTE: Make ventilation adjustments with at least a 10°F
EXAMPLE: CO2 sensor with 2 to 10 Vdc output range 0 to [6°C] temperature difference between outdoor and
2000 ppm. Two (2) Vdc is equal to 0 ppm, 10 Vdc is equal to return air.
2000 ppm, threshold is determined to be 1000 ppm. DCV
potentiometer to be set at 6 Vdc. 1. Calculate the appropriate mixed air temperature, see
Equation 1.
Adjust the potentiometer with a small screwdriver by turning Equation 1 will be used to set the damper positions for
the pot to the fully CCW then fully CW positions to determine MIN POS and DCV MAX. Without a DCV sensor con-
the end stops. Set the pot for 6 Vdc in the mid position. nected to AQ-AQ1, use the MIN POS pot and this proce-
dure to adjust the damper positions for minimum OA
when the space is occupied. When using a DCV sensor
Adjusting Minimum and Maximum you will need to set the MIN POS and DCV MAX posi-
Positions tions using this procedure. DCV MAX will be the same as
The minimum position is defined by the minimum outdoor air the MIN POS above (without a DCV sensor) and the MIN
flow required in the building during the occupied period. The POS will lower than the DCV MAX %.
MIN POS and DCV MAX position potentiometers allow the 2. Disconnect mixed air sensor from terminals T and T1.
installer to set the proper ventilation based on occupancy 3. Place a jumper across terminals T and T1.
63-2596—09 8
W7212, W7213, W7214 ECONOMIZER LOGIC MODULES
4. Ensure that either the factory-installed jumper is in place will return the OA damper to minimum position (this is either
across terminals P and P1 or, if remote damper position MIN POS if using a CO2 sensor or DCV MAX if a CO2 sensor
is required, that it is wired according to Fig. 6 and the is NOT used).
MIN POS potentiometer is turned fully clockwise.
5. Connect 24 Vac across terminals TR and TR1. Differential Enthalpy Changeover Setting
6. Carefully adjust the potentiometer on the face of the
device with a small screwdriver until the mixed air Differential enthalpy control uses two C7400 Enthalpy Sensors
temperature reaches the calculated value. connected to one logic module. The logic module compares
outdoor air to return air.
NOTE: Ensure that the sensed air is well mixed. NOTE: Turn the enthalpy setpoint potentiometer fully clock-
wise to the D (or E setting for W7212C) setting.
7. If all minimum (MIN POS) and maximum position (DCV
MAX) adjustments are complete, remove the T-T1 The logic module selects the lower enthalpy air (return or
jumper and reconnect the mixed air sensor. outdoor) for cooling. For example, when outdoor air has lower
enthalpy than return air, the module calls to open the outdoor
Equation 1.Formula to aid minimum position adjustment. air damper to bring in outdoor air for free cooling.
( T O × OA ) + ( T R × RA ) = T M
Where:
TO = Outdoor air temperature Exhaust Setpoint
OA = Percent of outdoor air The exhaust setpoint determines when the exhaust fan runs
TR = Return air temperature based on damper position. When the exhaust fan call is made,
RA = Percent of return air the module provides a 60 ±30 second delay before exhaust fan
TM = Resulting mixed air temperature activation. This delay allows the damper to reach the
appropriate position to avoid unnecessary fan overload.
NOTE: The following sample calculation uses only
Fahrenheit temperature. NOTES:
EXAMPLE: Assume local codes require 10% outdoor air dur- — EF and EF1 are 24V dry contacts only. An external
ing occupied conditions, outdoor air is 60°F and line voltage contactor is required to operate the
return air is 75°F. Under these conditions, what is exhaust fan.
the temperature of the mixed air? — When the exhaust fan is deactivated the EF and
EF1 contacts open immediately.
( 0.1 × 60°F ) + ( 0.9 × 75°F ) = 6.0°F + 67.5°F = 73.5°F
9 63-2596—09
W7212, W7213, W7214 ECONOMIZER LOGIC MODULES
S963B1128 REMOTE
POTENTIOMETER
R MINIMUM
CW P1 POSITION
CLOSE ADJUSTMENT
P
W B
CW
ECONOMIZER
M20603A
46
CONTROL CONTROL POINT
44
CURVE APPROX. °F (°C)
AT 50% RH 80
42
(27)
A 73 (23)
B 70 (21) 40
)
(%
R
C 67 (19)
AI
38
TY
D 63 (17)
RY
IDI
75
34 D D
36
UM
(24)
UN
EH
PO
TIV
R
32
PE
LA
70
U
30
BT
RE
(21)
—
PY
28
AL
0
10
90
26
TH
65
80
EN
(18)
70
24
60
22
60
50
(16)
20
A
40
55
18
(13) B
30
16
50
(10) C
20
14
45 D
12
(7)
40
(4) 10
35
(2)
1
B A
D C
Fig. 7. W7212A, W7213, W7214 performance characteristics for enthalpy changeover settings.
63-2596—09 10
W7212, W7213, W7214 ECONOMIZER LOGIC MODULES
46
CONTROL CONTROL POINT
44
CURVE APPROX. °F (°C)
AT 50% RH 80
42
(27)
A 73 (23)
40
B 70 (21)
)
(%
C 67 (19)
R
AI
38
TY
D 63 (17)
RY
IDI
E 55 (13) 75
34 D D
36
UM
(24)
UN
EH
PO
TIV
R
32
PE
LA
70
U
30
BT
RE
(21)
Y—
28
LP
0
HA
10
90
26
65
T
80
EN
(18)
70
24
60
22
60
50
(16)
20
40
55
18
(13) B
30
16
50
(10) C
20
14
45 D
12
(7)
40
(4) E 10
35
(2)
1
B A
D C
E
11 63-2596—09
W7212, W7213, W7214 ECONOMIZER LOGIC MODULES
N1 TR TR1
24 VAC HOT
MINIMUM POSITION 24 24 Vac
P1
ADJUSTMENT Vac COM
HOT 24 VAC COM
C7150B MIXED P
AIR OR C7046A T1 + –
DISCHARGE 2-10 VDC CONTROL
T
AIR SENSOR SIGNAL OUTPUT
1 2
AQ1
2-10 VDC – 5
AQ
INDOOR AIR
SENSOR + SO+ 3 4
SO
SR+ EF EF1
SR
M7215
C7400 W7212 5
OUTDOOR + 3
AIR
ENTHALPY 620 OHM L1
SENSOR S RESISTOR (HOT)
L2
EXHAUST
FAN
Y1 C
Y2 Y1 COOL 1
W2 Y2 COOL 2
W1
W2 HEAT 2
A2
4 W1 HEAT 1
A1
A2
G
A1
RH
G FAN
2
RC
L2
1
X R L1
(HOT)
T7300/Q7300 HVAC EQUIPMENT
THERMOSTAT TERMINAL STRIP
2 ENSURE THAT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR. USE THE SAME
TRANSFORMER FOR T7300 AND ECONOMIZER.
3 FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD NOT BE REMOVED. DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE
WITH SINGLE-STAGE COOLING SYSTEMS OR SINGLE-STAGE COOLING THERMOSTATS.
4 T7300 TERMINALS A1 AND A2 ARE CONNECTED WHEN COMMERCIAL THERMOSTAT IS IN THE OCCUPIED MODE.
Fig. 9. W7212 used with M7215 Damper Motor and T7300 Thermostat.
63-2596—09 12
W7212, W7213, W7214 ECONOMIZER LOGIC MODULES
N1 TR TR1
24 VAC HOT
MINIMUM POSITION 24 24 Vac
P1
ADJUSTMENT Vac COM
HOT 24 VAC COM
C7150B MIXED P
AIR OR C7046A T1 + –
2-10 VDC CONTROL
DISCHARGE T
SIGNAL OUTPUT
AIR SENSOR
1 2
AQ1
2-10 VDC – 5
AQ
INDOOR AIR
SENSOR + SO+ 3 4
SO
SR+ EF EF1
SR
M7215
C7400 W7212
OUTDOOR + 5
4
AIR 620 OHM L1
ENTHALPY S RESISTOR (HOT)
SENSOR L2
EXHAUST
FAN
Y1 C
Y2 Y1 COOL 1
W2 Y2 COOL 2
W1
3 W2 HEAT 2
AUX
W1 HEAT 1
A2
G
RH
G FAN
2
RC
L2
1
X R L1
(HOT)
T7350 HVAC EQUIPMENT
THERMOSTAT TERMINAL STRIP
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 ENSURE THAT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.
THE SAME TRANSFORMER CAN BE USED FOR THE COMMERCIAL THERMOSTAT AND ACTUATOR.
3 IF SEPARATE HEATING AND COOLING TRANSFORMERS ARE USED, REMOVE JUMPER AT THERMOSTAT.
T7350 - TERMINAL “AUX” IS POWERED BY THE HEATING TRANSFORMER (RH).
IF POWERING THE ECONOMIZER TERMINAL “N” WITH THE THERMOSTAT TERMINAL “AUX”, BE SURE THE ECONOMIZER IS POWERED BY THE
SAME TRANSFORMER AS TERMINAL “AUX”. IF NOT, USE AN ISOLATION RELAY TO POWER “N”.
4 FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD NOT BE REMOVED. DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE
WITH SINGLE-STAGE COOLING SYSTEMS OR SINGLE-STAGE COOLING THERMOSTATS.
Fig. 10. W7212 used with M7215 Damper Motor and T7350 Thermostat.
13 63-2596—09
W7212, W7213, W7214 ECONOMIZER LOGIC MODULES
N1 TR TR1
24 VAC HOT
MINIMUM POSITION 24 24 Vac
P1
ADJUSTMENT Vac COM
HOT 24 VAC COM
P
C7150B MIXED T1 + –
AIR OR C7046A 2-10 VDC CONTROL
DISCHARGE T
SIGNAL OUTPUT
AIR SENSOR
1 2
AQ1
2-10 VDC – 5
AQ
INDOOR AIR
SENSOR + SO+ 3 4
SO
SR+ EF EF1
SR
M7215
C7400 W7212
OUTDOOR + 5
4
AIR
ENTHALPY S 620 OHM L1
RESISTOR (HOT)
SENSOR
L2
EXHAUST
FAN
Y1 C
Y2 Y1 COOL 1
W2 Y2 COOL 2
W1
3 W2 HEAT 2
A
W1 HEAT 1
A
G
R
G FAN
2
RC
L2
X R L1 1
(HOT)
TB7220 OR TB8220 HVAC EQUIPMENT
THERMOSTAT TERMINAL STRIP
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD PROTECTION AS REQUIRED.
2 ENSURE THAT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.
THE SAME TRANSFORMER CAN BE USED FOR THE COMMERCIAL THERMOSTAT AND ACTUATOR.
3 IF SEPARATE HEATING AND COOLING TRANSFORMERS ARE USED, REMOVE JUMPER AT THERMOSTAT.
TB7220 - TERMINAL “A” IS POWERED BY THE COOLING TRANSFORMER (RC).
TB8220 - TERMINAL “A” IS POWERED BY THE HEATING TRANSFORMER (R).
IF POWERING THE ECONOMIZER TERMINAL “N” WITH THE THERMOSTAT TERMINAL “A”, BE SURE THE ECONOMIZER IS POWERED BY THE
SAME TRANSFORMER AS TERMINAL “A”. IF NOT, USE AN ISOLATION RELAY TO POWER “N”.
4 FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD NOT BE REMOVED. DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE
WITH SINGLE-STAGE COOLING SYSTEMS OR SINGLE-STAGE COOLING THERMOSTATS.
Fig. 11. W7212 used with M7215 Damper Motor and TB7220 or TB8220 Thermostats.
63-2596—09 14
W7212, W7213, W7214 ECONOMIZER LOGIC MODULES
N1 TR TR1
~ 1 N
2 MINIMUM POSITION
P1 24 24 Vac
ADJUSTMENT Vac COM
+ 3
C7150B MIXED P
HOT
4 AIR OR C7046A T1 + –
F DISCHARGE
5 T
AIR SENSOR
1 2
AQ1
MS7XXX 2-10 VDC – 5
AQ
HONEYWELL INDOOR AIR
ACTUATOR SENSOR + SO+ 3 4
SO
SR+ EF EF1
SR
4
W7212
3
C7400
OUTDOOR + 620 OHM
AIR RESISTOR
ENTHALPY
SENSOR S
C
L1
COOL 1 (HOT)
Y1 Y1
L2
EXHAUST
Y2 FAN
5 W2 W2 HEAT 2
UNOCCUPIED
W1 W1 HEAT 1 ST6008 6
TIMER
G FAN
DELAY OCCUPIED
RELAY
RH FDR
G FAN
2
RC
FDR L2
1
X R L1
(HOT)
COMMERCIAL HVAC EQUIPMENT
THERMOSTAT TERMINAL STRIP
2 ENSURE THAT TRANSFORMER IS SIZED TO HANDLE THE EXTRA LOAD OF THE ECONOMIZER AND ACTUATOR.
3 FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD NOT BE REMOVED. DIFFERENTIAL ENTHALPY NOT RECOMMENDED FOR USE
WITH SINGLE-STAGE COOLING SYSTEMS OR SINGLE-STAGE COOLING THERMOSTATS.
6 TIME CLOCK IS AN OPTION TO USING OCCUPIED CONTACTS ON THE COMMERCIAL THERMOSTAT. M13659C
Fig. 12. W7212 used in single-stage cooling system with single enthalpy changeover and
Honeywell actuator and time clock for occupancy.
15 63-2596—09
W7212, W7213, W7214 ECONOMIZER LOGIC MODULES
N1 TR TR1
~ 1
N
2 P1
MINIMUM POSITION 24 24 Vac
ADJUSTMENT Vac COM
+ 3 C7150B MIXED P
HOT
4 AIR OR C7046A T1 + –
DISCHARGE T
F 5
AIR SENSOR
1K
1S 1 2
3
AQ1 2K
AQ
INDOOR AIR
HONEYWELL SENSOR + SO+ 1S1 3 4
ACTUATOR SO
SR+ EF EF1
SR
C7400 W7212
5 7
OUTDOOR +
AIR 620 OHM
ENTHALPY S RESISTOR
SENSOR
C
L1
Y1 COOL 1 (HOT)
Y1 W T6031 AMBIENT L2
LOCKOUT
CONTROL COOL 2 EXHAUST
Y2 R Y2
FAN
50 F SETPOINT
W2 W2 HEAT 2
8 UNOCCUPIED
6
W1 W1 HEAT 1 ST6008
TIMER
G FAN
DELAY OCCUPIED 9
RELAY
RH FDR
G FAN
2
RC
FDR L2
4 1
X R L1
(HOT)
T7300 OR T874 HVAC EQUIPMENT
THERMOSTAT TERMINAL STRIP
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS AND OVERLOAD 6 USE THE FOLLOWING CONTACTS INSTEAD OF TIMER
PROTECTION AS REQUIRED. FOR T7300, USE A1 AND A2 TERMINALS.
FOR T7350 USE AUX TERMINAL.
2 ENSURE THAT TRANSFORMER IS SIZED TO HANDLE THE EXTRA FOR TB7220 OR TB8220 USE A TERMINAL
LOAD OF THE ECONOMIZER AND ACTUATOR. THE TERMINALS ARE CONNECTED WHEN THERMOSTAT IS IN THE OCCUPIED MODE.
3 1S IS AN ELECTRONIC SWITCH THAT CLOSES WHEN POWERED 7 EF AND EF1 ARE DRY CONTACTS IN THE LOGIC MODULE.
BY A 24 VAC INPUT.
8 SEE WIRING DIAGRAMS FIGS 9 AND 10 FOR T7350 AND TB7220/TB8220.
4 FOR T7300 ONLY
9 TIME CLOCK IS AN OPTION TO USING OCCUPIED CONTACTS ON THE
5 FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD BE COMMERCIAL THERMOSTAT.
REMOVED ONLY WHEN A C7400 ENTHALPY SENSOR IS ADDED TO
M13660B
SR AND SR+ FOR DIFFERENTIAL ENTHALPY.
Fig. 13. W7212 used in two-stage cooling system with Honeywell Series 72 Actuator and time clock for occupancy.
63-2596—09 16
W7212, W7213, W7214 ECONOMIZER LOGIC MODULES
1 L2
2 L1
(HOT)
~ 1
2
+ 3 N1 TR TR1
N
4
F 5 P1
MINIMUM POSITION 24 24 Vac
ADJUSTMENT Vac COM
HOT
MS7XXX C7150B MIXED P
HONEYWELL AIR OR C7046A T1 + –
ACTUATOR DISCHARGE T
AIR SENSOR
~ 1 1 2
2 AQ1
2-10 VDC – 5
+ 3 INDOOR AIR AQ
4 SENSOR + SO+ 3 4
SO
F 5
SR+ EF EF1
MS7XXX SR
HONEYWELL
ACTUATOR W7212
4
C7400 620 OHM 5
3 UNOCCUPIED
OUTDOOR + RESISTOR
ST6008 AIR
TIMER 7 ENTHALPY
SENSOR S
L1 OCCUPIED
(HOT)
1 L2
Y1 Y1 COOL 1
L1
Y2 Y2 (HOT)
COOL 2
1 POWER SUPPLY. PROVIDE DISCONNECT MEANS L2
AND OVERLOAD PROTECTION AS REQUIRED. EXHAUST
W2 W2 HEAT 2
FAN
2 ENSURE THAT TRANSFORMER IS SIZED TO HANDLE
THE LOAD OF ALL ACTUATORS. HEAT 1
W1 W1
3 USE THE FOLLOWING CONTACTS INSTEAD OF TIMER
FOR T7300, USE A1 AND A2 TERMINALS. G FAN
DELAY
FOR T7350 USE AUX TERMINAL. RELAY
FOR TB7220 OR TB8220 USE A TERMINAL
RH
THE TERMINALS ARE CONNECTED WHEN FDR
COMMERCIAL THERMOSTAT IS IN THE OCCUPIED MODE. G FAN
RC
4 FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR L2
SHOULD BE REMOVED ONLY WHEN A C7400 ENTHALPY FDR 1
X R
SENSOR IS ADDED TO SR AND SR+ FOR DIFFERENTIAL L1
ENTHALPY. (HOT)
COMMERCIAL HVAC EQUIPMENT
THERMOSTAT TERMINAL STRIP
5 EF AND EF1 ARE DRY CONTACTS IN THE
LOGIC MODULE. 6
6 SEE WIRING DIAGRAMS FIGS 9 AND 10 FOR T7350
AND TB7220/TB8220.
Fig. 14. W7212 controlling parallel-wired Honeywell Series 72 Actuators and time clock for occupancy.
17 63-2596—09
W7212, W7213, W7214 ECONOMIZER LOGIC MODULES
~ 1
2
5 O TR TR1
+ 3
N
4
MINIMUM POSITION 24 24 Vac
P1
F 5 ADJUSTMENT Vac COM
HOT
P
T1 + –
C7150B
T
DISCHARGE
MS7XXX AIR SENSOR
1 2
HONEYWELL
ACTUATOR AQ1
2-10 VDC – 4
AQ
INDOOR AIR
SENSOR + SO+ 3 5
SO
SR+ EF EF1
SR
W7214
3 2
C7400 620 OHM
OUTDOOR + RESISTOR
AIR
ENTHALPY
SENSOR S
A3
4
C
A2
Y1 Y1 COOL 1
L1
Y2 Y2 (HOT)
COOL 2
L2
EXHAUST
W2 W2 HEAT 2
FAN
W1 W1 HEAT 1
G G FAN
RH
L2
1
RC R L1
(HOT)
X
5
O O
3 FACTORY INSTALLED 620 OHM, 1 WATT, 5% RESISTOR SHOULD BE REMOVED ONLY WHEN A
C7400 ENTHALPY SENSOR IS ADDED TO SR AND SR+ FOR DIFFERENTIAL ENTHALPY.
4 T7300 TERMINALS A2 AND A3 ARE CONNECTED WHEN THERMOSTAT IS IN THE UNOCCUPIED MODE.
SEE T7350 AND TB7220/TB8220 WIRING.
63-2596—09 18
W7212, W7213, W7214 ECONOMIZER LOGIC MODULES
SELECT
TR TR1 OPTION N1 N TR TR1
(HOT) (COMMON) UNDER (HOT) (COMMON)
“THERMOSTAT
1 W7459 INSTALLER SELECT
OPTION UNDER 1 W7212
SETUP”
3 “THERMOSTAT
0400 = 2 INSTALLER 3
0174 = E SETUP”
0540 = 2 0400 = 2
0174 = E
0540 = 2 HVAC EQUIP
HVAC EQUIP
TERMINAL STRIP
TERMINAL
STRIP C
1
C VISION 1 2 Y1
COOL 1
1 Y1 PRO 2 Y1
3 Y2
1 2 Y1 COOL 1 IAQ 3 C Y2 COOL 2
VISION 2 3 Y2 R
PRO IAQ 3 C COOL 2 RC G
Y2 V1 G COM
R G RH T2 FAN
RC G R HOT
COM EIM
RH FAN
R HOT
M29973
EIM
M29974
19 63-2596—09
W7212, W7213, W7214 ECONOMIZER LOGIC MODULES
5.6K ohm, and 6.8K ohm resistors. Use Table 4 and Fig. 18 for P Min
checkout. T1
Pos
1 T
Open
DC VOLTMETER
DCV
CAUTION
Max
+ 2V 10V
AQ1
DCV
Equipment Damage Hazard. AQ DCV
Excessive force can damage potentiometer S
SO+
2V
Set
10V
controls. C7400 SO
Free
Use a small screwdriver when adjusting enthalpy + SR+ Cool
B C
SR
changeover and minimum damper position controls. A D
2
620 OHM RESISTOR
1 INSERT DC VOLTMETER BETWEEN AQ AND AQ1 FOR
CHECKOUT AND TROUBLESHOOTING.
Table 4. Checkout for W7212, W7213, W7214 Economizers Connected to Honeywell Actuator.
Step Checkout Procedure Proper Response
1. CHECKOUT PREPARATION FOR ECONOMIZING ONLY
Disconnect power at TR and TR1. All LED are off; Exhaust Fan contacts are open.
Disconnect devices at P and P1.
Jumper P to P1 (defaults to on board MIN POS potentiometer).
Place 5.6K ohm resistor across T and T1 (Blue sleeve- provides input to
economizer that the MAT is between 50-55F).
Jumper TR to 1 (call for cooling from the thermostat).
W7212 only: Jumper TR to N (places economizer in occupied mode).
If connected, remove C7400 Enthalpy Sensor from terminals SO and +.
Connect 1.2K ohm, from 4074EJM Checkout Resistor kit, (purple sleeve)
across terminals SO and + (makes OA enthalpy high).
Place 620 ohm resistor (white sleeve) across SR and + (makes return
enthalpy lower than OA).
Set MIN POS and DCV MAX potentiometers fully CCW.
Turn DCV setpoint potentiometer mid position (this sets the DCV ventilation
at approximately 1000 ppm).
Turn exhaust potentiometer to mid position (motor will be approximately 50%
open when the exhaust fan contacts make).
Set enthalpy potentiometer to D.
W7214 only: Jumper TR to O.
Apply power (24 Vac) to terminals TR and TR1.
63-2596—09 20
W7212, W7213, W7214 ECONOMIZER LOGIC MODULES
Table 4. Checkout for W7212, W7213, W7214 Economizers Connected to Honeywell Actuator. (Continued)
Step Checkout Procedure Proper Response
2. DIFFERENTIAL ENTHALPY
Execute step one, Checkout Preparation. —
Turn DCV MAX to mid position.
Place 620 ohm resistor across SO and + (white sleeve resistor makes OA —
enthalpy low).
Place 1.2K ohm resistor across SR and + (purple sleeve resistor makes RA Free cool LED turns on; motor drives to approximately 45 degrees (half)
enthalpy high). open.
Remove 620 ohm resistor from SO and +. Free cool LED turns off; motor drives closed
3. SINGLE ENTHALPY
Execute step one, Checkout Preparation. —
Turn DCV MAX to mid position.
Set enthalpy potentiometer to A (fully CCW). Free cool LED turns on; motor drives to approximately 45 degrees (half)
open.
Set enthalpy potentiometer to D or E for W7212C (fully CW). Free cool LED turns off; motor drives closed
4. DCV AND EXHAUST
Execute step one, Checkout Preparation. —
LED for both DCV and Exhaust should be off.
Turn DCV MAX to mid position. Motor drives to mid position, 45 degrees open.
Turn MIN POS fully CW. Motor drives fully open.
Turn MIN POS and DCV MAX to fully CCW. Motor drives closed.
Turn DCV MAX to mid position. LED for both DCV and Exhaust turn on.
Connect 9V battery positive to AQ and negative to AQ1. Actuator drives to 45 degrees open.
Remove jumper from N terminal (economizer goes into not occupied mode). Motor remains at 45 degrees open.
Adjust DCV MAX towards CW. Motor will move to position set by DCV MAX pot.
Adjust DCV MAX to fully CCW. Motor will drive closed.
Reconnect jumper to N terminal.
Adjust DCV MAX and MIN POS pots. Motor will drive to the most open position of the pots.
Adjust DCV MAX and MIN POS pots to fully CCW.
Remove power from N terminal adjust MIN POS towards CW Motor should not move.
Adjust DCV MAX towards CW. Motor will move to position set by DCV MAX pot.
5. MINIMUM AND MAXIMUM POSITION
Execute step one, Checkout Preparation. —
Connect 9V battery positive to AQ and negative to AQ1. Adjust DCV MAX DCV LED turns on. Actuator drives to 45 degrees open.
potentiometer to mid position.
Turn DCV maximum position potentiometer to fully CCW. Actuator drives fully closed.
Turn minimum position potentiometer to midpoint. Actuator drives to 45 degrees open.
Turn minimum position potentiometer fully CW. Actuator drives fully open.
Turn MIN POS to fully CCW. Actuator drives fully closed.
W7212: Remove jumper from TR and N. Actuator drives fully closed.
W7214: Jumper TR to O.
6. MIXED AIR INPUT
Execute step one, Checkout Preparation. —
Turn DCV MAX to mid position; set enthalpy potentiometer to A. Free cool LED turns on.
Actuator drives to 45 degrees open.
Remove 5.6K ohm resistor (green sleeve) and place jumper from T and T1. Actuator drives to 45 degrees open.
Remove jumper from T and T1 and leave open. Actuator drives fully closed.
21 63-2596—09
W7212, W7213, W7214 ECONOMIZER LOGIC MODULES
Table 4. Checkout for W7212, W7213, W7214 Economizers Connected to Honeywell Actuator. (Continued)
Step Checkout Procedure Proper Response
7. HEAT PUMP INPUT - W7213, W7214 ONLY
Execute step one, Checkout Preparation. —
Turn DCV MAX to mid position; set enthalpy potentiometer to A. Free cool LED turns on.
Actuator drives to 45 degrees open.
W7213: Jumper TR to B. Free cool LED turns off.
W7214: Remove jumper from TR and O. Actuator drives fully closed.
63-2596—09 22
W7212, W7213, W7214 ECONOMIZER LOGIC MODULES
23 63-2596—09
W7212, W7213, W7214 ECONOMIZER LOGIC MODULES