LENGTH LENGTH

4-16mm DIA. CONTINUOUS 10MM DIA. STIRRUPS SP. @ 4-12mm DIA. CONTINUOUS BARS 10MM DIA. STIRRUPS SP. @ 6-12mm DIA. CONTINUOUS BARS 0.15m thk. CHB
BARS 3-50MM, 3-100MM AND REST 3-50MM, 3-100MM AND REST EXTERIOR WALL
@ 200MM @ 200MM
10mmØ VERT. REINF. BARS
SPACED @ 0.60m O.C.
10mmØ HOR. REINF. BARS
EVERY 3 LAYERS OF CHB

FFL
4-16mm DIA. CONTINUOUS
BARS 200
L/5 EARTHFILL
200 NGL
2-12MM DIA.

250
4-12mmØ,2-12mmØ RSB

200
2-16MM DIA. 2-12MM DIA.
W/10mm TIES

250
SP.@0.25m O.C.
2-12MM DIA.
2-16MM DIA. 200

SCALE 1:20 SCALE 1:20

1 TIE BEAM DETAILS 2 ROOF BEAM DETAIL 3 WALL FOOTING


S 2 SCALE 1:40 S 2 SCALE 1:40 S 2 SCALE 1:40

849 3125

849 725 800 800 800 STRUCTURAL NOTES


1. IN THE INTERPRETATION OF THESE DRAWINGS, INDICATED
857 DIMENSIONS SHALL GOVERN. DISTANCES OR SIZES SHALL NOT

1031
457 BE SCALED FOR CONSTRUCTION PURPOSES.
400

2. INCASE OF CONFLICT IN DETAILS OR DIMENSIONS BETWEEN


C-PURLINS 2"X3"X1.2mm THE ARCHITECTURAL AND ENGINEERING DRAWINGS, REFER TO

198
THE CIVIL ENGINEER FOR FINAL DECISIONS.
.5mm LONG SPAN ROOFING
3. ALL WORKS SHALL CONFORM TO THE FOLLOWING CODES:
A. NATIONAL STRUCTURAL CODE OF THE PHILIPPINES
10mm SAGROD (NSCP)
B. AMERICAN CONCRETE INSTITUTE (ACI-318)
784 6125 829
C. AMERICAN INSTITUTE OF STEEL CONSTRUCTION (AISC)
2L-ABAR 121" X 121" X 4mm
800
(TOP & BOTTOM CHORD) FOUNDATION
300

800
225

7851
1. ASSUMED SOIL BEARING CAPACITY qu=120KPA
454

800 2L-ABAR 121"


X 121" X 4mm 2. THE CONTRACTOR SHALL NOTIFY THE DESIGNER IN THE EVENT
800 (WEB MEMBER)
800 THE ASSUMED SOIL BEARING CAPACITY IS BELOW 120KPA
800 3. NO FOOTING SHALL REST ON FILL.
4. MINIMUM PROTECTION FOR REINFORCEMENT SHALL BE
1704

800
475 50MM FOR CONCRETE DEPOSITED AGAINST FORMWORKS.
1250

846 75MM FOR CONCRETE DEPOSITED AGAINST THEGROUND.


1031

400
CONCRETE AND REINFORCEMENT
1. UNLESS OTHERWISE SPECIFIED, THE MINIMUM 28TH-DAY
CYLINDER COMPRESSIVE STRENGTH ARE AS FOLLOWS

160
SLAB ON GRADE-------------------------------------17.25 MPA
BEAMS AND COLUMNS----------------------------20.70 MPA
FOOTINGS----------------------------------------------20.70 MPA
2. STEEL REINFORCEMENT FOR 227MPA SHALL CONFORM TO
ASTM A-36M
4 TRUSS DETAILS CHB WALL
S 2 SCALE 1:50 1. FOR EXTERIOR WALL, USE 150 MM THICK CHB
2. FOR INTERIOR WALL, USE 100MM THICK CHB.

STRUCTURAL STEEL
1. ALL STRUCTURAL STEEL SHALL CONFORM TO ASTM A-36.
2. WELDING SHALL CONFORM TO AWS STANDARDS.

Drawings and Specicifications duly signed, or PROJECT TITLE SHEET CONTENT REVISION : APPROVED BY : SHEET NO.
CIVIL ENGINEER
stamped or sealed as instrument of service are the
properties of the Architect, whether the project for TIE BEAM DETAILS DRAWN BY: LSC

which they are made is executed or not. It shall be


S-2
ROOF BEAM DETAILS

unlawful for any person, without written consent of WALL FOOTING


DESIGNED BY:
the Architect or Author of the said documents for PROPOSED 4BEDROOM BUNGALOW HOUSE
TRUSS DETAILS

REG.NO.: PTR NO.:


use in the repetition of and for other projects or
buildings, whether executed partly or in whole. LOCATION :
STRUCTURAL NOTES
BEAM SCHEDULE
CHECKED BY: OWNER
5
DATE ISSUED : PLACED ISSUED : PD. 49 (RA 545) DATE: