Troubleshooting
G3520C and G3520E Generator Set Engines
Media Number -RENR5979-10 Publication Date -01/06/2008 Date Updated -02/06/2008
i02582609
Table 1
Event Code
Conditions which Activate the Code
Description System Response
Probable Causes
• Low operating voltage for the fuel metering valve
Recommended Repairs
Check the Operating Voltage for the Fuel Metering Valve
Check the operating voltage for the fuel metering valve. Refer to Troubleshooting, "Electrical
Power Supply - Test".
https://127.0.0.1/sisweb/sisweb/techdoc/techdoc_print_page.jsp?returnurl=/sisweb/sisw... 6/23/2020
G3520C Generator Set GZN00001-UP(SEBP3868 - 22)/Basic Search Page 2 of 2
Clean the valve, if necessary. If the valve is binding due to wear of internal components, refer to
Installation and Operation Manual, SEBU7630, "RAPTOR® Gas Regulation and Metering
Valve/Actuator System for Caterpillar".