Professional Documents
Culture Documents
A30
EXCITATION
CONTROLLER
HANDBOOK
9592020-00
REVISION D
ISSUE
February 2001
Operating and Maintenance Manual
for
PRISMIC A30
Excitation Controller
2
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
3
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
CONTENTS
1 INTRODUCTION................................................................................................................................... 6
2 RATINGS.............................................................................................................................................. 7
3 FEATURES........................................................................................................................................... 8
3.1 Complete system housed in a single 19” 6U rack........................................................................... 8
3.2 Independent main and hot standby excitation channels .................................................................. 8
3.3 PC Based Setup and Maintenance Software..................................................................................8
3.4 Communication Port #1 for SCADA communications...................................................................... 8
3.5 Communication Port #2 for set up and maintenance. ...................................................................... 8
3.6 Choice of setpoint adjustment method............................................................................................8
3.7 Line Voltage Control Mode............................................................................................................. 8
3.8 Power Factor Control Mode............................................................................................................ 8
3.9 VAr Control Mode...........................................................................................................................8
3.10 Soft Start Facility............................................................................................................................8
3.11 Fast Acting Field Current Limiter.................................................................................................... 9
3.12 Over Excitation Limiter ...................................................................................................................9
3.13 Under Excitation Limiter................................................................................................................. 9
3.14 Over Flux Limiter............................................................................................................................9
3.15 Selectable Standby System Control Mode ......................................................................................9
3.16 Rotating Diode Failure Alarm.......................................................................................................... 9
3.17 Adjustable Step Response............................................................................................................. 9
3.18 Event Recorder..............................................................................................................................9
4 HARDWARE DESCRIPTION .............................................................................................................. 11
4.1 The A30-RACK1 Mainframe......................................................................................................... 11
4.2 A30-CON card .............................................................................................................................13
4.3 A30-MON card.............................................................................................................................20
4.4 Utilities Card................................................................................................................................. 23
4.5 Standby Control Card................................................................................................................... 24
5 COMMISSIONING ..............................................................................................................................29
5.1 EMC Installation and Operating Guidelines................................................................................... 29
5.2 Pre-commissioning Checks.......................................................................................................... 30
5.3 Check Operation of DC Contactors, Switches and Indications with Machine at Standstill .............. 30
5.4 Check Standby Control................................................................................................................ 32
5.5 Check A30-CON and A30-MON Settings......................................................................................34
5.6 Check Display of Measured Parameters on the A30-CON and A30-MON card ............................35
5.7 Check Null Balance Indication when in Standby........................................................................... 35
5.8 Set-up Stability in Main Channel – Check this section ................................................................... 35
5.9 Check the Voltage range of the A30-CON card ............................................................................. 36
5.10 Check Soft Start...........................................................................................................................36
5.11 Check for Smooth Changeover from Standby to Main Channel ..................................................... 37
5.12 Check/Set-up Over Excitation Limiters and Monitors ..................................................................... 37
5.13 Over Voltage and Over Flux Monitors...........................................................................................39
5.14 Set/Check the Under Voltage Monitor Level................................................................................. 39
5.15 Check Parallel Operation.............................................................................................................. 40
5.16 Check Under Excitation Limiter.................................................................................................... 40
5.17 Check Under Excitation Monitor................................................................................................... 41
5.18 Check Power Factor Control (if applicable)................................................................................... 41
5.19 Check VAr Control (if applicable).................................................................................................. 42
5.20 Check the VAr Shed (if applicable)...............................................................................................42
5.21 Check Parallel Operation in Standby Line Voltage Control ............................................................43
5.22 Static Interrogation.......................................................................................................................43
6 INSTALLATION AND MECHANICAL DETAILS, CARD FITTING AND REMOVAL...............................44
6.1 Installation.................................................................................................................................... 44
6.2 Ventilation.................................................................................................................................... 44
6.3 Wiring to the A30 Excitation Controller.........................................................................................44
6.4 Wiring to the Plug.........................................................................................................................44
6.5 Safety .......................................................................................................................................... 45
4
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
5
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
1 INTRODUCTION
The PRISMIC A30 Excitation Controller is designed to control the excitation of a brushless generator.
Incorporating a wide range of features, the A30 is housed in a 19" rack assembly requiring only external
instruments and control switches to provide the complete excitation system as shown in Fig. 1.
For setup and commissioning of the A30 a PC is required. PC based software and two serial comms
cables are provided.
A copy of the factory test record and factory setup data is provided with the A30 in the form of a Brush
QC(T)48 document. When provided with a Brush generator, the A30 factory setup data will be matched
to the generator. The QC(T)48 document should be available when commissioning the A30.
6
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
2 RATINGS
Max field voltage for forcing 75% of single phase supply RMS voltage
Weight 14.5kg
7
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
3 FEATURES
Includes power semiconductor and control circuits, power supply transformers, contactors for
excitation changeover and field suppression and field suppression resistor.
The unit contains two power semiconductor circuits, one acting as a hot standby to the other.
Each circuit is controlled by an independent control card with automatic following to enable
smooth transfer from one to the other.
Transfer to the standby system is initiated by a separate monitor module in the following
circumstances:
• Voltage monitoring (over/under voltage on generator terminals)
• Excitation monitoring (over/under excitation with time delays)
• Control card failure
The settings for the monitor module are selected to enable the normal limiter settings to operate
first. (see Fig.1 Generator Capability Diagram)
The unit is provided with PC based setup and maintenance software and cable for connection to
a standard PC 9 pin serial port. A PC is required to setup the A30.
Provided to allow plant supervision computers to adjust setpoints and inspect generator and
excitation system data. Implemented using Modbus protocol.
In Line Voltage Control Mode, line voltage is controlled to a constant adjustable setpoint. In this
mode, parallel running capability is provided using quadrature current compensation (QCC) with
an adjustable droop setting.
After switching on excitation, line voltage is increased to the nominal level at an adjustable rate.
8
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Limits excitation current to prevent excessive line current during power system faults.
Using inverse time delay and temperature compensation if required, this facility is provided to
prevent overheating of the generator rotor.
This facility enables operation of the generator at maximum capability with a leading power
factor but avoiding the danger of the generator pole slipping.
Excitation is controlled to ensure that generator line voltage is limited to a preset adjustable
voltage / frequency ratio to avoid over fluxing of the generator.
The standby system may be setup to operate in either Generator Voltage or Exciter Field
Current Control Mode.
Detection of failed rotating diode or fuse is achieved by monitoring the ripple content of exciter
field current.
This facility enables an adjustable step increase in setpoint to be applied to evaluate the stability
settings of the excitation system. The PID parameters of the AVR may then be adjusted
accordingly. The rise time and overshoot values are recorded to help with commissioning.
The step reduction in setpoint may be used to evaluate the response of the underexcitation
limiter.
A log of major events, such as limiter and monitor operations, and field suppression is
maintained within the unit. The events may be displayed using a PC connected to the
commissioning comms port.
9
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
10
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
4 HARDWARE DESCRIPTION
The mainframe is a 19", 6U rack. At the front, on the left, is a fixed panel. Next is a vertically
hinged panel and, at the right, is a printed circuit Backboard that carries four pairs of sockets for
the plug-in cards.
A printed circuit board (the Auxiliaries Board) is fixed towards the top of the left-hand side plate.
This board carries four fuses, which are accessible on the fixed front panel. At the rear of the
board there are two, 16-way sockets. The board is also associated with the transformer that
provides the ac supply for the Main channel electronics power supply. The Auxiliaries Board
also contains four small, plug-in relays, PSR, FRS, ECCS and FSCS.
On the inside of the left-hand side plate, below the auxiliaries board, are mounted two
contactors, ECC and FSC and the field discharge resistor, FSR.
The mainframe has a substantial heat sink at the rear on which are fitted two separate, half-
controlled, single-phase bridges. These are used for the Main and Standby excitation systems.
Also mounted on the heat sink are a ballast resistor (BR) and a small PCB that provides voltage
suppression for the two bridges.
Connections to the mainframe are via six, 16-way sockets. Two of these, mentioned above, are
on the auxiliaries board while the remaining four are mounted on the Backboard and all provide
access at the rear. Facilities for connecting the higher current cables for the PMG and exciter
field are provided on a rail-mounted terminal block on the back of the unit.
A 25-way, serial communications socket is also provided at the rear of the unit.
In Main control, the PMG supply is connected via FSC-1, ECC-2, and ECC-3 to the
half controlled bridge comprising SCR1, SCR2, D1, and D2. The positive output of the
bridge is connected to the exciter field via DB1, FSC-2, FSC-3 and FSC-4. The
negative of the exciter field is connected through current measuring resistors R7 and
R8, to the negative of the Main and Standby power circuits which are commoned.
Note! The negative of the exciter field is earthed;the PMG must not be earthed.
In Standby control the PMG supply is connected via FSC-1, ECC-1 and ECC-4 to the
half controlled bridge comprising SCR3, SCR4, D3, and D4. The positive output of the
bridge is connected to the exciter field via DB2, FSC-2, FSC-3 and FSC-4. As in Main
control, the negative of the exciter field is connected through R7 and R8 to the
negative of the Main and Standby power circuits.
11
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Incorporated in the rack are a contactor (FSC) and a resistor (FSR) used
for suppression of the exciter field. Three contacts, FSC-2, FSC-3 and
FSC-4, are connected in series with the exciter field, each having a section
of FSR connected across it.
As these contacts open to suppress the field, current flows through FSR,
giving rapid decay of exciter field current.
A third contact, FSC-1, is used to break the ac supply from the PMG.
Contact FSCS-1 is used to input the state of FSC to the A30-CON and
A30-MON card via Q/24 on the main frame.
The contactor is mechanically latched so that a failure in the coil supply will
not produce any change in the contactor state. When the contactor is in the
tripped condition (recognised by the control button on the latching
mechanism being out) the field is suppressed.
In this condition the Standby power circuit is disconnected from the PMG
by ECC-1 and ECC-4 and from the exciter field by DB2.
Resistors R7 and R8, which are located on the Backboard measure exciter field
current. IC1 and IC2 amplify the low voltage signal before supplying it to the Main
Control, Monitor and Standby cards.
12
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Line current supplied to terminals 134 and 133 is supplied to current transformers T3
(for A30-CON and A30-MON) and T4 (for Standby). Links are provided across the
output of T3 to select for 5A or 1A primary (equivalent links are provided on the
Standby card).
Note! The Standby, A30-CON and A30-MON cards can be removed without open
circuiting the CT supply although the 5A / 1A feed should be shorted before removing
rear plugs.
The control card contains the microprocessor and its associated digital addressing circuitry,
digital counter timer, signal conditioning circuitry, thyristor firing pulse isolation circuitry, digital
input and output ports, and serial communication ports, see Figure 5.1.
This board carries a smaller mezzanine board, the A30-M188, which contains the majority of the
microprocessor-allied components. A large proportion of these is contained in an FPGA (Field
Programmable Gate Array – IC4) which is configured on power up by boot ROM IC3. The
EPROM (IC11-A) containing the working software is also on this board.
13
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
A 32MHz crystal (XTAL1) controls the Microprocessor (IC7) timing. It can be reset
either by the operation of the push button marked `Micro Reset' on the front panel or
by the watchdog (1C1) whenever the software stops updating the watchdog.
The memory address circuits (IC6-A,IC8-A and IC9-A) produce a 17-bit address.
128K of volatile RAM is fitted (IC10_A) and 8K of non-volatile memory EEPROM is
fitted to store the commissioning and operator adjusted settings when the AVR is shut
Two serial RS232-C ports are available for local and remote communication.
Two transformers on the Utilities card (T1 and T2) isolate the three-phase line voltage
before this is supplied to the A30-CON card. The voltage is then rectified and buffered
by IC3c to produce a smoothed dc voltage at TP9. Links 5A and 5B are used to select
the gain and smoothing according to whether single or three phase sensing is
required.
The dc output voltage of IC3b is fed to a voltage to frequency converter (IC12) whose
output frequency is proportional to the line voltage. This series of pulses is then
buffered and read into a counter timer, inside the FPGA on the A30-M188, over a fixed
sampling period to provide a number which is proportional to line voltage.
14
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Figure 5.2 shows the route between the sensing terminals and the control card.
The line current signal is supplied to current transformer T3 and T4 on the Backboard.
The current sensing signal for the A30-CON card is produced across R2 (1A primary)
or R1 (5A primary) connected across the output of T3. This ac voltage is fed to the
A30-CON card where it is rectified and smoothed by IC3a and IC3c before being fed
to voltage to frequency converter IC2 whose output frequency is proportional to line
current.
15
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Figure 5.3 shows the route between the current sensing terminals and the control
card. Table 5.1 shows typical voltage levels with 5A or 1A CT selections at rated or
test levels of CT current
16
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
The field current is measured by two resistors R7 & R8 connected in series with the
exciter field, and mounted on the Backboard. The low voltage signal is amplified by
IC1 on the Backboard and then fed to the A30-CON card.
The signal is then supplied to a voltage to frequency converter IC1 whose output is
proportional to exciter field current.
Figure 5.4 shows the circuitry used for exciter field current measurement. The dc
voltage on TP4, with respect to TP1, should be approximately 0.33 x the reading of
the field current ammeter.
17
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Any change in resistance of the RTD results in a change in the input signal to amplifier
IC3d, whose output is connected to a voltage to frequency converter IC5 to give a
frequency signal which is related to RTD temperature.
Figure 5.5 shows the circuitry used for temperature measurement with typical voltage
levels.
18
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
The PMG voltage is isolated by transformer T2 on the auxiliaries board and supplied
to the A30-CON card where it is rectified by D11 & D12. The rectified signal is
compared to a negative signal and the difference amplified by IC7-D to produce a
narrow pulse at TP16 every zero crossing of the PMG voltage. This signal is used to
reset a counter in the FPGA on the A30-M188.
A number calculated in the software (called DEMAND) is loaded into a counter timer
every half cycle of the PMG voltage. Each time the PMG waveform passes through
zero, the time begins to count, and when the counter reaches the number called
Demand’
‘ the thyristor is fired via a pulse transformer.
When the firing pulse is produced the counter is reset and begins counting again on
the next zero crossing of the PMG waveform.
External control panel inputs such as volts raise, volts lower, PF control, VAr shed etc
are optically isolated from the A30 electronic circuitry. Each input is de-coupled to filter
any transient spikes in the auxiliary dc supply. It can be used for 24/48V or 110/125V
dc supply, Link A being fitted for 24/48V supply, and Link B is fitted for 110/125V
supply.
19
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
4.3.1 Introduction
The A30-MON card contains the microprocessor and its associated digital addressing
circuitry, digital counter timer, signal conditioning circuitry, digital input and output
ports, and serial communication ports. A Mezzanine Board, the A30-M188 carries the
majority of the microprocessor components. This board is identical to the one on the
A30-CON card except for the software contained in the EPROM.
It is similar to the A30-CON card, except it does not have the thyristor firing circuit and
the PMG voltage input. See Figure 5.8.
A 32MHz crystal (XTAL1) controls the Microprocessor (IC7) timing. It can be reset
either by the operation of the push button marked `Micro Reset' on the front panel or
by the watchdog (1C1) whenever the software stops updating the watchdog.
The memory address circuits (IC6-A,IC8-A and IC9-A) produce a 17-bit address.
128K of volatile RAM is fitted (IC10_A) and 8K of non-volatile memory EEPROM is
fitted to store the commissioning and operator adjusted settings when the AVR is shut
down.
20
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Two serial RS232-C ports are available for local and remote communication. An HMI
can be connected to the local communication port via a `Comms' link to display
contract settings.
Two transformers (T1 and T2) isolate the three-phase line voltage on the Utilities card
before being supplied to the A30-MON card. The voltage is then rectified and buffered
by IC4d to produce a smooth dc voltage at TP4. Links 2A and 2B are used to select
the gain and smoothing according to whether single or three phase sensing is
required.
21
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
The dc output voltage of IC4d is fed to a voltage to frequency converter (IC3) whose
output frequency is proportional to the line voltage. This series of pulses is then
buffered and read into a counter timer over a fixed sampling period to provide a
number which is proportional to line voltage.
Figure 5.2 shows the route between the sensing terminals and the A30-MON card and
typical voltage measurements with 110V sensing signal applied.
The line current signal is supplied to current transformer T3 and T4 on the Backboard.
The current sensing signal for the A30-MON card is produced across R2 (1A primary)
or R1 (5A primary) connected across the output of T3. This ac voltage is fed to the
A30-MON card where it is rectified by IC10b and smoothed by IC10a before being fed
to voltage to frequency converter IC8 whose output frequency is proportional to line
current.
Figure 5.3 shows the route between the current sensing terminals and the A30-MON
card with typical voltages and 5A or 1A flowing.
The field current is measured by two resistors R7 & R8 connected in series with the
exciter field, and mounted on the Backboard. The low voltage signal is amplified by
IC2 on the Backboard and then fed to the A30-MON.
The signal is then supplied to a voltage to frequency converter IC1 whose output is
proportional to exciter field current.
Figure 5.4 shows the circuitry used for exciter field current measurement. The dc
voltage on TP15, with respect to TP1, should be approximately 0.348 x the reading of
the field current ammeter.
Figure 5.5 shows the circuitry used for temperature measurement with typical voltage
levels.
External control panel inputs such as field suppression contactor and monitor inhibit
etc. are optically isolated from the A30 Excitation Controller electronic circuitry. Each
input is de-coupled to filter any transient spikes in the auxiliary dc supply. It can be
used for 24/48V or 110V dc supply, Link A being fitted for 24/48V supply, and Link B is
fitted for 110/125V supply.
22
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
4.4.1 Introduction
The Utilities card contains ±15V and 5V-dc power supplies, and line voltage sensing
transformers for the A30-CON and A30-MON cards. Relays associated with AVR
logic, monitoring and indication facilities, together with the diode failure detector are
also included.
Figure 5.9 shows the circuitry that supplies the Utilities card with typical voltage levels
indicated. Allowance should be made when measuring transformer voltages for
different PMG voltage levels to those shown.
The PMG voltage on U1/5 and U1/9, supplied by the transformer T1 on the auxiliaries
board, is rectified by the diode bridges (DB2 and DB4) and smoothed by C2 and C8.
This unregulated dc voltage is then fed into a 5V dc regulator (IC1 or IC3) and the 5V
output supplied to A30-CON and A30-MON cards LED's 3 & 4 provide indication that
the 5V supply is energised. IC2 and IC4 monitor the 5V rail. If an over voltage
condition occurs, thyristor 1 or 2 will be fired and cause fuse FS3 or FS1 to rupture.
The transformer T1 on the auxiliaries board supplies the PMG voltage on U1/15,
U1/17, U1/19 and U1/21. The diode bridges DB1 and DB3 rectify this AC voltage. The
unregulated dc voltage is then fed into two zener diodes to produce ±15V for the A30-
CON and the A30-MON cards. The transistor VT1 and VT2 provide a constant current
source for the ±15V supplies. LED's 1 and 2 provide indication that the ±15V supplies
are energised.
23
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
A +9V dc power supply for the hand-held terminal. The dc voltage present at the
output of DB4 is fused by FS5 (100mA) and regulated at 9V by VT3, Z11 and
associated components before being supplied to a socket on the front plate of the
Utilities card.
Note! This feature is not used on the A30 Excitation Controller.
Input signals to the card include monitor trip at U2/18, general alarm at U2/24, and
limiter on at U2/20, are given by the A30-MON card and the A30-CON card. Logic 0’ ‘
at these terminals causes the corresponding FET3, FET5 or FET4 to turn on. This in
turn gives a corresponding LED indication and energises relays that provide external
indications.
Diode or fuse failure in the rotating assembly is detected by sensing ripple induced in
the exciter field current caused by unbalanced loading of the exciter output.
The voltage across R7 and R8 is amplified by IC2 on the Backboard and then supplied
to the diode failure circuit on the Utilities card.
Excessive ripple is detected by IC5b whose output is normally high and goes low
when ripple is detected. The output of IC5b if fed via D16 and R50 to IC5a which turns
on FET 2 after a time delay. FET2 turns on FET1 to energise the diode failure relay
RL1/1 and turn on LED 7 on the Utilities card.
The unit is supplied with fixed sensitivity but by fitting LK1, adjustable increasing
sensitivity is provided as RV1 is turned clockwise. Fitting LK2 and rotating RV1
clockwise can reduce the sensitivity.
4.5.1 Introduction
The Standby control card contains all the electronic circuitry to control the Standby
power circuit housed in the mainframe. It is designed to be independent of the Utilities,
A30-CON and A30-MON cards.
The power supply is derived from the PMG voltage applied to the primary of T3 via
FS1 and FS2. Links are used to select the correct PMG voltage.
The ±12V dc supplies are produced by VT1, VT2, Reg 1 and Reg 2 and associated
components. The supply is monitored by LED 3 to provide front of panel indications,
and IC9d that provides an isolated signal to the A30-MON card indicating the state of
the Standby power supply.
Figure 5.10 shows the simplified circuitry associated with the Standby power supply.
24
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
IC4, 3 and 1 form a 12 bit up down counter controlled by the raise/lower logic
described in Chapter 4.5.10.
The counter is limited to a maximum count when the 8 most significant bits reach logic
`1'. Under this condition the output of IC12 falls to logic `0' forcing the next clock pulse
to reduce the count.
Similarly, when the counter is in its `fully down' state the outputs will be at logic `0' and
provide minimum reference current.
At Standby minimum Pin 6 of IC4 and Pin 7 of IC1 are both zero which causes the
output of IC6c to fall to `0' and turn on FET 2 giving indication of Standby at minimum,
whilst simultaneously removing further clock pulses via IC8a and IC8c.
The thyristor in the Standby power circuit are phase controlled to provide the required
Standby output voltage. To control the instant of firing a triangular waveform at TP4
that is synchronised to the PMG output voltage is compared to a dc voltage at TP16.
When the voltage at TP4 exceeds that at TP16 the output of IC4d becomes positive
and thyristor firing pulses are produced by oscillator IC16a and associated
components. FET3 is pulsed on and transformer T2 supplies pulses to the gate of
thyristor SCR3 and SCR4.
The output of the Standby regulator is fed to the Standby card terminal S2/11. It is
then attenuated, smoothed and supplied via LK14 to the input of an amplifier, where it
is compared to the digital reference signal. The difference or error signal is amplified
and then inverted by IC4b and IC4c to produce a signal at TP16 that controls the firing
angle.
25
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
If the output of the Standby regulator is higher than the reference, the voltage at TP16
becomes more positive and the firing angle is retarded.
Line voltage is supplied to the Standby control card at S2/2 and S2/1. It is isolated by
T1 and rectified, attenuated and smoothed, and then supplied via LK15 to the input of
IC46 where it is compared to the digital reference signal. The error is amplified and
then inverted to produce a signal at TP16 that controls the firing angle. A line current
signal supplied at S1/1 and S1/3 provides a drooping voltage/lagging VAr
characteristic (QCC) LK12 is fitted for a 1A and LK13 is fitted for 5A current sensing.
Figure 5.11 shows the simplified circuits associated with field voltage and line voltage
control.
Figure 5.11 Simplified Circuits Associated with Field Voltage and Line Voltage Control
4.5.7 Stabilising
The field voltage signal present at C32 is smoothed by R74, 78, 79 (as appropriate)
and C21 and is then conditioned by IC11b and associated components and supplied
to the input of the error amplifier via C25, RV2 and R71. RV1 provides adjustment of
the quantity of stabilising signal provided and RV2 provides adjustment of the phase
shift. Links 25, 26 and 28 are set according to the exciter field time constant, refer to
table 14.3, Chapter 14.
The output of the Standby regulator at S2/11 is attenuated, smoothed and then
supplied to the input of an amplifier, IC11a, where it is compared to a reference signal.
26
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
If the attenuated field voltage exceeds the reference, the output of IC11a becomes
negative and the excitation is limited to that level by the signal flowing through LK24,
D5 and R83 to the input of IC15C. RV5 provides adjustment of the setting, and LK24
can be removed to inhibit the limiter if required.
The line voltage signal at the input of DB1 is converted to a triangular waveform at
TP22 whose height increases as frequency reduces.
When the frequency falls below a pre-set level set by RV3, the voltage at TP22
causes the output of IC10c to switch positive which provides a signal to the 12 bit
counter to set its output to zero via D9 and LK7. Links 8 and 9 select the cut-off
frequency for 50/60Hz machines.
When Standby mode is selected, the auto follower mode is turned off since no signal
is applied to S1/5. To raise the digital reference, auxiliary dc should be connected to
S1/11, or PB2 on the card should be closed. Provided the counter is not already at its
upper limit, TP9 at the output of IC5a becomes positive and TP10 also becomes
positive to gate the clock pulses (generated by IC5b and associated components) to
the counter.
Applying the dc supply to S1/9 or operating PB1 on the card lowers the digital
reference. In this case, TP9 is driven to a low level to make the clock pulses reduce
the counter setting.
When the raise or lower signals are removed the counter remains at its current setting.
The null balance detector compares the instant at which the Main channel and
Standby channel thyristor firing pulses occur and produces meter and LED indications
to show whether Standby is firing later than Main i.e. `STANDBY LOW', or earlier than
Main i.e. `STANDBY HIGH'. Signals are also produced by the null balance detector to
automatically match the firing angle of the Standby regulator to that of the Main. This
means that when Standby is selected from Main, it is set to the correct level.
Conversely, when in Standby, control signals are produced by the null balance
detector, which are supplied to the A30-CON card to match the firing angle of Main to
that of Standby. By this means it is possible to run on Standby and check
automatically that null balance can be obtained to indicate the state of the Main
channel.
The null balance detector receives a firing pulse signal from the A30-CON card at
S1/27, which is supplied, to IC14a. The firing pulse signal from the Standby pulse
circuit is supplied to IC14a and IC14b and are arranged to produce voltages at TP2
and TP3 which are equal when the firing angle of Main and Standby are balanced.
Any difference in firing angle is amplified by IC13b whose output is driven positive
when Main is higher than Standby and vice verse. The null balance meter is driven
from the output of IC13b through current limiting components.
27
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
IC13c and IC13d are voltage comparators arranged to produce raise and lower
signals to the auto follower, and also to give local LED indication of Standby high or
low. Due to the fast response to the null balance measurement circuits, fluctuation of
the null balance meter and Standby high/low LED's is normal particularly when
following an AVR channel.
When operating in Main without any excitation limiters operating, internal relay logic
applies the dc auxiliary supply to S1/5 which turns on opto isolator IC9a and drives the
output of IC7a to logic 1. LED 6 on the Standby card is also turned on to indicate
`Main Control' channel operation.
If the counter is not at the upper or lower limit, an `UP' or `DOWN' signal from the null
balance detector will set TP9 to level `1' to raise or `0' to lower, and drive TP10 to a
logic `1' to gate the clock pulses to the counter.
The counter is adjusted and the reference changed which results in a change in the
voltage at TP16 and a subsequent change of Standby firing angle. By this means, the
difference between Main and Standby firing angle is minimised.
When the Standby reference is at minimum, Pin 6 of IC4 and Pin 7 of IC1 become
zero and the output of IC6c falls to zero preventing any further lower signals via IC8a
and IC8c. At the same time FET 2 is turned on, RL2 is energised, and LED 5 turned
on to give Standby at minimum indication.
The Main channel ±15V supply is applied to S1/19 and S1/21 and provides a signal to
opto isolator IC12d. Loss of this supply causes RL1 and LED 4 to be turned on via
FET 1. A contact on RL1 causes FRS in the mainframe to energise and select the
Standby system.
28
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
5 COMMISSIONING
The A30 Excitation Controller is industrial equipment and meets the essential requirements of
the EEC EMC Directive 89/336/EMC when installed and operated in accordance with the
following guidelines.
5.1.1 Installation
Mobile phones and 'walkie talkies' should not be used near the equipment unless
covers are fitted and panel doors closed. Furthermore, the antenna power of such
transceivers should not exceed 5 watts and they should not be operated at a distance
less than 1 metre from the equipment.
5.1.3 Wiring
For excitation systems, for EMC purposes, signal and power cables may be classified
as follows:
29
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
5.1.4 Operation
The equipment must be used for the application for which it is designed and operated
within its specified duty. All outgoing relay contacts and switches must be used within
their rating and should be suppressed when used to switch inductive loads.
WARNING
If Standby control is to be used to excite the machine whilst running short circuited either for protection
testing or drying out it is essential that it is selected for FIELD VOLTAGE control as described in parts
5.4.1 to 5.4.3. (a). Line current and exciter field current should be carefully monitored at this stage.
Prior to commissioning the micro AVR unit, it is important to complete commissioning of the
protection system for the generator and associated power equipment. Having verified that these
are correct the following preliminary checks should be made on the excitation system: -
(1) Check that the PMG output is correctly wired and that PMG out
put is not earthed in its
terminal box.
(2) Check that the sensing signals (CTs and PTs) are correct in polarity and phasing.
(4) Check that all wiring external to the AVR is secure and correct to the contract circuit
diagram. Ensure that the earth stud is solidly earthed.
(5) Visually check that the AVR has not been physically damaged during transit to site. Ensure
that the contactors and other auxiliary equipment have not been disturbed and that the internal
wiring is secure. Check that the plug-in cards are correctly aligned and fully inserted.
(6) Check that the correct links are fitted to the AVR as detailed in the A30 Excitation Controller
test certificate QC.48. Standby card links should be in the despatch position.
(7) Check that the software version and check sums shown on the A30-CON and A30-MON
EPROMs and Boot ROM (IC11 and IC3 on the A30-M188) correspond to those given in the A30
Excitation Controller test certificate QC.48.
(8) Ensure that the auxiliary dc supply voltage corresponds to that indicated in the A30
Excitation Controller test certificate QC.48.
The A30 Excitation Controller is now ready for commissioning as detailed below. The following
information should be read in conjunction with any specific contract commissioning notes.
5.3 Check Operation of DC Contactors, Switches and Indications with Machine at Standstill
(1) Remove FS1 and FS2 (on the left hand, fixed, front panel). Apply the auxil
iary dc
supply and confirm correct value and polarity is applied to AVR terminals 1 (positive)
and 2 (negative) on Plug 5 at the rear of the AVR.
(2) Replace FS1 and FS2 and check that power supply monitor relay PSR is energised.
This relay is on the Auxiliaries board and its position is indicated on the diagram on
the inside of the hinged door. If outgoing contact PSR-1 is used for indication, check
correct indication is given.
30
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
(3) Check the correct operation of the following switches in local control nd
(a remote
control if applicable).
Simulate an exciter field trip signal and check FSC trips and FSCS de-
energises. Check FSC energises when the trip signal is reset. Confirm
correct excite/suppression indication via FSCS-2 if applicable.
Note! The nature of the circuit ensures that the voltage present on
the `opposite' terminal (e.g. TM 152 when a lower signal is given) is only
about 0.5V less than the target terminal.
31
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
5.4.1 Check Excitation Isolator is Off and Select Field Voltage Control.
Check that FSC is tripped (field suppressed) and Standby control selected. Ensure
that the Standby card is initially set to exciter field voltage control with the links set to
give this condition (refer to the QC.48 document.
Check that the PMG voltage and the PMG frequency are in accordance with that
specified on the QC.48 document. Close the excitation isolator to apply the PMG
supply to the AVR and reset FSC. Check that the following indicators are on:
(a) Operate the Standby raise switch on the control panel for approximately 1
second. Note that LED 5 goes off. Repeatedly pulse the raise switch,
pausing for a few seconds each time, and note that the exciter field current
begins to increase accompanied by an increase of line voltage. Confirm
from the excitation data on the QC.48 that the line voltage corresponds to
the value of field current.
(b) Set the line voltage to nominal and check that fine adjustment of voltage
can be obtained using the Standby raise/lower switches.
(d) Trip excitation and check that voltage collapses to residual. Open the
excitation isolator.
(e) Field voltage limiter setting: (This has been pre-set but may be checked if
necessary as follows):
32
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
iii) Close the excitation isolator and reset FSC, slowly increase
the setting of the Standby regulator until the voltage measured
across Tm8 and Tm9 reaches a ceiling level whereby further
raise signals make no difference, or until it is 20V above the
limit level specified in QC.48. If necessary, adjust the limiting
level by trimming RV5 on the Standby card using the extender
card to gain accessibility.
iv) Trip excitation. Turn the isolator to OFF. Replace the exciter
field connection to terminal 8. Remove the dc voltmeter.
iii) Slowly reduce the machine speed and check that the exciter
field current remains approximately constant until the speed
reaches approximately 85% nominal at which point it falls to
zero.
iv) Increase the machine speed to nominal and check that the
excitation remains at zero.
v) Trip FSC.
If Standby is to be left in Field Voltage Control Mode, (see QC.48 document) this
procedure may be omitted
(b) Close the excitation isolator and reset FSC. Note that the Standby at
Minimum (LED5) is turned on.
(c) Operate the Standby raise switch (again repeatedly pulsing the raise
switch and pausing for a few seconds each time) and observe gradual
increase of line voltage. Set the line voltage to nominal.
(d) The response of Standby voltage control can eb set using stabilising
controls Stab Q (RV1) and Stab P (RV2), accessible through the front
panel of the card. A useful starting point is to set Q (RV1) and P (RV2) ten
turns clockwise, reduce Q until the voltage begins to fluctuate, and then
turn Q clockwise to stabilise voltage. When the AVR is stable, exciter field
voltage should be steady.
Trip FSC. Turn the excitation isolator to OFF.
33
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
(e) The open circuit response can be optimised to give a particular response
by use of the 10% step change in reference PB3 on the card. Ideally, a
digital storage scope or UV response recorder should be used with a three
phase back-off unit. P and Q should be adjusted to give and open circuit
single overshoot of approximately 20% (of the step) with optimum rise time
and settling time. Further adjustments may need to be made on load to
give a particular response.
Note! The design settings for the contract are given in the QC.48 document . Any deviation
from the settings should be recorded in the `site settings' column and a copy should be returned
to Brush Electrical Machines Ltd.
5.5.1 Preliminary
Depress the `DF Test' pushbutton on the Utilities card; check that LED7 on
the Utilities card is illuminated after a 1-3 second delay.
Connect the HMI (HMI) with the control commissioning software installed to the control
card by inserting the comms cable into comm port 2 on the front of the card. Run the
HMI software and confirm communication by noting that the cursor in the bottom right
hand corner of the monitor is rotating.
Select the `edit maintenance presets' menu. Step through the each item sequentially
and check that the settings of each parameter correspond to the design settings
provided in the QC.48 document . Where a card is set up at the factory, the settings
are stored in E2PROM and should not change.
34
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Connect the HMI with the monitor commissioning software installed to the monitor
card by inserting the comms cable into comm port 2 on the front of the card. Run the
HMI software and confirm communication by noting that the cursor in the bottom right
hand corner of the monitor is rotating.
Select the `edit maintenance presets' menu. Step through the each item sequentially
and check that the settings of each parameter correspond to the design settings
provided in the QC.48 document. Where a card is set up at the factory, the settings
are stored in E2PROM and should not change.
5.6 Check Display of Measured Parameters on the A30-CON and A30-MON card
Reset Excitation by energising the excite input to FSC and raise Standby to produce nominal
line voltage indicated on the panel voltmeter. Use the HMI (Main Display) and check the
sensing line voltage, frequency, and exciter field current. Do this on the A30-MON and A30-
CON card. If the under volts monitor operates ignore it at this time (LED 6 on A30-MON card)
Confirm that the voltage and current values agree with the panel instruments. If calibration is
necessary refer to Chapter 8.
Also confirm that the A30-CON card displays the correct PMG frequency.
Turn off SW1 in the mainframe and check that the null balance indicator shows Standby high,
and that LED 2 on the Standby card is on.
Turn on SW1 in the mainframe. Check that the null balance meter returns to its centre position
after a short delay and LED 1 and LED 2 on the Standby card flicker when balance is indicated
on the meter.
Check that LED 1 on the A30-CON card is continuously on also indicating balance of the A30-
CON to the Standby. Also check that LED 6 on the A30-CON card is off, indicting that the alarm
that indicates that the Control Card is out of Balance with standby is OFF.
Select the Diagnostics Display and confirm that the HMI indicates Matched’
‘ in the Standby
Follower portion of the display.
(1) When running the generator on open circuit in standby control, ensure that the main
channel is matched using the HMI follower display or alternatively check the LED1 on
the A30 control card is continuously illuminated. Disable the UV Monitor via the
Enable/Disable Software Modules button on the monitor HMI.
(2) Confirm that the settings of the stabilising controls (prop Gain, Integral Gain, Diff Gain,
Boost Duration, P Boost, Boost Band) are set to the values shown in the QC (T) 48,
unless optimum stabilising settings have previously been established.
35
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Select Main.
Note: The PID stabilised settings given on the QC(T)48 are preliminary and may
require optimisation on the contract but in the event that they are unsuitable
settings of P=60, I=100 and D=50 provide a good starting point.
Optimisation of the stabilising settings is described in chapter 10 of this
handbook
(3) The PID stabilising settings given on the QC.48 are preliminary may require
optimisation on the contract.
This may be carried out initially by running the machine on open circuit and using the
VRef Step Up Test facility to produce a sudden increase in the reference voltage of
the AVR. This is accessed via the Activate/Deactivate Tests menu on the control HMI.
The size of the step is adjustable and the default setting of 5% is recommended.
Typically, the settings will be adjusted to achieve an overshoot of approximately 20%
(of the step) with an acceptable rise time. Use of the Diagnostics Display to display
overshoot and rise time will help to select the best settings. The Trend Data which
shows the shape of the voltage transient will also be helpful but is not updated
frequently enough to provide an accurate trace of the voltage response.
In some cases it may be necessary to optimise the stabilising settings by performing
load application and rejection tests to check the response.
Once the required response is achieved, the response data from the stability menu
should be recorded.
(1) Select self-centring by linking TML112 and TML17 and confirm that line voltage
returns to its nominal value. The rate at which the voltage set point is changed is the
same as the VRef Adjust Rate in the maintenance presets menu.
Disable the under voltage and over voltage monitors on the A30-MON card HMI
(Enable/Disable Software Modules menu).
(2) Use the Main channel voltage lower/raise controls to adjust line voltage and ensure
minimum and maximum settings are equal to the settings in the QC.48 document.
If operation of the over flux limiter prevents the maximum setting being obtained it will
be necessary to disable the over flux limiter and monitor after first ensuring no
equipment can be damaged by over voltage during the test.
(3) Enable the under voltage monitor and the over voltage monitor on the A30-MON card.
Enable the over flux limiter and monitor if disabled during this test.
Remove excitation by de-energising the “Excite”input and momentarily energising the “Trip”
input to the FSC as shown on Drawing B9630996. (The PMG isolator switch should not be
used.)
36
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Ensure that the “Trip”input to the FSC is de-energised and reapply excitation by energising the
“Excite”input to FSC. Observe that line voltage builds up slowly without large oscillations or any
significant overshoot.
Check that the null balance meter and standby LED’s indicate that standby is matched to main
and select standby. Lower standby and using the A30-CON HMI in the Diagnostics Display
(Standby Follower Panel) observe that Vref follows V Sensing. Note that when the line voltage
is below the minimum setting of V Ref, no further reduction is possible and LED1 on the CON
card begins to flash continuously. Note that after a delay, indication of mis-balance is given by
LED 6 being turned on and also on the HMI.
Increase the setting of standby to rated voltage and observe that balance is once more
obtained, indicated by LED 1 being on continuously and LED 6 turning off. Select Main and
check that there is negligible change in line voltage. If necessary the transient can be adjusted
using the Smooth Changeover P and D gain values in the maintenance presets.
Note! If the excitation requirement is less than 1.5A on open circuit the Fast OE
Limit Ref. should be reduced for this test.
(d) Adjust the Over Excitation Monitor Set Point to 5A (Maintenance Presets
menu), and enable the OE Mon x4 SensitivityEnable/Disable
( Software
Modules menu, F8).
37
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Note! If field current is limited to between 1.25A and 1.5A for this
test, the monitor tripping time will be correspondingly longer.
(g) Turn off the X4 sensitivity on the A30-MON card (Enable/Disable Software
Modules menu). Reset the monitor using the reset pushbutton.
(a) Adjust the Over Excitation Monitor Set Point (Maintenance Presets menu)
to the level given in the QC.48 document.
(b) Turn off the Fast OEL x8 Sensitivity and then the OEL x4 Sensitivity on the
control card (Enable/Disable Software Modules menu, F8 ).
Adjust the Fast OE Limit Ref (Maintenance Presets menu)to the level
given in the QC.48 document.
Adjust the OE Limit at 0ºC (Maintenance Presets menu) to the level given
in the QC.48 document.
(a) Connect a resistance of 100Ω between terminals 116 and 117. Terminals
116 and 118 should be connected together. Use the HMIEnable/Disable
(
Software Modules menu, F8) to enable the OEL Temp Compensation
module on the control card. Check that the OE Limiter Ambient
Temperature Compensation is set according to the QC.48 document.
Check that the A30-CON HMI (Main Display) indicates a temperature of 0
±2°C.
(c) Connect a resistance of 115Ω between terminals 116 and 117. Terminals
116 and 118 should be connected together.
On the A30-MON HMI (Main Display) check that the temperature reading
40°C ±2°C and that the Actual OE Mon Trip Point is below the 0 deg C Trip
Point.
On the A30-CON HMI (Main Display) check that the temperature reading
40°C ±2°C and that the Actual OE Limit is below the 0 deg C Limit.
(d) Reconnect the RTD to terminals 116, 117 and 118. Adjust the line voltage
to nominal in Standby. Check for Null balance and transfer to `Main'.
38
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
(b) Set the OverVolts Monitor Set Point 5% above the VT Nominal and the
OverVolts Monitor Delay to 30% second. (Maintenance Presets menu).
Raise the excitation in `Main' and set the sensing voltage to 10% above VT
Nominal.
(d) Lower the line voltage to the nominal level in Standby and reset the Over
Volts Monitor using the pushbutton on the A30-MON card.
(a) Run in Auto, at 100% volts and, use the HMI to set the OverFlux Monitor
Set Point to 1.1 pu (Maintenance Presets menu).
(b) Whilst running at rated speed, note the Flux Monitor Trip Point (Main
Display) which should be 10% above VT Nominal (any slight difference
could be due to frequency not being exactly at nominal). Increase the line
voltage to just above the monitor trip point (temporarily disable Flux Limiter
on the A30-CON if necessary) and note that the Flux Monitor Timer begins
to increasing slowly. Confirm that the monitor trips to standby when the
timer reaches 100% and that LED 7 on the A30-MON is turned on.
(c) Reduce the line voltage to nominal; reset the Flux Monitor, check for null
balance and transfer to Main.
(d) Set the Over Volts and Over Flux Monitor Set Points and Delays
(Maintenance Presets menu) to the levels given in the QC.48 document.
Confirm that the Over Flux Limit Set Point (Maintenance Presets menu) is
set to the level given in the QC.48 document.
(1) Use the HMI to disable the Under Volts Monitor Enable/Disable
( Software Modules
menu, F8). Set the Under Volts Monitor Set Point 5% below the VT Nominal and the
Under Volts Monitor Delay to 30% second (Maintenance Presets menu).
(2) Lower the excitation in Main to 10% below the nominal voltage.
Use the HMI to enable the Under Volts Monitor. Check that LED 6 on the A30-MON
card is illuminated and the AVR is tripped to Standby after approximately 6 seconds.
(3) Raise the line voltage to the nominal level in Standby and then reset the Under Volts
Monitor using the reset pushbutton on the A30-MON card. Check for null balance and
transfer from `Standby' to `Main'.
39
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
(4) Set the Under Volts Set Point and Delay (Maintenance Presets menu) to the level
given in the QC.48 document.
Check that the Over Flux Limiter Ref and Delay (Maintenance Presets menu) are set
to the levels given in the QC.48 document.
(1) Check excitation isolator is off and that FSC is tripped (field suppressed). Select the
Standby card to exciter field voltage control by fitting the links in the despatch position
shown on the QC.48 document.
(2) Close the excitation isolator and reset FSC. Raise the line voltage in Standby and set
it to nominal. Use the HMI (Maintenance Presets menu) to check that the QCC on the
control card is set to 15% and the QCC is turned on.
(3) Prepare to synchronise the generator with the grid system i.e. minimum slip, voltage
difference and phase difference.
(4) Close the paralleling breaker at the correct instant and check that the line
current
remains at a low constant value. In the event of line current suddenly increasing,
immediately open the breaker.
(5) Check that the sensing line current given by HMI (Main Display) on the A30-CON and
A30-MON cards are the same as the reading on the secondary CT line current. If
calibration is necessary refer to Chapter 8.
(6) Raise excitation in Standby to produce approximately 20% rated VArs lagging. Use
the A30-CON HMI (Diagnostics Display) and check that VControl is less than VRef
indicating that the line voltage will reduce as lagging VArs increase.
If this is not the case, the AVR CT and VT phasing is incorrect and must be re-
checked after shutting down the machine.
(7) Check for indication of null balance and transfer from `Standby' to `Ma
in' and check
that there is no sudden change in excitation or VArs.
(8) Confirm that VArs can be adjusted easily by raising or lowering the AVR setting using
the customer’s switches
(9) Depending upon the external reactance Xe and the configuration of ethsystem, the
amount of QCC should be reduced to a level that gives stable control of VArs as the
AVR datum is adjusted. Typically the QCC is set at 4% for Xe = 0.
(1) Run the machine in parallel with the grid system under M
ain AVR control at zero or
light load.
Check that the Under Excitation Limiter Software is enabled (Diagnostics Display) and
(Enable/Disable Software Modules menu, F8 ). Check that the Leading ISinØ Limit and
the external reactance (Xe) are set as shown in the QC.48 document. (Maintenance
Presets Menu).
40
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
(2) Slowly reduce the excitation observing the status of the UELimiter in the Diagnostics
Display. (Note: the Limit@0MW indicates only when running at leading PF)
Check that the Leading VArs are limited to alevel close to the set point and that the
excitation is reasonably stable. UE Limiter P, I D gains can be adjusted if necessary
(Maintenance Presets Menu)
Unless Xe is zero, the limiting level of VArs will reduce as power increases. Check that
LED 4 on the control card is on when limiting.
(3) Slowly raise the excitation to come off the under excitation limit.
(4) If possible check the characteristic of the under excitation limiter by measuring the
operating points of different load levels and plotting them on the capability diagram.
(5) The transient response of the UE Limiter can be observed using the VRef Step Down
facility (Activate/Deactivate Tests) refer to section 10 for details of this and UEL
stabilising adjustment.
(a) If continuing from previous test, run the machine in parallel at light load,
zero VArs.
(c) Check that the UE Monitor Software and Output are enabled (Main
Display) enabling if necessary. On the UE Monitor check that the Leading
ISinØ limit and the external reactance Xe (Maintenance Presets menu) are
set to the levels given in the QC.48 document.
(2) With the machine running in parallel with the grid supply at zero or light load, slowly
reduce the excitation observing in the Main Display the status of the UE Monitor. This
will show the timer start when the operating level is exceeded. Check that the UE
Monitor trips to Standby when the timer reaches 100% and that that LED 4 of the A30-
MON card is turned on.
(3) Raise Standby excitation and set the VArs to zero. Reset the monitor, check for null
balance between the AVR and standby and transfer from `Standby' to `Main' control.
(4) If possible, check the characteristic of the UE Monitor by measuring the operating
point at different load levels and plotting them on the capability diagram.
(5) Reduce VArs to zero and power to a low level under Mai n control. Enable the Under
Excitation limiter on the A30-CON card E
( nable/Disable Software Modules menu, F8 ).
(2) Run the set in parallel with the grid on Main control ta10% VArs lagging, 10% power.
Select PF Control and check that LED 5 on the A30-CON card is on.
41
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
(3) Use the Panel Switches to set the PF Ref to unity using the Main Display to observe
the PF Ref and the status of the panel switches.
(4) Enable the PF/VAr/VAr shed software (Enable/Disable Software Modules menu, F8
)
and check that the VArs are reduced to zero and remain stable.
(5) Adjust the PF Reference using the PF/VAr Raise/Lower panel switches to the required
setting (the set point is shown in the Main Display) and check that the PF is controlled
to the required level and is stable over the full range of power.
The rate at which the PF Reference is changed may be set in the Maintenance
Presets Menu.
If it is necessary, the PF Gain and PF Slug may be used to optimise the response of
the PF Controller.
(6) If it is required to adjust the PF Reference via the HMI, the Panel/HMI switch should
be set to HMI, and the PF Reference is then adjusted using the Edit Operator Presets
menu. In this case it is necessary to select whether the required PF Ref is Leading or
Lagging using the Activate/Deactivate Modes menu on the HMI.
(2) Run the set in parallel with the grid on Main AVR control at 10% VArs lagging. Check
that VAr control is selected and that LED 8 on the A30-CON card is on.
(3) Use the Panel Switches to set the VAr Ref to zero using the Main Display to observe
the VAr Ref and the status of the panel switches.
(4) Enable the PF/VAr/VAr shed software E( nable/Disable Software Modules menu, F8
)
and check that the VArs are reduced to zero and remain stable.
(5) Adjust the VAr Reference to the required setting using the PF/VAr Raise/Lower panel
switches (the set point may be observed in the Main Display) and check that VArs are
controlled to the required level and are stable over the required range of power.
The rate at which the VAr Reference is changed may be set in the Maintenance
Presets Menu.
If it is necessary, the PF Gain and PF Slug may be used to optimise the response of
the VAr Controller.
(6) If it is required to adjust the VAr Reference via the HMI, the Panel/HMI switch should
be set to HMI, and the VAr Reference is then adjusted using the Edit Operator Presets
menu. In this case it is necessary to select whether the required VAr Ref is Leading or
Lagging using the Activate/Deactivate Modes menu on the HMI.
(1) Parallel the set to the grid and then load the set with 10% of the generator MW. Raise
Main excitation to increase the lagging VArs to 10% of the generator capacity.
(2) Initiate `VAr Shed'. Check that LED 7 of the A30-CON is turned on. Check that the
VArs are reduced to zero and are controlled independently of the set MW.
42
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
If Standby is to be operated in Field Voltage control mode (see QC.48) this procedure may be
omitted.
(1) Slowly reduce the VAr and MW load on the generator. Open the grid breaker. Open
the excitation isolator switch. Check that FSC is tripped (field suppressed). Select the
Standby card to line volts control by fitting the links specified in the QC.48 document.
(2) Close the excitation isolator and reset FSC. Adjust the line voltage to nominal voltage
in Standby. Prepare to synchronise the generator with the grid system, i.e. minimum
slip, voltage difference and phase difference.
(3) Synchronise to the grid and check that the line current remains at a low constant
value. In the event of it being high or increasing, immediately open the breaker.
(4) Check that the VArs can be easily adjusted by changing the voltage setting point of
the Standby regulator.
(5) Check that the null balance meter is positioned at the centre. Tr
ansfer from `Standby'
to `Main'.
(6) Slowly reduce the VArs and the MWs on the generator. Open the grid breaker.
If the PMG supply is not available because the machine is not running, it is possible to use an
alternative ac supply to power the electronics. This will allow interrogation of the AVR by using
the PC and HMI software.
After working with the A30 using an alternative power supply ensure that the wiring is restored
and links re-set.
43
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
6.1 Installation
The A30 Excitation Controller is primarily designed for mounting into a standard 19" rack
cabinet, but can be mounted on any sturdy panel with a suitable cutout. Where the unit is fitted
into a cutout, some form of vertical stiffening is required behind the panel at each side of the
cutout to support the cantilevered weight of the unit. For fixing dimensions, refer to drawing no.
B 9630865 – see appendices.
In addition to the above stiffening, it is advisable to either provide support under the rear of the
unit, or to remove the unit during transit. If channels are provided either side of the AVR so that
the unit `sits' on these when in position, these will ease subsequent removal for inspection and
maintenance.
A minimum of 300mm must be provided in front of the unit to allow the plug-in cards to be fitted
into the extender card when commissioning/fault finding.
6.2 Ventilation
It is important to ensure a free air space of 150mm above and below the unit to allow adequate
thermal cooling of the unit.The top cover of the AVR is perforated to allow ventilation, and
should not be obstructed or covered.
Connections to the AVR are made to a fixed terminal rail and to 6 removable plugs for light
current connections. The fixed terminals rail is suitable for cables up to 4 square mm and the 6
light current plugs are suitable for cables up to 2.5mm² (if a crimped ferrule is used refer to 1)
All connections use a cage clamp type of terminal in which the clamping force adjusts
automatically to the conductor cross-section. The flat clamping face of the cage clamp spring
presses the conductor against the current bar without damage. Any deformation or movement
of the conductor is automatically compensated so eliminating the risk of a loose connection.
The types of conductors that are suitable are shown in Figure 8.1.
A sound earth connection must be made to the earth terminal at the rear of the AVR.
Care should be taken not to allow debris to drop through the cover of the AVR during
installation.
6.4.1 Method 1
(a) Firmly secure the plug in the approximate final position (the ideal way to do
this is to insert the plug into its socket on the A30 Excitation Controller).
(b) Strip back the insulation from the cable to a distance of 7mm to 8mm or fit
a crimped ferrule if a contract requirement.
(c) Insert the cage clamp tool or a small screwdriver into the terminal to open
the cage clamp, and insert the cable ensuring that the clamp grips the
conductor and that no stray strands are left exposed. See Fig 8.3.
44
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
6.4.2 Method 2 (using the special lever to open the cage clamp)
(b) Holding the plug in the hand, depress the special lever and insert the cable
into the clamp. See Fig 8.2.
(c) Release the lever and check that no cable strands remain exposed.
6.5 Safety
The A30 Excitation Controller should be installed in a manner so the rear connections cannot be
accidentally touched when the equipment is energised.
The A30 Excitation Controller is a standard 19" wide rack, 6u high, of overall dimensions
483mm wide, 266mm high, 400mm deep. Approximate weight is 14.5kg.
Drawing no. 9630865 (see appendices), shows the overall dimensions of the unit, the card
positions and positions of the rear connections.
WARNING Take anti-static precautions when handling cards. Ensure that you are
earthed (grounded) by using a wrist strap or similar device. An earth connection terminal is fitted
in the centre or the front right hand mounting bracket of the AVR to which a wrist strap may be
clipped.
Electronic cards can be damaged by static discharge and should be carried in anti static
protective containers wherever practicable. They should always be stored and transported in
anti static bags or boxes.
Each plug-in card is fitted with a captive securing screw and a card insertion/ejector mechanism
top and bottom.
To remove a card, first ensure that the mainframe switch SW1 is turned off if removing the
Utilities, A30-CON or A30-MON card. The two retaining screws should be released and the
ejector levers gently pushed apart to jack the board out of the rack.
To insert a board, ensure that the mainframe switch is off if fitting the Utilities, A30-CON or A30-
MON card. Push the ejector levers apart, and then insert the card in the correct position until
resistance is felt. Gently pull the levers together to draw the card into the rack. Finally, tighten
the two captive screws.
45
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
46
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Figure 8.2 Connection of Conductors - Side entry with lever for self-mounting
47
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
The A30-CON, A30-M-CON and A30-MON cards are setup using a PC connected using the supplied
serial commissioning cable. The commissioning software, (referred to as the Human Machine Interface
or HMI application), is supplied on a CD.
The software runs under Windows (NT4.0 or 95/98), and should install automatically when the
CD is inserted. If autorun is disabled on your PC the setup.exe application can be run directly
from the CD.
Using the supplied A30-COMCAB serial commissioning cable, connect the PC COM1 serial port
to the COM2 serial port of the card requiring setup.
48
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
On startup, the HMI will request the name and location of the event log file (see 7.4). To accept
the default, click on open’
‘ . The A30-MON and A30-M-CON cards have separate log files. The
HMI will remember the last card in use, and will ask for this log file on startup.
The HMI application can be used to work with various Brush PRISMIC Excitation Controller
circuits including the A30-MON, A30-M-CON, A30-CON cards. The menu File ‘ / Configuration’
selects which circuit the HMI software is required to work with. The A30-COMCAB serial cable
must be used to connect the COM1 port on the PC to the correct excitation controller circuit as
required.
The HMI software indicates healthy communication with the unit to be setup by showing a
rotating ’/’ symbol in the bottom right corner of the display.If this symbol is stationary, there is
no communication and the HMI cannot be used to display relevant data.
Close Close the HMI application in the normal manner for any Windows application, i.e. select
Exit’
‘ from the File’
‘ menu, press [Alt][F4] etc
When the HMI software is running, a screen should be displayed showing a diagram of the
generator and AVR system with some active values displayed. A number of other child windows
or “Displays”may also be viewed. The layout of the displays may be altered to suit the task in
hand, see section Error! Reference source not found. below. Display and window settings are
retained when the software is shut down.
The different functions of the HMI software are invoked using the standard Windows menus at
the top of the HMI window, and the row of buttons across the bottom.
49
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
The HMI can be used to adjust and display excitation controller settings. After commissioning
the HMI will normally be disconnected unless required for testing or diagnostic purposes.
HMI displays are accessed using the top menu bar. Multiple displays can be shown at the same
time. The displays can be re-sized and re-positioned if necessary. To move a display, highlight
the window. Left-click on the blue title, keeping the button down, and drag the window to its
desired location.
The Displays’
‘ menu contains 7 or more data tables:
Displays 1 – 3 typically show measured parameters, limiter and monitor operation, set point
values, selected mode of control etc.
Displays 4 - 7 typically show diagnostic information, the status of the various control functions,
switch settings. Stabilising settings and response measurements etc.
7.7 Logfile
The Event Log file records actions performed by the A30, together with a time and date stamp.
Log files are not overwritten – they are continued when the HMI program is next run.
Whenever the program is switched to controlling a different card, the log file for that card must
be specified.
The contents of all holding registers can be saved as a text file, to disk. The menu item
Logging’
‘ / Save
‘ registers to file’performs this. The text file can be printed out, or emailed as
necessary. An option to save the preset registers only, is also available under the same menu.
50
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
7.9 Passwords
To prevent accidental or unauthorised alteration of the AVR settings, two passwords are
provided as follows:
When adjusting presets, the passwords time out after 1 minute, and must be re-entered to make
further changes.
These passwords are not changeable and are intended to provide only a medium level of
security. To provide a higher level of security, access to this handbook and the HMI should be
controlled.
The following describes a typical configuration of the local HMI. In some instances the actual
HMI provided will vary slightly from the description given.
51
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Panel Switches PF Control These are functional provided the mode selection
Indicates the status VAr Control method is set to panel
‘ switches’
of switches, which VAr shed
may be mounted on Self Centre
the control panel. Volts Raise These are functional provided the panel local/HMI
Volts Lower switch is set to panel’
‘
PF Raise
PF Lower
Main/Standby
Panel/HMI
52
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
53
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Indicates the time when a change in the status of selected events occurs
.
BuildUpEnabled
FieldSuppressed
StandbyControlSelected
Booster On
OELimiterActive
FastOELimiterActive
UELimiterActive
FluxLimiterActive
RemoteAdjustOnPanelSelected
UEMonHealthy
OEMonHealthy
UVMonHealthy
OVMonHealthy
DiodeFailureDetected
MonSupervisoryHealthy
AllowDumpToE2PROM
E2PROMModesCRCError
E2PROMOldPresetCRCError
E2PROMPresetsCRCError
The trend display is used to show the value of the selected variable over a particular
time span. The speed of communication is such that the trend display is unsuitable for
accurately displaying generator response, but can be useful for displaying long term
changes.
Maintenance presets are used to set up an AVR for a particular contract. An AVR
which has not had its maintenance presets adjusted will contain values, which must be
changed to suit the machine before turning on excitation.
When the maintenance presets are changed, they are loaded into non-volatile
memory and are preserved when the AVR is turned off.
Presets
‘ / Maintenance Preset / Maintenance presets’allows the maintenance presets
to be viewed. Double – clicking on a value in the table allows the maintenance presets
to be changed.
The following table gives an example of the available maintenance presets. An actual
application may differ slightly
54
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
55
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Operator Presets are preset values that the operator may adjust during normal
operation.
Selection of the control mode may be made by hard-wired signals connected to the
AVR, or by signals provided by the local or remote HMI. Mode selection via HMI is
only possible when the Activate
‘ PF/VAr/VAr shed Via HMI’has been activated via the
modules’
‘ menu.. Unless this is active, mode selection is via hard-wired signals.
The HMI can be used to activate/deactivate modes provided. The status of the HMI
commands to select modes can be viewed in the main displays.
Use of this menu allows different software modules to be disabled if not required by
the application or during testing.
56
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
The Displays’
‘ menu contains 7 data tables:
Displays 1 – 3 give details of measured parameters, monitor status, operating levels, etc
The following describes a typical configuration of the HMI. In some instances the actual HMI
provided will vary slightly from the description given.
57
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
58
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Indicates the time when a change in the status of selected events occurs.
The trend display is used to show the value of the selected variable over a particular
time span. The speed of communication is such that the trend display is unsuitable for
accurately displaying generator response, but can be useful for displaying long term
changes.
59
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
This display is used to view the current values of holding registers and holding bits.
Maintenance presets are used to set up an AVR for a particular contract. An AVR
which has not had its maintenance presets adjusted will contain default values, which
must be changed to suit the machine before turning on excitation.
When the maintenance presets are changed, they are loaded into non-volatile
memory and are preserved when the AVR is switched off.
Presets
‘ / Maintenance Preset’allows selection and viewing of the relevant
maintenance preset page, Double clicking a value allows a maintenance preset to be
changed.
The following table gives an example of the available maintenance presets. An actual
application may differ slightly.
60
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Use of this menu allows different software modules to be disabled if not required by
the application or during testing. Status of s/w modules can be viewed in the Main or
Diagnostics displays.
Use of this menu simplifies testing of individual monitor time delays by first disabling
the monitor using the menu accessed via the monitors’
‘ button.
The monitored parameter is then set to a known level whilst running in standby.
When the tester is activated, the monitor output is turned on for 0.5 sec, then the
timing period commences. The time delay can be calculated from the event log display
contents. The tester is deactivated automatically after 0.5 sec, at which point the
monitor is automatically enabled.
61
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
The COM1 port on the front of the A30-CON card may be used to connect an external computer system
such as a SCADA system to the A30 for monitoring of generator data and adjustment of set-point.
An alternative 25 way D connector is available in the rear of the A30-RACK. Links must be set on the
A30-CON card to select whether the front or the rear SCADA comms connector is to be used.
The SCADA communications cannot be used for commissioning, and operates independently of
the commissioning HMI.
Protocol: Modbus RTU, A30 acting as slave, SCADA system acting as master.
Slave Number: 1
Front Connector
COM1 - 9 way male D type connector on front of control card provides isolated
RS232C requiring the following connections:
Pin 2 – receive data
Pin 3 – transmit data
Pin 5 – 0V
No handshaking is required.
Rear Connector
25 way female D type connector on rear panel of the controller provides isolated R
S232C requiring the following connections:
Pin 3 – receive data
Pin 2 – transmit data
Pin 7 – 0V
No handshaking is required.
62
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Note The A30-CON and A30-MON card transducers are calibrated at the factory prior to despatch
and will not normally require adjustment. Any slight discrepancy between the values indicated on the
HMI and panel instruments is more likely to be due to panel meter error rather than AVR error. Where a
replacement card is fitted to an existing installation, it may be necessary to check calibration of the card
in the mainframe, and in this case, measurements should be made using calibrated instruments with
accuracy better than ±1%.
(b) Insert the A30-CON card into the extender card and plug them into the correct
mainframe position.
(d) Plug the Comms link into the connector marked `COM 2' on the A30-CON front panel.
(e) With the machine running at rated speed, select `Standby' control and adjust the line
voltage to nominal.
(f) Use the HMI to indicate sensing voltage on the voltage menu and note the reading.
Check that the indicated value ie equal to the average value of the three mean line to
line voltages applied to the terminals 139, 140 and 141 when measured with a high
accuracy (better than ±1%) mean (average) responding voltmeter.
If the AVR is set to measure single-phase line voltage, the value displayed on the HMI
should correspond to the average line voltage supplied to terminals 140 & 141.
Use the HMI to display exciter field current on the `current' menu, and check that the value
indicated on the display is equal to that indicated on the panel field ammeter. If necessary, the
transducer can be calibrated against an ammeter with accuracy better than ±1% by adjusting
RV3 on the control card.
Fit the A30-CON card to the extender card and excite the machine in Standby control. Load the
machine to give approximately 80% rated line current (MW or MVAr).
Use the HMI to display line current on the `current' menu and check that the value indicated on
the display is equal to that indicated on the panel line ammeter. If necessary, the transducer can
be calibrated against an ammeter with accuracy better than ±1% by adjusting RV4 on the
control card.
(a) In the first instance, check that the temperature displayed on the HMI (temperature
menu) corresponds to the ambient temperature of the RTD.
63
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Check that the temperature compensation is specified on the QC.48 document and
that an RTD measuring `generator inlet air temperature' is connected to the AVR. Use
the HMI to display temperature (Main Display) and confirm that the indicated value
corresponds to the generator inlet air temperature in the location of the RTD.
(b) The temperature transducer can be calibrated using 100Ω and 115Ω resistors
(accuracy ±1%) as described below.
i) Trip FSC, and open SW1 in the mainframe. Connect the 100 Ω resistor
across terminals 116 and 117. Link terminals 116 and 118. Fit the A30-
CON card into the extender and insert in the mainframe. Close SW1 in the
mainframe. Use the HMI to check that temperature compensation software
is enabled (enable/disable software modules, F8). If it is turned off, confirm
that temperature compensation is required and if so, turn the software on.
Set the HMI to indicate temperature (Main Display) and adjust RV1 on the
control card so that the dc voltage between C2/4 and C2/11 is zero.
Adjust the dc voltage at TP7 wrt TP1 to 1.0V using RV6. Adjust the
temperature display on the HMI to 0°C using RV2.
ii) Open SW1 in the mainframe. Replace the 100 Ω test resistor by the 115Ω
resistor. Close SW1 and check that the HMI now indicates 40°C ±2°C and
TP7 wrt TP1 is 5V.
iii) If the temperature reading is not correct adjust RV6 for range and RV2 for
level.
The procedure is the same as Chapter 9.1, except that this is carried out on the A30-MON card.
The procedure is the same as Chapter 9.2, except that this is carried out on the A30-MON card.
The procedure is the same as Chapter 9.3, except that this is carried out on the A30-MON card.
The procedure is the same as Chapter 9.4, except measurements and adjustments of RV6 and
RV5 are made on the A30-MON card.
64
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Step response testing involves the sudden application of a step increase or reduction to the
regulator set point. This causes a disturbance in the output of the regulator that is reflected to
the output of the machine. The resulting transient provides information about the damping of the
regulator and is helpful when optimising the settings of the stability controls.
When line current greater than 0.1 per unit is present the maximum step is limited to 2%
Before starting any step response tests, first confirm that no equipment connected to the
generator is likely to be adversely affected by the tests.
Initially confirm that the test step size is set to the required level using the maintenance presets
menu on the HMI. A step of 5% is recommended.
It is recommended that the line voltage is initially set 10% below nominal until the stabilising
controls have been adjusted so as to reduce voltage overshoot during the response test. The
machine voltage may be increased to nominal when the settings are close to optimum.
The data displayed on the diagnostics display indicates the overshoot, undershoot and recovery
time. Each time a step response test is enabled, the previous values are destroyed.
The shape of the voltage transient may be viewed in the trending display although this is
unsuitable for taking accurate readings.
It is recommended that the step be allowed to time out for 20 sec, before returning to nominal
voltage.
The step response of the system may be optimised by adjusting the proportional (P), integral (I)
and differential gain (D) by accessing the maintenance presets menu.
The Integral Gain, when set correctly, has very little effect on the transient response and should
be set initially to 100.
In general increasing the Proportional Gain will give faster rise time but too much will give a
response which is difficult to damp out and probably a large overshoot.
65
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Damping can be improved and overshoot reduced by increasing the Differential Gain however,
too much will give poor rise time and may cause fluctuations in the exciter field voltage.
The diagnostics display shows the value “Mark – Angle”and this is an indication of the variation
of the thyristor firing angle. Under steady state conditions Mark should be almost constant, and
Mark – Angle will display the variation in the firing angle which should not normally exceed 10%
of the late firing limit. If this does occur it is recommended that the Differential Gain is reduced.
Integral time (I) will cause instability if too low typically less than 30. Instability depends on (P),
but if (P) is less than 60 then (I) will need to be higher, typically 500 for P = 35 on turbo
generators. Too high a value will give poor regulation and long rise time.
The contract settings in the QC.48 document provide a good starting point. If after a 5% step
the overshoot is too high, increase the Differential Gain to reduce the overshoot. If the
Differential Gain is unusually large it may be better to reduce Proportional Gain to reduce the
overshoot. The effect of this will be to reduce the rise time.
If the line voltage is oscillatory the Integral Gain may be too low (do not reduce below 100) Use
the 5% step to optimise the overshoot to about 15% -30% of the 5% step size . The under shoot
should be much less than the overshoot, typically 0% to 6% of the step size.
In the majority of applications, an adequate response with minimal overshoot can quite easily be
achieved using step response testing on open circuit and the facilities on the HMI. If the
application requires the best possible response this will necessitate recording equipment and
possibly load application and rejection testing.
Adjustable Proportional, Integral, and Differential gains controls have been added to the under
excitation limiter. It is recommended that they are set initially to I = 50, P = 20, D = 20.
When setting up the UEL response, steady state stability should initially have been proved by
running at zero power and slowly reducing the set point of the AVR until the under excitation
limiter turns on.
The response of the Under Excitation limiter may be tested by running the machine lightly
loaded when in parallel and initiating a step down in AVR set point. The excitation will reduce
and the machine will generate leading VArs. Check that the Under Excitation limiter turns on
immediately with no appreciable overshoot in the leading VArs. It may be necessary to optimise
the response by making adjustments to the UEL stabilising controls.
66
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
It is important to study operating procedures for the generator and turbine/engine system which
are beyond the scope of this manual. The following instructions should be followed to ensure
correct operation of the AVR.
It is important that the “Excite”input should be energised only after the AVR Main
Electronics Supply has been applied.
The excitation isolator should be provided for maintenance purposes and should be
left closed except during maintenance and commissioning.
The majority of applications for this AVR are designed to be fully automatic. In this
case the “Excite”input should be energised using a speed detector switch, external to
the AVR, which should be set to switch at 80% rated speed.
On shut down the speed switch should remove the “Excite” signal on speed reduction.
The PMG isolator should not be used to apply excitation, as its closure when the field
contactor is already closed does not allow an adequate initialisation period for the
AVR and may occasionally cause a malfunction.
Power factor or VAr Control is provided for generator operation in parallel with a power
system. These functions should be selected only when the paralleling circuit breaker is
closed. Power Factor or VAr control should not be selected on a single running
generator.
67
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
11.2 Maintenance
The A30 Excitation Controller is completely solid state, apart from relays, contactors and
switches, and requires very little maintenance. It is recommended that the AVR is inspected
approximately every 12 months to check for excessive dust build-up, and that all relays, fuses
and connections are secure. Excessive quantities of dust should be removed with a soft brush.
In common with generator protection systems, it is good practice to annually check the
calibration and the correct operation of all the various functions of the AVR because some
(monitors or limiters) may never have needed to operate since the equipment was installed.
This entails making checks that are carried out during commissioning and, if required, Brush
Service Department can provide this service.
WARNING Take anti-static precautions when handling cards. Ensure that you are earthed
(grounded) by using a wrist strap or similar device. An earth connection terminal is fitted in the
centre or the front right hand mounting bracket of the AVR to which a wrist strap may be
clipped.
Electronic cards can be damaged by static discharge and should be carried in anti static
protective containers wherever practicable. They should always be stored and transported in
anti static bags or boxes.
68
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
12 FAULT FINDING
Note! The advice given in the safety notice at the front of this handbook should be followed when fault
finding.
If the AVR does not function correctly, a test sequence is recommended in which the generator
and external wiring are first thoroughly checked before it is assumed that the fault lies in the
electronic equipment. The faultfinding procedure is designed to enable faults to be found
quickly. It is essential therefore, to follow the order in which they are presented.
In the event of finding a fault on any part of the AVR the company strongly recommends that no
attempt is made to repair the unit, but that it is replaced by a spare which should be re-
commissioned according to the relevant section of this handbook. The faulty unit should be
returned to the Works for repair quoting the relevant Type/Model and Contract No's, together
with the nature of the fault.
12.2 Precautions
Meggers, flash testers and bell sets must not be used to check any equipment connected to, or
incorporating semi-conductors.
If these devices are to be used to check the wiring to the AVR, first disconnect all cables to the
AVR.
WARNING Take anti-static precautions when handling cards. Ensure that youare
earthed (grounded) by using a wrist strap or similar device. An earth connection terminal is fitted
in the centre or the front right hand mounting bracket of the AVR to which a wrist strap may be
clipped.
Electronic cards can be damaged by static discharge and should be carried in anti static
protective containers wherever practicable. They should always be stored and transported in
anti static bags or boxes.
12.3 Procedure
Before commencing fault finding on the AVR unit, the following preliminary checks
should be carried out:
(a) Check correct operation of the generator, ie. PMG output available (if
applicable), the field and sensing signals are correct etc.
(c) Check all contactors, switches and other external components associated
with the AVR unit.
(d) Check that all the correct links are fitted in the AVR as detailed in the
contract QC.48 document.
(e) Check all fuses and replace any that have fai
led. Fuse ratings are given in
Chapter 16.
69
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Having completed these preliminary checks, if the problem remains, the cause may be
assumed to be internal to the AVR, or in its setting up. In this event the problem will
generally fall into one of the following categories:
The Main and Standby power circuits are single-phase half-controlled rectifiers each
comprising two diodes (in a single module) and two thyristors (in a single module).
The thyristors can be checked in situ with the aid of a battery, ammeter and two
resistors, after isolating the AVR and temporarily removing the relevant semi-
conductor fuse (FS5 or FS6) and unplugging plug Q from the Backboard.
(a) Initially, with switch S open and not having previously been closed, ensure
that the ammeter registers zero current.
(b) Close S and observe that the ammeter now registers approximately 0.75A.
(c) Re-open S and observe that the ammeter continues to register - ideally as
in (b) above.
If any of these three tests is not satisfied for either positive or negative arm thyristors,
then the thyristor module should be replaced.
Note! To reduce the current to zero after the thyristor has been triggered, as in
(b) above; the battery circuit must be disconnected
NOTE: In the following tables where reference is made to test point 1 (TP1) on
the A30-CON and MON cards, use TP1 on the main body of the card, not TP1 on
the A30-M188.
70
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
71
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
72
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
73
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Table 12.4 Low Excitation or Voltage on Open Circuit in Main Control Channel
No. Possible Fault Test Remedial Action
1 Main channel a) Check that fuse FS5 is healthy a) Replace if necessary
power circuit
fault in b) Check PMG volts applied to input of b) Examine wiring in rack and
mainframe Main control rectifier correct if necessary
b) Check dc voltage at TP4 wrt TP1 is 0.33 b) Trim using RV2 on Backboard. If
times the field ammeter reading not possible, IC1 on Backboard
faulty – replace Backboard
74
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
9 Incorrect FSC a) Use HMI to check FSC status a) If FSC OFF, status is correct. If
status read by (Diagnostics Display) FSC ON, proceed to test 9b) in this
A30-CON card table
b) Remove LK19 and check FSC status b) If still ON, card faulty – replace. If
FSC OFF with LK19 out, proceed to
test 9c) in this table
75
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
76
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Voltage
Field Current Refer to table 12.10
Line Current/Phase Refer to table 12.11
Temperature Refer to table 12.13
Frequency Refer to table 12.12
Refer to table 12.14
4 A30-MON settings Measure the monitored quantities If normal site transients
inconsistent with site during normal and transient operation are beyond initial
conditions monitor settings, refer
to works
77
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
78
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
79
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
d) Switch off SW1, fit utilities board on d) If volts low or high, double
extender card, close SW1 and check check that correct links are fitted.
ac supplies to utilities board terminals: If no volts, check wiring loom
U1/5 -1/9 between 15V-23V from auxiliaries board to
U1/15-1/17 between 60V-95V backboard. If ok, auxiliaries
U1/19-1/21 between 60V-95V board probably faulty and should
be replaced.
Table 12.17 Failure of ±15V A30-CON card Supply (other dc supplies present)
No. Possible Fault Test Remedial Action
1 FS4 blown on Utilities Turn off SW1 in mainframe. Replace if blown. If it blows
card Check fuse again, replace Utilities card
2 No PMG feed to U1/15 a) Check ac volts at U1/15 to a) If missing, proceed to test b)
and U1/17 U1/17 is between 60 and 95
volts
80
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
b) Remove Utilities card and repeat a) b) If volts now present, Utilities card
above faulty – replace. If still missing, proceed
to test c)
Table 12.19 Failure of +5V A30-CON card Supply (other dc supplies present)
No. Possible Fault Test Remedial Action
1 FS3 blown on Turn off SW1 in mainframe. Remove Replace if blown. If it blows again,
Utilities card control and Utilities card. Check fuse. replace Utilities card. If OK, proceed
Replace if necessary and test with to test b)
control card removed
2 Insufficient Remove control card. Fit extender card If OK, A30-CON card takes
current available alone in control card slot with LK3 excessive current - replace control
for A30-CON fitted. Check volts across Utilities: card. If volts low, proceed to test 3
card TP5-TP1 is 5V ±0.5V below
3 Low PMG a) Check ac volts at U1/5 to U1/9 is a) If OK, Utilities card faulty –
supply to between 15 and 23 volts replace. If low, proceed to b)
Utilities card
b) Remove Utilities card and repeat a) b) If now OK, Utilities card faulty –
above replace. If still low, proceed to test c)
81
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
TP11-TP1 is 5V ±0.5V
3 Low PMG supply to a) Check ac volts at U1/5 to a) If OK, Utilities card faulty –
Utilities card U1/9 is between 15 and 23 replace. If low, proceed to b)
volts
82
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
83
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
d) Replace module if
necessary
6 Bad connection from With system isolated, check with Investigate any faults and
Standby firing pulse ohmmeter the continuity between: rectify
output to thyristors S2/10 and G3
S2/12 and K3
S2/18 and G4
S2/20 and K4
7 If tests 1-6 above do not
indicate cause of fault,
replace Standby card
84
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Table 12.25 Standby Card Faults - line voltage unstable when machine on open circuit
No. Possible Fault Test Remedial Action
1 Governor instability Check that speed is not Stabilise governor if necessary
fluctuating
2 If governor stable and volts Reset RV1 (quantity) If stability cannot be achieved,
control selected, stability and RV2 (phase) to check that the appropriate
controls require adjustment produce a stable exciter stabilising link (LK25,26 or 28) for
field voltage exciter field time constant is fitted
refer to link chart for standby card
(appendix C). If still unstable, refer
to factory.
Table 12.26 Standby Control Faults - machine will not run in parallel
when selected in voltage control mode
No. Possible Fault Test Remedial Action
1 Incorrect phasing of sensing Check the 110V voltage sensing Make necessary
voltage and current to signal to S2/2 via 132 and S2/1 corrections
Standby card via 148 and the current sensing
signal to S1/3 and S1/1 via T4
on Backboard
2 Incorrect link selection on Check LK12 fitted for 1A CT and Correct as necessary
Standby card LK13 fitted for 5A CT
Table 12.27 Standby Control Faults - high excitation when in standby control
No. Possible Fault Test Remedial Action
1 Lack of line voltage sensing Check 110V sensing signal to Make necessary
when in line volts control S2/2 via 132 and S2/1 via 148 connections
mode
2 Permanent raise signal being Check the voltage to S1/11 via Make necessary
applied 152 is only present when a raise connections
signal is given
3 Lack of field voltage sensing Check the connection between Make necessary
signal when in field volts S2/11 and field positive via Q/2 connections
control mode
4 Thyristor failure Check Standby thyristors. Replace module if
necessary
85
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
To guarantee maximum generator availability with minimum downtime; a complete spare A30
should be purchased in addition to a set of fuses identified in the minimum spares list below.
The complete spare A30 may be setup by Brush to match the commissioned working A30
before dispatch. To achieve this, the commissioning settings, recorded on the QC(T)48 setup
data sheets, should be sent to Brush with the purchase order.
Table 10.1
Quantity Description Brush Reference
1 Standby Control Card 962243400
1 Utilities Card 961529800
1 A30-CON Card 962608900
1 A30-MON Card 962609000
1 Commissioning Software for Excitation Controllers 962609800
1 A30-COMCAB commissioning cable 962609700
4 Semi-conductor Fuse 20ET (Mainframe FS5, FS6) 962615908
4 Fuse 5A body size 0 (Front Panel FS1, FS2) 962615909
4 Fuse 2A body size 0 (Front Panel FS3, FS4) 962615936
6 Fuse 250mA 20mm x 5mm 962615912
(Standby FS1, FS2, FS3)
4 Fuse 250mA 20mm x 5mm 962615912
(Utilities FS2, FS4)
4 Fuse 1A 20mm x 5mm (Utilities FS1, FS3) 962615913
2 Fuse 100mA 20mm x 5mm (Utilities FS5) 962615914
86
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
87
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Connections Description
C1/1:M1/1:T3 IY Load (C,M)
C1/2:D1/2 SCADA COMMS RX (C)
C1/3:U1/1:S1/19:Pin7/IC1 +15V (C)
C1/4:LK4 If (C)
C1/5:M1/5:Q1/9 PMG 7
C1/6:U1/3:S1/21:Pin4/IC1 15V (C)
C1/7:U1/7 +5V (C)
C1/8:M1/8:U2/28 L1 25V Sens.
C1/9:M1/9:Q1/10 PMG 8
C1/10:U2/16 D.F.S. D.F.I. i/p
C1/11:M1/11:U2/26 L2 25V Sens.
C1/12:M2/29 Con Card Sup. o/p (1 = healthy)
C1/13:M1/13 Mon Card Sup. I/p (1 = healthy)
C1/14:S1/27 AVR Firing Pulse
C1/15:M1/15:U2/27 L3 25V Sens.
C1/16:M2/27 Reset 1 (low to reset/inhibit monitor)
C1/17:D1/3 SCADA COMMS TX (C)
C1/18:M2/23 Reset 2 (low to reset/inhibit monitor)
C1/19:M1/19 UEM. Sup. i/p
C1/20:M1/20 OEM. Sup. i/p
C1/21:M1/21 UVM. Sup. i/p
C1/22:M1/22 OVM. Sup. i/p
C1/23:M1/23:U2/22 Ph.Ref. 50
C1/24:S1/17 Logic level 0 when Standby Low
C1/25:U2/20 Lim. On
C1/26:M1/18 Spare
C1/27:S1/18 Logic level 0 when Standby High
C1/28:M1/28:U1/28:S1/28: Ground
C1/29:M1/29:U1/29:S1/29:Q1/8:155
C1/30:M1/30:U1/30:S1/30:Term.A etc.
88
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Connections Description
C2/1:100(Con2/1) Main V Raise
C2/2:116(Con2/2) RTD 3
C2/3:101(Con2/3) Main V Lower
C2/4:M2/4:117(Con2/4) RTD 1
C2/5:102(Con2/5) P.F.Select
C2/6:118(Con2/6) RTD 2
C2/7:103(Con2/7) VAr Control Select
C2/8:M2/8:S1/13:Q/1:153(Con1/12) Aux. DC –ve
C2/9:104(Con2/9) VAr Shed
C2/10:M2/10 Spare
C2/11:M2/11 RTD 4
C2/12:M2/12(linked to C2/17 from early 2000) See C2/17(used on twin)
C2/13:112(Con2/25) Self Centring
C2/14: 106(Con2/13) Panel Adjust/ Comms link adjust
C2/15:111(Con2/23) Mark/space o/p (used on twin)
C2/16:107(Con2/15) Analogue input
C2/17:Q/22(linked to C2/12 from early 2000) Standby (+ve)/Main(used on twin)
C2/18:M2/1:Q/24 FSC (+ve Aux Sup'd)
C2/19:105(Con2/11) P.F. Lower
C2/20: 110(Con2/21) P.F. Raise
C2/21 Not Connected
C2/22 Not Connected
C2/23 Not Connected
C2/24 Not Connected
C2/25:Q/12 K1 SCR1
C2/26:Q/16 G1 SCR1
C2/27:D1/7 SCADA COMMS Isolated Ground
C2/28 Not Connected
C2/29 Not Connected
C2/30 Not Connected
C2/31:Q/21 K2 SCR2
C2/32:Q/17 G2 SCR2
89
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Connections Description
M1/1:C1/1:T3 IY Load (C,M)
M1/2:D1/11 SCADA COMMS RX(M)
M1/3:U1/25:Pin7/IC2 +15V (M)
M1/4:U2/4:LK5 If(M)
M1/5:C1/5:Q1/9 PMG 7
M1/6:U1/11:Pin4/IC2 15V (M)
M1/7:U1/13 +5V (M)
M1/8:C1/8:U2/28 L1 25V Sens
M1/9:C1/9:Q1/10 PMG 8
M1/10 Not Connected
M1/11:C1/11:U2/26 L2 25V Sens
M1/12 Not Connected
M1/13:C1/13 Mon Card Sup. o/p
M1/14 Not Connected
M1/15:C1/15:U2/27 L3 25V Sens.
M1/16 Not Connected
M1/17:D1/12 SCADA COMMS TX(M)
M1/18:C1/26 Spare
M1/19:C1/19 UEM. Sup. o/p
M1/20:C1/20 OEM. Sup. o/p
M1/21:C1/21 UVM. Sup. o/p
M1/22:C1/22 OVM. Sup. o/p
M1/23:C1/23:U2/22 Ph.Ref. 50
M1/24:U2/24 Gen.Alarm Sig.
M1/25:U2/18 Mon.Trip Sig.
M1/26:U2/6 DFI Inh.
M1/27 Not Connected
M1/28:C1/28:U1/28:S1/28: Ground
M1/29:C1/29:U1/29:S1/29:Q1/8:155 Ground
M1/30:C1/30:U1/30:S1/30:Term A etc Ground
90
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Connections Description
M2/1:C2/18:Q/24 FSC(+ve Aux Sup'd)
M2/2 Not Connected
M2/3:113 Mon Inh
M2/4:C2/4:117 RTD 1
M2/5:130 Spare
M2/6 Not Connected
M2/7:114 Spare
M2/8:C2/8:S1/13:Q/1:153 Aux. DC –ve
M2/9:131 Spare
M2/10:C2/10 Spare
M2/11:C2/11 RTD 4
M2/12:C2/12 Spare
M2/13:115 Spare
M2/14 Spare
M2/15:124 Spare
M2/16 Not Connected
M2/17 Not Connected
M2/18 Not Connected
M2/19:S1/15 Manual Power Supply Fault (0 = healthy)
M2/20 Not Connected
M2/21 Not Connected
M2/22 Not Connected
M2/23:C1/18 Reset 2 (low to reset/inhibit monitor)
M2/24 Not Connected
M2/25 Not Connected
M2/26 Not Connected
M2/27:C1/16 Reset 1 (low to reset/inhibit monitor)
M2/28/D20 SCADA COMMS Isolated ground
M2/29:C1/12 Con Card Supervisory i/p (1=healthy)
M2/30 Not Connected
M2/31 Not Connected
M2/32 Not Connected
91
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Connections Description
U1/1:C1/3:S1/19:Pin7/IC1 +15V (C)
U1/2:S1/2 (linked to U2/29 from early 2000) See U2/29 (used on twin)
U1/3:C1/6:S1/21:Pin4/IC1 15V (C)
U1/4:S1/4 (Linked to U1/26 from early 2000) See U1/26 (used on twin)
U1/5:Q1/4 PMG 1
U1/6 Not Connected
U1/7:C1/7 +5V (C)
U1/8 Not Connected
U1/9:Q1/5 PMG 2
U1/10 Not Connected
U1/11:M1/6:Pin4/IC2 15V (M)
U1/12 Not Connected
U1/13:M1/7 +5V (M)
U1/14 Not Connected
U1/15:Q1/6 PMG 3
U1/16 Not Connected
U1/17:Q1/7 PMG 4
U1/18 Not Connected
U1/19:Q1/1 PMG 5
U1/20 Not Connected
U1/21:Q1/2 PMG 6
U1/22 Not Connected
U1/23 +9V (HMI) Not used on A30 Excitation
Controller
U1/24 Not Connected
U1/25:M1/3:Pin7/IC2 +15V (M)
U1/26:Q1/3 (linked to U1/4 from early 2000) Lim N.C. (used on twin)
U1/27:S1/5 (linked to U2/31 from early 2000) Follower Inh (used on twin)
U1/28:C1/28:M1/28:S1/28: Ground
U1/29:C1/29:M1/29:S1/29:Q1/8:155 Ground
U1/30:C1/30:M1/30:S1/30:Term.A etc. Ground
92
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Connections Description
U2/1:119 DFI Com
U2/2:135 DFI N.C.
U2/3:121 DFI N.O.
U2/4:M1/4:LK4 If(M)
U2/5:122 Lim. Com.
U2/6:M1/26 DFI Inh.
U2/7:123 Lim. N.C.
U2/8:136 Lim. N.O.
U2/9:125 Mon. Com.
U2/10:137 Mon. N.C.
U2/11:126 Mon. N.O.
U2/12:S1/23:Q/20 Mon.Trip Com.
U2/13:120 Mon.Trip N.C.
U2/14:S1/25:Q/23 Mon.Trip N.O.
U2/15:127 Alarm Com.
U2/16:C1/10 D.F.S.
U2/17:128 Alarm N.C.
U2/18:M1/25 Mon.Trip Sig.
U2/19:129 Alarm N.O.
U2/20:C1/25 Lim. On
U2/21:140 L1 110V Sens.
U2/22:C1/23:M1/23 Ph.Ref. 50
U2/23:141 L3 110V Sens.
U2/24:M1/24 Gen.Alarm Sig.
U2/25:139 L2 110V Sens.
U2/26:C1/11:M1/11 L2 25V Sens.
U2/27:C1/15:M1/15 L3 25V Sens.
U2/28:C1/8:M1/8 L1 25V Sens.
U2/29:142 (linked to U1/2 from early 2000) See U1/2 (used on twin)
U2/30: Not Connected
U2/31:143 (linked to U1/27 from early 2000) See U1/27 (used on twin)
U2/32: Not Connected
93
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Connections Description
S1/1:T4:Z1 IY Load (S)
S1/2:U1/2(linked to S1/27 from early 2000) Spare(used on twin)
S1/3:T4:Z2 IY Machine (S)
S1/4:U1/4 Spare
S1/5:U1/27 Follower Inh.
S1/6 Not Connected
S1/7 Test purposes only
S1/8 Not Connected
S1/9:151 Standby V Lower
S1/10 Not Connected
S1/11:152 Standby V Raise
S1/12 Not Connected
S1/13:C2/8:M2/8:Q/1:153 Aux. DC –ve
S1/14 Not Connected
S1/15:M2/19 Standby Power Supply Fault (0 = healthy)
S1/16 Not Connected
S1/17:C1/24 Low when Standby Low
S1/18:C1/27 Low when Standby High
S1/19:C1/3:U1/1:Pin7/IC1 +15V (C)
S1/20 Not Connected
S1/21:C1/6:U1/3:Pin4/IC1 15V (C)
S1/22 Not Connected
S1/23:U2/12:Q/20 Mon.Trip Com.
S1/24 U2/14:Q/23 Mon.Trip N.O.
S1/25:U2/14:Q/23 Mon.Trip N.O.
S1/26 Not Connected
S1/27:C1/14(linked to S1/27 from early 2000) AVR Firing Pulse (used on twin)
S1/28:C1/28:M1/28:U1/28: Ground
S1/29:C1/29:M1/29:U1/29:Q1/8:155 Ground
S1/30:C1/30:M1/30:U1/30:Term A etc. Ground
94
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Connections Description
S2/1:148 L1 110V Standby Sensing
S2/2:132 L3 110V Standby Sensing
S2/3 Not Connected
S2/4 Not Connected
S2/5 Not Connected
S2/6 Not Connected
S2/7 Not Connected
S2/8 Not Connected
S2/9 Not Connected
S2/10:Q/4 G3 SCR3
S2/11:Q/2 Field +ve
S2/12:Q/3 K3 SCR3
S2/13 Not Connected
S2/14 Not Connected
S2/15 Not Connected
S2/16 Not Connected
S2/17 Not Connected
S2/18:Q/5 G4 SCR4
S2/19:157 AC1 (PMG)
S2/20:Q/9 K4 SCR4
S2/21 Not Connected
S2/22 Not Connected
S2/23 Not Connected
S2/24 Not Connected
S2/25 Not Connected
S2/26:159 AC2 (PMG)
S2/27 Not Connected
S2/28 Not Connected
S2/29:162 NBM +ve (ground)
S2/30:146 Standby at min Com.
S2/31:163 NBM –ve
S2/32:147 Standby at min N.O.
95
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
96
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Connections Description
D1/2:C1/17 SCADA COMMS TX(C) A30-CON
D1/3:C1/2 SCADA COMMS RX(C) A30-CON
D1/7:C2/27. SCADA COMMS Isolated Ground
A30-CON
D1/11:M1/2 SCADA COMMS RX(C) A30-MON
D1/12:M1/17 SCADA COMMS TX(C) A30-MON
D1/20:M2/28 SCADA COMMS Isolated Ground
A30-MON
All Other pins Unconnected
Connections Description
100:C2/1 Main V Raise
101:C2/3 Main V Lower
102:C2/5 P.F.Select
103:C2/7 VAr Con. Select
104:C2/9 VAr Shed
105:C2/19 P.F. Lower
106:C2/14 Panel/HMI or SCADA comms adjust
107:C2/16 Analogue Input
108:C1,M1,U1/31,32:144:160:Term.A etc. Signal Ground
109 Not Connected
110:C2/20 P.F.Raise
111:C2/15 Used on Twin System
112:C2/13 Self Centring
113:M2/3 Mon. Inhibit
114:M2/7 Spare
115:M2/13 Used on Twin System
Connections Description
116:C2/2 RTD 3
117:C2/4:M2/4 RTD 1
118:C2/6 RTD 2
119:U2/1 DFI Com.
120:U2/13 Mon.Trip N.C.
121:
122:U2/5 Lim. Com.
123:U2/7 Lim. N.C.
124:M2/15 Spare
125:U2/9 Mon. Com.
126:U2/11 Mon. N.O.
127:U2/15 Alarm Com.
128:U2/17 Alarm N.C.
129:U2/19 Alarm N.O.
130:M2/5 Spare
131:M2/9 Spare
97
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Connections Description
132:S2/2 L3 110V (S)
133:T3 C/T IY Machine
134:T4 C/T IY Load
135:U2/2 DFI N.C.
136:U2/8 Lim. N.O.
137:U2/10 Mon. N.C.
138:S2/3 Spare
139:U2/25 L2 110V Sensing
140:U2/21 L1 110V Sensing
141:U2/23 L3 110V Sensing
142:U2/29 Used on Twin System
143:U2/31 Used on Twin System
144:C1,M1,U1/31,32:108: 160:Term.A etc. Signal Ground
145:LK4 If(C)
146:S2/30) St'by at Min. Com.
147:S2/32) St'by at Min. N.O.
Connections Description
148:S2/1 L1 110V (S)
149:T3 C/T IY Machine
150:T4 C/T IY Load
151:S1/9 St'by Volts Lower(different on twin
AVR)
152:S1/11 St'by Volts Raise(different on twin
AVR)
153:C2/8:M2/8:S1/13:Q/1 Aux. DC –ve
154:S2/4 Spare
155:C1,M1,U1,S1/28-31:Q1/8: Term.A etc. Ground
156 Not Connected
157:S2/19 AC1 (PMG)
158 Not Connected
159:S2/26 AC2 (PMG)
160 Not Connected
161:LK5 If(M)
162:S2/29 NBM +ve
163:S2/31 NBM -ve
98
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Connections Description
1 Aux DC +ve Input
Space Not used
2 Aux DC -ve Input
Space Not used
13 +ve for Standby
14 +ve for Main
15 +ve to Excite
16 +ve to Trip Excitation
17 +ve Aux D.C. Supply after FS1
17 +ve Aux D.C. Supply after FS1
17 +ve Aux D.C. Supply after FS1
19 -ve Aux D.C. Supply after FS2
19 -ve Aux D.C. Supply after FS2
20 Control State, Common
21 Control State, Closed in Main
22 Control State Closed in Standby
Connections Description
23 Excitation State (Com.)
24 Excitation State (Closed if Excited)
25 Excitation State (Closed if Tripped)
26 Aux DC State (Com.)
27 Aux DC State (Closed if Healthy)
28 Aux DC State (Closed if Faulty)
Space Not used
29 PMG (AC1) for Main Channel P.S.
Space Not used
30 PMG (AC2) for Main Channel P.S.
Space Not used
Space Not used
Space Not used
Space Not used
90 Spare
91 Spare
A30 Excitation Controller Outgoing Connections – Heavy Duty Terminals at Rear of Unit
99
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Link Description
1A For SCADA comms to COM 1 on front panel
1B For SCADA comms to REMOTE COMMS Socket on Rear Panel
2A For SCADA comms to COM 1 on front panel
2B For SCADA comms to REMOTE COMMS Socket on Rear Panel
3A Debugging comms to COM 2 on front panel (normally fitted)
3B Omit
4A Debugging comms to COM 2 on front panel (normally fitted)
4B Omit
5A Fit for Three-Phase Sensing (Omit LK5B)
5B Fit for Single-Phase Sensing (Omit LK5A)
6A For Analogue Input signal to bias sensing signal
6B For Analogue input signal to auxiliary transducer
6C Disable analogue input signal (Normally Fitted)
7A Firing angle to Standby (normally fitted on single AVR brushless system)
7B Disable Firing angle to Standby
8A Firing angle to output terminal 111 (normally omitted -used on twin system)
8B Disable Firing angle to terminal 111 (normally fitted)
9A-19A Fit for 24/48V D.C. Aux Supply (Omit LK9B-19B)
9B-19B Fit for 110/125V D.C. Aux Supply (Omit LK9A-19A)
9C-19C Park position for links 9 – 19
20A High Field Current Sensitivity ( normally omitted, fit on twin system)
20B Normal Field Current Sensitivity ( normally fitted)
Link Description
1A Watchdog Reset (normally fitted)
1B Disable Watchdog Reset (omit)
2A Fit for excitation source frequency 251 – 480 Hz (4MHz clock)
2B Fit for excitation source frequency 50 – 125 Hz (1MHz clock)
2C Fit for excitation source frequency 126 – 250Hz (2MHz clock)
3A Debugging Interrupt selector (omit)
3B Normal Interrupt selector (normally fitted)
4A Configure FPGA on watchdog reset (omit)
4B Configure FPGA on power up (normally fitted)
5A Excitation supply zero crossing signal (normally fitted)
5B Alternative excitation supply zero crossing signal (omit)
100
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Link Description
1A For Analogue Input signal to bias sensing signal
1B For Analogue input signal to auxiliary transducer
1C Disable analogue input signal (Normally Fitted)
2A Fit for Single-Phase Sensing (Omit LK2B)
2B Fit for Three-Phase Sensing (Omit LK2A)
3A SCADA comms to COM 1 on front panel (normally fitted)
3B SCADA comms to REMOTE COMMS Socket on Rear Panel (normally omitted)
4A Debugging comms to COM 2 on front panel (normally fitted)
4B Omit
5A SCADA comms to COM 1 on front panel (normally fitted)
5B SCADA comms to REMOTE COMMS Socket on Rear Panel (normally omitted)
6A Debugging comms to COM 2 on front panel (normally fitted)
6B Omit
7A-14A Fit for 24/48V D.C. Aux Supply (Omit LK7B-14B)
7B-14B Fit for 110/125V D.C. Aux Supply (Omit LK7A-14A)
7C-14C Park position for links 7 – 14
15A High Field Current Sensitivity ( normally omitted, fit on twin system)
15B Normal Field Current Sensitivity ( normally fitted)
101
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Link Description
LK1,3,6 Voltage selection links for 220/330V PMG (Omit LK2,4,5)
1,5,6 Voltage selection links for 165/250V PMG (Omit LK2,3,4)
2,3,4 Voltage selection links for 110/165V PMG (Omit LK1,5,6)
7 Remove to inhibit Low Frequency Cut-off.
8 Low Frequency Cut-off, Fit for 50Hz Machine (Omit LK9)
9 Low Frequency Cut-off, Fit for 60Hz Machine (Omit LK8)
10,11 Power Supply Test Links (Normally Fitted)
12 C.T. Selector Fit for 1 Amp Metering C.T. (Omit LK13)
13 C.T. Selector Fit for 5 Amp Metering C.T. (Omit LK12)
14 Fit to select Field Voltage Control (Omit LK15)
15 Fit to select Line Voltage Control (Omit LK14)
16 Fit to select High Range Field Voltage Control 0-200V (Omit LK17)
Fit when Line Voltage Control is Required
17 Fit to select Low Range Field Voltage Control 0-100V (Omit LK16)
18 Raise/Lower with 24/48V D.C. Aux Voltage (Omit LK19)
19 Raise/Lower with 110/125V D.C. Aux Voltage (Omit LK18)
20 Auto Follower with 24/48V D.C. Aux. Voltage (Omit LK21)
21 Auto Follower with 110/125V D.C. Aux. Voltage (Omit LK20)
22 Fit for PMG Frequency of 201Hz and above
23 Fit for PMG Frequency of 200Hz and below
24 Fit to select Field Votage Limit.
25 AVR Stabilising Link for Exciter Field Time Constant of 0.4 - 0.7 sec.
(Omit LK26, 27, 28)
26 AVR Stabilising Link for Exciter Field Time Constant of 0.1 - 0.4 SEC
(Omit LK25, 27, 28)
27 Fit when in Field Voltage Control (Omit LK26, 25, 28)
28 AVR Stabilising Link for Exciter Field Time Constant of 0.7 - 1.5 SEC
(Omit LK26, 25, 27)
29 Slow Clocking Link for Low Exciter Field Voltage (Normally Omitted)
Link Description
LK1 Fit to increase Sensitivity of D.F.I. (Normally Omitted)
LK2 Fit to decrease Sensitivity of D.F.I. (Normally Omitted)
LK3 Fit for continued operation of Auto Follower when Limiter Operates (Normally
Omitted)
Link Description
LK1A 5 Amp Metering CT selector (Omit LK1B)
1B 1 Amp metering CT selector (Omit LK1A)
2A Internal A30-CON Field Current Transducer (Normally Fitted)
2B External Field Current Transducer (Omit)
3A Internal A30-MON Field Current Transducer (Normally Fitted)
3B External Field Current Transducer (Omit)
102
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Link Description
LK1,3,6 Voltage selection Links for 220/330V PMG (Omit LK2,4,5)
1,5,6 Voltage selection Links for 165/230V PMG (Omit LK2,3,4)
2,3,4 Voltage selection Links for 110/165V PMG (Omit LK1,5,6)
LK7,8,9,10 Fit for 24V DC Aux Supply; Omit for110/125V DC Aux Supply
103
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Unless stated otherwise, all adjustments on this card are made using the HMI.
Selected by a link.
16.1.1.2 Accuracy
104
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Adjustable from 0% to 15% in 0.1% steps for rated current at zero power
factor lagging.
The ratio voltage/frequency is automatically limited to between 1.08 to 1.20 per unit,
the level being adjustable in increments of 0.001 per unit. (1 per unit voltage is the
nominal sensing voltage referred to in section 16.1.1.3).
After switching on excitation, line voltage is slowly increased to the nominal level.
Ramping rate is adjustable from 5V/s to 25V/s.
Excitation should only be switched on by energising the “Excite”input after the AVR
Main Electronics Supply has been applied. This should be achieved using a speed
detector switch, external to the AVR, which should be set to switch at 80% rated
speed.
The AVR provides excitation build up when 85% rated speed is reached. Excitation is
removed at 80% rated speed. Speed detection by the AVR uses PMG frequency
sensing. An external speed detector switch should also be fitted – see
16.1.4 above.
Power Factor: 0.6 lag to 0.9 lead in increments of less than 0.001
For PF control the range is adjustable from 1 to 20 seconds for 0.1 pf.
For VAr control the range is adjustable from 50ms/% (20% rated VArs per
sec) to 500 ms/%(2% rated VArs per sec)
16.1.6.4 Accuracy
105
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
106
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
The limit at zero power and 100% volts is adjustable between 0.1A and
5.5A in 0.01A increments This covers the whole range for 1A and 5A CTs.
The limit is automatically compensated in proportion to line voltage.
16.1.9.1 Range
When operating under Standby control and the sensing voltage is within
the specified range of the A30-CON card voltage reference, the reference
of the A30-CON is automatically adjusted so that line voltage and VArs do
not change when voltage control is transferred from Standby to back to
Auto.
If the A30-CON card has PF, VAr control or VAr shed selected when on
Standby, they will not affect the automatic tracking but will become
functional when automatic control is selected.
When in standby control, LED1 on the A30-CON card will flash while
tracking is not achieved. When tracking is achieved, the LED will be
continuously illuminated.
(Successful tracking is also indicated by the `high' or `low' LED indications
on the Standby regulator, and the external null balance meter (if fitted).
Normally LED 1 and LED 2 on the Standby card will alternate when
balanced. Occasionally both LEDs will be off when balanced but if either
LED is on permanently, this indicates a fault)
107
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
LED 1 In Main control this LED has no function and will be turned off.
In Standby control this LED will flash when Main has not matched standby.
It will be illuminated steadily when matching has been achieved.
LED 6 In Main control this LED indicates Over Flux limiter operating.
In Standby control it indicates that Main has failed to match Standby
within in a pre-set time.
108
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
The AVR can be configured to accept an auxiliary analogue input such as a signal
from a power system stabiliser. For this application, LK6A is fitted.
The card produces firing pulses that are supplied to a half controlled full Wave Bridge
located in the mainframe. The maximum voltage that can be applied to the field is
approximately 80% of the PMG voltage at the input to the bridge.
In order to adjust the set points via the HMI it is necessary for the
Panel/HMI switch to be set to HMI in which case the following set points
are adjustable via the communications link.
Note that unless Mode
‘ Selection via the HMI’has been activated via the
comms link, the mode will remain selectable by hard wired signals a
normal.
Note that the AVR will not allow a set point to be adjusted beyond the
specified range, and that following receipt of a new set point, the rate of
change from the previous to the new set point will be according to the
values set during commissioning.
Note also that for the Leading PF Reference to be used, the PF ‘ Ref
Leading’mode must be selected.
Set Points available are:
Voltage Reference
VAr Reference
PF Reference Lagging
PF Reference Leading
109
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
PF Reference Leading
P F Control
VAr Control
VAr Shed
Self Centre Voltage Reference
Reset Monitors
Allow mode selection Via Comms
The comms link can be used to provide digital and analogue data at the
remote terminal. The available data is given in Appendix F
Unless stated otherwise all adjustments to this card are made using the HMI.
Selected by a link.
Adjustable between 1.1 and 1.25 per unit in increments of 0.001 per unit.
110
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
16.2.3.2 Accuracy
At line frequency of less than 80% nominal the Under Voltage monitor is
inhibited.
The under voltage monitor is inhibited if the flux limiter on the A30-CON
Card is operating.
The under voltage monitor is inhibited if line current measured by the AVR
exceeds 1.5 pu.
111
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
The tripping level at zero power and 100%V is adjustable between 0.1A
and 5.5A in 0.01A increments. This covers the whole range for 1A and 5A
CTs. The trip level is automatically compensated in proportion to line
voltage. This should be to set at least 10% greater than the under
excitation limiter setting.
This is set by the `Xe' control and can be adjusted between 0 and 0.2 per
unit in steps of 0.01 per unit. This should normally be set to the same value
as the limiter.
LED 1 Spare
LED 2 Monitor watchdog dropout (program fails to cycle).
LED 3 Over Excitation monitor tripped.
LED 4 Under Excitation monitor tripped.
LED 5 Over Voltage monitor tripped.
LED 6 Under Voltage monitor tripped.
LED 7 Over Flux monitor tripped.
LED 8 Standby Power Supply Fault.
LED 9 A30-CON watchdog dropout alarm.
LED 10 Spare
112
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
One signal is provided to energise the monitor trip relay to select Standby
control when any of the following occur: -
A signal is provided to energise the general alarm relay on the Utilities card
and prevent automatic selection of Standby control when any of the
following occur:
When any of the monitors trip they remain latched until the fault is removed and the
reset pushbutton on the front of the card has been operated. Relay logic in the AVR
prevents return to A30-CON card until monitors are reset.
Operation of the monitor can be inhibited if required by an external switch signal. The
auxiliary dc supply is used and internal isolation is provided.
Remote communication with the A30-CON card in the AVR is particularly useful for
adjustment of settings, selection of operating modes, and acquisition of data for
display on a remote terminal via a serial link. Remote serial communication with the
A30-MON card is less useful not available on the standard system.
113
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
In this mode (which is selected by links), field voltage is controlled to a constant level.
Two links - selected ranges of 0-100V and 0-200V are available. The maximum field
voltage is approximately 80% of the PMG supply voltage.
60s to adjust the reference from minimum to maximum, or 187s if link 29 is fitted.
When the unit is energised (or re-energised after a power down) the set point is
automatically set to zero.
The output is reduced to zero when the frequency is below approximately 85%
nominal, to prevent over fluxing during run down. A link is provided to select 50/60Hz
nominal frequency.
By using raise/lower switch signals from the auxiliary dc supply (optical isolation is
provided). Local raise/lower pushbuttons are also provided on the Standby control
board.
114
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Automatic Follower
When the Main AVR channel is operating, the output of the Standby regulator is
continuously adjusted to match that of the Main AVR, so that on transfer to the
Standby regulator, there is minimal change in excitation. Note that the travel time
minimum to maximum introduces a time delay to the follower action.
After selection of Standby control, the set point remains constant unless adjusted by
the operator. If line voltage control is selected, regular adjustment of the set point of
the Standby regulator is unnecessary. This will prevent large variations of machine
output voltage (or power factor if paralleled) as the load varies which occurs on
manual regulators which control to a constant level of excitation.
16.3.7.1 Local
Two LED indicators are provided on the card which indicate `Manual High'
and `Manual Low'. When the output of the Main and Standby control
systems are matched, both LEDs are extinguished indicating balance
between AVR and Standby, irrespective of whether Standby or Main is
selected.
16.3.7.2 Remote
A field voltage limiter is included which is adjustable from 25V minimum to 200V or
80% of the PMG supply voltage.
A relay is energised in the event of failure of the A30-CON card power supply, its
output being used to initiate transfer to Standby control independently of the AVR
monitor relay which may be inoperative under a power supply failure situation.
16.3.10 Indications
115
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
(a) Optically isolated signals to control and monitor boards to indicate Standby
high, low and power supply failed.
(b) Normally open relay contact which closes on detecting A30-CON card
power supply failure. Used to initiate transfer to Standby control.
(c) Signal for 500-0-500 micro amp analogue null balance meter.
(d) Standby at minimum. A volt-free, normally open contact wired to the rear
plug assembly. Rating as in Chapter 4d(3)(a).
The Standby board contains its own supply independent of the Main channel and
Monitor. The power supply transformer primary is fused by FS1 and FS2 (250mA).
Link selected taps that cater for the following inputs, as seen in Table 4.1:
Table 4.1
Links Selected Nominal Voltage Rating Over Nominal Voltage Rating
66-480Hz Range at 50/60Hz
1, 3, 6 220 - 330V 250 ±10%
1, 5, 6 165 - 250V 187.5 ±10%
2, 3, 4 110 - 165V 125 ±10%
The unit is rated for 125% of the maximum for 1 minute to cater for over speed
condition.
The card produces firing pulses that are supplied to a full wave, half-controlled bridge
located in the mainframe. The maximum voltage that can be applied to the field is
approximately 80% of the PMG voltage at the input to the bridge.
The card produces the following fused power supplies (Table 4.2): -
Table 4.2
Card Supply Fuse Value
A30-CON ±15V ±5% FS4 250mA
+5V ±5% FS3 1A
A30-MON ±15V ±5% FS2 250mA
+5V ±5% FS1 1A
Hand-held Terminal +9V ±1V FS5 100mA
116
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Note! The Hand-held Terminal Supply is not used on the A30 Excitation Controller.
The +5V supplies are each fitted with over voltage protection.
The supplies are designed to operate in conjunction with the transformer mounted in
the mainframe, connected to the Auxiliaries Board and will operate over the following
voltage/frequency range:
Table 4.3
Auxiliaries Board Voltage Nominal Voltage Rating Nominal Voltage Rating
Links Selected 66-480Hz at 50/60Hz
1, 3, 6 220 - 330V 250 ±10%
1, 5, 6 165 - 250V 187.5 ±10%
2, 3, 4 110 - 165V 125 ±10%
The unit is rated for 125% of the maximum for 1 minute to cater for over speed
condition.
(a) This unit detects exciter field current ripple and when this exceeds a pre-set
limit local indication is given on the card and a relay is energised to give an
outgoing signal.
The Utilities card contains relays described below having output signals that are
accessible on the rear plug assembly.
All the relays on the Utilities card have the following rating:
117
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
Over Voltage
Under Voltage
Over Excitation
Under Excitation
Over Flux monitor
A30-CON card microprocessor fault
118
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
16.5 A30-RACK1
This contactor is mechanically latched in the excite or tripped condition. When tripped,
the ac supply to the thyristor circuits is disconnected and the field current decays
through the field suppression resistor.
The contactor is mechanically latched in the `Main' or `Standby' condition to select the
required power circuit.
The contact ratings of FSCS, ECCS, PSR and FRS are as follows: -
16.5.8 Fuses
119
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
The nominal voltage of the PMG must be within the range 110V to 330V.
The PMG voltage should not fall below 75% of the nominal when supplying
the maximum field current required under fault conditions.
The maximum voltage supplied to the exciter field will not be less than 80%
of the (loaded) PMG voltage supplied to the AVR.
20A continuous
30A 10 seconds.
16.5.9.6 Weight
120
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
121
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
122
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
123
Date: Feb 2001
PRISMIC A30
Excitation Controller Rev: D
Handbook 96
18 APPENDIX F - DRAWINGS
124