Professional Documents
Culture Documents
Operating Instructions
GB
Note: This document contains short form instructions for experienced users. Technical data:
Use last column in List of Parameters to document your individual settings.
Power supply 24VAC ±10%; 50/60 Hz; Class II
More detailed information can be found in the User Manual.
Power consumption 4VA max.
Communication TCP/IP Ethernet 10MBit/s
Terminals Removable screw terminals
wire size 0.14 … 1.5 mm2
Temperature
storage -20 … +65°C
operating 0 … +60°C
Pressure sensor input 24VDC, 4 … 20mA
Fan output relays Inductive (AC15) 250V / 2A
The EC2-712 has been designed to control condensers with up to four fans. The Resistive (AC1) 250V / 6A; 12A total return current
purpose of the controller is to keep condensing pressure to a minimum by
Digital inputs Volt free contacts 5V/0,1mA
switching fans on or off.
Humidity 0 … 80% rh. non condensing
Protection class IP65 (front protection with gasket)
Marking
Mounting
The EC2-712 can be mounted in panels with a 71 x
29 mm cutout. See dimensional drawing below for
space requirements including rear connectors.
Push controller into panel cutout.(1)
Make sure that mounting clamps are flush with
outside of controller housing
Insert allen key into front panel holes and turn
The PT5 pressure transmitter (5) senses condensing pressure and feeds the signal clockwise. Mounting clamp will turn and gradually
into a condensing pressure dead band control loop. Condensing pressure is move towards panel (2)
modulated by turning fan motors on and off. Turn allen key until mounting clamp barely touches
No change occurs as long as the condensing pressure remains within the dead band panel. Then move other mounting clamp to the same
(P1) around the condensing pressure setpoint (P0). The controller will add/remove position (3)
fan capacity when the condensing pressure goes beyond the limits of the Tighten both sides very carefully until controller is
condensing pressure dead band. For stable condenser operation, adjustable time secured. Do not over tighten as mounting clamps
delays for fan motor on and off are available. To avoid premature wear of will break easily.
individual fan motors, run time equalization is built into the controller.
Condensing Pressure
Electrical Installation
A fast recovery procedure can be used to immediately switch off all fans when the Refer to the electrical wiring diagram
condensing pressure falls below a set limit. Similarly an emergency routine can be (right) for electrical connections. A copy
activated automatically if the condensing pressure exceeds a definable limit. of this diagram is labelled on the
controller.
Use connection wires/cables suitable for
! Safety instructions: 90°C operation (EN 60730-1).
• Read installation instructions thoroughly. Failure to comply can result in EC2 analog inputs are for dedicated
device failure, system damage or personal injury. sensors only and should not be connected
• The product is intended for use by persons having the appropriate to any other devices. Volt free digital
knowledge and skills. inputs should only be connected to serial
• Ensure electrical ratings per technical data are not exceeded. control loops or relays with gold
• Disconnect all voltages from system before installation. contacts. They should not be connected
• Keep temperatures within nominal limits. to any other devices
• Comply with local electrical regulations when wiring Important: Keep controller and sensor wiring well separated from mains wiring.
Minimum recommended distance 30mm.
Warning: Use a class II category transformer for 24VAC power supply
(EN 60742). Do not ground the 24VAC lines. We recommend to use one
transformer per EC2 controller and to use separate transformers for 3rd party
controllers, to avoid possible interference or grounding problems in the power
supply. Connecting any EC2 inputs to mains voltage will permanently damage the
EC2.
OF Node is offline
The node is offline and no application is running. This is the result of a
network management command and will happen for example during node
installation.
Fan controller
/ DISPLAY PARAMETERS Min Max Unit Def Individ. u STEP ENABLE PARAMETERS Min Max Unit Def Individ.
u0 Reset operating time 0 5 - 0
/1 Value to be shown on display 0 2 - 0 0 = do nothing
0 = Fan states 1 = reset operating time fan 1
1 = condensing pressure (bar) 2 = reset operating time fan 2
2 = condensing temperature (°C) 3 = reset operating time fan 3
4 = reset operating time fan 4
5 = reset operating time all fans
r SENSOR PARAMETERS u1 Enable/disable fan 1 0 1 flag 1
r0 Condensing pressure sensor -1.0 50 bar 0.0 u2 Enable/disable fan 2 0 1 flag 1
minimum value
u3 Enable/disable fan 3 0 1 flag 1
r1 Condensing pressure sensor -1.0 50 bar 30
u4 Enable/disable fan 4 0 1 flag 1
maximum value
r2 Pressure offset for condensing -1.0 1.0 bar 0.0
C APPLICATION PARAMETERS
pressure
C1 Number of fans 1 4 - 4
r3 Refrigerant type 0 5 - 4
C4 Fan 1 (0 = standard control loop 0 1 - 0
0 = no temperature conversion;
1 = fan 1 act as base load)
1 = R22; 2 = R134a; 3 = R507; 4 = R404A; 5 = R407C
C5 Fan switch logic (Rotation) 0 1 flag 1
0 = FILO logic (First In, Last Out)
P SET-POINT PARAMETERS Capacity demand: Adds first fan.
P0 Pressure set-point (condensing) for -1.0 50 bar 14.0 Capacity excess: Removes last fan.
fan circuit 1 = Rotation enabled
P1 Pressure band (dead band for dead 0.0 50 bar 4.0 Capacity demand: Adds fan with lowest runtime out of
band control mode) available fans.
P3 Fast recovery from low pressure -9.9 50.0 bar 9 Capacity excess: Removes fan with highest runtime out of
P4 Enable set-point compensation 0 1 - 0 available fans.
0 = disabled; 1 = enabled C6 Number of fans to switch on in case 0 4 - 0
P5 Maximum pressure compensation -3.0 3.0 bar -3.0 of sensor failure
P6 Temperature at minimal shift value -50.0 50 °C 30
(0) H OTHER PARAMETERS
P7 Temperature at maximal shift value -50.0 50 °C 15.0 H2 Keyboard and IR remote control 0 3 - 3
(Shift Max) 0 = all disabled
P8 High discharge pressure recovery. -9.9 50 bar 20 (Caution, access to controller only via network possible)
1 = Keyboard enabled
t TIME PARAMETERS 2 = IR remote control enabled
t1(1) Time delay before adding capacity 0 99 10sec 3 3 = Keyboard and IR remote control enabled
t2(1) Time delay before removing capacity 0 99 10sec 3 H3 IR remote control access code 0 199 - 0
H5 Password 0 199 - 12
A ALARM PARAMETERS
A2 Minimum condensing pressure -1.0 50 bar 10.0
alarm limit
A3 Maximum condensing pressure -1.0 50 bar 27
alarm limit
A4(1) Delay time for minimum pressure 0 99 10sec 0
alarm limit
A5(1) Delay time for maximum pressure 0 99 10sec 0
alarm limit
A8(1) Fan serial alarm delay 0 99 10sec 0
A9(2) Fan run limit 0 99 10000hr 0
(1)
These values have a resolution of 10 sec, on the local display. Ex. A value 1 means 10 sec.
(2)
These values have a resolution of 10.000 hours, on the local display. Ex. A value 1 means 10.000 hours.
• Note: Concerning the indicated parameters, it is recommended to check, before installing, if the factory value is suitable for the required use
Emerson Electric GmbH & Co OHG is not to be held responsible for erroneous knowledge of today. It is intended only for use by persons having the appropriate
literature regarding capacities, dimensions, applications, etc. stated herein. technical knowledge and skills, at their own discretion and risk. Since conditions of
Products, specifications and data in this literature are subject to change without use are outside of EMERSON’s control we cannot assume any liability for results
notice. The information given herein is based on technical data and tests which obtained or damages occurred due to improper application.
EMERSON believes to be reliable and which are in compliance with technical This document replaces all former versions
Emerson Electric GmbH & Co OHG - Postfach 1251 - Heerstraße 111 - D-71332 Waiblingen - Germany - Phone .49-(0)7151-509-0 - Fax .49-(0)7151-509-200
www.emersonclimate.eu