TRANSFORMER OIL TEST RESULTS

RATING : 30 MVA ( After ) S.No. : BTR 3 - 731886-4 Make : HITACHI

YOM : 1976 Trafo Category : B Voltage Ratio : 132 KV Testing Date : 10-08-2020

Oil Temperature : 40 °C Sampling Date : 10-08-2020 Location : KTGTPS GRID

Recommended action limits as per


ns

n
tio

io
IEC Category

at
ica

S# Property Units Results

fic
si
cif

O, A, D B, E C

as
e

Cl
Sp

Kinematic viscosity
1 mm2 / sec 9.70 - < 12
' (at 40 0C )
60296

2 Density (at 20 0C) g/ml 0.824 - < 0.895


IEC

Flash Point 0 > 135


3 C 156 -

Good Clear & without visible contamination


4 Appearance Visual Dark Yellow Poor Dark and/or turbid

Good < 0.10 < 0.10 < 0.15


5 Acidity mg KOH /g 0.070 Fair 0.10 to 0.15 0.10 to 0.20 0.15 to 0.30
IEC 60422

Poor > 0.15 > 0.20 > 0.30


Good > 60 > 50 > 40
6 Breakdown voltage : kV 87 Fair 50 to 60 40 to 50 30 to 40
Poor < 50 < 40 < 30
O & A B & D C & E
7 Water Content ppm 11 Good < 15 < 20 < 30
Fair 15 to 20 20 to 30 30 to 40
Poor > 20 > 30 > 40
DISSOLVED GAS
Reference Limits
ANALYSES

1 Hydrogen (H2) ppm 0 < 1800


IEEE C57.104 - 2008

2 Methane (CH4) ppm 0 < 1000

3 Acytelene (C2H2 ) ppm 0 < 35

4 Ethylene (C2H4 ) ppm 0 < 200

5 Ethane (C2H6 ) ppm 0 < 150

6 Carbon monoxide (CO) ppm 75 < 1400

7 Carbon dioxide (CO2) ppm 179 < 10,000

Remarks :

Tested By : SYED SAMIULLAH Reviewed By :

Report. No. : TO - 05-08-2020 TSW - MATERIAL TESTING LABORATORY

Issue / Rev: Jul-19

Doc. No. F/MTL/01 page 1/1