You are on page 1of 130

Big solutions. From Helios.

Helios AIR1: The new force in energy-efficient


compact ventilation units.
A complete system
full of great solutions for 02
your applications.

12

16

116

Helios
Applications.
02 Even larger. Even more. Even simpler.
06 Application examples.
10 3 series. 22 types. More than 100 configurations.

Configuration.
.

12 Online configuration tool AIR1Select.


14 More options with AIR1Select.

Product series.
16 Quick selection.
18 The Helios AIR1 XC series: 500 to 3,200 m3/h.
40 The Helios AIR1 XH series: 1,000 to 8,500 m3/h.
76 The Helios AIR1 RH series: 1,500 to 15,000 m3/h.

System.
118 Various control options.
120 The KWL MultiZoneBox. The flexible partner from Helios AIR1.

Helios AIR1 1
Even
larger.
Even
more.
Even
simpler.

2 Helios
Work

More flexibility in working life: Whether


inside or outside – Helios AIR1 ven-
tilation units are suitable for almost
all installation sites. They can also be
perfectly integrated in central building
control systems thanks to modern
interfaces.

Public buildings
Office, commercial and
retail premises
Industrial buildings

Live

The new central building ventilation


system with heat recovery. Together
with the KWL MultiZoneBox,
Helios AIR1 is the energy-efficient and
convenient top solution for apartment
building construction.

Hotels
Residential buildings
Social facilities
Leisure

Flow rates up to 15,000 m3/h ensure


the best indoor climate, even in the
cinema. Also fully automated using
sensors.

Event rooms
Sports facilities
Leisure centres

Learn

The best conditions for reaching the


top in school: The new, compact
Helios AIR1 Series XC ceiling units.
With an innovative maintenance
concept and outstanding acoustics.

Kindergartens
Libraries
Educational facilities
As a pioneer in energy-efficient ventilation with decades of experi-
ence in development and production, Helios regularly sets miles-
tones in ventilation technology. The time has come again with the
new series Helios AIR1: The largest ventilation units with heat
recovery ever built by Helios. For more areas of application. And
an ingeniously simple configuration. Experience the new
dimension of energy-efficient compact ventilation units with us.

Helios AIR1 5
Work

Public buildings
Office, commercial and retail premises
Industrial buildings

The “work” application area often brings various challen-


ges for ventilation technology. The connection to common
central building control system standards provides the
necessary overview. With BACnet and ModBus, Helios
AIR1 offers two widely used interfaces for integrating the
ventilation systems into the building automation.

6 Helios
Hotels
Residential buildings
Social facilities

Besides high indoor air quality, individuality is particularly in


demand in residential complexes and apartment buildings.
Helios AIR1 offers a perfectly coordinated system solution
as a central ventilation unit: Individual air volume control
per residential unit is ensured in combination with the KWL
MultiZoneBox.

Live

Helios AIR1 Applications 7


Learn

Kindergartens
Libraries
Educational facilities

Whether it is pollen, fine dust or street noise – the reduction


of harmful environmental factors is essential for a healthy
indoor climate. Helios AIR1 units create ideal indoor con-
ditions thanks to the numerous room air quality sensors,
multi-stage filter concept and low-noise operation.

8 Helios
Meeting rooms
Sports facilities
Leisure centres

A wellness experience with all senses: This also includes


fresh and appropriately conditioned room air. Helios AIR1
always offers the right solution with wide-ranging accessory
components for heating and cooling the room air. Even
moisture recovery is possible thanks to rotary heat
exchangers

Leisure

Helios AIR1 Applications 9


3 series

22 types

>100
configurations

10 Helios
XC series

RH series XH series

If you have big plans, you will find exactly the right solution for The wide range of accessories with various heating and cooling
energy-efficient ventilation with heat recovery at Helios. The options, multiple air quality sensors and a multi-level filter con-
new Helios AIR1 product range offers various technical variants cept includes more than 100 configuration options.
in 3 series: for ceiling or floor-mounted installation, with highly
efficient cross-counterflow or rotary heat exchangers for use AIR1Select, the intuitive online software, provides the neces-
inside or outside. sary overview for the simple and quick selection of your
individual ventilation solution.
In this respect, no less than 22 models in a flow rate range
from 500 to 15,000 m3/h guarantee a suitable selection for Helios AIR1 offers the following:
virtually all areas of application and performance classes in the Fast delivery of all types
areas of living, leisure, working and learning. Flexible and simple installation
Immediately ready for use due to integrated controls
Eurovent-certified components

Helios AIR1 11
Online configuration as simple
as surfing the Internet.
With Helios AIR1, you can choose the perfect solution for your ap-
plication from more than 100 configuration options. In order to assist
you with the selection, we have developed AIR1Select - an online
configuration tool specifically for Helios AIR1 ventilation units.

AIR1Select allows the configuration of your ventilation unit with a few,


self-explanatory inputs. You can save, export and retrieve your results
at any time.

Simply run AIR1Select in your internet browser at:


www.AIR1Select.com

Simply precise!
Professional software has never been this uncomplicated:

Intuitive and modern user interface.


From the Cloud: Always up to date and available
everywhere.
Runs in browser: Optimised for
PC, laptop and tablet.
Advanced user management
including team functions.

12 Helios
Make it count!
Just a few inputs and your calculation results will appear
clearly arranged on the screen. All project-specific results
can be saved, printed and exported in various data formats.
AIR1Select also assists you with the quick and secure
selection of optional accessory components.

AIR1Select offers the following:

Detailed calculation results and diagrams


Selection of accessory components.
Orderable material lists.
Specification texts in Word format.
CAD/BIM data for direct import into your system.

PDF BIM LV

Helios AIR1 Configuration 13


The fastest way
to a customised
ventilation unit.
Very little basic data is required to configure your Helios AIR1 ventilation unit.
AIR1Select subsequently provides results including detailed calculation results at a glance –
simple, secure and in record-setting speed.

Intuitive and high-performance Everything from a single source


Cloud-based online software – always up-to-date Detailed calculation results and
and available everywhere. diagrams.
Modern operating concept for perfect Project-specific material lists,
results in the shortest possible time. also with price information upon registration.
Comprehensive range of matching accessory Specification texts for your Helios AIR1
components. unit and the selected accessories.

Homepage

Find the right unit with just


a few details.
Clear design and intuitive
operation.
Everything you need to
know is directly accessible.
Detailed information can be
accessed at any time.

14 Helios
Results

All data at a glance in compact form.


Detailed calculation results for unit
and accessories.
Clear ventilation diagrams.
Large amount of additional information,
such as dimensional drawings, main-
tenance areas and ERP product data
sheet.
Individual material list.

Data output

Free compilation of selected


information.
Dynamic generation of content
for units and accessories.
Incl. ERP data sheet, material lists,
and specification texts.
CAD/ BIM data available to download.

Project management

Overview of all projects.


Keyword search for quick
orientation.
Collection of a wealth of project
information.
Store multiple designs per project.
Team function, allows multiple editors.

Helios AIR1 Configuration 15


The ideal solution for every
Type Ref. no. Page Unit Installation Heat Unit dimensions Max. flow rate m³/h /
location position exchanger (L x H x W) mm stat. pressure Pa (1)

XC series 18

AIR1 XC 500 04330 22 1578 x 383 x 1050 570 / 200

AIR1 XC 700 04331 24 1628 x 385 x 1225 680 / 200


Cross-
AIR1 XC 1400 04332 26 Inside Ceiling counter- 1753 x 425 x 1525 1,450 / 250
flow
AIR1 XC 2200 04333 28 1978 x 508 x 1895 2,350 / 250

AIR1 XC 3200 04334 30 2128 x 594 x 2145 3,100 / 250

XH series 40

AIR1 XH 1000 04335 44 2005 x 1185 x 685 950 / 250

AIR1 XH 1500 04336 46 2090 x 1380 x 695 1,490 / 250

AIR1 XH 2500 04337 48 2345 x 1460 x 915 2,430 / 250

AIR1 XH 3500 04338 50 Inside Cross- 2970 x 1599 x 1017 3,150 / 250
Floor-
or counter-
AIR1 XH 4500 04339 52 standing 3515 x 2020 x 1070 4,150 / 250
outside flow

AIR1 XH 5500 04340 54 3555 x 2020 x 1280 5,400 / 400

AIR1 XH 7000 04341 56 3605 x 2020 x 1580 6,300 / 400

AIR1 XH 8500 04342 58 3655 x 2020 x 1930 8,300 / 400

RH series 76

AIR1 RH 1500 04343 80 1700 x 1320 x 810 1,600 / 250

AIR1 RH 2000 04344 82 1700 x 1420 x 910 2,100 / 250

AIR1 RH 3000 04345 84 1700 x 1530 x 1020 3,000 / 250

AIR1 RH 5000 04346 86 1845 x 1800 x 1290 5,150 / 400


Inside Conden-
Floor-
AIR1 RH 6000 04347 88 or sation 2015 x 1920 x 1410 6,200 / 400
standing
outside rotor
AIR1 RH 8000 04348 90 2185 x 2170 x 1660 8,000 / 400

AIR1 RH 9500 04349 92 2315 x 2270 x 1760 9,700 / 400

AIR1 RH 12000 04350 94 2450 x 2420 x 1910 13,300 / 400

AIR1 RH 15000 04351 96 2535 x 2670 x 2160 15,000 / 400

AIR1 RH 1500/SO 04352 80 1700 x 1320 x 810 1,520 / 250

AIR1 RH 2000/SO 04353 82 1700 x 1420 x 910 2,020 / 250

AIR1 RH 3000/SO 04354 84 1700 x 1530 x 1020 2,770 / 250

AIR1 RH 5000/SO 04355 86 1845 x 1800 x 1290 4,950 / 400


Inside
Floor- Adsorption
AIR1 RH 6000/SO 04356 88 or 2015 x 1920 x 1410 5,950 / 400
standing rotor
outside
AIR1 RH 8000/SO 04357 90 2185 x 2170 x 1660 7,650 / 400

AIR1 RH 9500/SO 04358 92 2315 x 2270 x 1760 9,400 / 400

AIR1 RH 12000/SO 04359 94 2450 x 2420 x 1910 12,800 / 400

AIR1 RH 15000/SO 04360 96 2535 x 2670 x 2160 14,700 / 400


(1) The information contains guideline values. Detailled information can be found at www.AIR1Select.com

16 Helios
area of application.
Minimum Optimal area of application Maximum m³/h

0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000 14,000 15,000

0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000 14,000 15,000

0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000 11,000 12,000 13,000 14,000 15,000

Helios AIR1 Types 17


The Helios AIR1 XC series:
®

500 to 3,200 m3/h.


5 unit types:

AIR1 XC 500
AIR1 XC 700
AIR1 XC 1400
AIR1 XC 2200
AIR1 XC 3200

During the development of the Helios AIR1 XC


series, the focus was already on the installation
situation in suspended system ceilings. The result
is a new generation of ceiling ventilation units
with an intelligent maintenance solution and
extremely compact unit dimensions.

Even if space is limited, an electric or warm water


auxiliary heater battery can be easily integrated
into the unit. The external cooling module can be
directly mounted to the supply air inlets of the unit
and thus also guarantees installation in confined
spaces.

18 Helios
Pre-heater as standard
equipment for optimal Compact and flat
year-round operation construction fits
everywhere

Flexible filter main-


tenance on the side
and below

Integrable auxiliary
heater register can be
retrofitted at any time
Condensate tray on
exhaust air and supply
air side, also with con-
densate pump upon
request

Helios AIR1 Series XC 19


The XC series in detail.

1 Housing
1 Compact housing in panel construction made of Aluzinc sheet steel, insula-
ted on all sides with 50 mm mineral wool for optimal thermal and acoustic
insulation. External corrosion-resistant coating on all sides of housing, RAL
7047, corrosion class C4, Aluzinc sheet steel inside. The smooth inner sur-
face meets the hygiene requirements for optimal cleaning in consideration of
the hygiene standard VDI 6022. Inspection openings on the on the under-
side of the unit for simple access to all unit components and optimal clea-
ning and maintenance. Additional inspection openings on the side for filter
replacement. Stainless steel condensate tray on the exhaust air and supply
air side. A corresponding condensate pump is optionally available for each
unit size. The XC units are designed so that an electric or hot water auxiliary
heater can be easily installed in the ventilation unit, even for retrofitting.
2
2 Heat exchanger
Eurovent-certified cross-counterflow plate heat exchanger made of alumini-
um with high thermal efficiency of up to 90 % in accordance with EN 308.
The heat exchanger has high internal leak tightness and it is thus particularly
suitable for applications with a risk of odour transmission. The heat exchan-
ger module has an automatic bypass damper mechanism for summer night
cooling as standard. An electrical pre-heater (standard equipment) heats the
outside air at very low outside temperatures. Thus, it prevents the freezing
of the heat exchanger and guarantees its safe functioning as well as optimal
heat recovery for the entire heating period.

3 3 Fans
The vibration dampened fans are located in the unit and they consist of
freewheeling, backward curved centrifugal impellers with direct drive via a
variable EC motor with low energy consumption and very low noise level.
The high performance plastic impeller is dynamically balanced in two levels.
Variably controllable via 0 – 10 V signal. Plug-in connections to all electrical
components for the simplification of maintenance work. Eurovent-certified
EC-motors in class IE4 with very low SFP values and high energy efficiency.

Pipe routing
Installation-friendly connection of outside, exhaust, extract and supply air to
a duct or pipe system. Adapters are optionally available as unit accessories
4 for adaption to a round duct system.

4 Control system
The ventilation unit is delivered ready for operation with a modern, all-round
control system. The control system is attached to the side of the unit in a
connection box for easy maintenance , factory-wired and function-tested.
Two controllers are available for selection (required accessory).

20 Helios
Overview of control functions:
5 Choice between ventilation modes Constant volume CAV, Constant pres-
sure CAP (accessory required) or Constant speed CRPM in %.
Multiple possible operating modes and levels.
Automatic control via humidity or room air quality sensors (can connect up
to three sensor types and maximum 18 sensors).
Automatic operation via integrated weekly programme.
Operating modes Free cooling (also night cooling/bypass function) and
active cooling (using cooling register) possible.
Commissioning assistant for simple, quick and faultless commissioning of
the unit and matching accessories.
Connection to the central building control system via BACnet or Modbus.
Digital output for collective fault signal.
6 Further information on the Helios AIR1 control system can be found on p. 118.

5 Accessories
There are a number of accessory components available for the Helios AIR1
units. A detailed overview and the matching accessories for your Helios
AIR1 unit can be found on the following product pages.

6 Air filters
Cassette filters with long service lives due to dynamic pressure monitoring.
Simple filter replacement at the side or below through insert frame and
quick clamp device.
Further information on the air filters and filter classes can be found on p. 39.

7
Overview of air filters Standard scope of delivery

Eurovent certification for the AIR1 XC Type Filter class

series has been applied for. The AIR1 ELF-AIR1 XC 500/ePM10 50%/96 ePM10 50% (M5)
Extract air filter

XC series is designed in accordance ELF-AIR1 XC 700/ePM10 50%/96 ePM10 50% (M5)

with the requirements of Directive VDI ELF-AIR1 XC 1400/ePM10 50%/96 ePM10 50% (M5)

6022 (hygiene requirements for building ELF-AIR1 XC 2200/ePM10 50%/96 ePM10 50% (M5)

ventilation systems). ELF-AIR1 XC 3200/ePM10 50%/96 ePM10 50% (M5)


ELF-AIR1 XC 500/ePM1 55%/96 ePM1 55% (F7)
Outside air filter

ELF-AIR1 XC 700/ePM1 55%/96 ePM1 55% (F7)


ELF-AIR1 XC 1400/ePM1 55%/96 ePM1 55% (F7)
ELF-AIR1 XC 2200/ePM1 55%/96 ePM1 55% (F7)
ELF-AIR1 XC 3200/ePM1 55%/96 ePM1 55% (F7)

Helios AIR1 Series XC 21


AIR1 XC 500 Performance curve

Dpfa
Pa

V· m3/h

Unit type

AIR1 XC 500
Ref. no. 04330
Heat exchanger Cross-counterflow

Technical data Sound data

Mechanical data Sound power level LwA dB(A) at 200 Pa external pressure
Area of application Inside 200 m³/h 400 m³/h 570 m³/h
Installation position Ceiling Supply air (LwA) 67 71 76
Maintenance access Side and underside Extract air (LwA) 61 64 68
Min. air volume 95 m³/h Outside air (LwA) 58 60 64
Max. air volume 570 m³/h (1) Exhaust air (LwA) 67 71 76
Weight, unit operational 130 kg Sound pressure level LpA db(A) of sound radiated from housing
Housing class (DIN 1886) T3 / TB3 / D2 200 m³/h 400 m³/h 570 m³/h
Filter Outside air ePM1 55% (F7) (2) Housing rad. 1 m 39 41 45
Filter Extract air ePM10 50% (M5) (2) Housing rad. 3 m 30 31 36
Media temperature (air) -20 to +50 °C Housing rad. 5 m 25 27 31
Ambient temperature (operation) 0 to +50 °C
The sound power at the connectors is calculated for the simultaneous
Protection class IP 31 operation of both fans. The sound pressure level is determined for the
Electrical data simultaneous operation of both fans at distances of 1, 3 and 5 m.

Central building control system BACnet, Modbus TCP/IP


Voltage / Frequency 230 V 1N ~, 50 Hz
Max. output Fans 2 x 170 W
Max. output Elec. pre-heater 1600 W
Nominal current
– Ventilation unit 10.3 A (3)
– Electrical auxiliary heater 7 A (4)
– max. total 17.3 A
Connection (wiring diagram no.) SS-1312

(1) = at 200 Pa external pressure loss ERP-compliant


(2) = Other filter classes see optional accessories
(3) = includes electrical pre-heater
(4) = Optional accessory

22 Helios
Bottom view
Ansicht von unten
Vue de dessous
Dimensional drawing

View A (from below) View C


Bottom view
Ansicht von unten 465 674 401
Vue de dessous 1050

(1) 320
394 521 G 1/2 300 M8

EHA ODA

65
383

170

150
465 674view
Bottom 401
Ansicht von unten 1050
Vue de dessous
320 130 254 412

88
394 521 G 1/2 300 M8 613 296 920
ø17,5
964

192
1540

313
EHA ODA
65
383

170

150
465 674 401
1050
Bottom view A
1578
254 320 412
88
Ansicht von unten

36,5
394613 521296 130
G 1/2 Vue de dessous
300 920 M8
ø17,5
964

12
ODA - Outdoor Air / Außenluf

192
View B1540
(from above) View D EHA - Exhaust Air / Fortluft /

313
EHA ODA
65
383

ETA - Extract Air / Abluft / Ai

170

150
EHA SUP SUP - Supply Air / Zuluft / Ai
B
1578 Top view

820
465 674 401 Ansicht von oben
254 412
88

36,5
1050
Vue de dessus
613 296 920
ø17,5
320
12

964 ODA / Air extérieur


ODA - Outdoor Air / Außenluft 130 ETA
394 521 G 1/2 Air / Fortluft /Air rejeté
EHA - Exhaust 300 M8
1540 ETA - Extract Air / Abluft / Air repris
EHA SUP SUP - Supply Air / Zuluft / Air soufflé

192
313
EHA ODA
65
Top view
383

170

150
820

1578
Ansicht von oben
Vue de dessus

ODA ETA 254 412


12

88

ODA - Outdoor Air / Außenluft / Air extérieur

36,5
613 296EHA - Exhaust Air / Fortluft /Air rejeté 920
ø17,5
ETA - Extract Air / Abluft / Air repris
EHA 964
SUP SUP - Supply Air / Zuluft / Air soufflé
1540
Top view
820

Ansicht von oben


Vue de dessus
C 1578
ODA ETA
12

ODA - Outdoor Air / Außenluft / Air extérieur


Dim. in mm (1) External thread ODA: Outside air EHA: Exhaust air ETA: Extract air SUP: Supply air
EHA - Exhaust Air / Fortluft /Air rejeté
ETA - Extract Air / Abluft / Air repris
EHA SUP SUP - Supply Air / Zuluft / Air soufflé
Top view
820

Ansicht von oben


Accessories Vue de dessus

ODA ETA

Heating and cooling registers Controls

Auxiliary heater Controllers


AIR1-ENH XC 500 AIR1-BE ECO Ref. no. 06186 Page 37
Ref. no. 03558 Page 32
Electrical, internal AIR1-BE TOUCH Ref. no. 06187 Page 38
AIR1-NH WW XC 500 Controller connection cable
Ref. no. 02490 Page 32
Hot water, internal
AIR1-SL 4/10 10 m Ref. no. 07073 Page 37
Hydraulic unit for hot water heating register
AIR1-SL 4/20 20 m Ref. no. 07121 Page 37
WHSH HE 24 V (0 – 10 V) Ref. no. 08318 Page 32
Sensors
Cooling register
KWL-CO2 Carbon dioxide sensor Ref. no. 04272 Page 38
AIR1-KR KW XC 500
Ref. no. 04185 Page 33 KWL-FTF Humidity-temperature sensor Ref. no. 04273 Page 38
Cold water, external
KWL-VOC Mixed gas sensor Ref. no. 04274 Page 38
AIR1-KR DX XC 500
Ref. no. 04867 Page 34
Direct evaporator DX, external AIR1-CO2 K Carbon dioxide sensor duct Ref. no. 07124 Page 38
Signal converter for sensors
Air routing
AIR1-SK Ref. no. 06019 Page 39
Multi-leaf dampers
Extension kit for constant pressure control
AIR1-JVK XC 500 Ref. no. 05421 Page 35 AIR1-CAP Ref. no. 06756 Page 38
Flexible connector
Air filters
AIR1-VS 30/15 Ref. no. 07400 Page 36
Adapter square-round Spare air filter and other filter classes

AIR1-ÜS XC 500 Ref. no. 04361 Page 36 ELF-AIR1 XC 500/ePM10 50%/96 (M5) Ref. no. 02171 Page 39
ELF-AIR1 XC 500/ePM1 55%/96 (F7) Ref. no. 02221 Page 39
Condensate drainage
ELF-AIR1 XC 500/ePM1 80%/96 (F9) Ref. no. 02272 Page 39
Condensate pump
The use of original spare air filters is mandatory to guarantee the specified
AIR1-KP XC 500-1400 Ref. no. 06867 Page 37 technical data and air volumes.
Ball siphon
AIR1-KS XC
Ref. no. 07170 Page 37
for unit and cooling register

Helios AIR1 Series XC 23


AIR1 XC 700 Performance curve

Dpfa
Pa

V· m3/h

Unit type

AIR1 XC 700
Ref. no. 04331
Heat exchanger Cross-counterflow

Technical data Sound data

Mechanical data Sound power level LwA dB(A) at 200 Pa external pressure
Area of application Inside 200 m³/h 500 m³/h 680 m³/h
Installation position Ceiling Supply air (LwA) 66 68 70
Maintenance access Side and underside Extract air (LwA) 61 61 63
Min. air volume 180 m³/h Outside air (LwA) 57 57 60
Max. air volume 680 m³/h (1) Exhaust air (LwA) 66 67 70
Weight, unit operational 155 kg Sound pressure level LpA db(A) of sound radiated from housing
Housing class (DIN 1886) T3 / TB3 / D2 200 m³/h 500 m³/h 680 m³/h
Filter Outside air ePM1 55% (F7) (2) Housing rad. 1 m 39 39 41
Filter Extract air ePM10 50% (M5) (2) Housing rad. 3 m 29 29 31
Media temperature (air) -20 to +50 °C Housing rad. 5 m 25 25 27
Ambient temperature (operation) 0 to +50 °C
The sound power at the connectors is calculated for the simultaneous
Protection class IP 31 operation of both fans. The sound pressure level is determined for the
Electrical data simultaneous operation of both fans at distances of 1, 3 and 5 m.

Central building control system BACnet, Modbus TCP/IP


Voltage / Frequency 400 V 3N ~, 50 Hz
Max. output Fans 2 x 170 W
Max. output Elec. pre-heater 2300 W
Nominal current
– Ventilation unit 6.4 / 3.4 / 3.7 A (3)
– Electrical auxiliary heater 3.3 / 3.3 / 3.3 A (4)
– max. total 9.7 / 6.7 / 7 A
Connection (wiring diagram no.) SS-1313

(1) = at 200 Pa external pressure loss ERP-compliant


(2) = Other filter classes see optional accessories
(3) = includes electrical pre-heater
(4) = Optional accessory

24 Helios
Bottom view
Ansicht von unten
Vue de dessous
Dimensional drawing

View A (from below) View C


Bottom view
Ansicht von unten
Vue de dessous 466 749 375 1225

(1) 420
399 556 G1/2 400

88
EHA ODA

220
200
385
Bottom view
466 Ansicht749
von unten 375 1225
Vue de dessous
420 130 300 487

86
399 556 G1/2 615 338
400 M8
ø17,5 1095
1024

182
1590

88
EHA ODA

315
220
200
385

466 749 375 1225


Bottom view A 1628
Ansicht von unten
420
300dessous 487
86
130

36,5
Vue de
399615 556338 G1/2 ODA - Outdoor Air / Außenlu

12
ø17,5 400 1095 M8 EHA - Exhaust Air / Fortluf
1024 ETA - Extract Air / Abluft / A
View B (from
1590 above) View D SUP - Supply Air / Zuluft / A

182
88

EHA ODA EHA SUP

315
220
200
385

1628 BTop view

995
Ansicht von oben
466 749 375 Vue de dessus
1225
300
ODA - Outdoor487
86

36,5
Air / Außenluft / Air extérieur
12

615 338 EHA - Exhaust Air / Fortluft /Air rejeté


ø17,5 1095 420 130
Air / Abluft / AirODA ETA
1024 399 556 ETA - Extract
G1/2
repris
SUP - Supply Air / Zuluft / Air soufflé 400 M8
EHA 1590 SUP

182
88
EHA ODA

315
D Top view

220
200
1628
385

995

Ansicht von oben


Vue de dessus
ODA - Outdoor Air / Außenluft / Air extérieur
12

ODA ETA EHA - Exhaust Air / Fortluft /Air rejeté 300 487
86

36,5
615 338
ETA - Extract Air / Abluft / Air repris
ø17,5
SUP - Supply Air / Zuluft / Air soufflé 1095
EHA 1024
SUP
1590
Top view
995

Ansicht von oben


Vue de dessus 1628
C
ODA ETA ODA - Outdoor Air / Außenluft / Air extérieur
12

EHA - Exhaust Air / Fortluft /Air rejeté


Dim. in mm (1) External thread ODA: Outside air EHA: ExhaustETA
air- Extract AirETA: Extract
/ Abluft air
/ Air repris SUP: Supply air
SUP - Supply Air / Zuluft / Air soufflé
EHA SUP

Top view
995

Ansicht von oben


Vue de dessus
Accessories
ODA ETA

Heating and cooling registers Controls

Auxiliary heater Controllers


AIR1-ENH XC 700 AIR1-BE ECO Ref. no. 06186 Page 37
Ref. no. 03559 Page 32
Electrical, internal AIR1-BE TOUCH Ref. no. 06187 Page 38
AIR1-NH WW XC 700 Controller connection cable
Ref. no. 03659 Page 32
Hot water, internal
AIR1-SL 4/10 10 m Ref. no. 07073 Page 37
Hydraulic unit for hot water heating register
AIR1-SL 4/20 20 m Ref. no. 07121 Page 37
WHSH HE 24 V (0 – 10 V) Ref. no. 08318 Page 32
Sensors
Cooling register
KWL-CO2 Carbon dioxide sensor Ref. no. 04272 Page 38
AIR1-KR KW XC 700
Ref. no. 04186 Page 33 KWL-FTF Humidity-temperature sensor Ref. no. 04273 Page 38
Cold water, external
KWL-VOC Mixed gas sensor Ref. no. 04274 Page 38
AIR1-KR DX XC 700
Ref. no. 04868 Page 34
Direct evaporator DX, external AIR1-CO2 K Carbon dioxide sensor duct Ref. no. 07124 Page 38
Signal converter for sensors
Air routing
AIR1-SK Ref. no. 06019 Page 39
Multi-leaf dampers
Extension kit for constant pressure control
AIR1-JVK XC 700 Ref. no. 05841 Page 35 AIR1-CAP Ref. no. 06756 Page 38
Flexible connector
Air filters
AIR1-VS 40/20 Ref. no. 07403 Page 36
Adapter square-round Spare air filter and other filter classes

AIR1-ÜS XC 700 Ref. no. 04362 Page 36 ELF-AIR1 XC 700/ePM10 50%/96 (M5) Ref. no. 02172 Page 39
ELF-AIR1 XC 700/ePM1 55%/96 (F7) Ref. no. 02223 Page 39
Condensate drainage
ELF-AIR1 XC 700/ePM1 80%/96 (F9) Ref. no. 02273 Page 39
Condensate pump
The use of original spare air filters is mandatory to guarantee the specified
AIR1-KP XC 500-1400 Ref. no. 06867 Page 37 technical data and air volumes.
Ball siphon
AIR1-KS XC
Ref. no. 07170 Page 37
for unit and cooling register

Helios AIR1 Series XC 25


AIR1 XC 1400 Performance curve

Dpfa
Pa

V· m3/h

Unit type

AIR1 XC 1400
Ref. no. 04332
Heat exchanger Cross-counterflow

Technical data Sound data

Mechanical data Sound power level LwA dB(A) at 250 Pa external pressure
Area of application Inside 250 m³/h 900 m³/h 1,450 m³/h
Installation position Ceiling Supply air (LwA) 68 71 78
Maintenance access Side and underside Extract air (LwA) 60 63 69
Min. air volume 190 m³/h Outside air (LwA) 56 60 66
Max. air volume 1450 m³/h (1) Exhaust air (LwA) 68 71 77
Weight, unit operational 200 kg Sound pressure level LpA db(A) of sound radiated from housing
Housing class (DIN 1886) T3 / TB3 / D2 250 m³/h 900 m³/h 1,450 m³/h
Filter Outside air ePM1 55% (F7) (2) Housing rad. 1 m 40 44 50
Filter Extract air ePM10 50% (M5) (2) Housing rad. 3 m 31 35 40
Media temperature (air) -20 to +50 °C Housing rad. 5 m 26 30 36
Ambient temperature (operation) 0 to +50 °C
The sound power at the connectors is calculated for the simultaneous
Protection class IP 31 operation of both fans. The sound pressure level is determined for the
Electrical data simultaneous operation of both fans at distances of 1, 3 and 5 m.

Central building control system BACnet, Modbus TCP/IP


Voltage / Frequency 400 V 3N ~, 50 Hz
Max. output Fans 2 x 500 W
Max. output Elec. pre-heater 4500 W
Nominal current
– Ventilation unit 8.7 / 8.7 / 6.8 A (3)
– Electrical auxiliary heater 6.5 / 6.5 / 6.5 A (4)
– max. total 15.2 / 15.2 / 13.3 A
Connection (wiring diagram no.) SS-1314

(1) = at 250 Pa external pressure loss ERP-compliant


(2) = Other filter classes see optional accessories
(3) = includes electrical pre-heater
(4) = Optional accessory

26 Helios
Bottom view
Ansicht von unten
Vue de dessous
Dimensional drawing

View A (from below) View C


Bottom view
Ansicht von unten
Vue de dessous 503 799 413 1525
(1) 520
414 606 G 1/2 500

116
EHA OD

270
250
425
Bottom view
503 Ansicht799
von unten 413 1525
Vue de dessous
395 605

85
520 653 373
414 606 G 1/2 130 1395
500 M8 ø17,5
1118

202
1715

116
EHA ODA

337
270
250
425

1753
503 799 413
Bottom view 1525 A
395von unten 605
85
Ansicht

36,5
653 373 520
Vue de dessous 1395

12
414 606 G 1/2
ø17,5 130 ODA - Outdoor Air / Außenluft
1118 500 M8
EHA - Exhaust Air / Fortluft /
View B (from
1715above) View D ETA - Extract Air / Abluft / Air

202
SUP - Supply Air / Zuluft / Air
116

EHA ODA EHA SUP

337
270
250
425

1753
BTop view

1295
Ansicht von oben
Vue de dessus
395 605 413
85

36,5
503 799 1525
12

653 373 ODA - Outdoor Air1395


/ Außenluft / Air extérieur
ø17,5 EHA - Exhaust Air / Fortluft /Air rejeté 520
1118 ODA ETA
414 606 G 1/2
ETA - Extract Air / Abluft / Air repris 130
1715 500 M8
SUP - Supply Air / Zuluft / Air soufflé
EHA SUP

202
116
Top view EHA ODA

337
1753
D

270
250
425

1295

Ansicht von oben


Vue de dessus
12

ODA - Outdoor Air / Außenluft / Air extérieur 395 605


85

36,5
ODA ETA
653 EHA
373- Exhaust Air / Fortluft /Air rejeté
ETA - Extract Air /ø17,5
Abluft / Air repris
1395
1118 SUP - Supply Air / Zuluft / Air soufflé
EHA SUP
1715
Top view
1295

Ansicht von oben


Vue de dessus 1753
C
12

ODA ETA ODA - Outdoor Air / Außenluft / Air extérieur


EHA - Exhaust Air / Fortluft /Air rejeté
Dim. in mm (1) External thread ODA: Outside air EHA: Exhaust air ETA: Extract air
ETA - Extract Air / Abluft / Air repris
SUP: Supply air
SUP - Supply Air / Zuluft / Air soufflé
EHA SUP
Top view
1295

Ansicht von oben


Vue de dessus
Accessories
ODA ETA

Heating and cooling registers Controls

Auxiliary heater Controllers


AIR1-ENH XC 1400 AIR1-BE ECO Ref. no. 06186 Page 37
Ref. no. 03574 Page 32
Electrical, internal AIR1-BE TOUCH Ref. no. 06187 Page 38
AIR1-NH WW XC 1400 Controller connection cable
Ref. no. 03661 Page 32
Hot water, internal
AIR1-SL 4/10 10 m Ref. no. 07073 Page 37
Hydraulic unit for hot water heating register
AIR1-SL 4/20 20 m Ref. no. 07121 Page 37
WHSH HE 24 V (0 – 10 V) Ref. no. 08318 Page 32
Sensors
Cooling register
KWL-CO2 Carbon dioxide sensor Ref. no. 04272 Page 38
AIR1-KR KW XC 1400
Ref. no. 04187 Page 33 KWL-FTF Humidity-temperature sensor Ref. no. 04273 Page 38
Cold water, external
KWL-VOC Mixed gas sensor Ref. no. 04274 Page 38
AIR1-KR DX XC 1400
Ref. no. 04869 Page 34
Direct evaporator DX, external AIR1-CO2 K Carbon dioxide sensor duct Ref. no. 07124 Page 38
Signal converter for sensors
Air routing
AIR1-SK Ref. no. 06019 Page 39
Multi-leaf dampers
Extension kit for constant pressure control
AIR1-JVK XC 1400 Ref. no. 05856 Page 35 AIR1-CAP Ref. no. 06756 Page 38
Flexible connector
Air filters
AIR1-VS 50/25 Ref. no. 07404 Page 36
Adapter square-round Spare air filter and other filter classes

AIR1-ÜS XC 1400 Ref. no. 04363 Page 36 ELF-AIR1 XC 1400/ePM10 50%/96 (M5) Ref. no. 02173 Page 39
ELF-AIR1 XC 1400/ePM1 55%/96 (F7) Ref. no. 02224 Page 39
Condensate drainage
ELF-AIR1 XC 1400/ePM1 80%/96 (F9) Ref. no. 02274 Page 39
Condensate pump
The use of original spare air filters is mandatory to guarantee the specified
AIR1-KP XC 500-1400 Ref. no. 06867 Page 37 technical data and air volumes.
Ball siphon
AIR1-KS XC
Ref. no. 07170 Page 37
for unit and cooling register

Helios AIR1 Series XC 27


AIR1 XC 2200 Performance curve

Dpfa
Pa

V· m3/h

Unit type

AIR1 XC 2200
Ref. no. 04333
Heat exchanger Cross-counterflow

Technical data Sound data

Mechanical data Sound power level LwA dB(A) at 250 Pa external pressure
Area of application Inside 700 m³/h 1,500 m³/h 2,350 m³/h
Installation position Ceiling Supply air (LwA) 69 73 81
Maintenance access Side and underside Extract air (LwA) 61 65 72
Min. air volume 200 m³/h Outside air (LwA) 57 61 68
Max. air volume 2350 m³/h (1) Exhaust air (LwA) 69 73 81
Weight, unit operational 285 kg Sound pressure level LpA db(A) of sound radiated from housing
Housing class (DIN 1886) T3 / TB3 / D2 700 m³/h 1,500 m³/h 2,350 m³/h
Filter Outside air ePM1 55% (F7) (2) Housing rad. 1 m 42 45 53
Filter Extract air ePM10 50% (M5) (2) Housing rad. 3 m 32 36 43
Media temperature (air) -20 to +40 °C Housing rad. 5 m 28 31 39
Ambient temperature (operation) 0 to +40 °C
The sound power at the connectors is calculated for the simultaneous
Protection class IP 31 operation of both fans. The sound pressure level is determined for the
Electrical data simultaneous operation of both fans at distances of 1, 3 and 5 m.

Central building control system BACnet, Modbus TCP/IP


Voltage / Frequency 400 V 3N ~, 50 Hz
Max. output Fans 2 x 780 W
Max. output Elec. pre-heater 7050 W
Nominal current
– Ventilation unit 13.6 / 13.6 / 10.5 A (3)
– Electrical auxiliary heater 10.2 / 10.2 / 10.2 A (4)
– max. total 23.8 / 23.8 / 20.7 A
Connection (wiring diagram no.) SS-1315

(1) = at 250 Pa external pressure loss ERP-compliant


(2) = Other filter classes see optional accessories
(3) = includes electrical pre-heater
(4) = Optional accessory

28 Helios
Bottom view
Ansicht von unten
Vue de dessous

Dimensional drawing

View A (from below) View C

557 932 451


1895

Bottom view 520


Ansicht von unten G 1/2
(1) 130
539 606 500 M8
Vue de dessous

254
163
EHA ODA

320
300
508
Bottom view
Ansicht von unten

36,5
Vue de dessous 454 854

89
737 436
ø17,5 1765
1275
557 932 451
1895 1940
520
130
539 606 G 1/2 500 M8 1978
A

254
163

ODA - Outdoor Air / Außenluft / Air extérieur

12
557 932 451 EHA ODA

430
320
300
EHA - Exhaust Air / Fortluft /Air rejeté
508

1895 ETA - Extract Air / Abluft / Air repris


SUP - Supply Air / Zuluft / Air soufflé
520
606 G 1/2 Bottom130
view
539 500 M8 EHA SUP

254 36,5
Ansicht von unten
454 854
89

Vue de dessous
737 436
1765
163

ø17,5 EHA ODA


1275

430
View B 1940
(from above) View
AnsichtD
320
300
Top view
508

von oben

1665
1803
Vue de dessus

1978

36,5
454 854
89

737 436
ø17,5 1765 ODA B ETA
ODA - Outdoor Air / Außenluft / Air extérieur
12

1275
EHA - Exhaust Air / Fortluft /Air rejeté
1940 557
ETA - Extract Air / Abluft / Air repris
932 451
1895
SUP - Supply Air / Zuluft / Air soufflé
1978 520
EHA SUP 130
539 606 G 1/2 500 M8
930 1048
ODA - Outdoor Air / Außenluft / Air extérieur
12

254
163
Top view EHA - Exhaust Air / Fortluft /Air rejeté EHA ODA
D

430
320
300
Ansicht von oben
508
1665
1803

ETA - Extract Air / Abluft / Air repris


Vue de dessus
SUP - Supply Air / Zuluft / Air soufflé

EHA SUP

36,5
454 854

89
ODA ETA 737 436
Top view ø17,5 1765
Ansicht von oben 1275
1665
1803

Vue de dessus
1940

1978
ODA 930 1048 ETA
ODA - Outdoor Air / Außenluft / Air extérieur
12

EHA - Exhaust Air / Fortluft /Air rejeté


C ETA - Extract Air / Abluft / Air repris
SUP - Supply Air / Zuluft / Air soufflé

EHA SUP
Dim. in mm (1)930
External thread
1048 ODA: Outside air EHA: Exhaust air ETA: Extract air SUP: Supply air
Top view
Ansicht von oben
1665
1803

Vue de dessus

Accessories ODA ETA

Heating and cooling registers Controls


930 1048

Auxiliary heater Controllers


AIR1-ENH XC 2200 AIR1-BE ECO Ref. no. 06186 Page 37
Ref. no. 03575 Page 32
Electrical, internal AIR1-BE TOUCH Ref. no. 06187 Page 38
AIR1-NH WW XC 2200 Controller connection cable
Ref. no. 03662 Page 32
Hot water, internal
AIR1-SL 4/10 10 m Ref. no. 07073 Page 37
Hydraulic unit for hot water heating register
AIR1-SL 4/20 20 m Ref. no. 07121 Page 37
WHSH HE 24 V (0 – 10 V) Ref. no. 08318 Page 32
Sensors
Cooling register
KWL-CO2 Carbon dioxide sensor Ref. no. 04272 Page 38
AIR1-KR KW XC 2200
Ref. no. 04188 Page 33 KWL-FTF Humidity-temperature sensor Ref. no. 04273 Page 38
Cold water, external
KWL-VOC Mixed gas sensor Ref. no. 04274 Page 38
AIR1-KR DX XC 2200
Ref. no. 04870 Page 34
Direct evaporator DX, external AIR1-CO2 K Carbon dioxide sensor duct Ref. no. 07124 Page 38
Signal converter for sensors
Air routing
AIR1-SK Ref. no. 06019 Page 39
Multi-leaf dampers
Extension kit for constant pressure control
AIR1-JVK XC 2200 Ref. no. 06000 Page 35
AIR1-CAP Ref. no. 06756 Page 38
Flexible connector
Air filters
AIR1-VS 50/30 Ref. no. 07407 Page 36
Adapter square-round Spare air filter and other filter classes

AIR1-ÜS XC 2200 Ref. no. 04364 Page 36 ELF-AIR1 XC 2200/ePM10 50%/96 (M5) Ref. no. 02174 Page 39
ELF-AIR1 XC 2200/ePM1 55%/96 (F7) Ref. no. 02225 Page 39
Condensate drainage
ELF-AIR1 XC 2200/ePM1 80%/96 (F9) Ref. no. 02285 Page 39
Condensate pump
The use of original spare air filters is mandatory to guarantee the specified
AIR1-KP XC 2200-3200 Ref. no. 06868 Page 37 technical data and air volumes.
Ball siphon
AIR1-KS XC
Ref. no. 07170 Page 37
for unit and cooling register

Helios AIR1 Series XC 29


AIR1 XC 3200 Performance curve

Dpfa
Pa

V· m3/h

Unit type

AIR1 XC 3200
Ref. no. 04334
Heat exchanger Cross-counterflow

Technical data Sound data

Mechanical data Sound power level LwA dB(A) at 250 Pa external pressure
Area of application Inside 1,000 m³/h 2,200 m³/h 3,100 m³/h
Installation position Ceiling Supply air (LwA) 70 77 85
Maintenance access Side and underside Extract air (LwA) 61 69 76
Min. air volume 240 m³/h Outside air (LwA) 57 65 72
Max. air volume 3100 m³/h (1) Exhaust air (LwA) 70 77 85
Weight, unit operational 370 kg Sound pressure level LpA db(A) of sound radiated from housing
Housing class (DIN 1886) T3 / TB3 / D2 1,000 m³/h 2,200 m³/h 3,100 m³/h
Filter Outside air ePM1 55% (F7) (2) Housing rad. 1 m 42 50 57
Filter Extract air ePM10 50% (M5) (2) Housing rad. 3 m 33 41 48
Media temperature (air) -20 to +45 °C Housing rad. 5 m 28 36 43
Ambient temperature (operation) 0 to +45 °C
The sound power at the connectors is calculated for the simultaneous
Protection class IP 31 operation of both fans. The sound pressure level is determined for the
Electrical data simultaneous operation of both fans at distances of 1, 3 and 5 m.

Central building control system BACnet, Modbus TCP/IP


Voltage / Frequency 400 V 3N ~, 50 Hz
Max. output Fans 2 x 1300 W
Max. output Elec. pre-heater 10500 W
Nominal current
– Ventilation unit 20.9 / 20.9 / 15.5 A (3)
– Electrical auxiliary heater 15.2 / 15.1 / 15.1 A (4)
– max. total 36.1 / 36 / 30.6 A
Connection (wiring diagram no.) SS-1316

(1) = at 250 Pa external pressure loss ERP-compliant


(2) = Other filter classes see optional accessories
(3) = includes electrical pre-heater
(4) = Optional accessory

30 Helios
Dimensional drawing Bottom view
Ansicht von unten
Vue de dessous

View A (from below) View C

597 967 526 2145


(1) 720
Bottom view 700 130
Ansicht von unten 614 606 G 3/4 M8
Vue de dessous

279
197
EHA ODA

480
420
400
594
Bottom view
Ansicht von unten
Vue de dessous

36,5
87
776 436 530 955
ø17,5 2015
1379
597 967 526 2145 2090
720
614 606 G 3/4 700 130 2128
M8
A

279
597 967 526 2145 ODA - Outdoor Air / Außenluft / Air extérieur
197

12
EHA ODA

502
EHA - Exhaust Air / Fortluft /Air rejeté

480
420
400
720
594

130 ETA - Extract Air / Abluft / Air repris


614 606 G 3/4 700 M8 SUP - Supply Air / Zuluft / Air soufflé

Bottom view
EHA SUP

279
Ansicht von unten
197

36,5
87

776 436 530 EHA 955 ODA

502
Vue de dessous
480
420
400
594

ø17,5
View B (from above)
1379 2015
View D
Top view
2090 Ansicht von oben

1915
2053
Vue de dessus

36,5
87

776 2128
436 530 955
ø17,5 2015
1379
2090 ODA - Outdoor Air / Außenluft / Air extérieur ODA B ETA
12

EHA - Exhaust Air / Fortluft /Air rejeté


2128 ETA - Extract Air / Abluft / Air repris
597 967 526 2145
SUP - Supply Air / Zuluft / Air soufflé
720
EHA SUP 614 606 G 3/4 700 130
ODA - Outdoor Air / Außenluft / Air extérieur M8
12

EHA - Exhaust Air / Fortluft /Air rejeté


ETA - Extract Air / Abluft / Air repris
1027 1101

279
197
EHA ODA
D Top view SUP - Supply Air / Zuluft / Air soufflé

502
480
420
400
594

Ansicht von oben


1915
2053

EHA Vue de dessus SUP

36,5
87
Top view 776 436 530 955
ODA Ansicht von oben ETA
ø17,5
1915
2053

Vue de dessus 1379 2015


2090

2128
ODA ETA

1027 1101 ODA - Outdoor Air / Außenluft / Air extérieur


12

EHA - Exhaust Air / Fortluft /Air rejeté


ETA - Extract Air / Abluft / Air repris
C SUP - Supply Air / Zuluft / Air soufflé

1027 1101 EHA SUP

Dim. in mm (1) External thread ODA: Outside air EHA: Exhaust air ETA: Extract air SUP: Supply air
Top view
Ansicht von oben
1915
2053

Vue de dessus

ODA ETA
Accessories

Heating and cooling registers 1027 Controls


1101

Auxiliary heater Controllers


AIR1-ENH XC 3200 AIR1-BE ECO Ref. no. 06186 Page 37
Ref. no. 02489 Page 32
Electrical, internal AIR1-BE TOUCH Ref. no. 06187 Page 38
AIR1-NH WW XC 3200 Controller connection cable
Ref. no. 03663 Page 32
Hot water, internal
AIR1-SL 4/10 10 m Ref. no. 07073 Page 37
Hydraulic unit for hot water heating register
AIR1-SL 4/20 20 m Ref. no. 07121 Page 37
WHSH HE 24 V (0 – 10 V) Ref. no. 08318 Page 32
Sensors
Cooling register
KWL-CO2 Carbon dioxide sensor Ref. no. 04272 Page 38
AIR1-KR KW XC 3200
Ref. no. 04190 Page 33 KWL-FTF Humidity-temperature sensor Ref. no. 04273 Page 38
Cold water external
KWL-VOC Mixed gas sensor Ref. no. 04274 Page 38
AIR1-KR DX XC 3200
Ref. no. 04871 Page 34
Direct evaporator DX, external AIR1-CO2 K Carbon dioxide sensor duct Ref. no. 07124 Page 38
Signal converter for sensors
Air routing
AIR1-SK Ref. no. 06019 Page 39
Multi-leaf dampers
Extension kit for constant pressure control
AIR1-JVK XC 3200 Ref. no. 06003 Page 35
AIR1-CAP Ref. no. 06756 Page 38
Flexible connector
Air filters
AIR1-VS 70/40 Ref. no. 07408 Page 36
Adapter square-round Spare air filter and other filter classes

AIR1-ÜS XC 3200 Ref. no. 04365 Page 36 ELF-AIR1 XC 3200/ePM10 50%/96 (M5) Ref. no. 02175 Page 39
ELF-AIR1 XC 3200/ePM1 55%/96 (F7) Ref. no. 02226 Page 39
Condensate drainage
ELF-AIR1 XC 3200/ePM1 80%/96 (F9) Ref. no. 02286 Page 39
Condensate pump
The use of original spare air filters is mandatory to guarantee the specified
AIR1-KP XC 2200-3200 Ref. no. 06868 Page 37 technical data and air volumes.
Ball siphon
AIR1-KS XC
Ref. no. 07170 Page 37
for unit and cooling register

Helios AIR1 Series XC 31


Accessories for the XC series.

Electrical auxiliary heater


Electrical auxiliary heater internal
For installation in the ventilation unit. Provides demand-oriented temperature
control of supply air. Mains power supply and connection to the ventilation unit
control system through pre-wired plug contacts. Variable controls.

Detailed calculations / technical information: www.AIR1Select.com.

Technical data
Type Ref. no. Output Current consumption Weight approx.
AIR1-ENH XC 500 03558 1.6 kW 7.0 A 1.1 kg
AIR1-ENH XC 700 03559 2.3 kW 3.3 A 1.9 kg
AIR1-ENH XC 1400 03574 4.5 kW 6.5 A 3.0 kg
AIR1-ENH XC 2200 03575 7.1 kW 10.2 A 3.6 kg
AIR1-ENH XC 3200 02489 10.5 kW 15.2 A 6.7 kg

Hot water auxiliary heater


Hot water auxiliary heater internal
For installation in the ventilation unit. Provides demand-oriented temperature
control of supply air. The heating elements consist of copper piping with formed
aluminium fins, and copper pipe water connections for flow and return. Further
accessories are required for supply air temperature control (see below; Hydraulic
unit WHSH HE 24V).

Detailed calculations / technical information: www.AIR1Select.com.

Technical data

Weight
Type Ref. no. Water content Hydraulic unit Ref. no.
(without liquid)

AIR1-NH WW XC 500 02490 3.3 l 3.0 kg WHSH HE 24 V (0 – 10 V) 08318


AIR1-NH WW XC 700 03659 4.5 l 3.9 kg WHSH HE 24 V (0 – 10 V) 08318
AIR1-NH WW XC 1400 03661 8.6 l 5.3 kg WHSH HE 24 V (0 – 10 V) 08318
AIR1-NH WW XC 2200 03662 14.5 l 7.5 kg WHSH HE 24 V (0 – 10 V) 08318
AIR1-NH WW XC 3200 03663 19.3 l 9.5 kg WHSH HE 24 V (0 – 10 V) 08318

Hydraulic unit Hydraulic unit


Hydraulic unit for supply air temperature control by controlling the water flow rate
in the heater battery. Delivered as a complete unit consisting of the hydraulic unit
with 3-way valve with actuator and circulating pump, Flow / return temperature
display and flexible connection hoses.
Control voltage: 24 V (0 – 10 V)
Kvs value: 5.1
Flow rate: up to 3.3 m³/h
Connection diameter: G1 AG flat sealing (DN25, 1”)

Type Ref. no.


WHSH HE 24 V (0 – 10 V) 08318

32 Helios
Cold water cooling register
Cold water cooling register external
For demand-oriented temperature control (cooling) of supply air. Mounting
directly to the supply air duct of the ventilation unit including fixing material is
possible. Casing in robust panel construction, insulated on all sides with 50 mm
mineral wool for the minimisation of heat losses. External corrosion-resistant
coating of casing. Large inspection openings on both sides of unit for easy
access and optimised cleaning and maintenance. Stainless steel condensate
tray with condensate drain outlets.

Recommended accessory: Ball siphon AIR1-KS XC (Ref. no. 07170)

Detailed calculations / technical information: www.AIR1Select.com.

Technical data

Connection Weight Condensate


Type Ref. no. Water content
flow / return (1) (without liquid) connection

AIR1-KR KW XC 500 04185 1.2 l G 1/2 24.0 kg 17.5 mm


AIR1-KR KW XC 700 04186 1.3 l G 1/2 37.0 kg 17.5 mm
AIR1-KR KW XC 1400 04187 2.0 l G 1/2 43.0 kg 17.5 mm

12

12
12
AIR1-KR KW XC 2200 04188 3.2 l G 3/4 63.0 kg 17.5 mm
AIR1-KR KW XC 3200 04190 4.4 l G 3/4 80.0 kg 17.5 mm
(1) External thread Bottom view
Bottom
Bottom
Ansicht von view
unten view
unten SUP SUP

K
Vue Ansicht
deAnsicht
von
dessous von
unten SUP

K
K
VueVue
dede
dessous
dessous
Dimensional drawing

View from below Duct connection side Water connection side Unit connection side
643
643
643 R
RR
301 605 T
301
301 605
605 TT
12

W
W
U
S
V

U
U

Bottom view
S
S
V
V

Ansicht von unten SUP AC


B
B
AA
K

Vue de dessous ACAC


AA
AA
36,5

36,5
36,5

ø 17,5 9 60
56 M8 ø 17,5
ø 17,5 99 6060
5656 M8M8 302,5 P
302,5
302,5 PP
Y 77 C
643 CC
R YY 7777
301 605 T
Maße (mm)
Maße
Maße
(mm)
(mm)
Art.-Nr. Type B C K P R S T U V W Y AA AC
Dim. in mm Art.-Nr.
Art.-Nr.Type
Type B B C C K K P P R R S S T T U U V V W W Y Y AAAA ACAC
04185 AIR1-KR KW XC 500 437 437 317 234 320 170 300 150 - 192 467 96 G 1/2
W

04185
04185AIR1-KR
AIR1-KR
KW KW
XCXC500
500437
437437
437317
317234
234320
320170
170300
300150
150 - - 192
192467
467 9696 G 1/2
G 1/2
04186 AIR1-KR KW XC 700 490 537 417 284 420 220 400 200 - 218 467 96 G 1/2
04186
04186AIR1-KR
AIR1-KR
KW KW
XCXC700
700490
490537
537417
417284
284420
420220
220400
400200
200 - - 218
218467
467 9696 G 1/2
G 1/2
U
S

04187 AIR1-KR KW XC 1400 542 677 557 374 520 270 500 250 - 243 467 96 G 1/2
04187
04187AIR1-KR
AIR1-KR
KW KW
XCXC
1400
1400542
542677
677557
557374
374520
520270
270500
500250
250 - - 243
243467
467 9696 G 1/2
G 1/2
B

Dimensions AC 04188 AIR1-KR KW XC 2200 592 878 757 453 520 320 500 300 - 254 447 111 G 3/4
AA

04188
04188AIR1-KR
AIR1-KR
KW KW
XCXC
2200
2200592
592878
878757
757453
453520
520320
320500
500300
300 - - 254
254447
447111
111G 3/4
G 3/4
Type Ref. no. 04190B04190AIR1-KR
04190AIR1-KR
KW XC
CAIR1-KR
KWK3200
KW
XCXC
692
3200
957
P 692
3200
837
R
692957
479
957837
720 420
S479720
837479
700
T420
720
400
420700
480
U 400
700
279
V
400480
447
279W
480279
111
447
G
447111
3/4
YG 3/4
111 G 3/4AA AC (1)
AIR1-KR KWø 17,5
XC 500 04185 437 437 317 234 320 170 300 150 - 192 467 96 G 1/2
9 60
M8
AIR1-KR KW302,5
XC 700 04186 P 490 537 417 284 420 220 400 200 - 218 467 96 G 1/2
C
AIR1-KR KW XCY1400 77 04187 542 677 557 374 520 270 500 250 - 243 467 96 G 1/2
AIR1-KR KW XC 2200 04188 592 878 757 453 520 320 500 300 - 254 447 111 G 3/4
Maße (mm)
Type AIR1-KR
B C KW
K XC
P 3200
R S 04190
T U V W Y 692 AC
AA 957 837 479 720 420 700 400 480 279 447 111 G 3/4
AIR1-KR KW XC 500 437 437 317 234 320 170 300 150 - 192 467 96 G 1/2
(1) External thread
AIR1-KR KW XC 700 490 537 417 284 420 220 400 200 - 218 467 96 G 1/2
AIR1-KR KW XC 1400 542 677 557 374 520 270 500 250 - 243 467 96 G 1/2
AIR1-KR KW XC 2200 592 878 757 453 520 320 500 300 - 254 447 111 G 3/4
AIR1-KR KW XC 3200 692 957 837 479 720 420 700 400 480 279 447 111 G 3/4

Helios AIR1 Series XC 33


Accessories for the XC series.

Direct evaporator cooling register external Direct evaporator cooling register


For demand-oriented temperature control (cooling) of supply air. Mounting
directly to the supply air duct of the ventilation unit is possible. Suitable for use
with common refrigerants (selection list see www.AIR1Select.com).Casing in
robust panel construction, insulated on all sides with 50 mm mineral wool for
the minimisation of heat losses. External corrosion-resistant coating of casing.
Stainless steel condensate tray with condensate drain outlets. Large inspection
openings on both sides of unit for easy access and optimised cleaning and
maintenance. Condensate connection 17.5 mm.
Recommended accessory: Ball siphon AIR1-KS XC (Ref. no. 07170)

Detailed calculations / technical information: www.AIR1Select.com.

Technical data

Weight
Type Ref. no. Filling capacity Ø connection outlet Ø connection inlet
(without liquid)

AIR1-KR DX XC 500 04867 0.90 l 12 mm 9.5 mm 23.0 kg


AIR1-KR DX XC 700 04868 1.07 l 12 mm 9.5 mm 36.0 kg

12
12
12
AIR1-KR DX XC 1400 04869 1.71 l 19 mm 9.5 mm 44.0 kg
AIR1-KR DX XC 2200 04870 2.64 l 19 mm 12 mm 62.0 kg
AIR1-KR DX XC 3200 04871 3.64 l 22 mm 16 mm
Bottom view
AnsichtBottom
vonBottom
view view
unten
79.0 kg
SUP

K
Ansicht
Vue de Ansicht
von unten
dessous von unten
SUPSUP

K
K
Vue de
Vuedessous
de dessous

Dimensional drawing

View from below Duct connection side Water connection side Unit connection side
543
543543 R
R R
301 505 T
12

301301 505505 T T

W
W
W
SU
S
V

Bottom view Z
U
U
S
V
V

Z Z
B

Ansicht von unten


SUP
K

B
B

Vue de dessous
AC D
AC AC A AD AD
AA
AA
AA
36,5
36,5
36,5

Y ø 17,5 9 AB
56 M8 Y Y ø 17,5ø 17,5 9 9 AB AB
56 56 M8 M8
252,5 P
252,5
252,5 P P
543 C
R C C
301 505 T
Maße (mm)
Maße
Maße
(mm)
(mm)
Art.-Nr. Type B C K P R S T U V W Y Z AA AB AC AD
Dim. in mm Art.-Nr.
Art.-Nr.
TypeType B B C C K K P P R R S S T T U U V V W W Y Y Z Z AA AAAB ABAC ACAD AD
04867 AIR1-KR DX XC 500 437 437 317 234 320 170 300 150 - 192 230 60 85 106 12 9,5
W

04867
04867 AIR1-KR
AIR1-KR
DX DX
XC XC
500500437437
437437
317317
234234
320320
170170300300
150150- -192192 23023060 6085 8510610612 129,5 9,5
04868 AIR1-KR DX XC 700 490 537 417 284 420 220 400 200 - 218 240 49 89 141 12 9,5
04868
04868 AIR1-KR
AIR1-KR
DX DX
XC XC
700700490490
537537
417417
284284
420420
220220400400
200200- -218218 24024049 4989 8914114112 129,5 9,5
U
S

Z 04869 AIR1-KR DX XC 1400 542 677 557 374 520 270 500 250 - 243 240 49 90 141 19 9,5
B

04869
04869 AIR1-KR
AIR1-KR
DX DX
XC 1400
XC 1400542542
677677
557557
374374
520520
270270
500500250250- -243243 24024049 4990 9014114119 199,5 9,5
AC
Dimensions 04870 AIR1-KR DX XC 2200 592 878 757 453 520 320 500 300 - 254 240 54 98 128 19 12
AD 04870
04870 AIR1-KR
AIR1-KR
DX DX
XC 2200
XC 2200592592
878878
757757
453453
520520
320320
500500300300- -254254 24024054 5498 9812812819 1912 12
AA

04871 AIR1-KR DX XC 3200 692 957 837 479 720 420 700 400 480 279 240 54 98 128 22 16
Type Ref. no. B 04871
C04871 AIR1-KR
KAIR1-KR
DXPDX
XC 3200
XC 3200
R 692692957
S 957
837837
T 479479
720
U 720
420420
V700700400
W400480480
Y279279
240Z24054 54
AA98 9812812822 22
AB 16 16
AC AD
M8 AIR1-KR DX XCY 500ø 17,5 04867 437 9 437 317 AB
234 320 170 300 150 – 192 230 60 85 106 12 9.5
252,5 P
AIR1-KR DX XC 700 04868 490 537 417 284 420 220 400 200 – 218 240 49 89 141 12 9.5
C
AIR1-KR DX XC 1400 04869 542 677 557 374 520 270 500 250 – 243 240 49 90 141 19 9.5
AIR1-KR DX XC 2200 Maße (mm)
04870 592 878 757 453 520 320 500 300 – 254 240 54 98 128 19 12
B C K P R S T U V W Y Z AA AB AC AD
AIR1-KR DX XC 3200 04871
DX XC 500 437 437 317 234 320 170 300 150 -
692 957 837 479
192 230 60 85 106 12 9,5
720 420 700 400 480 279 240 54 98 128 22 16
DX XC 700 490 537 417 284 420 220 400 200 - 218 240 49 89 141 12 9,5
DX XC 1400 542 677 557 374 520 270 500 250 - 243 240 49 90 141 19 9,5
DX XC 2200 592 878 757 453 520 320 500 300 - 254 240 54 98 128 19 12
DX XC 3200 692 957 837 479 720 420 700 400 480 279 240 54 98 128 22 16

34 Helios
Multi-leaf damper
Multi-leaf damper external
Multi-leaf damper for preventing cold draughts when the fan is stationary. Frame-
work casing with connection flange on both sides. Counter-rotating blades, with
retracted sealing lip. Sealing class 2. Installation on outside of unit.

Technical data

Runtime Ambient Protection


Type Ref. no. Weight Actuator type
(open / closed) temperature class

AIR1-JVK XC 500 05421 75 s 1.6 kg -30 to +50 °C IP 42 24 V DC. spring return


AIR1-JVK XC 700 05841 75 s 2.6 kg -30 to +50 °C IP 42 24 V DC. spring return
AIR1-JVK XC 1400 05856 75 s 3.9 kg -30 to +50 °C IP 42 24 V DC. spring return
AIR1-JVK XC 2200 06000 75 s 4.5 kg -30 to +50 °C IP 42 24 V DC. spring return
AIR1-JVK XC 3200 06003 75 s 7.9 kg -30 to +50 °C IP 42 24 V DC. spring return

Dimensional drawing

R
T 76
U

B
S

D
Dim. in mm

Maße (mm)
Dimensions Art.-Nr. Type A B D R S T U
Type 05421 AIR1-JVK
Ref. no. A XC 500
B 340 185
D 430 320 R170 300 100
S T U
AIR1-JVK XC 500 05421 05841 AIR1-JVK
340 XC 700
185 440 235
430 523 420 220
320 400 150
170 300 100
05856 AIR1-JVK XC 1400 540 285 623 520 270 500 200
AIR1-JVK XC 700 05841 440 235 523 420 220 400 150
06000 AIR1-JVK XC 2200 540 335 623 520 320 500 250
AIR1-JVK XC 1400 05856 540 285 623 520 270 500 200
06003 AIR1-JVK XC 3200 740 435 823 720 420 700 350
AIR1-JVK XC 2200 06000 540 335 623 520 320 500 250
AIR1-JVK XC 3200 06003 740 435 823 720 420 700 350

Helios AIR1 Series XC 35


Accessories for the XC series.

Flexible connector Flexible connector


Flexible connector (uninsulated), with flange connections on both sides, for
mounting between the ventilation unit and duct system. Prevents structure-borne
sound transmission and bridges mounting tolerances. Elastic fabric sleeve,
operating temperature range from -10 °C to +80 °C.

Dimensional drawing Dimensions


XC units Type Ref. no. A B R S
AIR1-XC 500 AIR1-VS 30/15 07400 343 193 320 170
AIR1-XC 700 AIR1-VS 40/20 07403 443 243 420 220
AIR1-XC 1400 AIR1-VS 50/25 07404 543 293 520 270
AIR1-XC 2200 AIR1-VS 50/30 07407 543 343 520 320
B
S

10,5x14 AIR1-XC 3200 AIR1-VS 70/40 07408 743 443 720 420

R
A 5
14

Dim. in mm

Square-round adapter
Square-round adapter
Symmetrical adapter for connecting the ventilation unit to round air ducts/duct
systems. Made of galvanised steel sheet. The pressure loss of the adapter at
maximum air volume is < 10 Pa on both the intake and discharge side.

Dimensional drawing Dimensions


Type Ref. no. A B C ØD E R S

C D AIR1-ÜS XC 500 04361 342 192 200 200 40 320 170


AIR1-ÜS XC 700 04362 442 242 200 250 60 420 220
B

AIR1-ÜS XC 1400 04363 542 292 250 315 60 520 270


S

AIR1-ÜS XC 2200 04364 542 342 250 400 80 520 320


E AIR1-ÜS XC 3200 04365 742 442 300 450 80 720 420

10 21
R
A

Dim. in mm

36 Helios
Condensate pump Condensate pump
Condensate pump for mounting directly to unit, includes fixing material. Self-
priming. Thermal fuse with auto-restart. Protection class IP 20.

Technical data
Max. Max.
Max. flow Max. Voltage / frequency /
Type Ref. no. recommended water tem- Drain pipe ID
rate suction head output
discharge head perature
AIR1-KP XC 500-1400 06867 13 l/h 10 m 1.5 m 220-240 V 50 / 60 Hz 19 W 35 °C 6 mm
AIR1-KP XC 2200-3200 06868 40 l/h 10 m 2m 220-240 V 50 / 60 Hz 16 W 35 °C 6 mm

Ball siphon
Ball siphon Siphon for the drainage of condensate with over or underpressure in comparison
to the environment. Self-filling and self-closing, with float ball as non-return valve.
Screw cap for inspection purposes.
Suitable for a max. under/overpressure of ± 600 Pa.
For use with the units and the cooling register.
Connection diameter 40 mm.

Type Ref. no.


AIR1-KS XC 07170

Controller Eco
Controller Eco
Backlit display with 4 lines a 20 characters. The display menu system is operated
via seven buttons. There are two LEDs on the front side: One alarm LED and one
LED for the input mode. The controller is delivered with a 5 m cable as standard.
Cable lengths of 10 m and 20 m are optionally available. The maximum connec-
tion length is 100 m. The controller is designed for wall mounting. Alternatively,
it can also be attached to the unit casing using magnetic strips. Protection class
IP 40.

Technical data

Power Dimensions Ambient Ambient Connection Connection


Type Ref. no. Voltage
consumption (WxHxD) humidity temperature cable 10 m cable 20 m

Max. 90 % RH AIR1-SL 4/10 AIR1-SL 4/20


AIR1-BE ECO 06186 24 V DC 0.24 W 115 x 95 x 25 mm +5 °C to +40 °C
(non-condensing) Ref. no.: 07073 Ref. no.: 07121

Helios AIR1 Series XC 37


Accessories for the XC series.

Controller Touch
Controller Touch
Graphic user interface with intuitive menu structure and simple operation. The
display has a capacitive touch function and a size of 7”, incl. multi-colour colour
technology. Includes stainless steel casing for simple surface-mounting to the
wall. It is delivered with a 5 m cable as standard. Cable lengths of 10 m and 20 m
are optionally available. The maximum connection length is 100 m. Protection
class IP 20.

Technical data

Power Dimensions Ambient Ambient Connection Connection


Type Ref. no. Voltage
consumption (WxHxD) humidity temperature cable 10 m cable 20 m

(1) AIR1-SL 4/10 AIR1-SL 4/20


AIR1-BE TOUCH 06187 24 V DC 6W 185 x 131 x 50 mm Max. 90 % RH -10 °C to +60 °C
Ref. no.: 07073 Ref. no.: 07121

Room sensors
Room sensors For measuring the CO2, mixed gas (VOC) concentration or relative humidity
and temperature. Control according to highest measured value. Includes
control cable KWL-SL 4/3 (3 m long), other lengths available upon request.
Dimensions (W x H x D) 95 x 97 x 30 mm.

Technical data
Type Ref. no. Measurement range
KWL-CO2 04272 400 ... 2000 ppm
(1)
KWL-FTF 04273 0 ... 99 % RH and 0 ... 40 °C
KWL-VOC 04274 450 ... 2000 ppm

Carbon dioxide sensor for duct installation


Carbon dioxide sensor for duct installation
Sensor for measuring the carbon dioxide concentration in the air. For installation
in the ventilation duct. Installation depth 40 – 180 mm.

Technical data
Type Ref. no. Measurement range
AIR1-CO2 K 07124 0 ... 2000 ppm

Extension kit for CAP mode


Extension kit for CAP mode Differential pressure transmitter for constant pressure operation of the ventilation
unit. Vertical or horizontal installation possible. Protection class IP 54.
Scope of delivery: Pressure transmitter, pressure hose and sensor.

Technical data
Ambient Ambient
Type Ref. no. Voltage
humidity temperature

24 V AC / DC (1) -25 °C to
AIR1-CAP 06756 Max. 95 % RH
+15 % +50 °C

(1) Non-condensing

38 Helios
Signal converter for sensors Signal converter for sensors
Signal converter for the connection of up to six AIR1 room sensors of the same
sensor type. The AIR1-SK compares the connected inputs and forwards the
highest input signal to the max. output. Supplied pre-installed in the appropriate
terminal box incl. transformer 230 V / 24 V AC and terminal strip.
Dimensions terminal box (L x H x W): 218 x 149 x 97 mm

Technical data

Power Protection
Type Ref. no. Voltage Ambient humidity Ambient temperature
consumption class

Max. 90 % RH IP 20 / IP 66 in
AIR1-SK 06019 230 V, 50 Hz max. 15 VA -40 °C to +50 °C
(non-condensing) terminal box

Spare air filter


Spare air filter Helios AIR1 units are supplied with the filter classes ePM1 55%/F7 (outside air)
and ePM10 50%/M5 (extract air) as standard. Depending on the unit size, the
air filter consists of multiple (separate) air filter inserts. This is taken into account
when ordering the spare air filter.
In case of increased air quality requirements, other filter classes are available for
the outside air and extract air (see table below). All air filters are pressure-loss-
optimised cassette filters with large filter surfaces.

Extract air filter Outside or extract air filter ePM1 55% (F7)
ePM10 50% (M5) Outside air filter ePM1 80% (F9)

Technical data
Type Ref. no. Filter class
ELF-AIR1 XC 500/ePM10 50%/96 02171 ePM10 50% (M5)
Extract air filter

ELF-AIR1 XC 700/ePM10 50%/96 02172 ePM10 50% (M5)


ELF-AIR1 XC 1400/ePM10 50%/96 02173 ePM10 50% (M5)
ELF-AIR1 XC 2200/ePM10 50%/96 02174 ePM10 50% (M5)
ELF-AIR1 XC 3200/ePM10 50%/96 02175 ePM10 50% (M5)
ELF-AIR1 XC 500/ePM1 55%/96 02221 ePM1 55% (F7)
extract air filter
Outside or

ELF-AIR1 XC 700/ePM1 55%/96 02223 ePM1 55% (F7)


ELF-AIR1 XC 1400/ePM1 55%/96 02224 ePM1 55% (F7)
ELF-AIR1 XC 2200/ePM1 55%/96 02225 ePM1 55% (F7)
ELF-AIR1 XC 3200/ePM1 55%/96 02226 ePM1 55% (F7)
ELF-AIR1 XC 500/ePM1 80%/96 02272 ePM1 80% (F9)
Outside air filter

ELF-AIR1 XC 700/ePM1 80%/96 02273 ePM1 80% (F9)


ELF-AIR1 XC 1400/ePM1 80%/96 02274 ePM1 80% (F9)
ELF-AIR1 XC 2200/ePM1 80%/96 02285 ePM1 80% (F9)
ELF-AIR1 XC 3200/ePM1 80%/96 02286 ePM1 80% (F9)

Helios AIR1 Series XC 39


The Helios AIR1 XH series:
®

1,000 to 8,500 m3/h.


8 unit types:

AIR1 XH 1000
AIR1 XH 1500
AIR1 XH 2500
AIR1 XH 3500
AIR1 XH 4500
AIR1 XH 5500
AIR1 XH 7000
AIR1 XH 8500

The Helios AIR1 XH series stands for reliable and


high-performance compact ventilation units
and various area of application. The high-quality
housing construction allows installation inside and
outside and is modularly expandable.

The two-sided maintenance access to all unit com-


ponents and the universal right or left configuration
guarantee high flexibility at the construction site.
The multi-level filter concept, which enables the
optimal adaptation to individual circumstances and
requirements, provides the perfect indoor climate.

40 Helios
Multi-level filter
concept

Also suitable for


outdoor installation

Pre-heater as standard
equipment for optimal
Separable casing design
year-round operation
from 3,500 m3/h

Universal right / left


configuration
Maintenance access
on both sides for
simple service work

Helios AIR1 Series XH 41


The XH series in detail.

1 Housing
1
Housing consisting of robust and stable aluminium frame profiles, thermally
optimised to minimise thermal bridges. Double-walled panels made of Alu-
zinc sheet steel. Insulated on all sides with 50 mm mineral wool for optimal
thermal and acoustic insulation. External corrosion-resistant coating on all
sides of housing, RAL 7047, corrosion class C4 and thus suitable for ex-
ternal installation. Galvanised inside. The smooth inner surface meets the
hygiene requirements for optimal cleaning in consideration of the hygiene
standard VDI 6022. Large inspection openings on both sides of the unit for
simple access to all unit components and optimal maintenance. The service
doors are equipped with maintenance-free hinges and lockable lever locks.
The XH units are designed so that accessories, such as electric or hot water
auxiliary heaters, can be easily installed in the ventilation unit, even for retro-
2 fitting.

Housing and tightness classes according to DIN EN 1886


Thermal insulation T2
Thermal bridging factor TB2
Mechanical stability D1
Housing leakage in case of overpressure L1
Housing leakage in case of underpressure L1
Filter bypass leakage F9

Outdoor installation of unit


All units are suitable for internal and external installation. Additional accesso-
ries are mandatory for the external installation (e.g. weather protection cover,
intake/discharge hoods etc.). In this respect, please see the accessory list
3
or configure your unit with our online configuration software
www.AIR1Select.com.

2 Heat exchanger
Eurovent-certified cross-counterflow plate heat exchanger made of alumini-
um with high thermal efficiency of up to 90 % in accordance with EN 308.
The heat exchanger has high internal leak tightness and it is thus particularly
suitable for applications with a risk of odour transmission. The heat exch-
anger module has an automatic bypass damper mechanism with a fully
covered heat exchanger for summer night cooling. An electrical pre-heater
(standard equipment) heats the outside air at very low outside temperatures.
Thus, it prevents the freezing of the heat exchanger and guarantees its safe
functioning as well as optimal heat recovery for the entire heating period.
4
3 Separating the unit housing
The units can be separated to simplify transportation and for easier installa-
tion at the installation site for units above size XH 3500. Note: The units are
delivered in individual modules, i.e. in multiple delivery units.

42 Helios
4 Fans
5
The vibration dampened fans are located in the unit and they consist of
freewheeling, backward curved centrifugal impellers with direct drive via a
variable EC motor with low energy consumption and very low noise level.
The high performance plastic impeller is dynamically balanced in two levels.
Variably controllable via 0 – 10 V signal. Plug-in connections to all electrical
components for the simplification of maintenance work. Eurovent-certified
EC-motors in class IE4 with very low SFP values and high energy efficiency.

Pipe routing
Installation-friendly connection of outside, exhaust, extract and supply air to
a duct or pipe system. The floor-standing unit can be turned 180° for the
installation of the air duct system, so that the outside air/exhaust air and ex-
6 tract air/supply air connections can be on the left or right side. Adapters are
optionally available as unit accessories for adaption to a round duct system
up to unit size XH 5500.

5 Control system
The ventilation unit is delivered ready for operation with a modern, all-round
control system. The control system is attached on top of the unit in a
connection box for easy maintenance , factory-wired and function-tested.
Two controllers are available for selection (required accessory).

Overview of control functions:


Choice between ventilation modes Constant volume CAV, Constant pres-
sure CAP (accessory required) or Constant speed CRPM in %.
Multiple possible operating modes and levels.
7
Automatic control via humidity or room air quality sensors (can connect up
to three sensor types and maximum 18 sensors).
Automatic operation via integrated weekly programme.
Operating modes Free cooling (also night cooling/bypass function) and
active cooling (using cooling register) possible.
Commissioning assistant for simple, quick and faultless commissioning of
the unit and matching accessories.
Connection to the central building control system via BACnet or Modbus.
Digital output for collective fault signal.
Further information on the Helios AIR1 control system can be found on page 118.

6 Accessories
8 There are a number of accessory components available for the Helios AIR1
units. A detailed overview and the matching accessories for your Helios
Eurovent certification for the AIR1 XH AIR1 unit can be found on the following product pages.
series has been applied for.
The AIR1 XH series is designed in ac- 7 Air filters
cordance with the requirements of Di- Cassette filters with long service lives due to dynamic pressure monitoring.
rective VDI 6022 (hygiene requirements Simple filter replacement at the side or below through insert frame and
for building ventilation systems). quick clamp device. A multi-level filter concept inside the unit is optional.
Further information on the air filters can be found on page 75.

Helios AIR1 Series XH 43


AIR1 XH 1000 Performance curve

Dpfa
Pa

V· m3/h
Fig. shows accessories

Unit type

AIR1 XH 1000
Ref. no. 04335
Heat exchanger Cross-counterflow

Technical data Sound data

Mechanical data Sound power level LwA dB(A) at 250 Pa external pressure
Area of application Inside/outside 200 m³/h 700 m³/h 950 m³/h
Installation position Standing Supply air (LwA) 69 73 77
Maintenance access Side, both sides Extract air (LwA) 65 68 71
Min. air volume 160 m³/h Outside air (LwA) 62 64 67
Max. air volume 950 m³/h (1) Exhaust air (LwA) 69 63 76
Weight, unit operational 276 kg Sound pressure level LpA db(A) of sound radiated from housing
Delivery unit 1-part 200 m³/h 700 m³/h 950 m³/h
Unit segments 1 Housing rad. 1 m 43 46 48
Housing class (DIN 1886) T2 / TB2 / D1 Housing rad. 3 m 33 36 39
Filter Outside air ePM1 55% (F7) (2) Housing rad. 5 m 29 32 34
Filter Extract air ePM10 50% (M5) (2)
The sound power at the connectors is calculated for the simultaneous
Media temperature (air) -20 to +50 °C operation of both fans. The sound pressure level is determined for the
Ambient temperature (operation) 0 to +50 °C simultaneous operation of both fans at distances of 1, 3 and 5 m.

Protection class IP 31
Electrical data
Central building control system BACnet, Modbus TCP/IP
Voltage / Frequency 400 V 3N ~, 50 Hz
Max. output Fans 2 x 320 W
Max. output elec. pre-heater 2600 W
Nominal current
– Ventilation unit 5.2 / 5.2 / 4.6 A (3)
– Electrical auxiliary heater 3.8 / 3.8 / 3.8 A (4)
– max. total 8.9 / 8.9 / 8.3 A
Connection (wiring diagram no.) SS-1326

(1) = at 250 Pa external pressure loss ERP-compliant


(2) = other filter classes see optional accessories
(3) = includes electrical pre-heater
(4) = Optional accessories

44 Helios
343
SUP - Supply Air / Zuluft / Air soufflé
315

150

238
210
ODA ETA

max. 1185

437
855
Dimensional drawing

M8
EHA SUP

215
100

View A (from above) G 1/2


View B View C

145
ø32 ODA -ODA
Outdoor Air / Air
- Outdoor Außenluft / Air /extérieur
/ Außenluft Air extérieur

max. 80
613 613 317,5
EHA EHA
- Exhaust Air / Air
- Exhaust Fortluft /Air rejeté
/ Fortluft /Air rejeté
786 495 ETA -ETA
Extract Air / Air
- Extract Abluft / Air /repris
/ Abluft Air repris
SUP -SUP
Supply
- Supply A
Air / Air
Zuluft / Air /soufflé
/ Zuluft Air soufflé
343 343
315 315

150
150
716,5 568

238
210
238
210
ODAODA ETA ETA
C B
472

635

685

max. 1185
max. 1185

437
437
855
855
M8
M8
EHAEHA SUPSUP

215
215
81,5

100
100
40 390
2005 G 1/2 (1)
G 1/2

145
145
ø32 ø32

max. 80
max. 80
613 613 613 613 317,5
317,5
B
786 786 495 495

716,5
716,5 568 568

Dim. in mm (1) External thread ODA: Outside air EHA: Exhaust air ETA: Extract air SUP: Supply air

472

635

685
472

635

685
Accessories 81,5
81,5

40 40 390 390
Heating and cooling registers External installation
20052005

Auxiliary heater Cover for external installation


AIR1-ENH XH 1000 AIR1-AAD XH 1000
Ref. no. 03587 Page 60 Ref. no. 06305 Page 69
Electrical, internal Weather protection cover for the unit
AIR1-NH WW XH 1000 AIR1-AAD KR KW + DX XH 1000
Ref. no. 03664 Page 60
Hot water, internal Weather protection cover for cooling Ref. no. 06451 Page 70
register cold water or direct evaporator
Hydraulic unit for hot water heater register
Terminal box heater
WHSH HE 24 V (0 – 10 V) Ref. no. 08318 Page 61
AIR1-AAHK Ref. no. 07064 Page 71
Cooling register
Hoods
AIR1-KR KW XH 1000 L (1)
Ref. no. 03834 Page 75
Cold water, external AIR1-AAHA XH 1000
Ref. no. 06483 Page 71
Intake hood outside air
AIR1-KR KW XH 1000 R (1)
Ref. no. 04254 Page 75
Cold water, external AIR1-AAHF XH 1000
Ref. no. 06613 Page 72
Discharge hood exhaust air
AIR1-KR DX XH 1000 L (1)
Ref. no. 04403 Page 64
Direct evaporator DX, external
Controls
AIR1-KR DX XH 1000 R (1)
Ref. no. 04872 Page 64 Controllers
Direct evaporator DX, external
AIR1-BE ECO Ref. no. 06186 Page 73
Air routing
AIR1-BE TOUCH Ref. no. 06187 Page 73
Multi-leaf damper Controller connection cable
AIR1-JVK XH 1000 Ref. no. 06005 Page 66 AIR1-SL 4/10 10 m Ref. no. 07073 Page 73
Recirculation kit AIR1-SL 4/20 20 m Ref. no. 07121 Page 73
AIR1-ULK XH 1000 Ref. no. 06022 Page 66 Sensors
Flexible connector KWL-CO2 Carbon dioxide sensor Ref. no. 04272 Page 73
AIR1-VS 31/21 Ref. no. 04371 Page 67 KWL-FTF Humidity-temperature sensor Ref. no. 04273 Page 73
Adapter square-round KWL-VOC Mixed gas sensor Ref. no. 04274 Page 73
AIR1-ÜS XH 1000 Ref. no. 04366 Page 73 AIR1-CO2 K Carbon dioxide sensor duct Ref. no. 07124 Page 74

Condensate drainage Signal converter for sensors


AIR1-SK Ref. no. 06019 Page 74
Ball siphon
Extension kit for constant pressure control
AIR1-KS XH
Ref. no. 07169 Page 74 AIR1-CAP Ref. no. 06756 Page 74
for unit and cooling register
Air filters

Spare air filter and other filter classes


ELF-AIR1 XH 1000/ePM10 50%/48 (M5) Ref. no. 02176 Page 75
ELF-AIR1 XH 1000/ePM10 50%/96 (M5) Ref. no. 02203 Page 75
ELF-AIR1 XH 1000/ePM1 55%/96 (F7) Ref. no. 02227 Page 75
ELF-AIR1 XH 1000/ePM1 80%/96 (F9) Ref. no. 02288 Page 75
(1) = When looking at the cooling register from the air flow direction, The use of original spare air filters is mandatory to guarantee the specified
the service side is on the right for the R version and on the left for the L version technical data and air volumes.

Helios AIR1 Series XH 45


AIR1 XH 1500 Performance curve

Dpfa
Pa

V· m3/h
Fig. shows accessories

Unit type

AIR1 XH 1500
Ref. no. 04336
Heat exchanger Cross-counterflow

Technical data Sound data

Mechanical data Sound power level LwA dB(A) at 250 Pa external pressure
Area of application Inside/outside 250 m³/h 900 m³/h 1,490 m³/h
Installation position Standing Supply air (LwA) 67 72 76
Maintenance access Side, both sides Extract air (LwA) 60 65 68
Min. air volume 170 m³/h Outside air (LwA) 56 62 64
Max. air volume 1490 m³/h (1) Exhaust air (LwA) 67 71 76
Weight, unit operational 335 kg Sound pressure level LpA db(A) of sound radiated from housing
Delivery unit 1-part 250 m³/h 900 m³/h 1,490 m³/h
Unit segments 1 Housing rad. 1 m 40 48 48
Housing class (DIN 1886) T2 / TB2 / D1 Housing rad. 3 m 30 38 39
Filter Outside air ePM1 55% (F7) (2) Housing rad. 5 m 26 34 34
Filter Extract air ePM10 50% (M5) (2)
The sound power at the connectors is calculated for the simultaneous
Media temperature (air) -20 to +50 °C operation of both fans. The sound pressure level is determined for the
Ambient temperature (operation) 0 to +50 °C simultaneous operation of both fans at distances of 1, 3 and 5 m.

Protection class IP 31
Electrical data
Central building control system BACnet, Modbus TCP/IP
Voltage / Frequency 400 V 3N ~, 50 Hz
Max. output Fans 2 x 500 W
Max. output elec. pre-heater 3900 W
Nominal current
– Ventilation unit 7.9 / 7.9 / 6.5 A (3)
– Electrical auxiliary heater 5.6 / 5.6 / 5.6 A (4)
– max. total 13.5 / 13.5 / 12.1 A
Connection (wiring diagram no.) SS-1327

(1) = at 250 Pa external pressure loss ERP-compliant


(2) = other filter classes see optional accessories
(3) = includes electrical pre-heater
(4) = Optional accessories

46 Helios
338
310
ODA ETA

max. 1380

1050
518
M8
EHA SUP

Dimensional drawing

266

100

G 1/2
View A (from
ø32above) View B ODAAir- Outdoor View C

max. 80

145
322,5 ODA - Outdoor / Außenluft
Air //Außenluft
Air extérieur
/ Air extérieur
613 613 EHA - Exhaust
EHAAir / Fortluft
- Exhaust Air/Air rejeté /Air rejeté
/ Fortluft
780 567 ETA - Extract
ETAAir- Extract
/ Abluft Air
/ Air repris / Air repris
/ Abluft 378 378
SUP - Supply
SUP A
Air- /Supply
Zuluft Air
/ Air soufflé/ Air soufflé
/ Zuluft

150

150
350 350
759,5 568

338
310

338
310
C
472

695
645
ODA ODA ETA ETA

max. 1380

max. 1380
B

1050

1050
518

518
M8

M8
86,5

EHA EHA SUP SUP


40 376

266

266
2090

100

100
B G 1/2
(1)
G 1/2
ø32 ø32

max. 80

max. 80

145

145
613 613 613 613 322,5 322,5

780 780 567 567

759,5 759,5 568 568


Dim. in mm (1) External thread ODA: Outside air EHA: Exhaust air ETA: Extract air SUP: Supply air

472

472

695

695
645

645
Accessories
86,5

86,5

Heating and cooling registers External installation


40 376
40 376
2090 2090

Auxiliary heater Cover for external installation


AIR1-ENH XH 1500 AIR1-AAD XH 1500
Ref. no. 03588 Page 60 Ref. no. 06306 Page 69
Electrical, internal Weather protection cover for the unit
AIR1-NH WW XH 1500 AIR1-AAD KR KW + DX XH 1500
Ref. no. 03665 Page 60
Hot water, internal Weather protection cover for cooling Ref. no. 06455 Page 70
Hydraulic unit for hot water heater register register cold water or direct evaporator
Terminal box heater
WHSH HE 24 V (0 – 10 V) Ref. no. 08318 Page 61
AIR1-AAHK Ref. no. 07064 Page 71
Cooling register
Hoods
AIR1-KR KW XH 1500 L (1)
Ref. no. 03842 Page 75
Cold water, external AIR1-AAHA XH 1500/RH 1500
Ref. no. 06484 Page 71
Intake hood outside air
AIR1-KR KW XH 1500 R (1)
Ref. no. 04255 Page 75
Cold water, external AIR1-AAHF XH 1500/RH 1500
Ref. no. 06643 Page 72
Discharge hood exhaust air
AIR1-KR DX XH 1500 L (1)
Ref. no. 04406 Page 64
Direct evaporator DX, external Controls
AIR1-KR DX XH 1500 R (1)
Ref. no. 04873 Page 64 Controllers
Direct evaporator DX, external
AIR1-BE ECO Ref. no. 06186 Page 73
Air routing
AIR1-BE TOUCH Ref. no. 06187 Page 73
Multi-leaf damper Controller connection cable
AIR1-JVK XH 1500/RH 1500 Ref. no. 06006 Page 66 AIR1-SL 4/10 10 m Ref. no. 07073 Page 73
Recirculation kit AIR1-SL 4/20 20 m Ref. no. 07121 Page 73
AIR1-ULK XH 1500 Ref. no. 06023 Page 66 Sensors
Flexible connector KWL-CO2 Carbon dioxide sensor Ref. no. 04272 Page 73
AIR1-VS 35/31 Ref. no. 04372 Page 67 KWL-FTF Humidity-temperature sensor Ref. no. 04273 Page 73
Adapter square-round KWL-VOC Mixed gas sensor Ref. no. 04274 Page 73
AIR1-ÜS XH 1500/RH 1500 Ref. no. 04367 Page 73 AIR1-CO2 K Carbon dioxide sensor duct Ref. no. 07124 Page 74

Condensate drainage Signal converter for sensors


AIR1-SK Ref. no. 06019 Page 74
Ball siphon
Extension kit for constant pressure control
AIR1-KS XH
Ref. no. 07169 Page 73 AIR1-CAP Ref. no. 06756 Page 74
for unit and cooling register
Air filters

Spare air filter and other filter classes


ELF-AIR1 XH 1500/ePM10 50%/48 (M5) Ref. no. 02178 Page 75
ELF-AIR1 XH 1500/ePM10 50%/96 (M5) Ref. no. 02204 Page 75
ELF-AIR1 XH 1500/ePM1 55%/96 (F7) Ref. no. 02228 Page 75
ELF-AIR1 XH 1500/ePM1 80%/96 (F9) Ref. no. 02289 Page 75
(1) = When looking at the cooling register from the air flow direction, The use of original spare air filters is mandatory to guarantee the specified
the service side is on the right for the R version and on the left for the L version technical data and air volumes.

Helios AIR1 Series XH 47


AIR1 XH 2500 Performance curve

Dpfa
Pa

V· m3/h
Fig. shows accessories

Unit type

AIR1 XH 2500
Ref. no. 04337
Heat exchanger Cross-counterflow

Technical data Sound data

Mechanical data Sound power level LwA dB(A) at 250 Pa external pressure
Area of application Inside/outside 800 m³/h 1,700 m³/h 2,430 m³/h
Installation position Standing Supply air (LwA) 71 74 78
Maintenance access Side, both sides Extract air (LwA) 62 65 69
Min. air volume 240 m³/h Outside air (LwA) 58 61 66
Max. air volume 2430 m³/h (1) Exhaust air (LwA) 71 73 78
Weight, unit operational 508 kg Sound pressure level LpA db(A) of sound radiated from housing
Delivery unit 1-part 800 m³/h 1,700 m³/h 2,430 m³/h
Unit segments 1 Housing rad. 1 m 43 46 51
Housing class (DIN 1886) T2 / TB2 / D1 Housing rad. 3 m 34 37 41
Filter Outside air ePM1 55% (F7) (2) Housing rad. 5 m 29 32 37
Filter Extract air ePM10 50% (M5) (2)
The sound power at the connectors is calculated for the simultaneous
Media temperature (air) -20 to +40 °C operation of both fans. The sound pressure level is determined for the
Ambient temperature (operation) 0 to +50 °C simultaneous operation of both fans at distances of 1, 3 and 5 m.

Protection class IP 31
Electrical data
Central building control system BACnet, Modbus TCP/IP
Voltage / Frequency 400 V 3N ~, 50 Hz
Max. output Fans 2 x 780 W
Max. output elec. pre-heater 6600 W
Nominal current
– Ventilation unit 13 / 13 / 10.4 A (3)
– Electrical auxiliary heater 9.5 / 9.5 / 9.5 A (4)
– max. total 22.5 / 22.5 / 19.9 A
Connection (wiring diagram no.) SS-1328

(1) = at 250 Pa external pressure loss ERP-compliant


(2) = other filter classes see optional accessories
(3) = includes electrical pre-heater
(4) = Optional accessories

48 Helios
338
310
ODA ETA

max. 1460

1130
532
M8
EHA
Dimensional drawing SUP

300
100

View A (from above) G 1/2


View B View C
ODA - Outdoor
Air /Air / Außenluft
/ Air/extérieur
Air extérieur

145
ø32 ODA - Outdoor Außenluft

max. 80
613 613 432,5 EHA
EHA - Exhaust
- Exhaust Air /Air / Fortluft
Fortluft /Air /Air rejeté
rejeté
ETA
ETA - Extract
- Extract Air /Air / Abluft
Abluft / Air/repris
Air repris
498
875 599 SUP - SupplyAAir / Zuluft / Air
SUP - Supply Air / Zuluft / Air soufflésoufflé 498

150
150
470 470
846,5 568

338
310
338
310
ODA
ODA ETA ETA
472

865
915

1460
max.1460
B

1130
532

1130
532
max.

M8

M8
EHA SUP
EHA SUP

300

300
196,5

40 445

100
100
2345 (1)
G 1/2

145
ø32 G 1/2

max. 80
432,5

145
B 613 ø32 613

max. 80
613 613 432,5
875 599
875 599
846,5 568
846,5 568

Dim. in mm (1) External thread ODA: Outside air EHA: Exhaust air ETA: Extract air SUP: Supply air

472

865
915
472

865
915
Accessories 196,5

40 445
Heating and cooling registers External installation
196,5

2345
40 445
2345
Auxiliary heater Cover for external installation
AIR1-ENH XH 2500 AIR1-AAD XH 2500
Ref. no. 03590 Page 60 Ref. no. 06315 Page 69
Electrical, internal Weather protection cover for the unit
AIR1-NH WW XH 2500 AIR1-AAD KR KW + DX XH 2500
Ref. no. 03679 Page 60
Hot water, internal Weather protection cover for cooling Ref. no. 06461 Page 70
register cold water or direct evaporator
Hydraulic unit for hot water heater register
Terminal box heater
WHSH HE 24 V (0 – 10 V) Ref. no. 08318 Page 61
AIR1-AAHK Ref. no. 07064 Page 71
Cooling register
Hoods
AIR1-KR KW XH 2500 L (1)
Ref. no. 03844 Page 75
Cold water, external AIR1-AAHA XH 2500/RH 2000
Ref. no. 06539 Page 71
Intake hood outside air
AIR1-KR KW XH 2500 R (1)
Ref. no. 04264 Page 75
Cold water, external AIR1-AAHF XH 2500/RH 2000
Ref. no. 06646 Page 72
Discharge hood exhaust air
AIR1-KR DX XH 2500 L (1)
Ref. no. 04407 Page 64
Direct evaporator DX, external
Controls
AIR1-KR DX XH 2500 R (1)
Ref. no. 04877 Page 64 Controllers
Direct evaporator DX, external
AIR1-BE ECO Ref. no. 06186 Page 73
Air routing
AIR1-BE TOUCH Ref. no. 06187 Page 73
Multi-leaf damper Controller connection cable
AIR1-JVK XH 2500/RH 2000 Ref. no. 06007 Page 66 AIR1-SL 4/10 10 m Ref. no. 07073 Page 73
Recirculation kit AIR1-SL 4/20 20 m Ref. no. 07121 Page 73
AIR1-ULK XH 2500 Ref. no. 06024 Page 66 Sensors
Flexible connector KWL-CO2 Carbon dioxide sensor Ref. no. 04272 Page 73
AIR1-VS 47/31 Ref. no. 04373 Page 67 KWL-FTF Humidity-temperature sensor Ref. no. 04273 Page 73
Adapter square-round KWL-VOC Mixed gas sensor Ref. no. 04274 Page 73
AIR1-ÜS XH 2500/RH 2000 Ref. no. 04368 Page 73 AIR1-CO2 K Carbon dioxide sensor duct Ref. no. 07124 Page 74
Condensate drainage Signal converter for sensors
AIR1-SK Ref. no. 06019 Page 74
Ball siphon
Extension kit for constant pressure control
AIR1-KS XH
Ref. no. 07169 Page 73 AIR1-CAP Ref. no. 06756 Page 74
for unit and cooling register
Air filters

Spare air filter and other filter classes


ELF-AIR1 XH 2500/ePM10 50%/48 (M5) Ref. no. 02179 Page 75
ELF-AIR1 XH 2500/ePM10 50%/96 (M5) Ref. no. 02205 Page 75
ELF-AIR1 XH 2500/ePM1 55%/96 (F7) Ref. no. 02229 Page 75
ELF-AIR1 XH 2500/ePM1 80%/96 (F9) Ref. no. 02290 Page 75
(1) = When looking at the cooling register from the air flow direction, The use of original spare air filters is mandatory to guarantee the specified
the service side is on the right for the R version and on the left for the L version technical data and air volumes.

Helios AIR1 Series XH 49


AIR1 XH 3500 Performance curve

Dpfa
Pa

V· m3/h
Fig. shows accessories

Unit type

AIR1 XH 3500
Ref. no. 04338
Heat exchanger Cross-counterflow

Technical data Sound data

Mechanical data Sound power level LwA dB(A) at 250 Pa external pressure
Area of application Inside/outside 1,000 m³/h 2,200 m³/h 3,150 m³/h
Installation position Standing Supply air (LwA) 79 81 83
Maintenance access Side, both sides Extract air (LwA) 71 73 75
Min. air volume 375 m³/h Outside air (LwA) 67 69 71
Max. air volume 3150 m³/h (1) Exhaust air (LwA) 79 81 83
Weight, unit operational 687 kg Sound pressure level LpA db(A) of sound radiated from housing
Delivery unit 3-part 1,000 m³/h 2,200 m³/h 3,150 m³/h
Unit segments 3 Housing rad. 1 m 51 52 54
Housing class (DIN 1886) T2 / TB2 / D1 Housing rad. 3 m 42 43 45
Filter Outside air ePM1 55% (F7) (2) Housing rad. 5 m 37 38 40
Filter Extract air ePM10 50% (M5) (2)
The sound power at the connectors is calculated for the simultaneous
Media temperature (air) -20 to +50 °C operation of both fans. The sound pressure level is determined for the
Ambient temperature (operation) 0 to +50 °C simultaneous operation of both fans at distances of 1, 3 and 5 m.

Protection class IP 31
Electrical data
Central building control system BACnet, Modbus TCP/IP
Voltage / Frequency 400 V 3N ~, 50 Hz
Max. output Fans 2 x 1500 W
Max. output elec. pre-heater 9600 W
Nominal current
– Ventilation unit 18.5 / 18.5 / 19.2 A (3)
– Electrical auxiliary heater 13.9 / 13.9 / 13.9 A (4)
– max. total 32.4 / 32.4 / 33.1 A
Connection (wiring diagram no.) SS-1329

(1) = at 250 Pa external pressure loss ERP-compliant


(2) = other filter classes see optional accessories
(3) = includes electrical pre-heater
(4) = Optional accessories

50 Helios
580

438
410
ODA ETA

max. 1599
34

602
1269
G 1/2

M8
484
EHA SUP
Dimensional drawing

334
89
100

659 View Aø32(from above)


ø32 384 View B View C

145
max. 80
132 132 ODA - Outdoor
ODA - Outdoor Air / Außenluft
Air / Außenluft / Air extérieur
/ Air extérieur
180 180 157 EHA - Exhaust
EHA - Exhaust Air / Fortluft
Air / Fortluft /Air rejeté
/Air rejeté
483,5 ETA - Extract
ETA - Extract Air / Abluft
Air / Abluft / Air repris
/ Air repris 608 608
SUP - Supply
SUP - Supply A Air / Zuluft
Air / Zuluft / Air soufflé
/ Air soufflé

150
150
580 580
715 1475 780

438
410
438
410
ODA ODA ETA ETA

1017

max. 1599
472

max. 1599
967
34 34
B

602
602

1269
(1)

1269
G 1/2G 1/2

M8
M8
484
484
EHA EHA SUP SUP

334
334
247,5

89
89
1166,5 568

100
100
2970
659 659 ø32 ø32 ø32 ø32 384 384

145
max. 80

145
max. 80
132 132 132 132
B 180 180 180 180 157 157
483,5483,5

715 715 1475 1475 780 780

Dim. in mm (1) External thread ODA: Outside air EHA: Exhaust air ETA: Extract air SUP: Supply air

1017
1017
472
472

967
967
Accessories
247,5
247,5

1166,5
1166,5 568 568

Heating and cooling registers External installation


2970 2970

Auxiliary heater Cover for external installation


AIR1-ENH XH 3500 AIR1-AAD XH 3500
Ref. no. 03592 Page 60 Ref. no. 06316 Page 69
Electrical, internal Weather protection cover for the unit
AIR1-NH WW XH 3500 AIR1-AAD KR KW + DX XH 3500
Ref. no. 03683 Page 60
Hot water, internal Weather protection cover for cooling Ref. no. 06462 Page 70
register cold water or direct evaporator
Hydraulic unit for hot water heater register
Terminal box heater
WHSH HE 24 V (0 – 10 V) Ref. no. 08318 Page 61
AIR1-AAHK Ref. no. 07064 Page 71
Cooling register
Hoods
AIR1-KR KW XH 3500 L (1)
Ref. no. 03910 Page 75
Cold water, external AIR1-AAHA XH 3500-4500/RH 3000
Ref. no. 06487 Page 71
Intake hood outside air
AIR1-KR KW XH 3500 R (1)
Ref. no. 04268 Page 75
Cold water, external AIR1-AAHF XH 3500-4500/RH 3000
Ref. no. 06647 Page 72
Discharge hood exhaust air
AIR1-KR DX XH 3500 L (1)
Ref. no. 04408 Page 64
Direct evaporator DX, external
Controls
AIR1-KR DX XH 3500 R (1)
Ref. no. 04878 Page 64 Controllers
Direct evaporator DX, external
AIR1-BE ECO Ref. no. 06186 Page 73
Air routing
AIR1-BE TOUCH Ref. no. 06187 Page 73
Multi-leaf damper Controller connection cable
AIR1-JVK XH 3500-4500/RH 3000 Ref. no. 06009 Page 66 AIR1-SL 4/10 10 m Ref. no. 07073 Page 73
Recirculation kit AIR1-SL 4/20 20 m Ref. no. 07121 Page 73
AIR1-ULK XH 3500 Ref. no. 06025 Page 66 Sensors
Flexible connector KWL-CO2 Carbon dioxide sensor Ref. no. 04272 Page 73
AIR1-VS 58/41 Ref. no. 04374 Page 67 KWL-FTF Humidity-temperature sensor Ref. no. 04273 Page 73
Adapter square-round KWL-VOC Mixed gas sensor Ref. no. 04274 Page 73
AIR1-ÜS XH 3500-4500/RH 3000 Ref. no. 04369 Page 73 AIR1-CO2 K Carbon dioxide sensor duct Ref. no. 07124 Page 74
Condensate drainage Signal converter for sensors
AIR1-SK Ref. no. 06019 Page 74
Ball siphon
Extension kit for constant pressure control
AIR1-KS XH
Ref. no. 07169 Page 74 AIR1-CAP Ref. no. 06756 Page 74
for unit and cooling register
Air filters

Spare air filter and other filter classes


ELF-AIR1 XH 3500/ePM10 50%/48 (M5) Ref. no. 02180 Page 75
ELF-AIR1 XH 3500/ePM10 50%/96 (M5) Ref. no. 02206 Page 75
ELF-AIR1 XH 3500/ePM1 55%/96 (F7) Ref. no. 02230 Page 75
ELF-AIR1 XH 3500/ePM1 80%/96 (F9) Ref. no. 02291 Page 75
(1) = When looking at the cooling register from the air flow direction, The use of original spare air filters is mandatory to guarantee the specified
the service side is on the right for the R version and on the left for the L version technical data and air volumes.

Helios AIR1 Series XH 51


AIR1 XH 4500 Performance curve

Dpfa
Pa

V· m3/h
Fig. shows accessories

Unit type

AIR1 XH 4500
Ref. no. 04339
Heat exchanger Cross-counterflow

Technical data Sound data

Mechanical data Sound power level LwA dB(A) at 250 Pa external pressure
Area of application Inside/outside 1,300 m³/h 2,900 m³/h 4,150 m³/h
Installation position Standing Supply air (LwA) 71 75 81
Maintenance access Side, both sides Extract air (LwA) 62 65 72
Min. air volume 380 m³/h Outside air (LwA) 58 61 67
Max. air volume 4150 m³/h (1) Exhaust air (LwA) 70 75 81
Weight, unit operational 750 kg Sound pressure level LpA db(A) of sound radiated from housing
Delivery unit 3-part 1,300 m³/h 2,900 m³/h 4,150 m³/h
Unit segments 3 Housing rad. 1 m 43 47 53
Housing class (DIN 1886) T2 / TB2 / D1 Housing rad. 3 m 34 38 43
Filter Outside air ePM1 55% (F7) (2) Housing rad. 5 m 29 33 39
Filter Extract air ePM10 50% (M5) (2)
The sound power at the connectors is calculated for the simultaneous
Media temperature (air) -20 to +50 °C operation of both fans. The sound pressure level is determined for the
Ambient temperature (operation) 0 to +50 °C simultaneous operation of both fans at distances of 1, 3 and 5 m.

Protection class IP 31
Electrical data
Central building control system BACnet, Modbus TCP/IP
Voltage / Frequency 400 V 3N ~, 50 Hz
Max. output Fans 2 x 2500 W
Max. output elec. pre-heater 12900 W
Nominal current
– Ventilation unit 26.3 / 26.3 / 27 A (3)
– Electrical auxiliary heater 18.6 / 18.6 / 18.6 A (4)
– max. total 44.9 / 44.9 / 45.6 A
Connection (wiring diagram no.) SS-1330

(1) = at 250 Pa external pressure loss ERP-compliant


(2) = other filter classes see optional accessories
(3) = includes electrical pre-heater
(4) = Optional accessories

52 Helios
15
452 580 131

438
410
ODA ETA

max. 2020
34

1690
814
G 1/2

~ 1500
Dimensional drawing

M8
684
EHA
SUP

437
89
100

View A (from above) View B


ODA - Outdoor
EHA - Exhaust
Air / Außenluft
ODA - Outdoor
EHA - Exhaust
/ Air extérieur
Air / Außenluft
Air / Fortluft /Air rejeté
Air / Fortluft
/ Air extérieur
/Air rejeté
View C

145
ø32 ø32 132 132

max. 80
733 439 ETA - Extract Air / Abluft
ETA - Extract Air //Abluft
Air repris
/ Air repris

180 180 157 510 SUP - Supply


SUP - Air / Zuluft
Supply A
Air //Zuluft
Air soufflé
/ Air soufflé
608 608

150

150
452 452 580 580 131 131

790 1895 830

438
410
438
410
ODA ODA ETA ETA
C

1020
1070

max. 2020

max. 2020
34
472

34

1690

1690
B

814

814
(1)
G 1/2 G 1/2

~ 1500

~ 1500
274

M8

M8
684

684
EHA EHA
SUP SUP

437

437
89
1451,5 568

89
100

100
3515

145
ø32 ø32 132 132

145
ø32 ø32 439 132 132

max. 80

max. 80
733 733 439
B 510 510
180 180 180 180 157 157

790 790 1895 1895 830 830

Dim. in mm (1) External thread ODA: Outside air EHA: Exhaust air ETA: Extract air SUP: Supply air

1020
1070
1020
1070
472

472
274

274
Accessories
1451,51451,5 568 568

3515 3515
Heating and cooling registers External installation

Auxiliary heater Cover for external installation


AIR1-ENH XH 4500 AIR1-AAD XH 4500
Ref. no. 03593 Page 60 Ref. no. 06347 Page 69
Electrical, internal Weather protection cover for the unit
AIR1-NH WW XH 4500 AIR1-AAD KR KW + DX XH 4500
Ref. no. 03684 Page 60
Hot water, internal Weather protection cover for cooling Ref. no. 06463 Page 70
Hydraulic unit for hot water heater register register cold water or direct evaporator
Terminal box heater
WHSH HE 24 V (0 – 10 V) Ref. no. 08318 Page 61
AIR1-AAHK Ref. no. 07064 Page 71
Cooling register
Hoods
AIR1-KR KW XH 4500 L (1)
Ref. no. 03919 Page 75
Cold water, external AIR1-AAHA XH 3500-4500/RH 3000
Ref. no. 06487 Page 71
Intake hood outside air
AIR1-KR KW XH 4500 R (1)
Ref. no. 04278 Page 75
Cold water, external AIR1-AAHF XH 3500-4500/RH 3000
Ref. no. 06647 Page 72
Discharge hood exhaust air
AIR1-KR DX XH 4500 L (1)
Ref. no. 04409 Page 64
Direct evaporator DX, external
Controls
AIR1-KR DX XH 4500 R (1)
Ref. no. 04879 Page 64 Controllers
Direct evaporator DX, external
AIR1-BE ECO Ref. no. 06186 Page 73
Air routing
AIR1-BE TOUCH Ref. no. 06187 Page 73
Multi-leaf damper Controller connection cable
AIR1-JVK XH 3500-4500/RH 3000 Ref. no. 06009 Page 66 AIR1-SL 4/10 10 m Ref. no. 07073 Page 73
Recirculation kit AIR1-SL 4/20 20 m Ref. no. 07121 Page 73
AIR1-ULK XH 4500 Ref. no. 06026 Page 66 Sensors
Flexible connector KWL-CO2 Carbon dioxide sensor Ref. no. 04272 Page 73
AIR1-VS 58/41 Ref. no. 04374 Page 67 KWL-FTF Humidity-temperature sensor Ref. no. 04273 Page 73
Adapter square-round KWL-VOC Mixed gas sensor Ref. no. 04274 Page 73
AIR1-ÜS XH 3500-4500/RH 3000 Ref. no. 04369 Page 73 AIR1-CO2 K Carbon dioxide sensor duct Ref. no. 07124 Page 74

Condensate drainage Signal converter for sensors


AIR1-SK Ref. no. 06019 Page 74
Ball siphon
Extension kit for constant pressure control
AIR1-KS XH
Ref. no. 07169 Page 73 AIR1-CAP Ref. no. 06756 Page 74
for unit and cooling register
Air filters

Spare air filter and other filter classes


ELF-AIR1 XH 4500/ePM10 50%/48 (M5) Ref. no. 02182 Page 75
ELF-AIR1 XH 4500/ePM10 50%/96 (M5) Ref. no. 02207 Page 75
ELF-AIR1 XH 4500/ePM1 55%/96 (F7) Ref. no. 02231 Page 75
ELF-AIR1 XH 4500/ePM1 80%/96 (F9) Ref. no. 02292 Page 75
(1) = When looking at the cooling register from the air flow direction, The use of original spare air filters is mandatory to guarantee the specified
the service side is on the right for the R version and on the left for the L version technical data and air volumes.

Helios AIR1 Series XH 53


AIR1 XH 5500 Performance curve

Dpfa
Pa

V· m3/h
Fig. shows accessories

Unit type

AIR1 XH 5500
Ref. no. 04340
Heat exchanger Cross-counterflow

Technical data Sound data

Mechanical data Sound power level LwA dB(A) at 400 Pa external pressure
Area of application Inside/outside 1,800 m³/h 3,800 m³/h 5,400 m³/h
Installation position Standing Supply air (LwA) 76 78 83
Maintenance access Side, both sides Extract air (LwA) 67 68 74
Min. air volume 400 m³/h Outside air (LwA) 63 64 70
Max. air volume 5400 m³/h (1) Exhaust air (LwA) 76 78 83
Weight, unit operational 873 kg Sound pressure level LpA db(A) of sound radiated from housing
Delivery unit 3-part 1,800 m³/h 3,800 m³/h 5,400 m³/h
Unit segments 3 Housing rad. 1 m 49 50 55
Housing class (DIN 1886) T2 / TB2 / D1 Housing rad. 3 m 39 41 46
Filter Outside air ePM1 55% (F7) (2) Housing rad. 5 m 35 36 41
Filter Extract air ePM10 50% (M5) (2)
The sound power at the connectors is calculated for the simultaneous
Media temperature (air) -20 to +40 °C operation of both fans. The sound pressure level is determined for the
Ambient temperature (operation) 0 to +50 °C simultaneous operation of both fans at distances of 1, 3 and 5 m.

Protection class IP 31
Electrical data
Central building control system BACnet, Modbus TCP/IP
Voltage / Frequency 400 V 3N ~, 50 Hz
Max. output Fans 2 x 2400 W
Max. output elec. pre-heater 17700 W
Nominal current
– Ventilation unit 32.9 / 32.9 / 33.7 A (3)
– Electrical auxiliary heater 25.5 / 25.5 / 25.5 A (4)
– max. total 58.4 / 58.4 / 59.2 A
Connection (wiring diagram no.) SS-1331

(1) = at 400 Pa external pressure loss ERP-compliant


(2) = other filter classes see optional accessories
(3) = includes electrical pre-heater
(4) = Optional accessories

54 Helios
452

15
855 131

438
410
ODA ETA

max. 2020
28

1690
779
~ 1500
G 3/4

M8
Dimensional drawing

680
EHA

498
SUP

454
91
100

View A (from above) View BODA ODA


- Outdoor Air / Air
- Outdoor Außenluft / Air /extérieur
/ Außenluft Air extérieur
View C
733 ø32 ø32 515

145
132 132 EHA EHA
- Exhaust Air / Air
- Exhaust Fortluft /Air rejeté
/ Fortluft /Air rejeté

max. 80
ETA -ETA
Extract Air / Air
- Extract Abluft / Air /repris
/ Abluft Air repris
180 180 128 615 SUP SUP
- Supply Air / Air
- Supply
A
Zuluft / Air /soufflé
/ Zuluft Air soufflé 883 883

150
150
452 452 855 855 131 131
790 1895 870

438
410
438
410
ODAODA ETAETA
472

1230

1280

max. 2020
max. 2020
28 28 B

1690
1690
779
779
(1)

~ 1500
~ 1500
G 3/4
G 3/4
379

498M8
M8
680
680

498
EHAEHA SUPSUP

454
454
91
91
1451,5 568

100
100
3555
733 733 ø32 ø32 ø32 ø32 515 515

145
145
132 132 132 132
B

max. 80
max. 80
180 180 180 180 128 128 615 615

790 790 18951895 870 870

Dim. in mm (1) External thread ODA: Outside air EHA: Exhaust air ETA: Extract air SUP: Supply air

472

1230

1280
472

1230

1280
Accessories 379
379

1451,5
1451,5 568 568
Heating and cooling registers External installation
35553555

Auxiliary heater Cover for external installation


AIR1-ENH XH 5500 AIR1-AAD XH 5500
Ref. no. 03595 Page 60 Ref. no. 06349 Page 69
Electrical, internal Weather protection cover for the unit
AIR1-NH WW XH 5500 AIR1-AAD KR KW + DX XH 5500
Ref. no. 03687 Page 60
Hot water, internal Weather protection cover for cooling Ref. no. 06464 Page 70
register cold water or direct evaporator
Hydraulic unit for hot water heater register
Terminal box heater
WHSH HE 24 V (0 – 10 V) Ref. no. 86318 Page 61
AIR1-AAHK Ref. no. 07064 Page 71
Cooling register
Hoods
AIR1-KR KW XH 5500 L (1)
Ref. no. 03932 Page 75
Cold water, external AIR1-AAHA XH 5500/RH 5000-6000
Ref. no. 06496 Page 71
Intake hood outside air
AIR1-KR KW XH 5500 R (1)
Ref. no. 04279 Page 75
Cold water, external AIR1-AAHF XH 5500/RH 5000-6000
Ref. no. 06648 Page 72
Discharge hood exhaust air
AIR1-KR DX XH 5500 L (1)
Ref. no. 04410 Page 64
Direct evaporator DX, external
Controls
AIR1-KR DX XH 5500 R (1)
Ref. no. 04883 Page 64 Controllers
Direct evaporator DX, external
AIR1-BE ECO Ref. no. 06186 Page 73
Air routing
AIR1-BE TOUCH Ref. no. 06187 Page 73
Multi-leaf damper Controller connection cable
AIR1-JVK XH 5500/RH 5000-6000 Ref. no. 06010 Page 66 AIR1-SL 4/10 10 m Ref. no. 07073 Page 73
Recirculation kit AIR1-SL 4/20 20 m Ref. no. 07121 Page 73
AIR1-ULK XH 5500 Ref. no. 06027 Page 66 Sensors
Flexible connector KWL-CO2 Carbon dioxide sensor Ref. no. 04272 Page 73
AIR1-VS 85/41 Ref. no. 04375 Page 67 KWL-FTF Humidity-temperature sensor Ref. no. 04273 Page 73
Adapter square-round KWL-VOC Mixed gas sensor Ref. no. 04274 Page 73
AIR1-ÜS XH 5500/RH 5000-6000 Ref. no. 04370 Page 73 AIR1-CO2 K Carbon dioxide sensor duct Ref. no. 07124 Page 74

Condensate drainage Signal converter for sensors


AIR1-SK Ref. no. 06019 Page 74
Ball siphon
Extension kit for constant pressure control
AIR1-KS XH
Ref. no. 07169 Page 73 AIR1-CAP Ref. no. 06756 Page 74
for unit and cooling register
Air filters

Spare air filter and other filter classes


ELF-AIR1 XH 5500/ePM10 50%/48 (M5) Ref. no. 02186 Page 75
ELF-AIR1 XH 5500/ePM10 50%/96 (M5) Ref. no. 02208 Page 75
ELF-AIR1 XH 5500/ePM1 55%/96 (F7) Ref. no. 02233 Page 75
ELF-AIR1 XH 5500/ePM1 80%/96 (F9) Ref. no. 02293 Page 75
(1) = When looking at the cooling register from the air flow direction, The use of original spare air filters is mandatory to guarantee the specified
the service side is on the right for the R version and on the left for the L version technical data and air volumes.

Helios AIR1 Series XH 55


AIR1 XH 7000 Performance curve

Dpfa
Pa

V· m3/h
Fig. shows accessories

Unit type

AIR1 XH 7000
Ref. no. 04341
Heat exchanger Cross-counterflow

Technical data Sound data

Mechanical data Sound power level LwA dB(A) at 400 Pa external pressure
Area of application Inside/outside 2,200 m³/h 4,400 m³/h 6,300 m³/h
Installation position Standing Supply air (LwA) 77 80 86
Maintenance access Side, both sides Extract air (LwA) 68 69 75
Min. air volume 500 m³/h Outside air (LwA) 64 65 71
Max. air volume 6300 m³/h (1) Exhaust air (LwA) 77 80 86
Weight, unit operational 1080 kg Sound pressure level LpA db(A) of sound radiated from housing
Delivery unit 3-part 2,200 m³/h 4,400 m³/h 6,300 m³/h
Unit segments 3 Housing rad. 1 m 50 52 58
Housing class (DIN 1886) T2 / TB2 / D1 Housing rad. 3 m 40 43 48
Filter Outside air ePM1 55% (F7) (2) Housing rad. 5 m 36 38 44
Filter Extract air ePM10 50% (M5) (2)
The sound power at the connectors is calculated for the simultaneous
Media temperature (air) -20 to +50 °C operation of both fans. The sound pressure level is determined for the
Ambient temperature (operation) 0 to +50 °C simultaneous operation of both fans at distances of 1, 3 and 5 m.

Protection class IP 31
Electrical data
Central building control system BACnet, Modbus TCP/IP
Voltage / Frequency 400 V 3N ~, 50 Hz
Max. output Fans 2 x 3600 W
Max. output elec. pre-heater 21000 W
Nominal current
– Ventilation unit 41.3 / 41.3 / 42.3 A (3)
– Electrical auxiliary heater 30.3 / 30.3 / 30.3 A (4)
– max. total 71.6 / 71.6 / 72.6 A
Connection (wiring diagram no.) SS-1332

(1) = at 400 Pa external pressure loss ERP-compliant


(2) = other filter classes see optional accessories
(3) = includes electrical pre-heater
(4) = Optional accessories

56 Helios
SUP - Supply Air / Zuluft / Air soufflé
1083

150
452 1055 131

438
410
ODA ETA
28

max. 2020

1690
834
361,1
G 3/4
Dimensional drawing

~ 1500

M8
680

498
EHA SUP

431
91
100

View A (from above) View B View C


ODA - Outdoor Air / Außenluft
ODA - Outdoor / Air extérieur
Air / Außenluft / Air extérieur
ø32 ø32

145
max. 80
733 529 132 132 EHA - Exhaust Air / Fortluft
EHA - Exhaust /Air rejeté
Air / Fortluft /Air rejeté
ETA - Extract
ETA - Air / Abluft
Extract Air // Abluft
Air repris
/ Air repris
180 180 161 765 SUP - Supply
SUP - Air / Zuluft
Supply A
Air // Zuluft
Air soufflé
/ Air soufflé
1083 1083

150

150
452 452 1055 1055 131 131
790 1895 920

438
410
438
410
ODA ODA ETA ETA

1530
1580
28 28
472

max. 2020

max. 2020
B

1690

1690
834
361,1 361,1

834
(1)
G 3/4 G 3/4

~ 1500

~ 1500

M8

M8
529

680

680

498

498
EHA EHA SUP SUP

431

431
91

91
100

100
1451,5 568
ø32 ø32 ø32 ø32

145

145
max. 80

max. 80
3605 733 733 529 529 132 132 132 132
180 180 180 180 161 161 765 765
B
790 790 1895 1895 920 920

Dim. in mm (1) External thread ODA: Outside air EHA: Exhaust air ETA: Extract air SUP: Supply air

1530
1580
1530
1580
472

472
Accessories 529

529

1451,51451,5 568 568


Heating and cooling registers External installation
3605 3605

Auxiliary heater Cover for external installation


AIR1-ENH XH 7000 AIR1-AAD XH 7000
Ref. no. 03603 Page 60 Ref. no. 06350 Page 69
Electrical, internal Weather protection cover for the unit
AIR1-NH WW XH 7000 AIR1-AAD KR KW + DX XH 7000
Ref. no. 03689 Page 60
Hot water, internal Weather protection cover for cooling Ref. no. 06465 Page 70
register cold water or direct evaporator
Hydraulic unit for hot water heater register
Terminal box heater
WHSH HE 24 V (0 – 10 V) M Ref. no. 06310 Page 61
AIR1-AAHK Ref. no. 07064 Page 71
Cooling register
Hoods
AIR1-KR KW XH 7000 L (1)
Ref. no. 03945 Page 75
Cold water, external AIR1-AAHA XH 7000/RH 8000
Ref. no. 06497 Page 71
Intake hood outside air
AIR1-KR KW XH 7000 R (1)
Ref. no. 04281 Page 75
Cold water, external AIR1-AAHF XH 7000/RH 8000
Ref. no. 06841 Page 72
Discharge hood exhaust air
AIR1-KR DX XH 7000 L (1)
Ref. no. 04414 Page 64
Direct evaporator DX, external
Controls
AIR1-KR DX XH 7000 R (1)
Ref. no. 03123 Page 64 Controllers
Direct evaporator DX, external
AIR1-BE ECO Ref. no. 06186 Page 73
Air routing
AIR1-BE TOUCH Ref. no. 06187 Page 73
Multi-leaf damper Controller connection cable
AIR1-JVK XH 7000/RH 8000 Ref. no. 06012 Page 66 AIR1-SL 4/10 10 m Ref. no. 07073 Page 73
Recirculation kit AIR1-SL 4/20 20 m Ref. no. 07121 Page 73
AIR1-ULK XH 7000 Ref. no. 06028 Page 66 Sensors
Flexible connector KWL-CO2 Carbon dioxide sensor Ref. no. 04272 Page 73
AIR1-VS 105/41 Ref. no. 04376 Page 67 KWL-FTF Humidity-temperature sensor Ref. no. 04273 Page 73
KWL-VOC Mixed gas sensor Ref. no. 04274 Page 73
AIR1-CO2 K Carbon dioxide sensor duct Ref. no. 07124 Page 74
Condensate drainage Signal converter for sensors
AIR1-SK Ref. no. 06019 Page 74
Ball siphon
Extension kit for constant pressure control
AIR1-KS XH
Ref. no. 07169 Page 74 AIR1-CAP Ref. no. 06756 Page 74
for unit and cooling register
Air filters

Spare air filter and other filter classes


ELF-AIR1 XH 7000/ePM10 50%/48 (M5) Ref. no. 02187 Page 75
ELF-AIR1 XH 7000/ePM10 50%/96 (M5) Ref. no. 02209 Page 75
ELF-AIR1 XH 7000/ePM1 55%/96 (F7) Ref. no. 02234 Page 75
ELF-AIR1 XH 7000/ePM1 80%/96 (F9) Ref. no. 02435 Page 75
(1) = When looking at the cooling register from the air flow direction, The use of original spare air filters is mandatory to guarantee the specified
the service side is on the right for the R version and on the left for the L version technical data and air volumes.

Helios AIR1 Series XH 57


AIR1 XH 8500 Performance curve

Dpfa
Pa

V· m3/h
Fig. shows accessories

Unit type

AIR1 XH 8500
Ref. no. 04342
Heat exchanger Cross-counterflow

Technical data Sound data

Mechanical data Sound power level LwA dB(A) at 400 Pa external pressure
Area of application Inside/outside 2,800 m³/h 5,800 m³/h 8,300 m³/h
Installation position Standing Supply air (LwA) 77 79 86
Maintenance access Side, both sides Extract air (LwA) 68 70 77
Min. air volume 630 m³/h Outside air (LwA) 64 66 73
Max. air volume 8300 m³/h (1) Exhaust air (LwA) 77 79 85
Weight, unit operational 1260 kg Sound pressure level LpA db(A) of sound radiated from housing
Delivery unit 3-part 2,800 m³/h 5,800 m³/h 8,300 m³/h
Unit segments 3 Housing rad. 1 m 50 52 59
Housing class (DIN 1886) T2 / TB2 / D1 Housing rad. 3 m 40 42 50
Filter Outside air ePM1 55% (F7) (2) Housing rad. 5 m 36 38 45
Filter Extract air ePM10 50% (M5) (2)
The sound power at the connectors is calculated for the simultaneous
Media temperature (air) -20 to +50 °C operation of both fans. The sound pressure level is determined for the
Ambient temperature (operation) 0 to +50 °C simultaneous operation of both fans at distances of 1, 3 and 5 m.

Protection class IP 31
Electrical data
Central building control system BACnet, Modbus TCP/IP
Voltage / Frequency 400 V 3N ~, 50 Hz
Max. output Fans 2 x 3600 W
Max. output elec. pre-heater 22000 W
Nominal current
– Ventilation unit 42.4 / 42.4 / 43.4 A (3)
– Electrical auxiliary heater 31.8 / 31.8 / 31.8 A (4)
– max. total 74.2 / 74.2 / 75.2 A
Connection (wiring diagram no.) SS-1333

(1) = at 400 Pa external pressure loss ERP-compliant


(2) = other filter classes see optional accessories
(3) = includes electrical pre-heater
(4) = Optional accessories

58 Helios
EHA - Exhaust Air / Fortluft /Air rejeté
ETA - Extract Air / Abluft / Air repris
SUP - Supply Air / Zuluft / Air soufflé
1228
452

150
1200 131

438
410
ODA ETA

max. 2020
28

834
Dimensional drawing 409,4

1690
G 3/4

~ 1500

M8
680

498
EHA SUP

431
91
View A (from above) View B View C
100

ODAAir
ODA - Outdoor - Outdoor Air / Außenluft
/ Außenluft / Air extérieur
/ Air extérieur
EHA Air
EHA - Exhaust - Exhaust Air/Air
/ Fortluft / Fortluft
rejeté /Air rejeté
733 ø32 ø32 579 132 132 ETAAir
- Extract
ETA - Extract / AbluftAir / Abluft
/ Air repris/ Air repris

145
max. 80
180 180 161 940
SUP
SUP - Supply - Supply
Air A
/ ZuluftAir / Zuluft
/ Air / Air soufflé
soufflé
1228 1228
452

150
452

150
1200 1200 131 131
790 1895 970

438
410
438
410
ODA ODA ETA ETA

max. 2020
max. 2020
28 28
C

834
834
409,4 B

1690
409,4

1690
1880

1930
(1) G 3/4
472

G 3/4

~ 1500
~ 1500

M8
M8
680

498
680

91498
EHA EHA SUP SUP

431
431
91
704

100
100
733 ø32 ø32 ø32 ø32 579 132 132
733 579 132 132

145
145
max. 80
max. 80
1451,5 568 180 180 180 161
180 161 940 940
3655
790 790 1895 1895 970 970
B

Dim. in mm (1) External thread ODA: Outside air EHA: Exhaust air ETA: Extract air SUP: Supply air

1880

1930
1880

1930
472
472
Accessories
704
704

1451,5 1451,5 568 568

Heating and cooling registers External


3655 installation
3655

Auxiliary heater Cover for external installation


AIR1-ENH XH 8500 AIR1-AAD XH 8500
Ref. no. 03604 Page 60 Ref. no. 06378 Page 69
Electrical, internal Weather protection cover for the unit
AIR1-NH WW XH 8500 AIR1-AAD KR KW + DX XH 8500
Ref. no. 03793 Page 60
Hot water, internal Weather protection cover for cooling Ref. no. 06466 Page 70
register cold water or direct evaporator
Hydraulic unit for hot water heater register
Terminal box heater
WHSH HE 24 V (0 – 10 V) M Ref. no. 06310 Page 61
AIR1-AAHK Ref. no. 07064 Page 71
Cooling register
Hoods
AIR1-KR KW XH 8500 L (1)
Ref. no. 03946 Page 75
Cold water, external AIR1-AAHA XH 8500/RH 9500
Ref. no. 06499 Page 71
Intake hood outside air
AIR1-KR KW XH 8500 R (1)
Ref. no. 04282 Page 75
Cold water, external AIR1-AAHF XH 8500/RH 9500
Ref. no. 06864 Page 72
Discharge hood exhaust air
AIR1-KR DX XH 8500 L (1)
Ref. no. 04415 Page 64
Direct evaporator DX, external
Controls
AIR1-KR DX XH 8500 R (1)
Ref. no. 03052 Page 64 Controllers
Direct evaporator DX, external
AIR1-BE ECO Ref. no. 06186 Page 73
Air routing
AIR1-BE TOUCH Ref. no. 06187 Page 73
Multi-leaf damper Controller connection cable
AIR1-JVK XH 8500/RH 9500 Ref. no. 06013 Page 66 AIR1-SL 4/10 10 m Ref. no. 07073 Page 73
Recirculation kit AIR1-SL 4/20 20 m Ref. no. 07121 Page 73
AIR1-ULK XH 8500 Ref. no. 06029 Page 66 Sensors
Flexible connector KWL-CO2 Carbon dioxide sensor Ref. no. 04272 Page 73
AIR1-VS 120/41 Ref. no. 04377 Page 67 KWL-FTF Humidity-temperature sensor Ref. no. 04273 Page 73
KWL-VOC Mixed gas sensor Ref. no. 04274 Page 73
AIR1-CO2 K Carbon dioxide sensor duct Ref. no. 07124 Page 74
Condensate drainage Signal converter for sensors
AIR1-SK Ref. no. 06019 Page 74
Ball siphon
Extension kit for constant pressure control
AIR1-KS XH
Ref. no. 07169 Page 74 AIR1-CAP Ref. no. 06756 Page 74
for unit and cooling register
Air filters

Spare air filter and other filter classes


ELF-AIR1 XH 8500/ePM10 50%/48 (M5) Ref. no. 02189 Page 75
ELF-AIR1 XH 8500/ePM10 50%/96 (M5) Ref. no. 02210 Page 75
ELF-AIR1 XH 8500/ePM1 55%/96 (F7) Ref. no. 02235 Page 75
ELF-AIR1 XH 8500/ePM1 80%/96 (F9) Ref. no. 02334 Page 75
(1) = When looking at the cooling register from the air flow direction, The use of original spare air filters is mandatory to guarantee the specified
the service side is on the right for the R version and on the left for the L version technical data and air volumes.

Helios AIR1 Series XH 59


Accessories for the XH series.

Electrical auxiliary heater


Electrical auxiliary heater internal
For installation in the ventilation unit. Provides demand-oriented temperature
control of supply air. Mains power supply and connection to the ventilation unit
control system through pre-wired plug contacts. Variable controls.

Detailed calculations / technical information: www.AIR1Select.com.

Technical data
Type Ref. no. Output Current consumption Weight
AIR1-ENH XH 1000 03587 2.6 kW 3.8 A 5.5 kg
AIR1-ENH XH 1500 03588 3.9 kW 5.6 A 7.0 kg
AIR1-ENH XH 2500 03590 6.6 kW 9.5 A 10.0 kg
AIR1-ENH XH 3500 03592 9.6 kW 13.9 A 12.5 kg
AIR1-ENH XH 4500 03593 12.9 kW 18.6 A 15.0 kg
AIR1-ENH XH 5500 03595 17.7 kW 25.5 A 17.0 kg
AIR1-ENH XH 7000 03603 21.0 kW 30.3 A 19.0 kg
AIR1-ENH XH 8500 03604 22.0 kW 31.8 A 20.0 kg

Hot water auxiliary heater internal Hot water auxiliary heater


For installation in the ventilation unit. Provides demand-oriented temperature
control of supply air. The heating elements consist of copper piping with formed
aluminium fins, and copper pipe water connections for flow and return. Further
accessories are required for supply air temperature control (see below; Hydraulic
unit WHSH HE 24V on page 61).

Detailed calculations / technical information: www.AIR1Select.com.

Technical data

Connection Weight
Type Ref. no. Water content Hydraulic unit Ref. no.
flow / return (1) (without liquid)

AIR1-NH WW XH 1000 03664 4.6 l G 1/2 3.6 kg WHSH HE 24 V (0 – 10 V) 08318


AIR1-NH WW XH 1500 03665 7.9 l G 1/2 4.4 kg WHSH HE 24 V (0 – 10 V) 08318
AIR1-NH WW XH 2500 03679 12.2 l G 1/2 6.3 kg WHSH HE 24 V (0 – 10 V) 08318
AIR1-NH WW XH 3500 03683 18.0 l G 1/2 7.7 kg WHSH HE 24 V (0 – 10 V) 08318
AIR1-NH WW XH 4500 03684 23.1 l G 1/2 10.2 kg WHSH HE 24 V (0 – 10 V) 08318
AIR1-NH WW XH 5500 03687 28.7 l G 3/4 12.5 kg WHSH HE 24 V (0 – 10 V) 08318
AIR1-NH WW XH 7000 03689 35.2 l G 3/4 15.6 kg WHSH HE 24 V (0 – 10 V) M 06310
AIR1-NH WW XH 8500 03793 45.3 l G 3/4 18.8 kg WHSH HE 24 V (0 – 10 V) M 06310
(1) External thread

60 Helios
Hydraulic unit Hydraulic unit
Hydraulic unit for supply air temperature control by controlling the water flow rate
in the heater battery. Delivered as a complete unit consisting of the hydraulic unit
with 3-way valve with actuator and circulating pump, Flow / return temperature
display and flexible connection hoses.
Control voltage: 24 V (0 – 10 V)
Kvs value: 5.1
Flow rate: up to 3.3 m³/h
Connection diameter: G1 AG flat sealing (DN25, 1”)

Types

Control
XH units Type Ref. no. Kvs value Flow rate Connection diameter
voltage

AIR1-XH 1000 WHSH HE 24 V (0 – 10 V) 08318 24 V (0 – 10 V) 5.1 0.2 to 3.3 m³/h G1 AG flat sealing (DN25, 1”)
AIR1-XH 1500 WHSH HE 24 V (0 – 10 V) 08318 24 V (0 – 10 V) 5.1 0.2 to 3.3 m³/h G1 AG flat sealing (DN25, 1”)
AIR1-XH 2500 WHSH HE 24 V (0 – 10 V) 08318 24 V (0 – 10 V) 5.1 0.2 to 3.3 m³/h G1 AG flat sealing (DN25, 1”)
AIR1-XH 3500 WHSH HE 24 V (0 – 10 V) 08318 24 V (0 – 10 V) 5.1 0.2 to 3.3 m³/h G1 AG flat sealing (DN25, 1”)
AIR1-XH 4500 WHSH HE 24 V (0 – 10 V) 08318 24 V (0 – 10 V) 5.1 0.2 to 3.3 m³/h G1 AG flat sealing (DN25, 1”)
AIR1-XH 5500 WHSH HE 24 V (0 – 10 V) 08318 24 V (0 – 10 V) 5.1 0.2 to 3.3 m³/h G1 AG flat sealing (DN25, 1”)
AIR1-XH 7000 WHSH HE 24 V (0 – 10 V) M 06310 24 V (0 – 10 V) 8.1 0.0 to 4.0 m³/h G2 AG flat sealing (DN32, 1 1/4”)
AIR1-XH 8500 WHSH HE 24 V (0 – 10 V) M 06310 24 V (0 – 10 V) 8.1 0.0 to 4.0 m³/h G2 AG flat sealing (DN32, 1 1/4”)

Helios AIR1 Series XH 61


Accessories for the XH series.

Cold water cooling register


Cold water cooling register external
For demand-oriented temperature control (cooling) of supply air. Mounting
directly to the supply air duct of the ventilation unit including fixing material is
possible. Casing in robust panel construction, insulated on all sides with 50 mm
mineral wool for the minimisation of heat losses. External corrosion-resistant
coating of casing. Large inspection openings on both sides of unit for easy
access and optimised cleaning and maintenance. Stainless steel condensate
tray with condensate drain outlets. Condensate connection 32 mm. Cooling
register suitable for internal and external installation. Note: A weather protection
cover is required for external installation.
Recommended accessory: Ball siphon AIR1-KS XH (Ref. no. 07169)

Detailed calculations / technical information: www.AIR1Select.com.

Technical data

Connection Weight
Type Ref. no. Version Water content
flow / return (1) (without liquid)

AIR1-KR KW XH 1000 L 03834 left 1.3 l G 1/2 57.0 kg


AIR1-KR KW XH 1000 R 04254 right 1.3 l G 1/2 57.0 kg
AIR1-KR KW XH 1500 L 03842 left 1.9 l G 3/4 64.0 kg
AIR1-KR KW XH 1500 R 04255 right 1.9 l G 3/4 64.0 kg
AIR1-KR KW XH 2500 L 03844 left 3.0 l G 3/4 86.0 kg
AIR1-KR KW XH 2500 R 04264 right 3.0 l G 3/4 86.0 kg
AIR1-KR KW XH 3500 L 03910 left 3.9 l G1 112.0 kg
AIR1-KR KW XH 3500 R 04268 right 3.9 l G1 112.0 kg
AIR1-KR KW XH 4500 L 03919 left 6.3 l G 1 1/4 148.0 kg
AIR1-KR KW XH 4500 R 04278 right 6.3 l G 1 1/4 148.0 kg
AIR1-KR KW XH 5500 L 03932 left 9.3 l G 1 1/4 173.0 kg
AIR1-KR KW XH 5500 R 04279 right 9.3 l G 1 1/4 173.0 kg
AIR1-KR KW XH 7000 L 03945 left 12.4 l G 1 1/2 213.0 kg
AIR1-KR KW XH 7000 R 04281 right 12.4 l G 1 1/2 213.0 kg
AIR1-KR KW XH 8500 L 03946 left 15.1 l G 1 1/2 250.0 kg
AIR1-KR KW XH 8500 R 04282 right 15.1 l G 1 1/2 250.0 kg
(1) External thread

62 Helios
Dimensional drawing

Version left (L) Version right (R)

R A A R

T N 500 500 N T
W
70 W Z Z 70

AC

max. E
SUP AC SUP
U

AB
B

U
S
V

max. E

S
V
AB

B
AA
P

AA

P
100
100

115 M8 ø 32
145

Y ø 32 M8 115
max. 80

145
Y

max. 80
O O
F F
C C

Maße (mm)
Maße (mm)
Art.-Nr. Type A B C E F N O P R S T U V W Y Z AA AB AC
Art.-Nr. Type A B C E F N O P R S T U V W Y Z AA AB AC
03834 AIR1-KR KW XH 1000 L 1000 495 635 675 250 350 318 215 343 238 315 210 - - 176 104 91 308 G 1/2 When looking
04254 AIR1-KR KW XH 1000 R 1000 495
04255 AIR1-KR KW XH 1500 R 1000 570
at the cooling register
635 675
from the
250
238 315 210
645 750 250 350 323 266 378 338 350 310
-
-
air-- flow
350 318
178
direction,
215
176 104
98
343
91
93
308 G 1/2
379 G 3/4
03842 AIR1-KR KW XH 1500 L 1000 570 645 750 250 350 323 266 378 338 350 310 - - 178 98 93 379 G 3/4
Dim. in mm
03844 AIR1-KR KW XH 2500 L 1000 620 865 800 250 350 433 285 498 338 470 310 - - 178 98 93 429 G 3/4the service side is on the right for the R version and on the left for the L version.
04264 AIR1-KR KW XH 2500 R 1000 620 865 800 250 350 433 285 498 338 470 310 - - 178 98 93 429 G 3/4
04268 AIR1-KR KW XH 3500 R 1100 670 967 850 275 450 484 320 608 438 580 410 - - 182 92 97 471 G1
03910 AIR1-KR KW XH 3500 L 1100 670 967 850 275 450 484 320 608 438 580 410 - - 182 92 97 471 G1
04278 AIR1-KR KW XH 4500 R 1100 870 1020 1050 275 450 510 433 608 438 580 410 - - 186 83 101 663 G 1 1/4
03919 AIR1-KR KW XH 4500 L 1100 870 1020 1050 275 450 510 433 608 438 580 410 - - 186 83 101 663 G 1 1/4
04279 AIR1-KR KW XH 5500 R 1100 870 1230 1050 275 450 615 433 883 438 855 410 498 - 186 118 101 663 G 1 1/4
03932 AIR1-KR KW XH 5500 L 1100 870 1230 1050 275 450 615 433 883 438 855 410 498 - 186 118 101 663 G 1 1/4
04281 AIR1-KR KW XH 7000 R 1100 870 1530 1050 275 450 765 433 1083 438 1055 410 498 361,1 189 112 104 657 G 1 1/2
Dimensions
03945 AIR1-KR KW XH 7000 L 1100 870 1530 1050 275 450 765 433 1083 438 1055 410 498 361,1 189 112 104 657 G 1 1/2
04282 AIR1-KR KW XH 8500 R 1100 870 1880 1050 275 450 940 433 1228 438 1200 410 498 409,4 189 112 104 657 G 1 1/2
03946 AIR1-KR KW XH 8500 L 1100 870 1880 1050 275 450 940 433 1228 438 1200 410 498 409,4 189 112 104 657 G 1 1/2

Type Ref. no. A B C E F N O P R S


AIR1-KR KW XH 1000 L 03834 1000 495 635 675 250 350 318 215 343 238
AIR1-KR KW XH 1000 R 04254 1000 495 635 675 250 350 318 215 343 238
AIR1-KR KW XH 1500 L 03842 1000 570 645 750 250 350 323 266 378 338
AIR1-KR KW XH 1500 R 04255 1000 570 645 750 250 350 323 266 378 338
AIR1-KR KW XH 2500 L 03844 1000 620 865 800 250 350 433 285 498 338
AIR1-KR KW XH 2500 R 04264 1000 620 865 800 250 350 433 285 498 338
AIR1-KR KW XH 3500 L 03910 1100 670 967 850 275 450 484 320 608 438
AIR1-KR KW XH 3500 R 04268 1100 670 967 850 275 450 484 320 608 438
AIR1-KR KW XH 4500 L 03919 1100 870 1020 1050 275 450 510 433 608 438
AIR1-KR KW XH 4500 R 04278 1100 870 1020 1050 275 450 510 433 608 438
AIR1-KR KW XH 5500 L 03932 1100 870 1230 1050 275 450 615 433 883 438
AIR1-KR KW XH 5500 R 04279 1100 870 1230 1050 275 450 615 433 883 438
AIR1-KR KW XH 7000 L 03945 1100 870 1530 1050 275 450 765 433 1083 438
AIR1-KR KW XH 7000 R 04281 1100 870 1530 1050 275 450 765 433 1083 438
AIR1-KR KW XH 8500 L 03946 1100 870 1880 1050 275 450 940 433 1228 438
AIR1-KR KW XH 8500 R 04282 1100 870 1880 1050 275 450 940 433 1228 438

Type Ref. no. T U V W Y Z AA AB AC (1)


AIR1-KR KW XH 1000 L 03834 315 210 – – 176 104 91 308 G 1/2
AIR1-KR KW XH 1000 R 04254 315 210 – – 176 104 91 308 G 1/2
AIR1-KR KW XH 1500 L 03842 350 310 – – 178 98 93 379 G 3/4
AIR1-KR KW XH 1500 R 04255 350 310 – – 178 98 93 379 G 3/4
AIR1-KR KW XH 2500 L 03844 470 310 – – 178 98 93 429 G 3/4
AIR1-KR KW XH 2500 R 04264 470 310 – – 178 98 93 429 G 3/4
AIR1-KR KW XH 3500 L 03910 580 410 – – 182 92 97 471 G1
AIR1-KR KW XH 3500 R 04268 580 410 – – 182 92 97 471 G1
AIR1-KR KW XH 4500 L 03919 580 410 – – 186 83 101 663 G 1 1/4
AIR1-KR KW XH 4500 R 04278 580 410 – – 186 83 101 663 G 1 1/4
AIR1-KR KW XH 5500 L 03932 855 410 498 – 186 118 101 663 G 1 1/2
AIR1-KR KW XH 5500 R 04279 855 410 498 – 186 118 101 663 G 1 1/2
AIR1-KR KW XH 7000 L 03945 1055 410 498 361 189 112 104 657 G 1 1/2
AIR1-KR KW XH 7000 R 04281 1055 410 498 361 189 112 104 657 G 1 1/2
AIR1-KR KW XH 8500 L 03946 1200 410 498 409 189 112 104 657 G 1 1/2
AIR1-KR KW XH 8500 R 04282 1200 410 498 409 189 112 104 657 G 1 1/2
(1) External thread

Helios AIR1 Series XH 63


Accessories for the XH series.

Direct evaporator cooling register


Direct evaporator cooling register external
For demand-oriented temperature control (cooling) of supply air. Mounting
directly to the supply air duct of the ventilation unit is possible. Suitable for use
with common refrigerants (selection list see www.AIR1Select.com).Casing in
robust panel construction, insulated on all sides with 50 mm mineral wool for
the minimisation of heat losses. External corrosion-resistant coating of casing.
Stainless steel condensate tray with condensate drain outlets. Large inspection
openings on both sides of unit for easy access and optimised cleaning and main-
tenance. Condensate connection 32 mm. Cooling register suitable for internal
and external installation. Note: A weather protection cover is required for external
installation.
Recommended accessory: Ball siphon AIR1-KS XH (Ref. no. 07169)

Detailed calculations / technical information: www.AIR1Select.com.

Technical data

Weight Filling Ø connection Ø connection


Type Ref. no. Version
(without liquid) capacity outlet inlet

AIR1-KR DX XH 1000 L 04403 left 56.0 kg 1.11 l 16 mm 9.5 mm


AIR1-KR DX XH 1000 R 04872 right 56.0 kg 1.11 l 16 mm 9.5 mm
AIR1-KR DX XH 1500 L 04406 left 63.0 kg 1.49 l 16 mm 9.5 mm
AIR1-KR DX XH 1500 R 04873 right 63.0 kg 1.49 l 16 mm 9.5 mm
AIR1-KR DX XH 2500 L 04407 left 85.0 kg 2.47 l 19 mm 12 mm
AIR1-KR DX XH 2500 R 04877 right 85.0 kg 2.47 l 19 mm 12 mm
AIR1-KR DX XH 3500 L 04408 left 110.0 kg 3.23 l 22 mm 16 mm
AIR1-KR DX XH 3500 R 04878 right 110.0 kg 3.23 l 22 mm 16 mm
AIR1-KR DX XH 4500 L 04409 left 145.0 kg 4.88 l 28 mm 16 mm
AIR1-KR DX XH 4500 R 04879 right 145.0 kg 4.88 l 28 mm 16 mm
AIR1-KR DX XH 5500 L 04410 left 173.0 kg 7.85 l 28 mm 22 mm
AIR1-KR DX XH 5500 R 04883 right 173.0 kg 7.85 l 28 mm 22 mm
AIR1-KR DX XH 7000 L 04414 left 211.0 kg 10.28 l 28 mm 22 mm
AIR1-KR DX XH 7000 R 03123 right 211.0 kg 10.28 l 28 mm 22 mm
AIR1-KR DX XH 8500 L 04415 left 250.0 kg 12.90 l 35 mm 22 mm
AIR1-KR DX XH 8500 R 03052 right 250.0 kg 12.90 l 35 mm 22 mm

64 Helios
Dimensional drawing

Version left (L) Version right (R)

R R
A
T A T
N 500
70 W 500 N W 70

AD AD

max. E
SUP SUP
U
B

S
V

U
S
V
max. E

B
AB

AB
AC

AA
AC
P

AA

P
100
100

115 M8 ø 32 ø 32 M8 115
145

145
max. 80

max. 80
O Z Y Y Z O
F F
C C

Maße (mm)
Maße (mm)
Art.-Nr. Type A B C E F N O P R S T U V W Y Z AA AB AC AD
Art.-Nr. Type A B C E F N O P R S T U V W Y Z AA AB AC AD
04872 AIR1-KR DX XH 1000 R 1000 495 635 675 250 350 318 248 343 238 315 210 - - 203 47 111 153 16 9,5
04403 AIR1-KR DX XH 1000 L 1000 495 635 675 250 350 318 248 343 238 315 210 - - 203 47 111 153 16 9,5
04873 AIR1-KR DX XH 1500 R 1000 570 645 750 250 350 323 285 378 338 350 310 - - 203 47 101 218 16 9,5
04406 AIR1-KR DX XH 1500 L 1000 570 645 750 250 350 323 285 378 338 350 310 - - 203 47 101 218 16 9,5
04877
When looking at the cooling register from
AIR1-KR DX XH 2500 R 1000 620 865 800 250 350 433 310 498 338 470 310 -
the
-
air 47flow
203
direction,
105 250 19 12
04407 AIR1-KR DX XH 2500 L 1000 620 865 800 250 350 433 310 498 338 470 310 - - 203 47 105 250 19 12
Dim. in mm
04408 AIR1-KR DX XH 3500 L 1100 670 967 850 275 450 484 320 608 438 580 410 - - 203 47 107 306 22
04878
16 the service
AIR1-KR side
DX XH 3500 is 670
R 1100 on 967
the850
right
275 for
450 the
484 R
320version
608 438 and on the
580 410 - -left203
for47the107L 306
version.
22 16
04879 AIR1-KR DX XH 4500 R 1100 870 1020 1050 275 450 510 433 608 438 580 410 - - 203 47 110 400 28 16
04409 AIR1-KR DX XH 4500 L 1100 870 1020 1050 275 450 510 433 608 438 580 410 - - 203 47 110 400 28 16
04883 AIR1-KR DX XH 5500 R 1100 870 1230 1050 275 450 615 433 883 438 855 410 498 - 210 202 97 426 28 22
04410 AIR1-KR DX XH 5500 L 1100 870 1230 1050 275 450 615 433 883 438 855 410 498 - 210 202 97 426 28 22
03123 AIR1-KR DX XH 7000 R 1100 870 1530 1050 275 450 765 433 1083 438 1055 410 498 361,1 210 202 97 426 28 22
04414 AIR1-KR DX XH 7000 L 1100 870 1530 1050 275 450 765 433 1083 438 1055 410 498 361,1 210 202 97 426 28 22
03052 AIR1-KR DX XH 8500 R 1100 870 1880 1050 275 450 940 433 1228 438 1200 410 498 409,4 210 202 101 418 35 22
Dimensions
04415 AIR1-KR DX XH 8500 L 1100 870 1880 1050 275 450 940 433 1228 438 1200 410 498 409,4 210 202 101 418 35 22

Type Ref. no. A B C E F N O P R S


AIR1-KR DX XH 1000 L 04403 1000 495 635 675 250 350 318 248 343 238
AIR1-KR DX XH 1000 R 04872 1000 495 635 675 250 350 318 248 343 238
AIR1-KR DX XH 1500 L 04406 1000 570 645 750 250 350 323 285 378 338
AIR1-KR DX XH 1500 R 04873 1000 570 645 750 250 350 323 285 378 338
AIR1-KR DX XH 2500 L 04407 1000 620 865 800 250 350 433 310 498 338
AIR1-KR DX XH 2500 R 04877 1000 620 865 800 250 350 433 310 498 338
AIR1-KR DX XH 3500 L 04408 1100 670 967 850 275 450 484 320 608 438
AIR1-KR DX XH 3500 R 04878 1100 670 967 850 275 450 484 320 608 438
AIR1-KR DX XH 4500 L 04409 1100 870 1020 1050 275 450 510 433 608 438
AIR1-KR DX XH 4500 R 04879 1100 870 1020 1050 275 450 510 433 608 438
AIR1-KR DX XH 5500 L 04410 1100 870 1230 1050 275 450 615 433 883 438
AIR1-KR DX XH 5500 R 04883 1100 870 1230 1050 275 450 615 433 883 438
AIR1-KR DX XH 7000 L 04414 1100 870 1530 1050 275 450 765 433 1083 438
AIR1-KR DX XH 7000 R 03123 1100 870 1530 1050 275 450 765 433 1083 438
AIR1-KR DX XH 8500 L 04415 1100 870 1880 1050 275 450 940 433 1228 438
AIR1-KR DX XH 8500 R 03052 1100 870 1880 1050 275 450 940 433 1228 438

Type Ref. no. T U V W Y Z AA AB AC AD


AIR1-KR DX XH 1000 L 04403 315 210 – – 203 47 111 153 16 9.5
AIR1-KR DX XH 1000 R 04872 315 210 – – 203 47 111 153 16 9.5
AIR1-KR DX XH 1500 L 04406 350 310 – – 203 47 101 218 16 9.5
AIR1-KR DX XH 1500 R 04873 350 310 – – 203 47 101 218 16 9.5
AIR1-KR DX XH 2500 L 04407 470 310 – – 203 47 105 250 19 12
AIR1-KR DX XH 2500 R 04877 470 310 – – 203 47 105 250 19 12
AIR1-KR DX XH 3500 L 04408 580 410 – – 203 47 107 306 22 16
AIR1-KR DX XH 3500 R 04878 580 410 – – 203 47 107 306 22 16
AIR1-KR DX XH 4500 L 04409 580 410 – – 203 47 110 400 28 16
AIR1-KR DX XH 4500 R 04879 580 410 – – 203 47 110 400 28 16
AIR1-KR DX XH 5500 L 04410 855 410 498 – 210 202 97 426 28 22
AIR1-KR DX XH 5500 R 04883 855 410 498 – 210 202 97 426 28 22
AIR1-KR DX XH 7000 L 04414 1055 410 498 361 210 202 97 426 28 22
AIR1-KR DX XH 7000 R 03123 1055 410 498 361 210 202 97 426 28 22
AIR1-KR DX XH 8500 L 04415 1200 410 498 409 210 202 101 418 35 22
AIR1-KR DX XH 8500 R 03052 1200 410 498 409 210 202 101 418 35 22

Helios AIR1 Series XH 65


Accessories for the XH series.

Multi-leaf damper
Multi-leaf damper internal
Multi-leaf damper for preventing cold draughts when the fan is stationary. Frame-
work casing with connection flange on both sides. Counter-rotating blades, with
retracted sealing lip. Sealing class 2. Installation inside of unit.

Technical data

Runtime Ambient
Type Ref. no. Weight Actuator type
(open / closed) temperature

AIR1-JVK XH 1000 06005 40 ... 75 s 2.5 kg -30 bis +50 °C 24 V DC. spring return
AIR1-JVK XH 1500/RH 1500 06006 40 ... 75 s 3.0 kg -30 bis +50 °C 24 V DC. spring return
AIR1-JVK XH 2500/RH 2000 06007 40 ... 75 s 4.0 kg -30 bis +50 °C 24 V DC. spring return
AIR1-JVK XH 3500-4500/RH 3000 06009 40 ... 75 s 5.0 kg -30 bis +50 °C 24 V DC. spring return
AIR1-JVK XH 5500/RH 5000-6000 06010 40 ... 75 s 6.6 kg -30 bis +50 °C 24 V DC. spring return
AIR1-JVK XH 7000/RH 8000 06012 40 ... 75 s 7.8 kg -30 bis +50 °C 24 V DC. spring return
AIR1-JVK XH 8500/RH 9500 06013 40 ... 75 s 8.6 kg -30 bis +50 °C 24 V DC. spring return

Recirculation kit
Recirculation kit
Recirculation kit for the 100% recirculation of the extract air into the building.
Multi-leaf dampers are required for recirculation operation.
The kit consists of a recirculation damper including drive. For mounting to bypass
duct of ventilation unit. Plug-in connection to the mains power supply and venti-
lation unit control system.

Type Ref. no.


AIR1-ULK XH 1000 06022
AIR1-ULK XH 1500 06023
AIR1-ULK XH 2500 06024
AIR1-ULK XH 3500 06025
AIR1-ULK XH 4500 06026
AIR1-ULK XH 5500 06027
AIR1-ULK XH 7000 06028
AIR1-ULK XH 8500 06029

66 Helios
Flexible connector
Flexible connector
Flexible connector (uninsulated), with flange connections on both sides, for
mounting between the ventilation unit and duct system. Prevents structure-borne
sound transmission and bridges mounting tolerances. Elastic fabric sleeve,
operating temperature range from -10 °C to +80 °C.

Only suitable for internal installation.

Dimensional drawing Dimensions


XH units Type Ref. no. A B R S
AIR1-XH 1000 AIR1-VS 31/21 04371 363 258 343 238
AIR1-XH 1500 AIR1-VS 35/31 04372 398 358 378 338
AIR1-XH 2500 AIR1-VS 47/31 04373 518 358 498 338
B

AIR1-XH 3500 AIR1-VS 58/41 04374 628 458 608 438


S

10,5x14 AIR1-XH 4500 AIR1-VS 58/41 04374 628 458 608 438
AIR1-XH 5500 AIR1-VS 85/41 04375 903 458 883 438
AIR1-XH 7000 AIR1-VS 105/41 04376 1103 458 1083 438

R AIR1-XH 8500 AIR1-VS 120/41 04377 1248 458 1228 438

A
145

Dim. in mm

Helios AIR1 Series XH 67


Accessories for the XH series.

Square-round adapter Square-round adapter


Symmetrical adapter for connecting the ventilation unit to round air ducts/duct
systems. Made of galvanised steel sheet. The pressure loss of the adapter at
maximum air volume is < 10 Pa on both the intake and discharge side.

Only suitable for internal installation.

Dimensional drawing

C D
B
S

10 21
R
A

Dim. in mm

Dimensions
Type Ref. no. A B C D E R S
AIR1-ÜS XH 1000 04366 365 260 200 250 60 343 238
AIR1-ÜS XH 1500/RH 1500 04367 400 360 200 315 60 378 338
AIR1-ÜS XH 2500/RH 2000 04368 520 360 250 400 80 498 338
AIR1-ÜS XH 3500-4500/RH 3000 04369 630 460 300 500 80 608 438
AIR1-ÜS XH 5500/RH 5000-6000 04370 905 460 350 630 80 883 438

Ball siphon Ball siphon


Siphon for the drainage of condensate with over or underpressure in comparison
to the environment. Self-filling and self-closing, with float ball as non-return valve.
Screw cap for inspection purposes.
Suitable for a max. under/overpressure of ± 600 Pa.
For use with the units and the cooling register.
Connection diameter 40 mm.

Type Ref. no.


AIR1-KS XH 07169

68 Helios
Weather protection cover for the unit
Weather protection cover for the unit
Weather protection cover for the external installation of AIR1 ventilation units.
Made of galvanised steel sheet, in weather-resistant design/coating. Increases
the protection class of the unit to IP 54.

Dimensional drawing Dimensions


Type Ref. no. A B C D
G AIR1-AAD XH 1000 06305 2005 106 635 785
F 1170 F D

850 640
AIR1-AAD XH 1500 06306 2085 106 643 790
AIR1-AAD XH 2500 06315 2346 120 860 1000
115

E

AIR1-AAD XH 3500 06316 2970 134 970 1010


B

A C

Type Ref. no. E F G


G Maße (mm)
F 1170
Art.-Nr. Type
F
A B C D D E F G Teilbar AIR1-AAD XH 1000 06305 205 469 2107
06305 AIR1-AAD XH 1000 2005 106 635 785 205 469 2107 -
850
06306 AIR1-AAD XH 1500 2085 106
640
643 790 205 509 2187 -
AIR1-AAD XH 1500 06306 205 509 2187
115

06315 AIR1-AAD XH 2500 2346 120 860 1000 230 639 2448 -
AIR1-AAD XH 2500 06315 230 639 2448

06316 AIR1-AAD XH 3500 2970 134 970 1010 235 951 3072 x
B

AIR1-AAD XH 3500 06316 235 951 3072


A C

Dim. in mm Maße (mm) AIR1 XH 1000 – 3500


Art.-Nr. Type A B C D E F G Teilbar
06305 AIR1-AAD XH 1000 2005 106 635 785 205 469 2107 -
06306 AIR1-AAD XH 1500 2085 106 643 790 205 509 2187 -
06315
Dimensional
AIR1-AAD XH 2500
drawing
2346 120 860 1000 230 639 2448 -
Dimensions
06316 AIR1-AAD XH 3500 2970 134 970 1010 235 951 3072 x
Type Ref. no. A B C D
G
AIR1-AAD XH 4500 06347 3515 142 1050 1090
F
1170
AIR1-AAD XH 5500 06349 3555 160 1260 1435
D
850 640
AIR1-AAD XH 7000 06350 3605 185 1560 1730
115

AIR1-AAD XH 8500 06378 3655 218 1910 2080



E

C
A
G Type Ref. no. E F G
F
AIR1-AAD XH 4500 06347 230 2395 3620
1170 Maße (mm)
D
850
Art.-Nr. Type A B C D E F G Teilbar
AIR1-AAD XH 5500 06349 250 2415 3660
06347 AIR1-AAD XH 4500 3515 142 1050 1090640
230 2395 3620 x
AIR1-AAD XH 7000 06350 270 2440 3710
115

06349 AIR1-AAD XH 5500 3555 160 1260 1435 250 2415 3660 x

06350 AIR1-AAD XH 7000 3605 185 1560 1730 270 2440 3710 x
E

06378 AIR1-AAD XH 8500 3655 218 1910 2080 280 2465 3760 x AIR1-AAD XH 8500 06378 280 2465 3760
C
A

Dim. in mm AIR1 XH 4500 – 8500


Maße (mm)
Art.-Nr. Type A B C D E F G Teilbar
06347 AIR1-AAD XH 4500 3515 142 1050 1090 230 2395 3620 x
06349 AIR1-AAD XH 5500 3555 160 1260 1435 250 2415 3660 x
06350 AIR1-AAD XH 7000 3605 185 1560 1730 270 2440 3710 x
06378 AIR1-AAD XH 8500 3655 218 1910 2080 280 2465 3760 x

Helios AIR1 Series XH 69


Accessories for the XH series.

Weather protection cover for external cold water or direct


Weather protection cover cooling register
evaporator cooling registers
Weather protection cover for the external installation of external cold water
or direct evaporator cooling registers. Made of galvanised steel sheet, in
weather-resistant design/coating. Increases the protection class of the cooling
register to IP 54.

Dimensional drawing Dimensions


Type Ref. no. A C
AIR1-AAD KR KW + DX XH 1000 06451 1000 805
AIR1-AAD KR KW + DX XH 1500 06455 1000 812

A AIR1-AAD
C KR KW + DX XH 2500 06461 1000 1037
AIR1-AAD KR KW + DX XH 3500 06462 1100 1138
35

AIR1-AAD KR KW + DX XH 4500 06463 1100 1220


AIR1-AAD KR KW + DX XH 5500 06464 1100 1430

C AIR1-AAD KR KW + DX XH 7000 06465 1100 1730


AIR1-AAD
Maße (mm) KR KW + DX XH 8500 06466 1100 2080
Art.-Nr. Type A C
06451 AIR1-AAD KR KW+DX XH 1000 1000 805
06455 AIR1-AAD KR KW+DX XH 1500 1000 812
06461 AIR1-AAD KR KW+DX XH 2500 1000 1037
Dim. in mm Maße (mm)
06462 AIR1-AAD KR KW+DX XH 3500 1100 1138
Art.-Nr. Type A C
06463 AIR1-AAD KR KW+DX XH 4500 1100 1220
06451 AIR1-AAD KR KW+DX XH 1000 1000 805
06464 AIR1-AAD KR KW+DX XH 5500 1100 1430
06455 AIR1-AAD KR KW+DX XH 1500 1000 812
06465 AIR1-AAD KR KW+DX XH 7000 1100 1730
06461 AIR1-AAD KR KW+DX XH 2500 1000 1037
06466 AIR1-AAD KR KW+DX XH 8500 1100 2080
06462 AIR1-AAD KR KW+DX XH 3500 1100 1138
06463 AIR1-AAD KR KW+DX XH 4500 1100 1220
06464 AIR1-AAD KR KW+DX XH 5500 1100 1430
06465 AIR1-AAD KR KW+DX XH 7000 1100 1730
06466 AIR1-AAD KR KW+DX XH 8500 1100 2080

70 Helios
Heating element for the terminal box
Heating element for the terminal box
Heating element for the electrical terminal box of the ventilation unit. Recommen-
ded for the external installation of AIR ventilation units in cold climate zones to
prevent condensate formation and protect the control system against tempera-
tures below 0 °C.
Heat output automatically controlled depending on the outside air temperature.
Max. heat output: 100 W
Supply voltage: 230 V

Type Ref. no.


AIR1-AAHK 07064

Intake hood outside air


Intake hood outside air
Intake hood outside air for external installation. Includes drainage tray and droplet
separator. Mounting via flange connection to the unit connector. Surface with
weather-resistant coating.

Dimensional drawing

X
R
T
W C
B
U
S
V

9
A D

Dim. in mm

Maße (mm)
Art.-Nr. Type A B C D R S T U V W X
Dimensions
06483 AIR1-AAHA XH 1000 375 270 332 162 343 238 315 210 - - -
Type Ref. no.XH 1500/RH 1500
06484 AIR1-AAHA A B 410 C 486
370 195D 378 338R 350 310S - - T - U V W
06539 AIR1-AAHA XH 2500/RH 2000
AIR1-AAHA XH 1000 06483 375 270 530 370
332 486 195
162498 338
343470 310
238 - -
315 - 210 – –
06487 AIR1-AAHA XH 3500-4500/RH 3000 640 470 525 200 608 438 580 410 - - -
AIR1-AAHA XH 1500/RH 1500 06484 XH 5500/RH 410
06496 AIR1-AAHA 5000-6000 370 915 486 525
530 195883
200 378855
438 338498
410 - 350 - 310 – –
AIR1-AAHA XH 2500/RH 2000 06497 AIR1-AAHA
06539 XH 7000/RH 530
8000 370 1115 530
486 525 200
1951083 438
4981055 410
338498 361,1
470 - 310 – –
06499 AIR1-AAHA XH 8500/RH 9500 1260 530 525 200 1228 438 1200 410 498 409,4 -
AIR1-AAHA XH 3500-4500/RH 3000 06487
06611 AIR1-AAHA RH 12000
640 470 1595 525
630 575
200
200 1503
608
538 1475
438
510 598
580
501,1 1563
410 – –
AIR1-AAHA XH 5500/RH 5000-6000 06496 RH 15000
06612 AIR1-AAHA 915 530 1720 830
525 675 2001628 738
200 8831600 710
438798 814,2
8551688 410 498 –
AIR1-AAHA XH 7000/RH 8000 06497 1115 530 525 200 1083 438 1055 410 498 361
AIR1-AAHA XH 8500/RH 9500 06499 1260 530 525 200 1228 438 1200 410 498 409

Helios AIR1 Series XH 71


Accessories for the XH series.

Discharge hood exhaust air


Discharge hood exhaust air
Discharge hood exhaust air for external installation. Includes protection guard.
Mounting via flange connection to the unit connector. Surface with weather-
resistant coating.

Dimensional drawing

X
R
T
W C

B
U
S
V

9
A 50

Dim. in mm
Maße (mm)
Art.-Nr. Type A B C R S T U V W X
Dimensions
06613 AIR1-AAHF XH 1000 375 270 235 343 238 315 210 - - -
Type Ref.
06643 no. XH 1500/RH
AIR1-AAHF A1500 B 410 C
370 338 378R 338 350 S310 - T- - U V W
06646 AIR1-AAHF XH 2500/RH 2000 530 370 338 498 338 470 310 - - -
AIR1-AAHF XH 1000 06613 375 270 235 343 238 315 210 – –
06647 AIR1-AAHF XH 3500-4500/RH 3000 640 470 375 608 438 580 410 - - -
AIR1-AAHF XH 1500/RH 1500 06643
06648 410
AIR1-AAHF XH 5500/RH 5000-6000 370 915 338 375
530 378438
883 855 338
410 498 350
- - 310 – –
06841 AIR1-AAHF XH 7000/RH 8000 1115 530 375 1083 438 1055 410 498 361,1 -
AIR1-AAHF XH 2500/RH 2000 06646 530 370 338 498 338 470 310 – –
06864 AIR1-AAHF XH 8500/RH 9500 1260 530 375 1228 438 1200 410 498 409,4 -
AIR1-AAHF XH 3500-4500/RH 3000 06647
06865 AIR1-AAHF RH 12000640 470 1595 375
630 415 608538
1503 1475438
510 598 580
501,1 1563 410 – –
06866 AIR1-AAHF RH 15000 1720 830 566 1628 738 1600 710 798 814,2 1688
AIR1-AAHF XH 5500/RH 5000-6000 06648 915 530 375 883 438 855 410 498 –
AIR1-AAHF XH 7000/RH 8000 06841 1115 530 375 1083 438 1055 410 498 361
AIR1-AAHF XH 8500/RH 9500 06864 1260 530 375 1228 438 1200 410 498 409

72 Helios
Controller Eco
Controller Eco
Backlit display with 4 lines a 20 characters. The display menu system is operated
via seven buttons. There are two LEDs on the front side: One alarm LED and one
LED for the input mode. The controller is delivered with a 5 m cable as standard.
Cable lengths of 10 m and 20 m are optionally available. The maximum connec-
tion length is 100 m. The controller is designed for wall mounting. Alternatively,
it can also be attached to the unit casing using magnetic strips. Protection class
IP 40.

Technical data

Power Dimensions Ambient Ambient Connection Connection


Type Ref. no. Voltage
consumption (WxHxD) humidity temperature cable 10 m cable 20 m

(1) AIR1-SL 4/10 AIR1-SL 4/20


AIR1-BE ECO 06186 24 V DC 0.24 W 115 x 95 x 25 mm Max. 90 % RH +5 °C to +40 °C
Ref. no.: 07073 Ref. no.: 07121

Controller Touch
Controller Touch
Graphic user interface with intuitive menu structure and simple operation. The
display has a capacitive touch function and a size of 7”, incl. multi-colour colour
technology. Includes stainless steel casing for simple surface-mounting to the
wall. It is delivered with a 5 m cable as standard. Cable lengths of 10 m and 20 m
are optionally available. The maximum connection length is 100 m. Protection
class IP 20.

Technical data

Power Dimensions Ambient Ambient Connection Connection


Type Ref. no. Voltage
consumption (WxHxD) humidity temperature cable 10 m cable 20 m

(1) AIR1-SL 4/10 AIR1-SL 4/20


AIR1-BE TOUCH 06187 24 V DC 6W 185 x 131 x 50 mm Max. 90 % RH -10 °C to +60 °C
Ref. no.: 07073 Ref. no.: 07121

Room sensors Room sensors


For measuring the CO2, mixed gas (VOC) concentration or relative humidity
and temperature. Control according to highest measured value. Includes
control cable KWL-SL 4/3 (3 m long), other lengths available upon request.
Dimensions (W x H x D) 95 x 97 x 30 mm.

Technical data
Type Ref. no. Measurement range
KWL-CO2 04272 400 ... 2000 ppm
(1)
KWL-FTF 04273 0 ... 99 % RH and 0 ... 40 °C
KWL-VOC 04274 450 ... 2000 ppm

(1) Non-condensing

Helios AIR1 Series XH 73


Accessories for the XH series.

Carbon dioxide sensor for duct installation


Carbon dioxide sensor for duct installation
Sensor for measuring the carbon dioxide concentration in the air. For installation
in the ventilation duct. Installation depth 40 – 180 mm.

Technical data
Type Ref. no. Measurement range
AIR1-CO2 K 07124 0 ... 2000 ppm

Signal converter Signal converter for sensors


Signal converter for the connection of up to six AIR1 room sensors of the same
sensor type. The AIR1-SK compares the connected inputs and forwards the
highest input signal to the max. output. Supplied pre-installed in the appropriate
terminal box incl. transformer 230 V / 24 V AC and terminal strip.
Dimensions terminal box (L x H x W): 218 x 149 x 97 mm

Technical data

Power Protection
Type Ref. no. Voltage Ambient humidity Ambient temperature
consumption class

(1) IP 20 / IP 66 in
AIR1-SK 06019 230 V, 50 Hz max. 15 VA Max. 90 % RH -40 °C to +50 °C
terminal box

Extension kit for CAP mode Extension kit for CAP mode
Differential pressure transmitter for constant pressure operation of the ventilation
unit. Vertical or horizontal installation possible.
Scope of delivery: Pressure transmitter, pressure hose and sensor.

Technical data
Type Ref. no. Voltage Ambient humidity Ambient temperature Protection class

(1)
AIR1-CAP 06756 24 V AC / DC ± 15 % Max. 95 % RH -25 °C to +50 °C IP 54

(1) Non-condensing

74 Helios
Spare air filter Spare air filter
Helios AIR1 units are supplied with the filter classes ePM1 55%/F7 (outside air)
and ePM10 50%/M5 (extract air) as standard. Depending on the unit size, the
(1) (2) (3)
air filter consists of multiple (separate) air filter inserts. This is taken into account
when ordering the spare air filter.
In case of increased air quality requirements, other filter classes are available for
the outside air and extract air (see table below). All air filters are pressure-loss-
optimised cassette filters with large filter surfaces.

(1) (2) (3)


Pre-filter outs. air Extract air filter Outs. or extract air filter ePM1 55% (F7)
ePM10 50% (M5) ePM10 50% (M5) Outside air filter ePM1 80% (F9)

Technical data
Type Ref. no. Filter class
ELF-AIR1 XH 1000/ePM10 50%/48 02176 ePM10 50% (M5)
ELF-AIR1 XH 1500/ePM10 50%/48 02178 ePM10 50% (M5)
Pre-filter outside air

ELF-AIR1 XH 2500/ePM10 50%/48 02179 ePM10 50% (M5)


ELF-AIR1 XH 3500/ePM10 50%/48 02180 ePM10 50% (M5)
ELF-AIR1 XH 4500/ePM10 50%/48 02182 ePM10 50% (M5)
ELF-AIR1 XH 5500/ePM10 50%/48 02186 ePM10 50% (M5)
ELF-AIR1 XH 7000/ePM10 50%/48 02187 ePM10 50% (M5)
ELF-AIR1 XH 8500/ePM10 50%/48 02189 ePM10 50% (M5)
ELF-AIR1 XH 1000/ePM10 50%/96 02203 ePM10 50% (M5)
ELF-AIR1 XH 1500/ePM10 50%/96 02204 ePM10 50% (M5)
Extract air filter

ELF-AIR1 XH 2500/ePM10 50%/96 02205 ePM10 50% (M5)


ELF-AIR1 XH 3500/ePM10 50%/96 02206 ePM10 50% (M5)
ELF-AIR1 XH 4500/ePM10 50%/96 02207 ePM10 50% (M5)
ELF-AIR1 XH 5500/ePM10 50%/96 02208 ePM10 50% (M5)
ELF-AIR1 XH 7000/ePM10 50%/96 02209 ePM10 50% (M5)
ELF-AIR1 XH 8500/ePM10 50%/96 02210 ePM10 50% (M5)
ELF-AIR1 XH 1000/ePM1 55%/96 02227 ePM1 55% (F7)
Outside or extract air filter

ELF-AIR1 XH 1500/ePM1 55%/96 02228 ePM1 55% (F7)


ELF-AIR1 XH 2500/ePM1 55%/96 02229 ePM1 55% (F7)
ELF-AIR1 XH 3500/ePM1 55%/96 02230 ePM1 55% (F7)
ELF-AIR1 XH 4500/ePM1 55%/96 02231 ePM1 55% (F7)
ELF-AIR1 XH 5500/ePM1 55%/96 02233 ePM1 55% (F7)
ELF-AIR1 XH 7000/ePM1 55%/96 02234 ePM1 55% (F7)
ELF-AIR1 XH 8500/ePM1 55%/96 02235 ePM1 55% (F7)
ELF-AIR1 XH 1000/ePM1 80%/96 02288 ePM1 80% (F9)
ELF-AIR1 XH 1500/ePM1 80%/96 02289 ePM1 80% (F9)
Outside air filter

ELF-AIR1 XH 2500/ePM1 80%/96 02290 ePM1 80% (F9)


ELF-AIR1 XH 3500/ePM1 80%/96 02291 ePM1 80% (F9)
ELF-AIR1 XH 4500/ePM1 80%/96 02292 ePM1 80% (F9)
ELF-AIR1 XH 5500/ePM1 80%/96 02293 ePM1 80% (F9)
ELF-AIR1 XH 7000/ePM1 80%/96 02435 ePM1 80% (F9)
ELF-AIR1 XH 8500/ePM1 80%/96 02334 ePM1 80% (F9)

Helios AIR1 Series XH 75


The Helios AIR1 RH series:
®

1,500 to 15,000 m3/h.


9 unit types:

AIR1 RH 1500
AIR1 RH 2000
AIR1 RH 3000
AIR1 RH 5000
AIR1 RH 6000
AIR1 RH 8000
AIR1 RH 9500
AIR1 RH 12000
AIR1 RH 15000

The ventilation units in the Helios AIR1 RH series


are equipped with highly efficient rotary heat
exchangers including rinsing chambers as stan-
dard. The additional moisture recovery provides
an optimal indoor climate and improved energy
balance.

Alternatively, an adsorption heat exchanger for


maximum humidity and heat transfer can be
selected in case of special requirements. Further-
more, the rotary technology allows shorter housing
dimensions and thus more freedom when selecting
the installation site.

76 Helios
Optional adsorption heat
Integrated rinsing exchanger for specific
chamber as standard requirements

Compact design

Maintenance access Moisture recovery with


on both sides for rotary heat exchanger
simple service work

Separable housing Universal right / left


construction from configuration
5,000 m3/h

Helios AIR1 Series RH 77


The RH series in detail.
1 Housing
1
Housing made of robust and stable aluminium frame profiles, thermally
optimised to minimise thermal bridges. Double-walled panels made of Alu-
zinc sheet steel. Insulated on all sides with 50 mm mineral wool for optimal
thermal and acoustic insulation. External corrosion-resistant coating on all
sides of housing, RAL 7047, corrosion class C4 and thus suitable for ex-
ternal installation. Galvanised inside. The smooth inner surface meets the
hygiene requirements for optimal cleaning in consideration of the hygiene
standard VDI 6022. Large inspection openings on both sides of the unit for
simple access to all unit components and optimal maintenance. The service
doors are equipped with maintenance-free hinges and lockable lever locks.
The XH units are designed so that accessories, such as electric or hot
water auxiliary heaters, can be easily installed in the ventilation unit, even for
retrofitting.
2
Housing and tightness classes according to DIN EN 1886
Thermal insulation T2
Thermal bridging factor TB2
Mechanical stability D1
Housing leakage in case of overpressure L1
Housing leakage in case of underpressure L1
Filter bypass leakage F9

Outdoor installation of unit


All units are suitable for internal and external installation. Additional acces-
sories are mandatory for the external installation (e.g. weather protection
cover, intake/discharge hoods etc.). In this respect, please see the acces-
3 sory list or configure your unit with our online configuration software www.
AIR1Select.com.

2 Heat exchanger
Eurovent-certified rotary heat exchanger made of aluminium (condensation
wheel) produced according to the latest production standards and guaran-
tees the highest quality and high thermal efficiency. The heat exchanger is
suitable for heat and cold recovery for additional humidity transfer and it gua-
rantees freezing protection to approx. -15 °C outside air temperature. Optimal
hygiene is guaranteed by an ingenious sealing system, and a rinsing chamber
included in the scope of delivery. The rotor is drive by an energy-efficient step
motor for the continuous and precise controlling of the rotor rotation speeds.
The innovative “power belt” drive belt guarantees high wear resistance, a long
4 service life, and simple replacement. The unit types “SO” are equipped with
an adsorption rotor for the increased transfer of humidity and heat/cold with
humidity retention levels up to 90 %. This heat exchanger type also has free-
zing protection to an outside air temperature of approx. -20 °C.

3 Separating the unit housing


The units can be separated to simplify transportation and for easier installa-
tion at the installation site for units above size RH 5000. Note: The units are
delivered in individual modules, i.e. in multiple delivery units.

78 Helios
4 Fans
5
The vibration dampened fans are located in the unit and they consist of
freewheeling, backward curved centrifugal impellers with direct drive via a
variable EC motor with low energy consumption and very low noise level.
The high performance plastic impeller is dynamically balanced in two levels.
Variably controllable via 0 – 10 V signal. Plug-in connections to all electrical
components for the simplification of maintenance work. Eurovent-certified
EC-motors in class IE4 with very low SFP values and high energy efficiency.

Pipe routing
Installation-friendly connection of outside, exhaust, extract and supply air to
a duct or pipe system. The floor-standing unit can be turned 180° for the
installation of the air duct system, so that the outside air/exhaust air and ex-
tract air/supply air connections can be on the left or right side. Adapters are
6 optionally available as unit accessories for adaption to a round duct system
up to unit size RH 6000.

5 Control system
The ventilation unit is delivered ready for operation with a modern, all-round
control system. The control system is attached on top of the unit in a
connection box for easy maintenance , factory-wired and function-tested.
Two controllers are available for selection (required accessory).

Overview of control functions:


C  hoice between ventilation modes Constant volume CAV, Constant pressure
CAP (accessory required) or Constant speed CRPM in %.
Multiple possible operating modes and levels.
7 Automatic control via humidity or room air quality sensors (can connect up to
three sensor types and maximum 18 sensors).
Automatic operation via integrated weekly programme.
Operating modes Free cooling (also night cooling/bypass function) and active
cooling (using cooling register) possible.
Commissioning assistant for simple, quick and faultless commissioning of the
unit and matching accessories.
Connection to the central building control system via BACnet or Modbus.
Digital output for collective fault signal.
Further information on the Helios AIR1 control system can be found on page 118.

6 Accessories
There are a number of accessory components available for the Helios AIR1
units. A detailed overview and the matching accessories for your Helios
8 AIR1 unit can be found on the following product pages.

Eurovent certification for the AIR1 RH 7 Air filters


series has been applied for. Cassette filters with long service lives due to dynamic pressure monitoring.
The AIR1 RH series is designed in ac- Simple filter replacement at the side or below through insert frame and
cordance with the requirements of Di- quick clamp device. A multi-level filter concept inside the unit is optional.
rective VDI 6022 (hygiene requirements Further information on the air filters can be found on page 115.
for building ventilation systems).

Helios AIR1 Series RH 79


AIR1 RH 1500 Performance curve

Dpfa
Pa

V· m3/h

Fig. shows accessories

Unit types

AIR1 RH 1500 AIR1 RH 1500/SO


Ref. no. 04343 04352
Heat exchanger Condensation rotor Adsorption rotor (4)

Technical data Sound data AIR1 RH 1500

Mechanical data Sound power level LwA dB(A) at 250 Pa external pressure
Area of application Inside/outside 450 m³/h 1,200 m³/h 1,600 m³/h
Installation position Standing Supply air (LwA) 69 72 76
Maintenance access Side, both sides Extract air (LwA) 62 65 68
Min. air volume 150 m³/h Outside air (LwA) 58 62 64
Max. air volume 1600 m³/h (1) (1520 m³/h (5)) Exhaust air (LwA) 69 72 76
Weight, unit operational 230 kg (236 kg (5)) Sound pressure level LpA db(A) of sound radiated from housing
Delivery unit 1-part 450 m³/h 1,200 m³/h 1,600 m³/h
Unit segments 1 Housing rad. 1 m 42 46 49
Housing class (DIN 1886) T2 / TB2 / D1 Housing rad. 3 m 33 36 39
Filter Outside air ePM1 55% (F7) (2) Housing rad. 5 m 28 32 35
Filter Extract air ePM10 50% (M5) (2)
The sound power at the connectors is calculated for the simultaneous
Media temperature (air) -20 to +50 °C operation of both fans. The sound pressure level is determined for the
Ambient temperature (operation) 0 to +50 °C simultaneous operation of both fans at distances of 1, 3 and 5 m.

Protection class IP 31
Electrical data
Central building control system BACnet, Modbus TCP/IP Sound data AIR1 RH 1500/SO
Voltage / Frequency 400 V 3N ~, 50 Hz
Sound power level LwA dB(A) at 250 Pa external pressure
Max. output Fans 2 x 500 W
450 m³/h 1,200 m³/h 1,520 m³/h
Nominal current
Supply air (LwA) 70 73 76
– Ventilation unit 2.2 / 2.2 / 1.3 A
Extract air (LwA) 63 67 68
– Electrical auxiliary heater 6.1 / 6.1 / 6.1 A (3)
Outside air (LwA) 59 62 64
– max. total 8.3 / 8.3 / 7.4 A
Exhaust air (LwA) 70 73 76
Connection (wiring diagram no.) SS-1317
Sound pressure level LpA db(A) of sound radiated from housing
450 m³/h 1,200 m³/h 1,520 m³/h
(1) = at 250 Pa external pressure loss ERP-compliant
(2) = other filter classes see optional accessories Housing rad. 1 m 43 47 48
(3) = Optional accessories Housing rad. 3 m 33 38 39
(4) = with increased humidity recovery
(5) = AIR RH 1500/SO Housing rad. 5 m 29 33 34

The sound power at the connectors is calculated for the simultaneous


operation of both fans. The sound pressure level is determined for the
simultaneous operation of both fans at distances of 1, 3 and 5 m.

80 Helios
SUP - Supply Air / Zuluft / Air soufflé 378

150
350

338
310
ETA EHA

max. 1320
34

463,2
990
G 1/2
Dimensional drawing

M8

339
SUP ODA

263,4
View A (from above) View B View C
76

ODA
ODA - Outdoor Air-/Outdoor Air // Air
Außenluft Außenluft / Air extérieur
extérieur
100

EHA
EHA - Exhaust Air- /Exhaust
FortluftAir
/Air/ Fortluft
rejeté /Air rejeté
ETA - ExtractETA
Air -/ Extract
Abluft /Air
Air/repris
Abluft / Air repris
360 520 380 378 378

max. 80
SUP - SupplySUP
Air /- Supply
Zuluft /Air
Air/soufflé
Zuluft / Air soufflé
A

150

150
145 350 350

338
310

338
310
ETA ETA EHA EHA

C B

max. 1320

max. 1320
34 34
472

760
810

463,2

463,2
990

990
G 1/2 (1)
G 1/2 G 1/2

M8

M8
339

339
SUP SUP ODA ODA
144

263,4

263,4
655 568

76

76
100

100
1700
360 360 520 520 380 380

max. 80

max. 80
B 145 145

Dim. in mm (1) External thread ODA: Outside air EHA: Exhaust air ETA: Extract air SUP: Supply air

472

472

760
810

760
810
Accessories
144

144
655 655 568 568
Heating and cooling registers External
1700 1700 installation

Pre-heater Cover for external installation


AIR1-EVH RH 1500 AIR1-AAD RH 1500
Ref. no. 01262 Page 98 Ref. no. 06382 Page 108
Electrical, external Weather protection cover for the unit
Auxiliary heater AIR1-AAD KR KW + DX RH 1500
Weather protection cover for cooling Ref. no. 06467 Page 110
AIR1-ENH RH 1500
Ref. no. 03605 Page 99 register cold water or direct evaporator
Electrical, internal
Terminal box heater
AIR1-NH WW RH 1500
Ref. no. 03805 Page 100
Hot water, internal AIR1-AAHK Ref. no. 07064 Page 111

Hydraulic unit for hot water heater register Hoods

WHSH HE 24 V (0 – 10 V) Ref. no. 08318 Page 101 AIR1-AAHA XH 1500/RH 1500


Ref. no. 06484 Page 111
Intake hood outside air
Cooling register
AIR1-AAHF XH 1500/RH 1500
AIR1-KR KW RH 1500 L (1) Ref. no. 06643 Page 112
Ref. no. 03958 Page 102 Discharge hood exhaust air
Cold water, external
AIR1-KR KW RH 1500 R (1) Controls
Ref. no. 04283 Page 102
Cold water, external
Controllers
AIR1-KR DX RH 1500 L (1)
Ref. no. 04416 Page 104 AIR1-BE ECO Ref. no. 06186 Page 113
Direct evaporator DX, external
AIR1-KR DX RH 1500 R (1) AIR1-BE TOUCH Ref. no. 06187 Page 113
Ref. no. 05001 Page 104
Direct evaporator DX, external Controller connection cable
AIR1-SL 4/10 10 m Ref. no. 07073 Page 113
Air routing
AIR1-SL 4/20 20 m Ref. no. 07121 Page 113
Multi-leaf damper
Sensors
AIR1-JVK XH 1500/RH 1500 Ref. no. 06006 Page 106
KWL-CO2 Carbon dioxide sensor Ref. no. 04272 Page 113
Flexible connector
KWL-FTF Humidity-temperature sensor Ref. no. 04273 Page 113
AIR1-VS 35/31 Ref. no. 04372 Page 107
KWL-VOC Mixed gas sensor Ref. no. 04274 Page 113
Adapter square-round
AIR1-CO2 K Carbon dioxide sensor duct Ref. no. 07124 Page 114
AIR1-ÜS XH 1500/RH 1500 Ref. no. 04367 Page 107
Signal converter for sensors
AIR1-SK Ref. no. 06019 Page 114
Extension kit for constant pressure control
AIR1-CAP Ref. no. 06756 Page 114

Air filters

Spare air filter and other filter classes


ELF-AIR1 RH 1500/ePM10 50%/48 (M5) Ref. no. 02192 Page 115
ELF-AIR1 RH 1500/ePM10 50%/96 (M5) Ref. no. 02211 Page 115
ELF-AIR1 RH 1500/ePM1 55%/96 (F7) Ref. no. 02236 Page 115
ELF-AIR1 RH 1500/ePM1 80%/96 (F9) Ref. no. 02374 Page 115

(1) = When looking at the cooling register from the air flow direction, The use of original spare air filters is mandatory to guarantee the specified
the service side is on the right for the R version and on the left for the L version technical data and air volumes.

Helios AIR1 Series RH 81


AIR1 RH 2000 Performance curve

Dpfa
Pa

V· m3/h

Fig. shows accessories

Unit types

AIR1 RH 2000 AIR1 RH 2000/SO


Ref. no. 04344 04353
Heat exchanger Condensation rotor Adsorption rotor (4)

Technical data Sound data AIR1 RH 2000

Mechanical data Sound power level LwA dB(A) at 250 Pa external pressure
Area of application Inside/outside 600 m³/h 1,500 m³/h 2,100 m³/h
Installation position Standing Supply air (LwA) 68 74 80
Maintenance access Side, both sides Extract air (LwA) 60 65 71
Min. air volume 150 m³/h Outside air (LwA) 57 61 67
Max. air volume 2100 m³/h (1) (2020 m³/h (5)) Exhaust air (LwA) 68 74 80
Weight, unit operational 361 kg (368 kg (5)) Sound pressure level LpA db(A) of sound radiated from housing
Delivery unit 1-part 600 m³/h 1,500 m³/h 2,100 m³/h
Unit segments 1 Housing rad. 1 m 43 45 52
Housing class (DIN 1886) T2 / TB2 / D1 Housing rad. 3 m 33 36 42
Filter Outside air ePM1 55% (F7) (2) Housing rad. 5 m 29 31 38
Filter Extract air ePM10 50% (M5) (2)
The sound power at the connectors is calculated for the simultaneous
Media temperature (air) -20 to +40 °C operation of both fans. The sound pressure level is determined for the
Ambient temperature (operation) 0 to +50 °C simultaneous operation of both fans at distances of 1, 3 and 5 m.

Protection class IP 31
Electrical data
Central building control system BACnet, Modbus TCP/IP Sound data AIR1 RH 2000/SO
Voltage / Frequency 400 V 3N ~, 50 Hz
Sound power level LwA dB(A) at 250 Pa external pressure
Max. output Fans 2 x 780 W
600 m³/h 1,500 m³/h 2,020 m³/h
Nominal current
Supply air (LwA) 69 74 79
– Ventilation unit 3.4 / 3.4 / 1.3 A
Extract air (LwA) 61 65 70
– Electrical auxiliary heater 8.4 / 8.4 / 8.4 A (3)
Outside air (LwA) 57 61 66
– max. total 11.8 / 11.8 / 9.7 A
Exhaust air (LwA) 69 74 79
Connection (wiring diagram no.) SS-1318
Sound pressure level LpA db(A) of sound radiated from housing
600 m³/h 1,500 m³/h 2,020 m³/h
(1) = at 250 Pa external pressure loss ERP-compliant
(2) = other filter classes see optional accessories Housing rad. 1 m 44 46 50
(3) = Optional accessories
Housing rad. 3 m 34 37 40
(4) = with increased humidity recovery
(5) = AIR RH 2000/SO Housing rad. 5 m 30 32 36

The sound power at the connectors is calculated for the simultaneous


operation of both fans. The sound pressure level is determined for the
simultaneous operation of both fans at distances of 1, 3 and 5 m.

82 Helios
338
310
ETA EHA

max. 1420
34

514,2
1090
G 1/2

M8
Dimensional drawing

389
SUP ODA

286,4
76
100

ODA - Outdoor Air / Außenluft / Air extérieur


View A (from above) View B
EHA - ExhaustODA
Air /- Outdoor Air /rejeté
Fortluft /Air Außenluft / Air extérieur View C
360 520 EHA
ETA - Extract Air - Exhaust
/ Abluft / AirAir / Fortluft /Air rejeté
repris 498
430

max. 80
ETA
SUP - Supply Air - Extract
/ Zuluft Airsoufflé
/ Air / Abluft / Air repris 498

150
145 A
SUP - Supply Air / Zuluft / Air soufflé 470

150
470

338
310
ETA EHA

338
310
EHA
C ETA
B

max. 1420
472

860

910

max. 1420
34

514,2
34

514,2
1090

1090
G 1/2 (1)
G 1/2 G 1/2

M8

M8
194

389
SUP ODA

389
SUP ODA

286,4

286,4
640 568

76

76
100

100
1700
360 360 520 520 430 430

max. 80

max. 80
B 145 145

Dim. in mm (1) External thread ODA: Outside air EHA: Exhaust air ETA: Extract air SUP: Supply air

472

860

910
472

860

910
Accessories
194
194

640 568
640 568
Heating and cooling registers External installation
1700
1700
Pre-heater Cover for external installation
AIR1-EVH RH 2000 AIR1-AAD RH 2000
Ref. no. 01710 Page 98 Ref. no. 06431 Page 108
Electrical, external Weather protection cover for the unit
Auxiliary heater AIR1-AAD KR KW + DX RH 2000
Weather protection cover for cooling Ref. no. 06468 Page 110
AIR1-ENH RH 2000
Ref. no. 03616 Page 99 register cold water or direct evaporator
Electrical, internal
Terminal box heater
AIR1-NH WW RH 2000
Ref. no. 03806 Page 100
Hot water, internal AIR1-AAHK Ref. no. 07064 Page 111

Hydraulic unit for hot water heater register Hoods

WHSH HE 24 V (0 – 10 V) Ref. no. 08318 Page 101 AIR1-AAHA XH 2500/RH 2000


Ref. no. 06539 Page 111
Intake hood outside air
Cooling register
AIR1-AAHF XH 2500/RH 2000
AIR1-KR KW RH 2000 L (1) Ref. no. 06646 Page 112
Ref. no. 03959 Page 102 Discharge hood exhaust air
Cold water, external
AIR1-KR KW RH 2000 R (1) Controls
Ref. no. 04285 Page 102
Cold water, external
Controllers
AIR1-KR DX RH 2000 L (1)
Ref. no. 04417 Page 104 AIR1-BE ECO Ref. no. 06186 Page 113
Direct evaporator DX, external
AIR1-KR DX RH 2000 R (1) AIR1-BE TOUCH Ref. no. 06187 Page 113
Ref. no. 05025 Page 104
Direct evaporator DX, external Controller connection cable
AIR1-SL 4/10 10 m Ref. no. 07073 Page 113
Air routing
AIR1-SL 4/20 20 m Ref. no. 07121 Page 113
Multi-leaf damper
Sensors
AIR1-JVK XH 2500/RH 2000 Ref. no. 06007 Page 106
KWL-CO2 Carbon dioxide sensor Ref. no. 04272 Page 113
Flexible connector
KWL-FTF Humidity-temperature sensor Ref. no. 04273 Page 113
AIR1-VS 47/31 Ref. no. 04373 Page 107
KWL-VOC Mixed gas sensor Ref. no. 04274 Page 113
Adapter square-round
AIR1-CO2 K Carbon dioxide sensor duct Ref. no. 07124 Page 114
AIR1-ÜS XH 2500/RH 2000 Ref. no. 04368 Page 107
Signal converter for sensors
AIR1-SK Ref. no. 06019 Page 114
Extension kit for constant pressure control
AIR1-CAP Ref. no. 06756 Page 114

Air filters

Spare air filter and other filter classes


ELF-AIR1 RH 2000/ePM10 50%/48 (M5) Ref. no. 02193 Page 115
ELF-AIR1 RH 2000/ePM10 50%/96 (M5) Ref. no. 02212 Page 115
ELF-AIR1 RH 2000/ePM1 55%/96 (F7) Ref. no. 02237 Page 115
ELF-AIR1 RH 2000/ePM1 80%/96 (F9) Ref. no. 02384 Page 115

(1) = When looking at the cooling register from the air flow direction, The use of original spare air filters is mandatory to guarantee the specified
the service side is on the right for the R version and on the left for the L version technical data and air volumes.

Helios AIR1 Series RH 83


AIR1 RH 3000 Performance curve

Dpfa
Pa

V· m3/h

Fig. shows accessories

Unit types

AIR1 RH 3000 AIR1 RH 3000/SO


Ref. no. 04345 04354
Heat exchanger Condensation rotor Adsorption rotor (4)

Technical data Sound data AIR1 RH 3000

Mechanical data Sound power level LwA dB(A) at 250 Pa external pressure
Area of application Inside/outside 900 m³/h 2,200 m³/h 3,000 m³/h
Installation position Standing Supply air (LwA) 79 82 82
Maintenance access Side, both sides Extract air (LwA) 71 74 74
Min. air volume 150 m³/h Outside air (LwA) 67 70 70
Max. air volume 3000 m³/h (1) (2770 m³/h (5)) Exhaust air (LwA) 79 82 82
Weight, unit operational 438 kg (450 kg (5)) Sound pressure level LpA db(A) of sound radiated from housing
Delivery unit 1-part 900 m³/h 2,200 m³/h 3,000 m³/h
Unit segments 1 Housing rad. 1 m 52 54 55
Housing class (DIN 1886) T2 / TB2 / D1 Housing rad. 3 m 42 44 45
Filter Outside air ePM1 55% (F7) (2) Housing rad. 5 m 38 40 41
Filter Extract air ePM10 50% (M5) (2)
The sound power at the connectors is calculated for the simultaneous
Media temperature (air) -20 to +50 °C operation of both fans. The sound pressure level is determined for the
Ambient temperature (operation) 0 to +50 °C simultaneous operation of both fans at distances of 1, 3 and 5 m.

Protection class IP 31
Electrical data
Central building control system BACnet, Modbus TCP/IP Sound data AIR1 RH 3000/SO
Voltage / Frequency 400 V 3N ~, 50 Hz
Sound power level LwA dB(A) at 250 Pa external pressure
Max. output Fans 2 x 1500 W 900 m³/h 2,200 m³/h 2,770 m³/h
Nominal current Supply air (LwA) 79 83 83
– Ventilation unit 4.6 / 4.6 / 5.8 A Extract air (LwA) 72 75 74
– Electrical auxiliary heater 13.1 / 13.1 / 13.1 A (3) Outside air (LwA) 68 71 70
– max. total 17.7 / 17.7 / 18.9 A Exhaust air (LwA) 79 83 82
Connection (wiring diagram no.) SS-1319
Sound pressure level LpA db(A) of sound radiated from housing
900 m³/h 2,200 m³/h 2,770 m³/h
(1) = at 250 Pa external pressure loss ERP-compliant
(2) = other filter classes see optional accessories Housing rad. 1 m 52 55 54
(3) = Optional accessories Housing rad. 3 m 43 46 45
(4) = with increased humidity recovery
(5) = AIR RH 3000/SO Housing rad. 5 m 38 41 40

The sound power at the connectors is calculated for the simultaneous


operation of both fans. The sound pressure level is determined for the
simultaneous operation of both fans at distances of 1, 3 and 5 m.

84 Helios
438
410
ETA EHA

max. 1530
34

1200
600
G 1/2
Dimensional drawing

M8
439
SUP ODA

300
View A (from above) View B
ODA - Outdoor Air / Außenluft / Air extérieur View C
76

ODA - Outdoor
EHA - Exhaust Air / Außenluft
Air / Fortluft /Air rejeté/ Air extérieur 608
100

EHA -Air
ETA - Extract Exhaust Air/ /Air
/ Abluft Fortluft
repris/Air rejeté 608
580

150
ETA - Air
SUP - Supply Extract Air // Abluft
/ Zuluft / Air repris
Air soufflé
360 520 A 580

150
485 SUP - Supply Air / Zuluft / Air soufflé

max. 80
145

438
410
ETA EHA

438
410
ETA EHA

max. 1530
C 34

max. 1530

1200
600
1020
34
472

970

1200
600
G 1/2 (1)
G 1/2
G 1/2

M8

M8
439
SUP ODA

439
SUP ODA
249

300

300
76

76
655 568

100

100
1700 360 520 485

max. 80
360 520 485

max. 80
145
145
B
Dim. in mm (1) External thread ODA: Outside air EHA: Exhaust air ETA: Extract air SUP: Supply air

1020
Accessories
472

970

1020
472

970
249

249

Heating and cooling registers External installation


655 568
655
Pre-heater Cover568
1700
for external installation
1700
AIR1-EVH RH 3000 AIR1-AAD RH 3000
Ref. no. 01711 Page 98 Ref. no. 06432 Page 108
Electrical, external Weather protection cover for the unit
Auxiliary heater AIR1-AAD KR KW + DX RH 3000
Weather protection cover for cooling Ref. no. 06469 Page 110
AIR1-ENH RH 3000
Ref. no. 03617 Page 99 register cold water or direct evaporator
Electrical, internal
Terminal box heater
AIR1-NH WW RH 3000
Ref. no. 03824 Page 100
Hot water, internal AIR1-AAHK Ref. no. 07064 Page 111

Hydraulic unit for hot water heater register Hoods

WHSH HE 24 V (0 – 10 V) Ref. no. 08318 Page 101 AIR1-AAHA XH 3500-4500/RH 3000


Ref. no. 06487 Page 111
Intake hood outside air
Cooling register
AIR1-AAHF XH 3500-4500/RH 3000
AIR1-KR KW RH 3000 L (1) Ref. no. 06647 Page 112
Ref. no. 03967 Page 102 Discharge hood exhaust air
Cold water, external
AIR1-KR KW RH 3000 R (1) Controls
Ref. no. 04286 Page 102
Cold water, external
Controllers
AIR1-KR DX RH 3000 L (1)
Ref. no. 04422 Page 104 AIR1-BE ECO Ref. no. 06186 Page 113
Direct evaporator DX, external
AIR1-KR DX RH 3000 R (1) AIR1-BE TOUCH Ref. no. 06187 Page 113
Ref. no. 05028 Page 104
Direct evaporator DX, external Controller connection cable
AIR1-SL 4/10 10 m Ref. no. 07073 Page 113
Air routing
AIR1-SL 4/20 20 m Ref. no. 07121 Page 113
Multi-leaf damper
Sensors
AIR1-JVK XH 3500-4500/RH 3000 Ref. no. 06009 Page 106
KWL-CO2 Carbon dioxide sensor Ref. no. 04272 Page 113
Flexible connector
KWL-FTF Humidity-temperature sensor Ref. no. 04273 Page 113
AIR1-VS 58/41 Ref. no. 04374 Page 107
KWL-VOC Mixed gas sensor Ref. no. 04274 Page 113
Adapter square-round
AIR1-CO2 K Carbon dioxide sensor duct Ref. no. 07124 Page 114
AIR1-ÜS XH 3500-4500/RH 3000 Ref. no. 04369 Page 107
Signal converter for sensors
AIR1-SK Ref. no. 06019 Page 114
Extension kit for constant pressure control
AIR1-CAP Ref. no. 06756 Page 114

Air filters

Spare air filter and other filter classes


ELF-AIR1 RH 3000/ePM10 50%/48 (M5) Ref. no. 02194 Page 115
ELF-AIR1 RH 3000/ePM10 50%/96 (M5) Ref. no. 02213 Page 115
ELF-AIR1 RH 3000/ePM1 55%/96 (F7) Ref. no. 02238 Page 115
ELF-AIR1 RH 3000/ePM1 80%/96 (F9) Ref. no. 02425 Page 115

(1) = When looking at the cooling register from the air flow direction, The use of original spare air filters is mandatory to guarantee the specified
the service side is on the right for the R version and on the left for the L version technical data and air volumes.

Helios AIR1 Series RH 85


AIR1 RH 5000 Performance curve

Dpfa
Pa

V· m3/h

Fig. shows accessories

Unit types

AIR1 RH 5000 AIR1 RH 5000/SO


Ref. no. 04346 04355
Heat exchanger Condensation rotor Adsorption rotor (3)

Technical data Sound data AIR1 RH 5000

Mechanical data Sound power level LwA dB(A) at 400 Pa external pressure
Area of application Inside/outside 1,500 m³/h 3,700 m³/h 5,150 m³/h
Installation position Standing Supply air (LwA) 75 80 86
Maintenance access Side, both sides Extract air (LwA) 66 70 76
Min. air volume 150 m³/h Outside air (LwA) 62 66 72
Max. air volume 5150 m³/h (1) (4950 m³/h (4)) Exhaust air (LwA) 75 80 86
Weight, unit operational 629 kg (645 kg (4)) Sound pressure level LpA db(A) of sound radiated from housing
Delivery unit 2-part 1,500 m³/h 3,700 m³/h 5,150 m³/h
Unit segments 2 Housing rad. 1 m 48 52 57
Housing class (DIN 1886) T2 / TB2 / D1 Housing rad. 3 m 39 43 48
Filter Outside air ePM1 55% (F7) (2) Housing rad. 5 m 34 38 43
Filter Extract air ePM10 50% (M5) (2)
The sound power at the connectors is calculated for the simultaneous
Media temperature (air) -20 to +50 °C operation of both fans. The sound pressure level is determined for the
Ambient temperature (operation) 0 to +50 °C simultaneous operation of both fans at distances of 1, 3 and 5 m.

Protection class IP 31
Electrical data
Central building control system BACnet, Modbus TCP/IP Sound data AIR1 RH 5000/SO
Voltage / Frequency 400 V 3N ~, 50 Hz
Sound power level LwA dB(A) at 400 Pa external pressure
Max. output Fans 2 x 2500 W
1,500 m³/h 3,700 m³/h 4,950 m³/h
Nominal current 7.6 / 7.6 / 8.9 A (7.6 / 7.6 / 9.5 A (4))
Supply air (LwA) 75 80 85
Connection (wiring diagram no.) SS-1320
Extract air (LwA) 67 71 75
Outside air (LwA) 63 67 71
(1) = at 400 Pa external pressure loss ERP-compliant
(2) = other filter classes see optional accessories Exhaust air (LwA) 75 80 85
(3) = with increased humidity recovery
Sound pressure level LpA db(A) of sound radiated from housing
(4) = AIR RH 5000/SO
1,500 m³/h 3,700 m³/h 4,950 m³/h
Housing rad. 1 m 49 52 57
Housing rad. 3 m 39 43 47
Housing rad. 5 m 35 38 43

The sound power at the connectors is calculated for the simultaneous


operation of both fans. The sound pressure level is determined for the
simultaneous operation of both fans at distances of 1, 3 and 5 m.

86 Helios
438
410
ETA EHA

max. 1800

725
1470
~1500
Dimensional drawing

M8
498
SUP ODA

372,5
100
ODA - Outdoor Air ODA
/ Außenluft
- Outdoor/ Air
Airextérieur
/ Außenluft / Air extérieur
View A (from above) View B
EHA - Exhaust AirEHA
/ Fortluft /Air rejeté
- Exhaust Air / Fortluft /Air rejeté View C
555 690 ETA - Extract Air /ETA
Abluft / Air repris
- Extract Air / Abluft / Air repris

max. 80
620 SUP - Supply Air /SUP
Zuluft / Air soufflé
- Supply Air / Zuluft / Air soufflé
883 883
A

150

150
855 106
855 106
610 1235

438

438
410

410
ETA ETA EHA EHA

1240
1290
472

max. 1800

max. 1800

725

725
1470

1470
~1500

~1500
384

M8

M8
498

498
SUP SUP ODA ODA

372,5

372,5
40 568

100

100
1845
555 555 690 690

max. 80

max. 80
620 620

B
610 610 1235 1235

Dim. in mm ODA: Outside air EHA: Exhaust air ETA: Extract air SUP: Supply air

1240
1290

1240
1290
472

472
Accessories
384

384

Heating and cooling registers External installation


40 568 40 568
Pre-heater 1845 Cover for external installation
1845

AIR1-EVH RH 5000 AIR1-AAD RH 5000


Ref. no. 01791 Page 98 Ref. no. 06433 Page 108
Electrical, external Weather protection cover for the unit
Auxiliary heater AIR1-AAD RH 5000/ULM
Weather protection cover for the unit incl. Ref. no. 06439 Page 109
AIR1-ENH RH 5000
Ref. no. 03618 Page 99 recirculation module
Electrical, external
AIR1-AAD KR KW + DX RH 5000
AIR1-NH WW RH 5000
Ref. no. 03825 Page 100 Weather protection cover for cooling Ref. no. 06470 Page 110
Hot water, external
register cold water or direct evaporator
Hydraulic unit for hot water heater register
AIR1-AAD NH EL + WW RH 5000
Ref. no. 06445 Page 110
WHSH HE 24 V (0 – 10 V) M Ref. no. 06310 Page 101 Weather protection cover for aux. heater
Cooling register Terminal box heater
AIR1-KR KW RH 5000 L (1) AIR1-AAHK Ref. no. 07064 Page 111
Ref. no. 03971 Page 102
Cold water, external
Hoods
AIR1-KR KW RH 5000 R (1)
Ref. no. 04287 Page 102 AIR1-AAHA XH 5500/RH 5000-6000
Cold water, external Ref. no. 06496 Page 111
Intake hood outside air
AIR1-KR DX RH 5000 L (1)
Ref. no. 04424 Page 104 AIR1-AAHF XH 5500/RH 5000-6000
Direct evaporator DX, external Ref. no. 06648 Page 112
Discharge hood exhaust air
AIR1-KR DX RH 5000 R (1)
Ref. no. 05046 Page 104
Direct evaporator DX, external Controls

Air routing Controllers


AIR1-BE ECO Ref. no. 06186 Page 113
Multi-leaf damper
AIR1-BE TOUCH Ref. no. 06187 Page 113
AIR1-JVK XH 5500/RH 5000-6000 Ref. no. 06010 Page 106
Controller connection cable
Recirculation module
AIR1-SL 4/10 10 m Ref. no. 07073 Page 113
AIR1-ULM RH 5000 Ref. no. 06040 Page 106
AIR1-SL 4/20 20 m Ref. no. 07121 Page 113
Flexible connector
Sensors
AIR1-VS 85/41 Ref. no. 04375 Page 107
KWL-CO2 Carbon dioxide sensor Ref. no. 04272 Page 113
Adapter square-round
KWL-FTF Humidity-temperature sensor Ref. no. 04273 Page 113
AIR1-ÜS XH 5500/RH 5000-6000 Ref. no. 04370 Page 107
KWL-VOC Mixed gas sensor Ref. no. 04274 Page 113
Air filters
AIR1-CO2 K Carbon dioxide sensor duct Ref. no. 07124 Page 114
Spare air filter and other filter classes Signal converter for sensors
ELF-AIR1 RH 5000/ePM10 50%/48 (M5) Ref. no. 02196 Page 115 AIR1-SK Ref. no. 06019 Page 114
ELF-AIR1 RH 5000/ePM10 50%/96 (M5) Ref. no. 02214 Page 115 Extension kit for constant pressure control
ELF-AIR1 RH 5000/ePM1 55%/96 (F7) Ref. no. 02239 Page 115 AIR1-CAP Ref. no. 06756 Page 114
ELF-AIR1 RH 5000/ePM1 80%/96 (F9) Ref. no. 02446 Page 115

The use of original spare air filters is mandatory to guarantee the specified
technical data and air volumes.

(1) = When looking at the cooling register from the air flow direction,
the service side is on the right for the R version and on the left for the L version

Helios AIR1 Series RH 87


AIR1 RH 6000 Performance curve

Dpfa
Pa

V· m3/h

Fig. shows accessories

Unit types

AIR1 RH 6000 AIR1 RH 6000/SO


Ref. no. 04347 04356
Heat exchanger Condensation rotor Adsorption rotor (3)

Technical data Sound data AIR1 RH 6000

Mechanical data Sound power level LwA dB(A) at 400 Pa external pressure
Area of application Inside/outside 1,900 m³/h 4,400 m³/h 6,200 m³/h
Installation position Standing Supply air (LwA) 76 79 86
Maintenance access Side, both sides Extract air (LwA) 67 70 77
Min. air volume 150 m³/h Outside air (LwA) 63 66 73
Max. air volume 6200 m³/h (1) (5950 m³/h (4)) Exhaust air (LwA) 76 79 85
Weight, unit operational 775 kg (787 kg (4)) Sound pressure level LpA db(A) of sound radiated from housing
Delivery unit 2-part 1,900 m³/h 4,400 m³/h 6,200 m³/h
Unit segments 2 Housing rad. 1 m 49 51 59
Housing class (DIN 1886) T2 / TB2 / D1 Housing rad. 3 m 39 42 49
Filter Outside air ePM1 55% (F7) (2) Housing rad. 5 m 35 37 45
Filter Extract air ePM10 50% (M5) (2)
The sound power at the connectors is calculated for the simultaneous
Media temperature (air) -20 to +40 °C operation of both fans. The sound pressure level is determined for the
Ambient temperature (operation) 0 to +50 °C simultaneous operation of both fans at distances of 1, 3 and 5 m.

Protection class IP 31
Electrical data
Central building control system BACnet, Modbus TCP/IP Sound data AIR1 RH 6000/SO
Voltage / Frequency 400 V 3N ~, 50 Hz
Sound power level LwA dB(A) at 400 Pa external pressure
Max. output Fans 2 x 2400 W
1,900 m³/h 4,400 m³/h 5,950 m³/h
Nominal current 7.3 / 7.3 / 8.8 A (7.3 / 7.3 / 9.3 A (4))
Supply air (LwA) 76 79 85
Connection (wiring diagram no.) SS-1321
Extract air (LwA) 67 70 76
Outside air (LwA) 63 66 72
(1) = at 400 Pa external pressure loss ERP-compliant
(2) = other filter classes see optional accessories Exhaust air (LwA) 76 79 85
(3) = with increased humidity recovery
Sound pressure level LpA db(A) of sound radiated from housing
(4) = AIR RH 6000/SO
1,900 m³/h 4,400 m³/h 5,950 m³/h
Housing rad. 1 m 49 52 58
Housing rad. 3 m 40 42 48
Housing rad. 5 m 35 38 44

The sound power at the connectors is calculated for the simultaneous


operation of both fans. The sound pressure level is determined for the
simultaneous operation of both fans at distances of 1, 3 and 5 m.

88 Helios
438
410
ETA EHA

max. 1920

1590
785
~1500
Dimensional drawing

M8
498
SUP ODA

402,5
View A (from above) View B
ODA - Outdoor Air /ODA
Außenluft / AirAir
- Outdoor extérieur
/ Außenluft / Air extérieur View C
100

EHA - Exhaust Air /EHA


Fortluft /Air rejeté
- Exhaust Air / Fortluft /Air rejeté
ETA - Extract Air / Abluft / Air repris
ETA - Extract Air / Abluft / Air repris
625 748 680 SUP - Supply Air / Zuluft / Air soufflé 883 883

max. 80
SUP - Supply Air / Zuluft / Air soufflé
A

150

150
855 106
855 106

680 1335

438
410

438
410
ETA ETA EHA EHA
B
C

max. 1920

max. 1920
1360

1410

1590

1590
472

785

785
~1500

~1500

M8

M8
498

498
SUP ODA
444

SUP ODA

402,5

402,5
100

100
100 568
2015 625 625 748 748 680 680

max. 80

max. 80
B
680 680 1335 1335
Dim. in mm ODA: Outside air EHA: Exhaust air ETA: Extract air SUP: Supply air

Accessories

1360

1410

1360

1410
472

472
444

444

Heating and cooling registers External installation

Pre-heater Cover for external installation


100 568100 568
AIR1-EVH RH 6000 2015 AIR1-AAD
2015 RH 6000
Ref. no. 01792 Page 98 Ref. no. 06434 Page 108
Electrical, external Weather protection cover for the unit
Auxiliary heater AIR1-AAD RH 6000/ULM
Weather protection cover for the unit incl. Ref. no. 06440 Page 109
AIR1-ENH RH 6000
Ref. no. 03625 Page 99 recirculation module
Electrical, external
AIR1-AAD KR KW + DX RH 6000
AIR1-NH WW RH 6000
Ref. no. 03826 Page 100 Weather protection cover for cooling Ref. no. 06471 Page 110
Hot water, external
register cold water or direct evaporator
Hydraulic unit for hot water heater register
AIR1-AAD NH EL + WW RH 6000
Ref. no. 06446 Page 110
WHSH HE 24 V (0 – 10 V) M Ref. no. 06310 Page 101 Weather protection cover for aux. heater
Cooling register Terminal box heater
AIR1-KR KW RH 6000 L (1) AIR1-AAHK Ref. no. 07064 Page 111
Ref. no. 03976 Page 102
Cold water, external
Hoods
AIR1-KR KW RH 6000 R (1)
Ref. no. 04288 Page 102 AIR1-AAHA XH 5500/RH 5000-6000
Cold water, external Ref. no. 06496 Page 111
Intake hood outside air
AIR1-KR DX RH 6000 L (1)
Ref. no. 04425 Page 104 AIR1-AAHF XH 5500/RH 5000-6000
Direct evaporator DX, external Ref. no. 06648 Page 112
Discharge hood exhaust air
AIR1-KR DX RH 6000 R (1)
Ref. no. 05239 Page 104
Direct evaporator DX, external Controls

Air routing Controllers


AIR1-BE ECO Ref. no. 06186 Page 113
Multi-leaf damper
AIR1-BE TOUCH Ref. no. 06187 Page 113
AIR1-JVK XH 5500/RH 5000-6000 Ref. no. 06010 Page 106
Controller connection cable
Recirculation module
AIR1-SL 4/10 10 m Ref. no. 07073 Page 113
AIR1-ULM RH 6000 Ref. no. 06160 Page 106
AIR1-SL 4/20 20 m Ref. no. 07121 Page 113
Flexible connector
Sensors
AIR1-VS 85/41 Ref. no. 04375 Page 107
KWL-CO2 Carbon dioxide sensor Ref. no. 04272 Page 113
Adapter square-round
KWL-FTF Humidity-temperature sensor Ref. no. 04273 Page 113
AIR1-ÜS XH 5500/RH 5000-6000 Ref. no. 04370 Page 107
KWL-VOC Mixed gas sensor Ref. no. 04274 Page 113
Air filters
AIR1-CO2 K Carbon dioxide sensor duct Ref. no. 07124 Page 114
Spare air filter and other filter classes Signal converter for sensors
ELF-AIR1 RH 6000/ePM10 50%/48 (M5) Ref. no. 02220 Page 115 AIR1-SK Ref. no. 06019 Page 114
ELF-AIR1 RH 6000/ePM10 50%/96 (M5) Ref. no. 02215 Page 115 Extension kit for constant pressure control
ELF-AIR1 RH 6000/ePM1 55%/96 (F7) Ref. no. 02240 Page 115 AIR1-CAP Ref. no. 06756 Page 114
ELF-AIR1 RH 6000/ePM1 80%/96 (F9) Ref. no. 02451 Page 115

The use of original spare air filters is mandatory to guarantee the specified
technical data and air volumes.

(1) = When looking at the cooling register from the air flow direction,
the service side is on the right for the R version and on the left for the L version

Helios AIR1 Series RH 89


AIR1 RH 8000 Performance curve

Dpfa
Pa

V· m3/h

Fig. shows accessories

Unit types

AIR1 RH 8000 AIR1 RH 8000/SO


Ref. no. 04348 04357
Heat exchanger Condensation rotor Adsorption rotor (3)

Technical data Sound data AIR1 RH 8000

Mechanical data Sound power level LwA dB(A) at 400 Pa external pressure
Area of application Inside/outside 2,400 m³/h 5,800 m³/h 8,000 m³/h
Installation position Standing Supply air (LwA) 77 83 90
Maintenance access Side, both sides Extract air (LwA) 67 72 79
Min. air volume 150 m³/h Outside air (LwA) 63 69 75
Max. air volume 8000 m³/h (1) (7650 m³/h (4)) Exhaust air (LwA) 77 83 90
Weight, unit operational 888 kg (905 kg (4)) Sound pressure level LpA db(A) of sound radiated from housing
Delivery unit 2-part 2,400 m³/h 5,800 m³/h 8,000 m³/h
Unit segments 2 Housing rad. 1 m 49 55 61
Housing class (DIN 1886) T2 / TB2 / D1 Housing rad. 3 m 40 46 51
Filter Outside air ePM1 55% (F7) (2) Housing rad. 5 m 35 41 47
Filter Extract air ePM10 50% (M5) (2)
The sound power at the connectors is calculated for the simultaneous
Media temperature (air) -20 to +50 °C operation of both fans. The sound pressure level is determined for the
Ambient temperature (operation) 0 to +50 °C simultaneous operation of both fans at distances of 1, 3 and 5 m.

Protection class IP 31
Electrical data
Central building control system BACnet, Modbus TCP/IP Sound data AIR1 RH 8000/SO
Voltage / Frequency 400 V 3N ~, 50 Hz
Sound power level LwA dB(A) at 400 Pa external pressure
Max. output Fans 2 x 3600 W
2,400 m³/h 5,800 m³/h 7,650 m³/h
Nominal current 11 / 11 / 12.4 A (11 / 11 / 14.1 A (4))
Supply air (LwA) 77 84 89
Connection (wiring diagram no.) SS-1322
Extract air (LwA) 67 72 80
Outside air (LwA) 63 69 76
(1) = at 400 Pa external pressure loss ERP-compliant
(2) = other filter classes see optional accessories Exhaust air (LwA) 77 84 89
(3) = with increased humidity recovery
Sound pressure level LpA db(A) of sound radiated from housing
(4) = AIR RH 8000/SO
2,400 m³/h 5,800 m³/h 7,650 m³/h
Housing rad. 1 m 50 55 62
Housing rad. 3 m 40 46 52
Housing rad. 5 m 36 41 48

The sound power at the connectors is calculated for the simultaneous


operation of both fans. The sound pressure level is determined for the
simultaneous operation of both fans at distances of 1, 3 and 5 m.

90 Helios
438
410
ETA EHA

max. 2170

1840
910
361,1

~1500

M8
498
SUP
Dimensional drawing ODA

465
ODA - Outdoor Air / Außenluft / Air extérieur
ODA - Outdoor Air / Außenluft / Air extérieur
EHA - Exhaust Air / Fortluft /Air rejeté
View A (from above) View B View C
100

EHA - Exhaust Air / Fortluft /Air rejeté


ETA - Extract Air / Abluft / Air repris
ETA - Extract Air / Abluft / Air repris
SUP - Supply Air / Zuluft / Air soufflé
714 755 SUP - Supply Air / Zuluft / Air soufflé 1083

max. 80
805 1083

150
A 1055 106

150
770 1415 1055 106

438
410
ETA EHA

438
410
ETA EHA

C B

1610
1660

max. 2170
472

1840
910
max. 2170

1840
910
361,1
361,1

~1500

~1500

M8
498
569

SUP ODA

M8
498
SUP ODA

465

465
100
85 568

100
2185 714 755

max. 80
714 755 805

max. 80
805
770 1415
B 770 1415
Dim. in mm ODA: Outside air EHA: Exhaust air ETA: Extract air SUP: Supply air

Accessories

1610
1660
472

1610
1660
472

Heating and cooling registers External installation


569

569

Pre-heater Cover for external installation


AIR1-EVH RH 8000 AIR1-AAD RH 8000
Ref. no. 01819 Page 98 85 85
568
568 Ref. no. 06435 Page 108
Electrical, external Weather
2185
2185
protection cover for the unit
Auxiliary heater AIR1-AAD RH 8000/ULM
Weather protection cover for the unit incl. Ref. no. 06441 Page 109
AIR1-ENH RH 8000
Ref. no. 03626 Page 99 recirculation module
Electrical, external
AIR1-AAD KR KW + DX RH 8000
AIR1-NH WW RH 8000
Ref. no. 03827 Page 100 Weather protection cover for cooling Ref. no. 06472 Page 110
Hot water, external
register cold water or direct evaporator
Hydraulic unit for hot water heater register
AIR1-AAD NH EL + WW RH 8000
Ref. no. 06310 Page 101 Ref. no. 06447 Page 110
WHSH HE 24 V (0 – 10 V) M Weather protection cover for aux. heater
Cooling register Terminal box heater
AIR1-KR KW RH 8000 L (1) AIR1-AAHK Ref. no. 07064 Page 111
Ref. no. 03983 Page 102
Cold water, external
Hoods
AIR1-KR KW RH 8000 R (1)
Ref. no. 04382 Page 102 AIR1-AAHA XH 7000/RH 8000
Cold water, external Ref. no. 06497 Page 111
Intake hood outside air
AIR1-KR DX RH 8000 L (1)
Ref. no. 04426 Page 104 AIR1-AAHF XH 7000/RH 8000
Direct evaporator DX, external Ref. no. 06841 Page 112
Discharge hood exhaust air
AIR1-KR DX RH 8000 R (1)
Ref. no. 05240 Page 104
Direct evaporator DX, external Controls

Air routing Controllers


AIR1-BE ECO Ref. no. 06186 Page 113
Multi-leaf damper
AIR1-BE TOUCH Ref. no. 06187 Page 113
AIR1-JVK XH 7000/RH 8000 Ref. no. 06012 Page 106
Controller connection cable
Recirculation module
AIR1-SL 4/10 10 m Ref. no. 07073 Page 113
AIR1-ULM RH 8000 Ref. no. 06184 Page 106
AIR1-SL 4/20 20 m Ref. no. 07121 Page 113
Flexible connector
Sensors
AIR1-VS 105/41 Ref. no. 04376 Page 107
KWL-CO2 Carbon dioxide sensor Ref. no. 04272 Page 113
Air filters
KWL-FTF Humidity-temperature sensor Ref. no. 04273 Page 113
Spare air filter and other filter classes KWL-VOC Mixed gas sensor Ref. no. 04274 Page 113
ELF-AIR1 RH 8000/ePM10 50%/48 (M5) Ref. no. 02199 Page 115 AIR1-CO2 K Carbon dioxide sensor duct Ref. no. 07124 Page 114
ELF-AIR1 RH 8000/ePM10 50%/96 (M5) Ref. no. 02216 Page 115 Signal converter for sensors
ELF-AIR1 RH 8000/ePM1 55%/96 (F7) Ref. no. 02241 Page 115 AIR1-SK Ref. no. 06019 Page 114
ELF-AIR1 RH 8000/ePM1 80%/96 (F9) Ref. no. 02460 Page 115 Extension kit for constant pressure control

The use of original spare air filters is mandatory to guarantee the specified AIR1-CAP Ref. no. 06756 Page 114
technical data and air volumes.

(1) = When looking at the cooling register from the air flow direction,
the service side is on the right for the R version and on the left for the L version

Helios AIR1 Series RH 91


AIR1 RH 9500 Performance curve

Dpfa
Pa

V· m3/h

Fig. shows accessories

Unit types

AIR1 RH 9500 AIR1 RH 9500/SO


Ref. no. 04349 04358
Heat exchanger Condensation rotor Adsorption rotor (3)

Technical data Sound data AIR1 RH 9500

Mechanical data Sound power level LwA dB(A) at 400 Pa external pressure
Area of application Inside/outside 2,900 m³/h 7,000 m³/h 9,700 m³/h
Installation position Standing Supply air (LwA) 77 81 88
Maintenance access Side, both sides Extract air (LwA) 68 72 79
Min. air volume 150 m³/h Outside air (LwA) 64 68 75
Max. air volume 9700 m³/h (1) (9400 m³/h (4)) Exhaust air (LwA) 77 81 88
Weight, unit operational 1090 kg (1111 kg (4)) Sound pressure level LpA db(A) of sound radiated from housing
Delivery unit 2-part 2,900 m³/h 7,000 m³/h 9,700 m³/h
Unit segments 2 Housing rad. 1 m 50 54 61
Housing class (DIN 1886) T2 / TB2 / D1 Housing rad. 3 m 40 45 52
Filter Outside air ePM1 55% (F7) (2) Housing rad. 5 m 36 40 47
Filter Extract air ePM10 50% (M5) (2)
The sound power at the connectors is calculated for the simultaneous
Media temperature (air) -20 to +50 °C operation of both fans. The sound pressure level is determined for the
Ambient temperature (operation) 0 to +50 °C simultaneous operation of both fans at distances of 1, 3 and 5 m.

Protection class IP 31
Electrical data
Central building control system BACnet, Modbus TCP/IP Sound data AIR1 RH 9500/SO
Voltage / Frequency 400 V 3N ~, 50 Hz
Sound power level LwA dB(A) at 400 Pa external pressure
Max. output Fans 2 x 3500 W
2,900 m³/h 7,000 m³/h 9,400 m³/h
Nominal current 10.7 / 10.7 / 12.7 A (10.7 / 10.7 / 13.8 A (4))
Supply air (LwA) 77 82 88
Connection (wiring diagram no.) SS-1323 Extract air (LwA) 69 72 78
Outside air (LwA) 65 68 74
(1) = at 400 Pa external pressure loss ERP-compliant
(2) = other filter classes see optional accessories Exhaust air (LwA) 77 82 88
(3) = with increased humidity recovery
Sound pressure level LpA db(A) of sound radiated from housing
(4) = AIR RH 9500/SO
2,900 m³/h 7,000 m³/h 9,400 m³/h
Housing rad. 1 m 50 55 61
Housing rad. 3 m 41 45 51
Housing rad. 5 m 36 41 47

The sound power at the connectors is calculated for the simultaneous


operation of both fans. The sound pressure level is determined for the
simultaneous operation of both fans at distances of 1, 3 and 5 m.

92 Helios
438
410
ETA EHA

max. 2270

960
409,4

1940
~1500

M8
498
SUP ODA
Dimensional drawing

490,5
100

ODA - Outdoor
ODAAir-/Outdoor
Außenluft
Air // Air extérieur
Außenluft / Air extérieur
View A (from above) View B
EHA - Exhaust
EHAAir- /Exhaust
FortluftAir
/Air rejeté /Air rejeté
/ Fortluft View C

max. 80
775 775 855 ETA - ExtractETA
Air / Abluft /Air
- Extract Air/repris
Abluft / Air repris
SUP - SupplySUP
Air /- Supply
Zuluft /Air
Air/soufflé
Zuluft / Air soufflé 1228 1228
A

150

150
1200 1200 106 106
830 1485

438
410

438
410
ETA ETA EHA EHA

max. 2270
B

max. 2270
1710

1760
472

960

960
409,4 409,4

1940

1940
~1500

~1500
619

M8

M8
498

498
SUP SUP ODA ODA

490,5

490,5
100

100
100 568
2315

max. 80

max. 80
775 775 775 775 855 855
B
830 830 1485 1485
Dim. in mm ODA: Outside air EHA: Exhaust air ETA: Extract air SUP: Supply air

Accessories

1710

1760

1710

1760
472

472

Heating and cooling registers External installation


619

619

Pre-heater Cover for external installation


100 568
100 568
AIR1-EVH RH 9500 AIR1-AAD RH 9500
Ref. no. 01830 Page 98 2315 2315 Ref. no. 06436 Page 108
Electrical, external Weather protection cover for the unit
Auxiliary heater AIR1-AAD RH 9500/ULM
Weather protection cover for the unit incl. Ref. no. 06442 Page 109
AIR1-ENH RH 9500
Ref. no. 03627 Page 99 recirculation module
Electrical, external
AIR1-AAD KR KW + DX RH 9500
AIR1-NH WW RH 9500
Ref. no. 03830 Page 100 Weather protection cover for cooling Ref. no. 06473 Page 110
Hot water, external
register cold water or direct evaporator
Hydraulic unit for hot water heater register
AIR1-AAD NH EL + WW RH 9500
Ref. no. 06448 Page 110
WHSH HE 24 V (0 – 10 V) L Ref. no. 06311 Page 101 Weather protection cover for aux. heater
Cooling register Terminal box heater
AIR1-KR KW RH 9500 L (1) AIR1-AAHK Ref. no. 07064 Page 111
Ref. no. 03984 Page 102
Cold water, external
Hoods
AIR1-KR KW RH 9500 R (1)
Ref. no. 04383 Page 102 AIR1-AAHA XH 8500/RH 9500
Cold water, external Ref. no. 06499 Page 111
Intake hood outside air
AIR1-KR DX RH 9500 L (1)
Ref. no. 04864 Page 104 AIR1-AAHF XH 8500/RH 9500
Direct evaporator DX, external Ref. no. 06864 Page 112
Discharge hood exhaust air
AIR1-KR DX RH 9500 R (1)
Ref. no. 05280 Page 104
Direct evaporator DX, external Controls

Air routing Controllers


AIR1-BE ECO Ref. no. 06186 Page 113
Multi-leaf damper
AIR1-BE TOUCH Ref. no. 06187 Page 113
AIR1-JVK XH 8500/RH 9500 Ref. no. 06013 Page 106
Controller connection cable
Recirculation module
AIR1-SL 4/10 10 m Ref. no. 07073 Page 113
AIR1-ULM RH 9500 Ref. no. 06185 Page 106
AIR1-SL 4/20 20 m Ref. no. 07121 Page 113
Flexible connector
Sensors
AIR1-VS 120/41 Ref. no. 04377 Page 107
KWL-CO2 Carbon dioxide sensor Ref. no. 04272 Page 113
Air filters
KWL-FTF Humidity-temperature sensor Ref. no. 04273 Page 113
Spare air filter and other filter classes KWL-VOC Mixed gas sensor Ref. no. 04274 Page 113
ELF-AIR1 RH 9500/ePM10 50%/48 (M5) Ref. no. 02200 Page 115 AIR1-CO2 K Carbon dioxide sensor duct Ref. no. 07124 Page 114
ELF-AIR1 RH 9500/ePM10 50%/96 (M5) Ref. no. 02217 Page 115 Signal converter for sensors
ELF-AIR1 RH 9500/ePM1 55%/96 (F7) Ref. no. 02261 Page 115 AIR1-SK Ref. no. 06019 Page 114
ELF-AIR1 RH 9500/ePM1 80%/96 (F9) Ref. no. 02463 Page 115 Extension kit for constant pressure control

The use of original spare air filters is mandatory to guarantee the specified AIR1-CAP Ref. no. 06756 Page 114
technical data and air volumes.

(1) = When looking at the cooling register from the air flow direction,
the service side is on the right for the R version and on the left for the L version

Helios AIR1 Series RH 93


AIR1 RH 12000 Performance curve

Dpfa
Pa

V· m3/h

Fig. shows accessories

Unit types

AIR1 RH 12000 AIR1 RH 12000/SO


Ref. no. 04350 04359
Heat exchanger Condensation rotor Adsorption rotor (3)

Technical data Sound data AIR1 RH 12000

Mechanical data Sound power level LwA dB(A) at 400 Pa external pressure
Area of application Inside/outside 4,000 m³/h 9,500 m³/h 13,300 m³/h
Installation position Standing Supply air (LwA) 77 82 89
Maintenance access Side, both sides Extract air (LwA) 69 74 81
Min. air volume 150 m³/h Outside air (LwA) 65 70 77
Max. air volume 13300 m³/h (1) (12800 m³/h (4)) Exhaust air (LwA) 77 82 89
Weight, unit operational 1190 kg (1215 kg (4)) Sound pressure level LpA db(A) of sound radiated from housing
Delivery unit 2-part 4,000 m³/h 9,500 m³/h 13,300 m³/h
Unit segments 2 Housing rad. 1 m 50 55 63
Housing class (DIN 1886) T2 / TB2 / D1 Housing rad. 3 m 40 45 53
Filter Outside air ePM1 55% (F7) (2) Housing rad. 5 m 36 41 49
Filter Extract air ePM10 50% (M5) (2)
The sound power at the connectors is calculated for the simultaneous
Media temperature (air) -20 to +40 °C operation of both fans. The sound pressure level is determined for the
Ambient temperature (operation) 0 to +50 °C simultaneous operation of both fans at distances of 1, 3 and 5 m.

Protection class IP 31
Electrical data
Central building control system BACnet, Modbus TCP/IP Sound data AIR1 RH 12000/SO
Voltage / Frequency 400 V 3N ~, 50 Hz
Sound power level LwA dB(A) at 400 Pa external pressure
Max. output Fans 2 x 5000 W
4,000 m³/h 9,500 m³/h 12,800 m³/h
Nominal current 15.2 / 15.2 / 17.2 A (15.2 / 15.2 / 18.4 A (4))
Supply air (LwA) 77 82 88
Connection (wiring diagram no.) SS-1324
Extract air (LwA) 70 75 79
Outside air (LwA) 66 71 75
(1) = at 400 Pa external pressure loss ERP-compliant
(2) = other filter classes see optional accessories Exhaust air (LwA) 77 82 88
(3) = with increased humidity recovery
Sound pressure level LpA db(A) of sound radiated from housing
(4) = AIR RH 12000/SO
4,000 m³/h 9,500 m³/h 12,800 m³/h
Housing rad. 1 m 50 55 59
Housing rad. 3 m 41 46 50
Housing rad. 5 m 36 41 45

The sound power at the connectors is calculated for the simultaneous


operation of both fans. The sound pressure level is determined for the
simultaneous operation of both fans at distances of 1, 3 and 5 m.

94 Helios
538
510
ETA EHA

max. 2420

1035
501,1

2090
~1500
Dimensional drawing

M8
598
SUP ODA

527,5
ODA - Outdoor Air / Außenluft / Air extérieur
View A (from above) View B
EHA - Exhaust Air /ODA
Fortluft /Air rejeté
- Outdoor Air / Außenluft / Air extérieur
View C
100

ETA - Extract Air / Abluft 1563


EHA - /Exhaust
Air repris
Air / Fortluft /Air rejeté
SUP - Supply Air / Zuluft / Air soufflé
ETA - Extract Air / Abluft / Air repris 1563
930 1503

max. 80
840 845
A
SUP - Supply Air / Zuluft / Air soufflé 1503

150
1475 106

150
1475 106
895 1555

538
510
ETA EHA

538
510
ETA EHA
C B

max. 2420

1035
max. 2420
501,1

2090
1860

1910
472

1035
501,1

2090
~1500

~1500

M8
598
SUP ODA

M8
694

598
SUP ODA

527,5

527,5
100

100
95 568
930

max. 80
2450 840 845
930

max. 80
840 845

B 895 1555
895 1555
Dim. in mm ODA: Outside air EHA: Exhaust air ETA: Extract air SUP: Supply air

Accessories

1860

1910
472

1860

1910
472
694

Heating and cooling registers External installation


694

Pre-heater Cover for external installation


95 568
95 568
AIR1-EVH RH 12000 2450 AIR1-AAD RH 12000
Ref. no. 01871 Page 98 2450 Ref. no. 06437 Page 108
Electrical, external Weather protection cover for the unit
Auxiliary heater AIR1-AAD RH 12000/ULM
Weather protection cover for the unit incl. Ref. no. 06443 Page 109
AIR1-ENH RH 12000
Ref. no. 03628 Page 99 recirculation module
Electrical, external
AIR1-AAD KR KW + DX RH 12000
AIR1-NH WW RH 12000
Ref. no. 03831 Page 100 Weather protection cover for cooling Ref. no. 06474 Page 110
Hot water, external
register cold water or direct evaporator
Hydraulic unit for hot water heater register
AIR1-AAD NH EL + WW RH 12000
Ref. no. 06449 Page 110
WHSH HE 24 V (0 – 10 V) L Ref. no. 06311 Page 101 Weather protection cover for aux. heater
Cooling register Terminal box heater
AIR1-KR KW RH 12000 L (1) AIR1-AAHK Ref. no. 07064 Page 111
Ref. no. 04183 Page 102
Cold water, external
Hoods
AIR1-KR KW RH 12000 R (1)
Ref. no. 04389 Page 102 AIR1-AAHA RH 12000
Cold water, external Ref. no. 06611 Page 111
Intake hood outside air
AIR1-KR DX RH 12000 L (1)
Ref. no. 04865 Page 104 AIR1-AAHF RH 12000
Direct evaporator DX, external Ref. no. 06865 Page 112
Discharge hood exhaust air
AIR1-KR DX RH 12000 R (1)
Ref. no. 05281 Page 104
Direct evaporator DX, external Controls

Air routing Controllers


AIR1-BE ECO Ref. no. 06186 Page 113
Multi-leaf damper
AIR1-BE TOUCH Ref. no. 06187 Page 113
AIR1-JVK RH 12000 Ref. no. 06020 Page 106
Controller connection cable
Recirculation module
AIR1-SL 4/10 10 m Ref. no. 07073 Page 113
AIR1-ULM RH 12000 Ref. no. 06170 Page 106
AIR1-SL 4/20 20 m Ref. no. 07121 Page 113
Flexible connector
Sensors
AIR1-VS 147/51 Ref. no. 04378 Page 107
KWL-CO2 Carbon dioxide sensor Ref. no. 04272 Page 113
Air filters
KWL-FTF Humidity-temperature sensor Ref. no. 04273 Page 113
Spare air filter and other filter classes KWL-VOC Mixed gas sensor Ref. no. 04274 Page 113
ELF-AIR1 RH 12000/ePM10 50%/48 (M5) Ref. no. 02201 Page 115 AIR1-CO2 K Carbon dioxide sensor duct Ref. no. 07124 Page 114
ELF-AIR1 RH 12000/ePM10 50%/96 (M5) Ref. no. 02218 Page 115 Signal converter for sensors
ELF-AIR1 RH 12000/ePM1 55%/96 (F7) Ref. no. 02264 Page 115 AIR1-SK Ref. no. 06019 Page 114
ELF-AIR1 RH 12000/ePM1 80%/96 (F9) Ref. no. 02471 Page 115 Extension kit for constant pressure control

The use of original spare air filters is mandatory to guarantee the specified AIR1-CAP Ref. no. 06756 Page 114
technical data and air volumes.

(1) = When looking at the cooling register from the air flow direction,
the service side is on the right for the R version and on the left for the L version

Helios AIR1 Series RH 95


AIR1 RH 15000 Performance curve

Dpfa
Pa

V· m3/h

Fig. shows accessories

Unit types

AIR1 RH 15000 AIR1 RH 15000/SO


Ref. no. 04351 04360
Heat exchanger Condensation rotor Adsorption rotor (3)

Technical data Sound data AIR1 RH 15000

Mechanical data Sound power level LwA dB(A) at 400 Pa external pressure
Area of application Inside/outside 5,000 m³/h 10,500 m³/h 15,000 m³/h
Installation position Standing Supply air (LwA) 77 84 92
Maintenance access Side, both sides Extract air (LwA) 69 76 83
Min. air volume 150 m³/h Outside air (LwA) 65 73 80
Max. air volume 15000 m³/h (1) (14700 m³/h (4)) Exhaust air (LwA) 77 84 92
Weight, unit operational 1500 kg (1531 kg (4)) Sound pressure level LpA db(A) of sound radiated from housing
Delivery unit 2-part 5,000 m³/h 10,500 m³/h 15,000 m³/h
Unit segments 2 Housing rad. 1 m 50 57 66
Housing class (DIN 1886) T2 / TB2 / D1 Housing rad. 3 m 40 48 56
Filter Outside air ePM1 55% (F7) (2) Housing rad. 5 m 36 43 52
Filter Extract air ePM10 50% (M5) (2)
The sound power at the connectors is calculated for the simultaneous
Media temperature (air) -20 to +40 °C operation of both fans. The sound pressure level is determined for the
Ambient temperature (operation) 0 to +50 °C simultaneous operation of both fans at distances of 1, 3 and 5 m.

Protection class IP 31
Electrical data
Central building control system BACnet, Modbus TCP/IP Sound data AIR1 RH 15000/SO
Voltage / Frequency 400 V 3N ~, 50 Hz
Sound power level LwA dB(A) at 400 Pa external pressure
Max. output Fans 2 x 6000 W
5,000 m³/h 10,500 m³/h 14,700 m³/h
Nominal current 18.3 / 18.3 / 20.3 A (18.3 / 18.3 / 21.4 A (4))
Supply air (LwA) 77 84 92
Connection (wiring diagram no.) SS-1325
Extract air (LwA) 69 75 83
Outside air (LwA) 65 71 79
(1) = at 400 Pa external pressure loss ERP-compliant
(2) = other filter classes see optional accessories Exhaust air (LwA) 77 84 92
(3) = with increased humidity recovery
Sound pressure level LpA db(A) of sound radiated from housing
(4) = AIR RH 15000/SO
5,000 m³/h 10,500 m³/h 14,700 m³/h
Housing rad. 1 m 50 55 65
Housing rad. 3 m 40 45 56
Housing rad. 5 m 36 41 51

The sound power at the connectors is calculated for the simultaneous


operation of both fans. The sound pressure level is determined for the
simultaneous operation of both fans at distances of 1, 3 and 5 m.

96 Helios
1600 106

738
710
ETA EHA

max. 2670

1160
814,2

2340
Dimensional drawing

M8
~1500

798
SUP ODA

589,5
View A (from above) View B View C
ODA - Outdoor Air / ODA - Outdoor
Außenluft / AirAir / Außenluft / Air extérieur
extérieur
100

EHA - Exhaust Air /EHA - Exhaust


Fortluft Air / Fortluft /Air rejeté
/Air rejeté 1688 1688
ETA - /Extract
ETA - Extract Air / Abluft Air / Abluft / Air repris
Air repris
A

max. 80
885 870 1055 SUP -/Supply
SUP - Supply Air / Zuluft Air / Zuluft / Air soufflé
Air soufflé 1628 1628

150
150
1600 1600
106 106
940 1595

738
710
738
710
ETA ETA EHA EHA

max. 2670
max. 2670
C

2110

2160
472

1160
1160
814,2 814,2

2340
2340
M8
M8
~1500
~1500
819

798
798
SUP SUP ODA ODA

589,5
589,5
100
100
100 568

max. 80
max. 80
2535 885 885 870 870 1055 1055

B 940 940 1595 1595


Dim. in mm ODA: Outside air EHA: Exhaust air ETA: Extract air SUP: Supply air

Accessories

2110

2160
2110

2160
472
472

819
819

Heating and cooling registers External installation

Pre-heater Cover for external installation


100 568 100 568
AIR1-EVH RH 15000 2535
AIR1-AAD
2535
RH 15000
Ref. no. 01883 Page 98 Ref. no. 06438 Page 108
Electrical, external Weather protection cover for the unit
Auxiliary heater AIR1-AAD RH 15000/ULM
Weather protection cover for the unit incl. Ref. no. 06444 Page 109
AIR1-ENH RH 15000
Ref. no. 03642 Page 99 recirculation module
Electrical, external
AIR1-AAD KR KW + DX RH 15000
AIR1-NH WW RH 15000
Ref. no. 03833 Page 100 Weather protection cover for cooling Ref. no. 06482 Page 110
Hot water, external
register cold water or direct evaporator
Hydraulic unit for hot water heater register
AIR1-AAD NH EL + WW RH 15000
Ref. no. 06450 Page 110
WHSH HE 24 V (0 – 10 V) L Ref. no. 06311 Page 101 Weather protection cover for aux. heater
Cooling register Terminal box heater
AIR1-KR KW RH 15000 L (1) AIR1-AAHK Ref. no. 07064 Page 111
Ref. no. 04184 Page 102
Cold water, external
Hoods
AIR1-KR KW RH 15000 R (1)
Ref. no. 04391 Page 102 AIR1-AAHA RH 15000
Cold water, external Ref. no. 06612 Page 111
Intake hood outside air
AIR1-KR DX RH 15000 L (1)
Ref. no. 04866 Page 104 AIR1-AAHF RH 15000
Direct evaporator DX, external Ref. no. 06866 Page 112
Discharge hood exhaust air
AIR1-KR DX RH 15000 R (1)
Ref. no. 05282 Page 104
Direct evaporator DX, external Controls

Air routing Controllers


AIR1-BE ECO Best.-Nr. 06186 Page 113
Multi-leaf damper
AIR1-BE TOUCH Ref. no. 06187 Page 113
AIR1-JVK RH 15000 Ref. no. 06021 Page 106
Controller connection cable
Recirculation module
AIR1-SL 4/10 10 m Ref. no. 07073 Page 113
AIR1-ULM RH 15000 Ref. no. 06182 Page 106
AIR1-SL 4/20 20 m Ref. no. 07121 Page 113
Flexible connector
Sensors
AIR1-VS 160/71 Ref. no. 04379 Page 107
KWL-CO2 Carbon dioxide sensor Ref. no. 04272 Page 113
Air filters
KWL-FTF Humidity-temperature sensor Ref. no. 04273 Page 113
Spare air filter and other filter classes KWL-VOC Mixed gas sensor Ref. no. 04274 Page 113
ELF-AIR1 RH 15000/ePM10 50%/48 (M5) Ref. no. 02202 Page 115 AIR1-CO2 K Carbon dioxide sensor duct Ref. no. 07124 Page 114
ELF-AIR1 RH 15000/ePM10 50%/96 (M5) Ref. no. 02219 Page 115 Signal converter for sensors
ELF-AIR1 RH 15000/ePM1 55%/96 (F7) Ref. no. 02271 Page 115 AIR1-SK Ref. no. 06019 Page 114
ELF-AIR1 RH 15000/ePM1 80%/96 (F9) Ref. no. 02479 Page 115 Extension kit for constant pressure control
The use of original spare air filters is mandatory to guarantee the specified AIR1-CAP Ref. no. 06756 Page 114
technical data and air volumes.

(1) = When looking at the cooling register from the air flow direction,
the service side is on the right for the R version and on the left for the L version

Helios AIR1 Series RH 97


Accessories for the RH series.

Electrical pre-heater external Electrical pre-heater


For heating the outside air at very low external temperatures. For mounting
directly to the supply air duct of the ventilation unit including fixing material.
Casing in robust panel construction, insulated on all sides with 50 mm mineral
wool for the minimisation of heat losses. External corrosion-resistant coating of
casing. Large inspection openings on both sides of unit for easy access and
optimised cleaning and maintenance. Suitable for internal installation.

Detailed calculations / technical information: www.AIR1Select.com.

Technical data
Type Ref. no. Output max. Power consumption max. Weight
AIR1-EVH RH 1500 01262 4.2 kW 6.1 A 50.0 kg
AIR1-EVH RH 2000 01710 5.8 kW 8.4 A 61.0 kg
AIR1-EVH RH 3000 01711 9.1 kW 13.1 A 77.0 kg
AIR1-EVH RH 5000 01791 15.6 kW 22.5 A 110.0 kg
AIR1-EVH RH 6000 01792 18.1 kW 26.1 A 126.0 kg
AIR1-EVH RH 8000 01819 22.0 kW 31.8 A 135.0 kg
AIR1-EVH RH 9500 01830 22.0 kW 31.8 A 150.0 kg
AIR1-EVH RH 12000 01871 22.0 kW 31.8 A 174.0 kg
AIR1-EVH RH 15000 01883 22.0 kW 31.8 A 211.0 kg

Dimensional drawing

X
R
T
400
W 110
max. E

B
S
V

P
K

100
I

M8
max. 80

C
Dim. in mm

Maße (mm)
Art.-Nr. Type B C E I K O P R S T U V W X

Dimensions 01262 AIR1-EVH RH 1500 520 760 700 200 173 380 265 378 338 350 310 - - -
01710 AIR1-EVH RH 2000 580 860 760 250 173 430 295 498 338 470 310 - - -
Type Ref. no. B
01711 AIR1-EVH RH 3000
C E
640 970
I
820 250
K
173 485
O300 608
P438 580
R 410 -
S -
T
-
U V W X
AIR1-EVH RH 1500 01262 01791 AIR1-EVH
520 RH760
5000 780
700 1240 200
960 300 465
173 620380
375 883265
438 855
378410 498
338 - -
350 310 – – –
01792 AIR1-EVH RH 6000 830 1360 1010 300 465 680 400 883 438 855 410 498 - -
AIR1-EVH RH 2000 01710 580 RH860
01819 AIR1-EVH 8000 760 1610 250
950 1130 350 173
515 805 430 295
465 1083 498410
438 1055 338361,1
498 470
- 310 – – –
01830 AIR1-EVH RH 9500 1000 1710 1180 350 515 855 490 1228 438 1200 410 498 409,4 -
AIR1-EVH RH 3000 01711 640 970 820 250 173 485 300 608 438 580 410 – – –
01871 AIR1-EVH RH 12000 1080 1860 1260 350 515 930 530 1503 538 1475 510 598 501,1 1563
AIR1-EVH RH 5000 01791 01883 780 RH1240
AIR1-EVH 15000 960 2110 300
1200 1380 350 465
515 1055620
590 375
1628 738 883710
1600 438814,2 1688
798 855 410 498 – –
AIR1-EVH RH 6000 01792 830 1360 1010 300 465 680 400 883 438 855 410 498 – –
AIR1-EVH RH 8000 01819 950 1610 1130 350 515 805 465 1083 438 1055 410 498 361 –
AIR1-EVH RH 9500 01830 1000 1710 1180 350 515 855 490 1228 438 1200 410 498 409 –
AIR1-EVH RH 12000 01871 1080 1860 1260 350 515 930 530 1503 538 1475 510 598 501 1563
AIR1-EVH RH 15000 01883 1200 2110 1380 350 515 1055 590 1628 738 1600 710 798 814 1688

98 Helios
Electrical auxiliary heater
Electrical auxiliary heater internal/external
For the demand-oriented temperature control of supply air.
Internal up to RH 3000: Mains power supply and connection to the ventilation
unit control system through pre-wired plug contacts. Auxiliary heater for installati-
on in the ventilation unit.
External from RH 5000: For mounting directly to the supply air duct of the venti-
lation unit including fixing material. Casing in robust panel construction, insulated
on all sides with 50 mm mineral wool for the minimisation of heat losses. External
corrosion-resistant coating of casing. Large inspection openings on both sides
of unit for easy access and optimised cleaning and maintenance. Suitable for
internal and external installation. Note: A weather protection cover is required for
external installation.
internal external
Detailed calculations / technical information: www.AIR1Select.com.

Technical data
Type Ref. no. Output max. Current consumption max. Weight
AIR1-ENH RH 1500 03605 4.2 kW 6.1 A 8.0 kg
internal

AIR1-ENH RH 2000 03616 5.8 kW 8.4 A 10.0 kg


AIR1-ENH RH 3000 03617 9.1 kW 13.1 A 15.0 kg
AIR1-ENH RH 5000 03618 15.6 kW 22.5 A 110.0 kg
AIR1-ENH RH 6000 03625 18.1 kW 26.1 A 126.0 kg
external

AIR1-ENH RH 8000 03626 22.0 kW 31.8 A 135.0 kg


AIR1-ENH RH 9500 03627 29.2 kW 42.2 A 150.0 kg
AIR1-ENH RH 12000 03628 38.9 kW 56.2 A 174.0 kg
AIR1-ENH RH 15000 03642 44.0 kW 63.5 A 211.0 kg

Dimensional drawing

X
R
T
400
W 110
max. E

B
S
V

P
K

100
I

M8
max. 80

C
Dim. in mm

Maße (mm)
Art.-Nr. Type B C E I K O P R S T U V W X
Dimensions 03618 AIR1-ENH RH 5000 780 1240 960 300 465 620 375 883 438 855 410 498 - -

Type 03625
Ref. no. AIR1-ENH
BRH 6000 C 830 1360
E 1010 I300 465K 680 400
O 883 438
P 855 410
R 498 S - - T U V W X
03626 AIR1-ENH RH 8000 950 1610 1130 350 515 805 465 1083 438 1055 410 498 361,1 -
AIR1-ENH RH 5000 03618 03627 780RH 9500
AIR1-ENH 12401000 960
1710 1180300
350 465855
515 6201228 375
490 438 1200883
410 498438
409,4 -855 410 498 – –
AIR1-ENH RH 6000 03625 03628 AIR1-ENH RH 12000
830 136010801010
1860 1260 350
300 515
465930 530 1503 538 1475 510
680 400 883 598 501,1 1563
438 855 410 498 – –
03642 AIR1-ENH RH 15000 1200 2110 1380 350 515 1055 590 1628 738 1600 710 798 814,2 1688
external

AIR1-ENH RH 8000 03626 950 1610 1130 350 515 805 465 1083 438 1055 410 498 361 –
AIR1-ENH RH 9500 03627 1000 1710 1180 350 515 855 490 1228 438 1200 410 498 409 –
AIR1-ENH RH 12000 03628 1080 1860 1260 350 515 930 530 1503 538 1475 510 598 501 1563
AIR1-ENH RH 15000 03642 1200 2110 1380 350 515 1055 590 1628 738 1600 710 798 814 1688

Helios AIR1 Series RH 99


Accessories for the RH series.

Hot water auxiliary heater


Hot water auxiliary heater internal/external
For demand-oriented temperature control of supply air. Further accessories are
required for supply air temperature control (Hydraulic unit WHSH HE 24 V).
Internal up to RH 3000: For installation in the ventilation unit. The heating
elements consist of copper piping with formed aluminium fins, and copper pipe
water connections for flow and return.
External from RH 5000: For mounting directly to the supply air duct of the venti-
lation unit including fixing material. Casing in robust panel construction, insulated
on all sides with 50 mm mineral wool for the minimisation of heat losses. External
corrosion-resistant coating of casing. Large inspection openings on both sides
of unit for easy access and optimised cleaning and maintenance. For internal
and external installation. Note: A weather protection cover is required for external
installation.
Detailed calculations / technical information: www.AIR1Select.com.

Technical data

Water Connection Weight Temperature control


Type Ref. no. Ref. no.
content flow / return (1) (without liquid) system
AIR1-NH WW RH 1500 03805 7.6 l G 1/2 4.6 kg WHSH HE 24 V (0 – 10 V) 08318
internal

AIR1-NH WW RH 2000 03806 11.6 l G 1/2 5.8 kg WHSH HE 24 V (0 – 10 V) 08318


AIR1-NH WW RH 3000 03824 14.9 l G 1/2 7.0 kg WHSH HE 24 V (0 – 10 V) 08318
AIR1-NH WW RH 5000 03825 24.1 l G 1/2 103.0 kg WHSH HE 24 V (0 – 10 V) M 06310
AIR1-NH WW RH 6000 03826 30.5 l G 3/4 125.0 kg WHSH HE 24 V (0 – 10 V) M 06310
external

AIR1-NH WW RH 8000 03827 45.2 l G 3/4 171.0 kg WHSH HE 24 V (0 – 10 V) M 06310


AIR1-NH WW RH 9500 03830 53.7 l G1 195.0 kg WHSH HE 24 V (0 – 10 V) L 06311
AIR1-NH WW RH 12000 03831 67.1 l G1 228.0 kg WHSH HE 24 V (0 – 10 V) L 06311
AIR1-NH WW RH 15000 03833 80.5 l G 1 1/4 274.0 kg WHSH HE 24 V (0 – 10 V) L 06311
(1) External thread
Dimensional drawing

X
R
T
400
W 70

AC
max. E

AB

B
S
V
AA

P
I
100

M8
max. 80

Y 35 O

C
Dim. in mm

Maße (mm)
Art.-Nr. Type B C E I O P R S T U V W X Y AA AB AC
Dimensions 03825 AIR1-NH WW RH 5000 780 1240 960 300 620 375 883 438 855 410 498 - - 178 85 599 G 1/2
03826 AIR1-NH WW RH 6000 830 1360 1010 300 680 400 883 438 855 410 498 - - 180 93 641 G 3/4
Type 03827 AIR1-NH WW RH 8000
Ref. no.
950 1610 1130 350
B805 C
465 1083 438 1055 410
E498 361,1 -
I 180 93 761
OG 3/4 P R S T
03830 AIR1-NH WW RH 9500 1000 1710 1180 350 855 490 1228 438 1200 410 498 409,4 - 175 96 808
AIR1-NH WW RH 5000 03825 780 1240 960 300 620G 1 375 883 438 855
03831 AIR1-NH WW RH 12000 1080 1860 1260 350 930 530 1503 538 1475 510 598 501,1 1563 175 96 888 G1

AIR1-NH WW RH 6000
03833 03826 830
AIR1-NH WW RH 15000 1200 2110 1380 350 1055 590 1628 738 1600 710 1360 1010
798 300
814,2 1688 172 680
102 1002 G 1 1/4 400 883 438 855
external

AIR1-NH WW RH 8000 03827 950 1610 1130 350 805 465 1083 438 1055
AIR1-NH WW RH 9500 03830 1000 1710 1180 350 855 490 1228 438 1200
AIR1-NH WW RH 12000 03831 1080 1860 1260 350 930 530 1503 538 1475
AIR1-NH WW RH 15000 03833 1200 2110 1380 350 1055 590 1628 738 1600

Type Ref. no. U V W X Y AA AB AC (1)


AIR1-NH WW RH 5000 03825 410 498 – – 178 85 599 G 1/2
AIR1-NH WW RH 6000 03826 410 498 – – 180 93 641 G 3/4
external

AIR1-NH WW RH 8000 03827 410 498 361 – 180 93 761 G 3/4


AIR1-NH WW RH 9500 03830 410 498 409 – 175 96 808 G1
AIR1-NH WW RH 12000 03831 510 598 501 1563 175 96 888 G1
AIR1-NH WW RH 15000 03833 710 798 814 1688 172 102 1002 G 1 1/4
(1) External thread
100 Helios
Hydraulic unit Hydraulic unit
Hydraulic unit for supply air temperature control by controlling the water flow rate
in the heater battery. Delivered as a complete unit consisting of the hydraulic unit
with 3-way valve with actuator and circulating pump, Flow / return temperature
display and flexible connection hoses.
Control voltage: 24 V (0 – 10 V)
Kvs value: 5.1
Flow rate: up to 3.3 m³/h
Connection diameter: G1 AG flat sealing (DN25, 1”)

Types

Control
XH units Type Ref. no. Kvs value Flow rate Connection diameter
voltage

AIR1-RH 1500 WHSH HE 24 V (0 – 10 V) 08318 24 V (0 – 10 V) 5.1 0.2 to 3.3 m³/h G1 AG flat sealing (DN25, 1”)
AIR1-RH 2000 WHSH HE 24 V (0 – 10 V) 08318 24 V (0 – 10 V) 5.1 0.2 to 3.3 m³/h G1 AG flat sealing (DN25, 1”)
AIR1-RH 3000 WHSH HE 24 V (0 – 10 V) 08318 24 V (0 – 10 V) 5.1 0.2 to 3.3 m³/h G1 AG flat sealing (DN25, 1”)
AIR1-RH 5000 WHSH HE 24 V (0 – 10 V) M 06310 24 V (0 – 10 V) 8.1 0.0 to 4.0 m³/h G2 AG flat sealing (DN32, 1 1/4”)
AIR1-RH 6000 WHSH HE 24 V (0 – 10 V) M 06310 24 V (0 – 10 V) 8.1 0.0 to 4.0 m³/h G2 AG flat sealing (DN32, 1 1/4”)
AIR1-RH 8000 WHSH HE 24 V (0 – 10 V) M 06310 24 V (0 – 10 V) 8.1 0.0 to 4.0 m³/h G2 AG flat sealing (DN32, 1 1/4”)
AIR1-RH 9500 WHSH HE 24 V (0 – 10 V) L 06311 24 V (0 – 10 V) 15 0.0 to 8.0 m³/h G2 flat sealing (DN32, 1 1/4”)
AIR1-RH 12000 WHSH HE 24 V (0 – 10 V) L 06311 24 V (0 – 10 V) 15 0.0 to 8.0 m³/h G2 flat sealing (DN32, 1 1/4”)
AIR1-RH 15000 WHSH HE 24 V (0 – 10 V) L 06311 24 V (0 – 10 V) 15 0.0 to 8.0 m³/h G2 flat sealing (DN32, 1 1/4”)

Helios AIR1 Series RH 101


Accessories for the RH series.

Cold water cooling register


Cold water cooling register external
For demand-oriented temperature control (cooling) of supply air. Mounting
directly to the supply air duct of the ventilation unit including fixing material is
possible. Casing in robust panel construction, insulated on all sides with 50
mm mineral wool for the minimisation of heat losses. External corrosion-resis-
tant coating of casing. Large inspection openings on both sides of unit for easy
access and optimised cleaning and maintenance. Stainless steel condensate
tray with condensate drain outlets. Condensate connection 32 mm. Cooling
register suitable for internal and external installation. Note: A weather protection
cover is required for external installation.
Recommended accessory: Ball siphonAIR1-KS XH (Ref. no. 07169)

Detailed calculations / technical information: www.AIR1Select.com.

Technical data

Connection Weight
Type Ref. no. Version Water content
flow /return (1) (without liquid)

AIR1-KR KW RH 1500 L 03958 left 1.9 l G 1/2 66.0 kg


AIR1-KR KW RH 1500 R 04283 right 1.9 l G 1/2 66.0 kg
AIR1-KR KW RH 2000 L 03959 left 2.6 l G 3/4 80.0 kg
AIR1-KR KW RH 2000 R 04285 right 2.6 l G 3/4 80.0 kg
AIR1-KR KW RH 3000 L 03967 left 3.4 l G1 101.0 kg
AIR1-KR KW RH 3000 R 04286 right 3.4 l G1 101.0 kg
AIR1-KR KW RH 5000 L 03971 left 6.5 l G 1 1/4 158.0 kg
AIR1-KR KW RH 5000 R 04287 right 6.5 l G 1 1/4 158.0 kg
AIR1-KR KW RH 6000 L 03976 left 7.0 l G 1 1/4 180.0 kg
AIR1-KR KW RH 6000 R 04288 right 7.0 l G 1 1/4 180.0 kg
AIR1-KR KW RH 8000 L 03983 left 13.7 l G 1 1/2 242.0 kg
AIR1-KR KW RH 8000 R 04382 right 13.7 l G 1 1/2 242.0 kg
AIR1-KR KW RH 9500 L 03984 left 16.9 l G2 270.0 kg
AIR1-KR KW RH 9500 R 04383 right 16.9 l G2 270.0 kg
AIR1-KR KW RH 12000 L 04183 left 20.5 l G2 313.0 kg
AIR1-KR KW RH 12000 R 04389 right 20.5 l G2 313.0 kg
AIR1-KR KW RH 15000 L 04184 left 20.2 l G2 380.0 kg
AIR1-KR KW RH 15000 R 04391 right 20.2 l G2 380.0 kg
(1) External thread

102 Helios
Dimensional drawing
Version left (L) Version right (R)

X X
A A
R R
T N 500 500 N T
70 W Z Z W 70

max. E
SUP SUP

U
S
V
max. E
AB
U
S
V

AC
B

AB

B
AC

P
P

AA
AA

100
100

115 M8 ø 32 M8 115
ø 32
145

145
Y

max. 80
Y
max. 80

O O
F F
C C

Maße (mm) Maße (mm)


Art.-Nr. Type A B C E F N O P R S T U V W X Y Z AA AB AC Art.-Nr. Type WhenA looking
B C E atF the
N cooling
O P register
R S T from
U VtheW airX flowY direction,
Z AA AB AC

Dim. in mm
03958 AIR1-KR KW RH 1500 L
03959 AIR1-KR KW RH 2000 L
1000 520
1000 580
760
860
700
760
250
250
350
350
380
430
265
295
378
498
338
338
350
470
310
310
-
-
-
-
-
-
175
179
70
62
98
102
340
382
G 1/2
G 3/4
the04283
service side is on the right for the R version and on the -- left-- for-- the
AIR1-KR KW RH 1500 R 1000 520 760 700 250 350 380 265 378 338 350 310
04285 AIR1-KR KW RH 2000 R 1000 580 860 760 250 350 430 295 498 338 470 310
175
179
L70
62
version.
98 340 G 1/2
102 382 G 3/4
03967 AIR1-KR KW RH 3000 L 1000 640 970 820 250 350 485 300 608 438 580 410 - - - 182 56 105 426 G1 04286 AIR1-KR KW RH 3000 R 1000 640 970 820 250 350 485 300 608 438 580 410 - - - 182 56 105 426 G1
03971 AIR1-KR KW RH 5000 L 1100 780 1240 960 275 450 620 375 883 438 855 410 498 - - 186 83 109 568 G 1 1/4 04287 AIR1-KR KW RH 5000 R 1100 780 1240 960 275 450 620 375 883 438 855 410 498 - - 186 83 109 568 G 1 1/4
03976 AIR1-KR KW RH 6000 L 1100 830 1360 1010 275 450 680 400 883 438 855 410 498 - - 186 83 109 588 G 1 1/4 04288 AIR1-KR KW RH 6000 R 1100 830 1360 1010 275 450 680 400 883 438 855 410 498 - - 186 83 109 588 G 1 1/4

Dimensions1100
03983 AIR1-KR KW RH 8000 L
950 1610 1130
03984 AIR1-KR KW RH 9500 L
1100 1000 1710 1180
275
275
450
450
805
855
465 1083 438 1055 410
490 1228 438 1200 410
498 361,1
498 409,4
-
-
195
195
65
35
118
118
720 G 1 1/2
770 G2
04382 AIR1-KR KW RH 8000 R
04383 AIR1-KR KW RH 9500 R
1100 950 1610 1130 275
1100 1000 1710 1180 275
450
450
805
855
465 1083 438 1055 410
490 1228 438 1200 410
498 361,1
498 409,4
-
-
195
195
65
35
118
118
720 G 1 1/2
770 G2
04183 AIR1-KR KW RH 12000 L 1100 1080 1860 1260 275 450 930 530 1503 538 1475 510 598 501,1 1563 195 35 118 850 G2 04389 AIR1-KR KW RH 12000 R 1100 1080 1860 1260 275 450 930 530 1503 538 1475 510 598 501,1 1563 195 35 118 850 G2
Type
04184 AIR1-KR KW RH 15000 L 1100 1200 2110 1380 275 Ref. no.590
450 1055 1628 738 1600 710 A B
798 814,2 1688 195 100 118 C
970 G2 E F
04391 AIR1-KR KW RH 15000 R 1100 1200 2110 1380 275 N O
450 1055 590 1628 738 1600 710P R
798 814,2 1688 195 100 S
118 970 G2

AIR1-KR KW RH 1500 L 03958 1000 520 760 700 250 350 380 265 378 338
AIR1-KR KW RH 1500 R 04283 1000 520 760 700 250 350 380 265 378 338
AIR1-KR KW RH 2000 L 03959 1000 580 860 760 250 350 430 295 498 338
AIR1-KR KW RH 2000 R 04285 1000 580 860 760 250 350 430 295 498 338
AIR1-KR KW RH 3000 L 03967 1000 640 970 820 250 350 485 300 608 438
AIR1-KR KW RH 3000 R 04286 1000 640 970 820 250 350 485 300 608 438
AIR1-KR KW RH 5000 L 03971 1100 780 1240 960 275 450 620 375 883 438
AIR1-KR KW RH 5000 R 04287 1100 780 1240 960 275 450 620 375 883 438
AIR1-KR KW RH 6000 L 03976 1100 830 1360 1010 275 450 680 400 883 438
AIR1-KR KW RH 6000 R 04288 1100 830 1360 1010 275 450 680 400 883 438
AIR1-KR KW RH 8000 L 03983 1100 950 1610 1130 275 450 805 465 1083 438
AIR1-KR KW RH 8000 R 04382 1100 950 1610 1130 275 450 805 465 1083 438
AIR1-KR KW RH 9500 L 03984 1100 1000 1710 1180 275 450 855 490 1228 438
AIR1-KR KW RH 9500 R 04383 1100 1000 1710 1180 275 450 855 490 1228 438
AIR1-KR KW RH 12000 L 04183 1100 1080 1860 1260 275 450 930 530 1503 538
AIR1-KR KW RH 12000 R 04389 1100 1080 1860 1260 275 450 930 530 1503 538
AIR1-KR KW RH 15000 L 04184 1100 1200 2110 1380 275 450 1055 590 1628 738
AIR1-KR KW RH 15000 R 04391 1100 1200 2110 1380 275 450 1055 590 1628 738

Type Ref. no. T U V W X Y Z AA AB AC (1)


AIR1-KR KW RH 1500 L 03958 350 310 – – – 175 70 98 340 G 1/2
AIR1-KR KW RH 1500 R 04283 350 310 – – – 175 70 98 340 G 1/2
AIR1-KR KW RH 2000 L 03959 470 310 – – – 179 62 102 382 G 3/4
AIR1-KR KW RH 2000 R 04285 470 310 – – – 179 62 102 382 G 3/4
AIR1-KR KW RH 3000 L 03967 580 410 – – – 182 56 105 426 G1
AIR1-KR KW RH 3000 R 04286 580 410 – – – 182 56 105 426 G1
AIR1-KR KW RH 5000 L 03971 855 410 498 – – 186 83 109 568 G 1 1/4
AIR1-KR KW RH 5000 R 04287 855 410 498 – – 186 83 109 568 G 1 1/4
AIR1-KR KW RH 6000 L 03976 855 410 498 – – 186 83 109 588 G 1 1/4
AIR1-KR KW RH 6000 R 04288 855 410 498 – – 186 83 109 588 G 1 1/4
AIR1-KR KW RH 8000 L 03983 1055 410 498 361 – 195 65 118 720 G 1 1/2
AIR1-KR KW RH 8000 R 04382 1055 410 498 361 – 195 65 118 720 G 1 1/2
AIR1-KR KW RH 9500 L 03984 1200 410 498 409 – 195 35 118 770 G2
AIR1-KR KW RH 9500 R 04383 1200 410 498 409 – 195 35 118 770 G2
AIR1-KR KW RH 12000 L 04183 1475 510 598 501 1563 195 35 118 850 G2
AIR1-KR KW RH 12000 R 04389 1475 510 598 501 1563 195 35 118 850 G2
AIR1-KR KW RH 15000 L 04184 1600 710 798 814 1688 195 100 118 970 G2
AIR1-KR KW RH 15000 R 04391 1600 710 798 814 1688 195 100 118 970 G2

Helios AIR1 Series RH (1) External thread 103


Accessories for the RH series.

Direct evaporator cooling register


Direct evaporator cooling register external
For demand-oriented temperature control (cooling) of supply air. Mounting
directly to the supply air duct of the ventilation unit is possible. Suitable for use
with common refrigerants (selection list see www.AIR1Select.com).Casing in
robust panel construction, insulated on all sides with 50 mm mineral wool for
the minimisation of heat losses. External corrosion-resistant coating of casing.
Stainless steel condensate tray with condensate drain outlets. Large inspection
openings on both sides of unit for easy access and optimised cleaning and main-
tenance. Condensate connection 32 mm. Cooling register suitable for internal
and external installation. Note: A weather protection cover is required for external
installation.
Recommended accessory: Ball siphon AIR1-KS XH (Ref. no. 07169)

Detailed calculations / technical information: www.AIR1Select.com.

Technical data

Weight Ø connection Ø connection


Type Ref. no. Version Filling capacity
(without liquid) outlet inlet

AIR1-KR DX RH 1500 L 04416 left 65.0 kg 1.57 l 16 mm 12 mm


AIR1-KR DX RH 1500 R 05001 right 65.0 kg 1.57 l 16 mm 12 mm
AIR1-KR DX RH 2000 L 04417 left 79.0 kg 2.14 l 19 mm 12 mm
AIR1-KR DX RH 2000 R 05025 right 79.0 kg 2.14 l 19 mm 12 mm
AIR1-KR DX RH 3000 L 04422 left 100.0 kg 2.80 l 22 mm 16 mm
AIR1-KR DX RH 3000 R 05028 right 100.0 kg 2.80 l 22 mm 16 mm
AIR1-KR DX RH 5000 L 04424 left 156.0 kg 5.17 l 28 mm 16 mm
AIR1-KR DX RH 5000 R 05046 right 156.0 kg 5.17 l 28 mm 16 mm
AIR1-KR DX RH 6000 L 04425 left 180.0 kg 6.22 l 28 mm 16 mm
AIR1-KR DX RH 6000 R 05239 right 180.0 kg 6.22 l 28 mm 16 mm
AIR1-KR DX RH 8000 L 04426 left 240.0 kg 11.33 l 35 mm 22 mm
AIR1-KR DX RH 8000 R 05240 right 240.0 kg 11.33 l 35 mm 22 mm
AIR1-KR DX RH 9500 L 04864 left 265.0 kg 13.03 l 35 mm 22 mm
AIR1-KR DX RH 9500 R 05280 right 265.0 kg 13.03 l 35 mm 22 mm
AIR1-KR DX RH 12000 L 04865 left 303.0 kg 12.73 l 42 mm 22 mm
AIR1-KR DX RH 12000 R 05281 right 303.0 kg 12.73 l 42 mm 22 mm
AIR1-KR DX RH 15000 L 04866 left 380.0 kg 15.97 l 42 mm 28 mm
AIR1-KR DX RH 15000 R 05282 right 380.0 kg 15.97 l 42 mm 28 mm

104 Helios
Maßzeichnung
Dimensional drawing
Version left (L) Version right (R)

X X
R R
A
T A T
70 W N 500
500 N W 70

AD AD

max. E
SUP
U
S
V
B

SUP

B
S
V
max. E
AB

AB
AC

AA
AC
P

AA

P
100
100

115 M8 ø 32
145

max. 80

ø 32 M8 115

145
O Z Y

max. 80
Y Z O
C F
F C

Maße (mm) Maße (mm)


Art.-Nr. Type
04416 AIR1-KR DX RH 1500 L
A B
1000 520
C
760
E
700
F
250
N
350
O
380
P
265
R
378
S
338
T
350 310
U V
-
W
-
X
-
Y
206
Z
120
AA
137
AB
171
AC
16
AD
12
Art.-Nr. Type
When A
05001 AIR1-KR DX RH 1500 R
looking
B C
at the
E F N
cooling
O P
register
R S T
from
U
1000 520 760 700 250 350 380 265 378 338 350 310
V
-
theW- airX- flow
Y
direction,
Z AA AB
206 120 137 171
AC
16
AD
12

Dim. in mm
04417 AIR1-KR DX RH 2000 L
04422 AIR1-KR DX RH 3000 L
1000 580
1000 640
860
970
760
820
250
250
350
350
430
485
295
300
498
608
338
438
470
580
310
410
-
-
-
-
-
-
206
206
119
117
116
118
242
290
19
22
12
16
the service side is on the right for the R version and on the
05025 AIR1-KR DX RH 2000 R 1000 580 860 760 250 350 430 295 498 338 470 310
05028 AIR1-KR DX RH 3000 R 1000 640 970 820 250 350 485 300 608 438 580 410
-
-
left
-
-
for -
-
the L version.
206 119 116 242
206 117 118 290
19
22
12
16
04424 AIR1-KR DX RH 5000 L 1100 780 1240 960 275 450 620 375 883 438 855 410 498 - - 206 114 121 387 28 16 05046 AIR1-KR DX RH 5000 R 1100 780 1240 960 275 450 620 375 883 438 855 410 498 - - 206 114 121 387 28 16
04425 AIR1-KR DX RH 6000 L 1100 830 1360 1010 275 450 680 400 883 438 855 410 498 - - 206 114 121 382 28 16 05239 AIR1-KR DX RH 6000 R 1100 830 1360 1010 275 450 680 400 883 438 855 410 498 - - 206 114 121 382 28 16
04426 AIR1-KR DX RH 8000 L 1100 950 1610 1130 275 450 805 465 1083 438 1055 410 498 361,1 - 213 167 122 491 35 22 05240 AIR1-KR DX RH 8000 R 1100 950 1610 1130 275 450 805 465 1083 438 1055 410 498 361,1 - 213 167 122 491 35 22

Dimensions 1100 1000 1710 1180


04864 AIR1-KR DX RH 9500 L 275 450 855 490 1228 438 1200 410 498 409,4 - 230 203 122 526 35 22 05280 AIR1-KR DX RH 9500 R 1100 1000 1710 1180 275 450 855 490 1228 438 1200 410 498 409,4 - 230 203 122 526 35 22
04865 AIR1-KR DX RH 12000 L 1100 1080 1860 1260 275 450 930 530 1503 538 1475 510 598 501,1 1563 223 143 128 580 42 22 05281 AIR1-KR DX RH 12000 R 1100 1080 1860 1260 275 450 930 530 1503 538 1475 510 598 501,1 1563 223 143 128 580 42 22
04866 AIR1-KR DX RH 15000 L 1100 1200 2110 1380 275 450 1055 590 1628 738 1600 710 798 814,2 1688 241 177 128 650 42 28
Type Ref. no. A B C E05282 AIR1-KR DX RHF15000 R N
1100 1200 2110 1380 275
O
450 1055 590 1628 738 1600 710
P R
798 814,2 1688 241 177 128
S 650 42 28

AIR1-KR DX RH 1500 L 04416 1000 520 760 700 250 350 380 265 378 338
AIR1-KR DX RH 1500 R 05001 1000 520 760 700 250 350 380 265 378 338
AIR1-KR DX RH 2000 L 04417 1000 580 860 760 250 350 430 295 498 338
AIR1-KR DX RH 2000 R 05025 1000 580 860 760 250 350 430 295 498 338
AIR1-KR DX RH 3000 L 04422 1000 675 970 855 250 350 485 320 608 438
AIR1-KR DX RH 3000 R 05028 1000 675 970 855 250 350 485 320 608 438
AIR1-KR DX RH 5000 L 04424 1100 780 1240 960 275 450 620 375 883 438
AIR1-KR DX RH 5000 R 05046 1100 780 1240 960 275 450 620 375 883 438
AIR1-KR DX RH 6000 L 04425 1100 830 1360 1010 275 450 680 400 883 438
AIR1-KR DX RH 6000 R 05239 1100 830 1360 1010 275 450 680 400 883 438
AIR1-KR DX RH 8000 L 04426 1100 950 1610 1130 275 450 805 465 1083 438
AIR1-KR DX RH 8000 R 05240 1100 950 1610 1130 275 450 805 465 1083 438
AIR1-KR DX RH 9500 L 04864 1100 1000 1710 1180 275 450 855 490 1228 438
AIR1-KR DX RH 9500 R 05280 1100 1000 1710 1180 275 450 855 490 1228 438
AIR1-KR DX RH 12000 L 04865 1100 1080 1860 1260 275 450 930 530 1503 538
AIR1-KR DX RH 12000 R 05281 1100 1080 1860 1260 275 450 930 530 1503 538
AIR1-KR DX RH 15000 L 04866 1100 1200 2110 1380 275 450 1055 590 1628 738
AIR1-KR DX RH 15000 R 05282 1100 1200 2110 1380 275 450 1055 590 1628 738

Type Ref. no. T U V W X Y Z AA AB AC AD


AIR1-KR DX RH 1500 L 04416 350 310 – – – 206 120 137 171 16 12
AIR1-KR DX RH 1500 R 05001 350 310 – – – 206 120 137 171 16 12
AIR1-KR DX RH 2000 L 04417 470 310 – – – 206 119 116 242 19 12
AIR1-KR DX RH 2000 R 05025 470 310 – – – 206 119 116 242 19 12
AIR1-KR DX RH 3000 L 04422 580 410 498 – – 206 117 118 290 22 16
AIR1-KR DX RH 3000 R 05028 580 410 498 – – 206 117 118 290 22 16
AIR1-KR DX RH 5000 L 04424 855 410 498 – – 206 114 121 387 28 16
AIR1-KR DX RH 5000 R 05046 855 410 498 – – 206 114 121 387 28 16
AIR1-KR DX RH 6000 L 04425 855 410 498 – – 206 114 121 382 28 16
AIR1-KR DX RH 6000 R 05239 855 410 498 – – 206 114 121 382 28 16
AIR1-KR DX RH 8000 L 04426 1055 410 498 361 – 213 167 122 491 35 22
AIR1-KR DX RH 8000 R 05240 1055 410 498 361 – 213 167 122 491 35 22
AIR1-KR DX RH 9500 L 04864 1200 410 498 409 – 230 203 122 526 35 22
AIR1-KR DX RH 9500 R 05280 1200 410 498 409 – 230 203 122 526 35 22
AIR1-KR DX RH 12000 L 04865 1475 510 598 501 1563 223 143 128 580 42 22
AIR1-KR DX RH 12000 R 05281 1475 510 598 501 1563 223 143 128 580 42 22
AIR1-KR DX RH 15000 L 04866 1600 710 798 814 1688 241 177 128 650 42 28
AIR1-KR DX RH 15000 R 05282 1600 710 798 814 1688 241 177 128 650 42 28

Helios AIR1 Series RH 105


Accessories for the RH series.

Multi-leaf damper
Multi-leaf damper internal
Multi-leaf damper for preventing cold draughts when the fan is stationary. Frame-
work casing with connection flange on both sides. Counter-rotating blades, with
retracted sealing lip. Sealing class 2. Installation inside of unit.

Technical data

Runtime Ambient
Type Ref. no. Weight Actuator type
(open / closed) temperature

AIR1-JVK XH 1500/RH 1500 06006 40 ... 75 s 3.0 kg -30 to +50 °C 24 V DC. spring return
AIR1-JVK XH 2500/RH 2000 06007 40 ... 75 s 4.0 kg -30 to +50 °C 24 V DC. spring return
AIR1-JVK XH 3500-4500/RH 3000 06009 40 ... 75 s 5.0 kg -30 to +50 °C 24 V DC. spring return
AIR1-JVK XH 5500/RH 5000-6000 06010 40 ... 75 s 6.6 kg -30 to +50 °C 24 V DC. spring return
AIR1-JVK XH 7000/RH 8000 06012 40 ... 75 s 7.8 kg -30 to +50 °C 24 V DC. spring return
AIR1-JVK XH 8500/RH 9500 06013 40 ... 75 s 8.6 kg -30 to +50 °C 24 V DC. spring return
AIR1-JVK RH 12000 06020 40 ... 75 s 10.0 kg -30 to +50 °C 24 V DC. spring return
AIR1-JVK RH 15000 06021 40 ... 75 s 13.0 kg -30 to +50 °C 24 V DC. spring return

Recirculation module Recirculation module


Recirculation module for the 100% recirculation of the extract air into the buil-
ding. Multi-leaf dampers are required for recirculation operation. The module
consists of a recirculation damper including drive. For mounting between the
heat exchanger segment and supply air segment of the rotary heat exchanger
unit.

Plug-in connection to the mains power supply and ventilation unit control system.

Dimensional drawing Dimensions


Type Ref. no. B C E
480 C AIR1-ULM RH 5000 06040 1470 1240 1650
AIR1-ULM RH 6000 06160 1590 1360 1770
AIR1-ULM RH 8000 06184 1840 1610 2020
AIR1-ULM RH 9500 06185 1940 1710 2120
AIR1-ULM RH 12000 06170 2090 1860 2270
max. E

AIR1-ULM RH 15000 06182 2340 2110 2520


B
100
max. 80

Dim. in mm Maße (mm)


Art.-Nr. Type B C E
06040 AIR1-ULM RH 5000 1470 1240 1650
06160 AIR1-ULM RH 6000 1590 1360 1770
06184 AIR1-ULM RH 8000 1840 1610 2020
06185 AIR1-ULM RH 9500 1940 1710 2120
06170 AIR1-ULM RH 12000 2090 1860 2270

106 Helios
06182 AIR1-ULM RH 15000 2340 2110 2520
Flexible connector
Flexible connector
Flexible connector (uninsulated), with flange connections on both sides, for
mounting between the ventilation unit and duct system. Prevents structure-borne
sound transmission and bridges mounting tolerances. Elastic fabric sleeve,
operating temperature range from -10 °C to +80 °C.

Only suitable for internal installation.

Dimensional drawing Dimensions


RH units Type Ref. no. A B R S
AIR1-RH 1500 AIR1-VS 35/31 04372 398 358 378 338
AIR1-RH 2000 AIR1-VS 47/31 04373 518 358 498 338
AIR1-RH 3000 AIR1-VS 58/41 04374 628 458 608 438
B
S

AIR1-RH 5000 AIR1-VS 85/41 04375 903 458 883 438


10,5x14
AIR1-RH 6000 AIR1-VS 85/41 04375 903 458 883 438
AIR1-RH 8000 AIR1-VS 105/41 04376 1103 458 1083 438
AIR1-RH 9500 AIR1-VS 120/41 04377 1248 458 1228 438
R AIR1-RH 12000 AIR1-VS 147/51 04378 1523 558 1503 538

A
1 45 AIR1-RH 15000 AIR1-VS 160/71 04379 1648 758 1628 738

Dim. in mm

Square-round adapter Square-round adapter


Symmetrical adapter for connecting the ventilation unit to round air ducts/duct
systems. Made of galvanised steel sheet. The pressure loss of the adapter at
maximum air volume is < 10 Pa on both the intake and discharge side.

Only suitable for internal installation.

Dimensional drawing Dimensions


Type Ref. no. A B C D
AIR1-ÜS XH 1500/RH 1500 04367 400 360 200 315
C D
AIR1-ÜS XH 2500/RH 2000 04368 520 360 250 400
AIR1-ÜS XH 3500-4500/RH 3000 04369 630 460 300 500
B

AIR1-ÜS XH 5500/RH 5000-6000 04370 905 460 350 630


S

E
Type Ref. no. E R S
AIR1-ÜS XH 1500/RH 1500 04367 60 378 338
10 21 AIR1-ÜS XH 2500/RH 2000 04368 80 498 338
R
AIR1-ÜS XH 3500-4500/RH 3000 04369 80 608 438
A AIR1-ÜS XH 5500/RH 5000-6000 04370 80 883 438

Dim. in mm

Helios AIR1 Series RH 107


Accessories for the RH series.

Weather protection cover


Weather protection cover
Weather protection cover for the external installation of AIR1 ventilation units.
Made of galvanised steel sheet, in weather-resistant design/coating. Increases
the protection class of the unit to IP 54.

Dimensional drawing Dimensions


Type Ref. no. B C D E
1840 D AIR1-AAD RH 1500 06382 115 760 930 245
850 640 AIR1-AAD RH 2000 06431 125 860 1030 250
AIR1-AAD RH 3000
132 06432 135 970 1140 255
E

1700 C

1840 D
Maße (mm)
850 Art.-Nr. Type B 64
C0 D E Teilbar
06382 AIR1-AAD RH 1500 115 760 930 245 -
06431 AIR1-AAD RH 2000 125 860 1030 250 -
132

-

06432 AIR1-AAD RH 3000 135 970 1140 255


B

1700 C

Dim. in mm AIR1 RH 1500 – 3000


Maße (mm)
Art.-Nr. Type B C D E Teilbar
06382 AIR1-AAD RH 1500 115 760 930 245 -
Dimensional drawing
06431 AIR1-AAD RH 2000 125 860 1030 250 -
06432 AIR1-AAD RH 3000 135 970 1140 255 -

F 1100 F D
850 640
132

E

A C
G

F 1100 F D
850 Maße (mm)
640
Art.-Nr. Type A B C D E F G Teilbar
132

06433 AIR1-AAD RH 5000 1842 162 1280 1448 269 423 1946 x

B

06434 AIR1-AAD RH 6000 2012 172 1400 1568 275 508 2116 x
06435 AIR1-AAD RH 8000 2182 194 1650 1818 285 594 2288 x
A 06436 AIR1-AAD RH 9500 C 1918 290
2312 199 1750 656 2412 x
06437 AIR1-AAD RH 12000 2442 212 1900 2068 290 721 2542 x
06438 AIR1-AAD RH 15000 2532 234 2150 2318 300 766 2632 x
Dim. in mm AIR1 RH 5000 – 15000
Maße (mm)
Art.-Nr. Type A B C D E F G Teilbar
06433 AIR1-AAD RH 5000 1842 162 1280 1448 269 423 1946 x
Dimensions
06434 AIR1-AAD RH 6000 2012 172 1400 1568 275 508 2116 x
06435 AIR1-AAD RH 8000 2182 194 1650 1818 285 594 2288 x
Type Ref. no. A B C D E F G
06436 AIR1-AAD RH 9500 2312 199 1750 1918 290 656 2412 x

AIR1-AAD RH 50002442
06437 AIR1-AAD RH 12000 212 1900 2068 290 06433
721 2542 x 1842 162 1280 1448 269 423 1946
06438 AIR1-AAD RH 15000 2532 234 2150 2318 300 766 2632 x
AIR1-AAD RH 6000 06434 2012 172 1400 1568 275 508 2116
AIR1-AAD RH 8000 06435 2182 194 1650 1818 285 594 2288
AIR1-AAD RH 9500 06436 2312 199 1750 1918 290 656 2412
AIR1-AAD RH 12000 06437 2442 212 1900 2068 290 721 2542
AIR1-AAD RH 15000 06438 2532 234 2150 2318 300 766 2632

108 Helios
Weatherprotection cover for the unit Weather protection cover for the unit incl. recirculation module
including recirculation module Weather protection cover for the external installation of AIR1 ventilation units
with a recirculation module. Made of galvanised steel sheet, in weather-resistant
design/coating. Increases the protection class of the unit to IP 54.

Dimensional drawing

F 1100 H D

850 640

132

E

A C

F 1100 H D
Maße (mm)
Art.-Nr. Type A B C D E F G H Teilbar
850 640
06439 AIR1-AAD RH 5000/ULM 2322 162 1280 1448 269 423 2426 903 x
132

06440 AIR1-AAD RH 6000/ULM 2492 172 1400 1568 275 508 2596 988 x

06441 AIR1-AAD RH 8000/ULM 2662 194 1650 1818 285 594 2768 1074 x
B

06442 AIR1-AAD RH 9500/ULM 2792 199 1750 1918 290 656 2892 1136 x
A C
06443 AIR1-AAD RH 12000/ULM 2922 212 1900 2068 290 721 3022 1201 x
06444 AIR1-AAD RH 15000/ULM 3012 234 2150 2318 300 766 3112 1246 x
Dim. in mm
Maße (mm)
Art.-Nr. Type A B C D E F G H Teilbar
06439 AIR1-AADDimensions
RH 5000/ULM 2322 162 1280 1448 269 423 2426 903 x
06440 AIR1-AAD RH 6000/ULM 2492 172 1400 1568 275 508 2596 988 x
06441
Type
AIR1-AAD RH 8000/ULM 2662 194 1650
Ref. no.
1818 285 594 2768 1074
A x
B C D E F G H
AIR1-AAD
06442 AIR1-AAD RH 5000/ULM
RH 9500/ULM 06439
2792 199 1750 1918 290 2322x
656 2892 1136 162 1280 1448 269 423 2426 903
06443 AIR1-AAD RH 12000/ULM 2922 212 1900 2068 290 721 3022 1201 x
AIR1-AAD
06444 AIR1-AAD RH 6000/ULM
RH 15000/ULM 06440
3012 234 2150 2318 300 2492x
766 3112 1246 172 1400 1568 275 508 2596 988
AIR1-AAD RH 8000/ULM 06441 2662 194 1650 1818 285 594 2768 1074
AIR1-AAD RH 9500/ULM 06442 2792 199 1750 1918 290 656 2892 1136
AIR1-AAD RH 12000/ULM 06443 2922 212 1900 2068 290 721 3022 1201
AIR1-AAD RH 15000/ULM 06444 3012 234 2150 2318 300 766 3112 1246

Helios AIR1 Series RH 109


Accessories for the RH series.

Weather protection cover for external cold water or direct


Weather protection cover cooling register
evaporator cooling registers
Weather protection cover for the external installation of external cold water
or direct evaporator cooling registers. Made of galvanised steel sheet, in
weather-resistant design/coating. Increases the protection class of the
cooling register to IP 54.

Dimensional drawing Dimensions


Type Ref. no. A C
AIR1-AAD KR KW + DX RH 1500 06467 1000 932
AIR1-AAD KR KW + DX RH 2000 06468 1000 1032
A C AIR1-AAD KR KW + DX RH 3000 06469 1000 1102
AIR1-AAD KR KW + DX RH 5000 06470 1100 1424
35

AIR1-AAD KR KW + DX RH 6000 06471 1100 1544


A C Maße (mm) AIR1-AAD KR KW + DX RH 8000 06472 1100 1794
Art.-Nr. Type A C
06467 AIR1-AAD KR KW+DX RH 1500 1000 932
AIR1-AAD KR KW + DX RH 9500 06473 1100 1894
06468 AIR1-AAD KR KW+DX RH 2000 1000 1032
AIR1-AAD KR KW + DX RH 12000 06474 1100 2044
06469 AIR1-AAD KR KW+DX RH 3000 1000 1102
Maße06470
(mm) AIR1-AAD KR KW+DX RH 5000 1100 1424 AIR1-AAD KR KW + DX RH 15000 06482 1100 2294
Art.-Nr. Type A 06471C AIR1-AAD KR KW+DX RH 6000 1100 1544
06467 AIR1-AAD KR KW+DX RH 1500 1000 06472
932AIR1-AAD KR KW+DX RH 8000 1100 1794
06468 AIR1-AAD KR KW+DX RH 2000 1000 06473
1032AIR1-AAD KR KW+DX RH 9500 1100 1894
06469Dim. in mm
AIR1-AAD KR KW+DX RH 3000 1000 06474
1102AIR1-AAD KR KW+DX RH 12000 1100 2044
06470 AIR1-AAD KR KW+DX RH 5000 1100 06482
1424AIR1-AAD KR KW+DX RH 15000 1100 2294
06471 AIR1-AAD KR KW+DX RH 6000 1100 1544
06472 AIR1-AAD KR KW+DX RH 8000 1100 1794
06473 AIR1-AAD KR KW+DX RH 9500 1100 1894
06474 AIR1-AAD KR KW+DX RH 12000 1100 2044
06482 W KReather
AIR1-AAD KW+DX RH 15000protection
1100 2294 cover for auxiliary Weather protection cover for auxiliary heater
heater Weather protection cover for the external installation of electrical or hot water
auxiliary heater registers. Made of galvanised steel sheet, in weather-resistant
design/coating. Increases the protection class of the cooling register to IP 54.

Dimensional drawing Dimensions


Type Ref. no. C
AIR1-AAD NH EL + WW RH 5000 06445 1424
AIR1-AAD NH EL + WW RH 6000 06446 1544
400 C
AIR1-AAD NH EL + WW RH 8000 06447 1794
AIR1-AAD NH EL + WW RH 9500 06448 1894
35

AIR1-AAD NH EL + WW RH 12000 06449 2044


400 C
AIR1-AAD NH EL + WW RH 15000 06450 2294

Maß (mm)
Art.-Nr. Type C
06445 AIR1-AAD NH EL+WW RH 5000 1424
06446 AIR1-AAD NH EL+WW RH 6000 1544
06447 AIR1-AAD NH (mm)
Maß EL+WW RH 8000 1794

Art.-Nr. Type 06448 AIR1-AAD NHCEL+WW RH 9500 1894

06445 AIR1-AAD NH EL+WW06449 AIR1-AAD NH


RH 5000 EL+WW RH 12000
1424 2044
Dim. in06446
mm AIR1-AAD NH EL+WW06450 AIR1-AAD NH
RH 6000 EL+WW RH 15000
1544 2294

06447 AIR1-AAD NH EL+WW RH 8000 1794

110 06448 AIR1-AAD NH EL+WW RH 9500 1894


Helios
06449 AIR1-AAD NH EL+WW RH 12000 2044
06450 AIR1-AAD NH EL+WW RH 15000 2294
Heating element for the terminal box
Heating element for the terminal box
Heating element for the electrical terminal box of the ventilation unit. Recommen-
ded for the external installation of AIR ventilation units in cold climate zones to
prevent condensate formation and protect the control system against tempera-
tures below 0 °C.
Heat output automatically controlled depending on the outside air temperature.
Max. heat output: 100 W
Supply voltage: 230 V

Type Ref. no.


AIR1-AAHK 07064

Intake hood outside air


Intake hood outside air
Intake hood outside air for external installation. Includes drainage tray and droplet
separator. Mounting via flange connection to the unit connector. Surface with
weather-resistant coating.

Dimensional drawing

X
R
T
W C
B
U
S
V

9
A D

Dim. in mm

Maße (mm)

Dimensions Art.-Nr. Type A B C D R S T U V W X


06483 AIR1-AAHA XH 1000 375 270 332 162 343 238 315 210 - - -
Type Ref. no.XH 1500/RH 1500
06484 AIR1-AAHA A B 410 C
370 486 D195 378 R338 350S 310 -T - -U V W X
AIR1-AAHA XH 1500/RH 1500 06539 AIR1-AAHA
06484 XH 2500/RH410
2000 370 530 370
486 486195
195 498378
338 470
338310 -
350 - -
310 – – –
06487 AIR1-AAHA XH 3500-4500/RH 3000 640 470 525 200 608 438 580 410 - - -
AIR1-AAHA XH 2500/RH 2000 06496
06539 530
AIR1-AAHA XH 5500/RH 5000-6000
370 486
915 530
195
525 200
498
883 438
338
855 410
470
498 -
310
-
– – –
AIR1-AAHA XH 3500-4500/RH 3000 06487 XH 7000/RH640
06497 AIR1-AAHA 8000 470 1115 525
530 525200 608438 1055
200 1083 438410 580361,1
498 410
- – – –
06499 AIR1-AAHA XH 8500/RH 9500 1260 530 525 200 1228 438 1200 410 498 409,4 -
AIR1-AAHA XH 5500/RH 5000-6000 06496 915 530 525 200 883 438 855 410 498 – –
06611 AIR1-AAHA RH 12000 1595 630 575 200 1503 538 1475 510 598 501,1 1563
AIR1-AAHA XH 7000/RH 8000 06497 RH 15000
06612 AIR1-AAHA 1115 530 1720 525
830 675200 1083
200 1628 438710
738 1600 1055814,2 1688
798 410 498 361 –
AIR1-AAHA XH 8500/RH 9500 06499 1260 530 525 200 1228 438 1200 410 498 409 –
AIR1-AAHA RH 12000 06611 1595 630 575 200 1503 538 1475 510 598 501 1563
AIR1-AAHA RH 15000 06612 1720 830 675 200 1628 738 1600 710 798 814 1688

Helios AIR1 Series RH 111


Accessories for the RH series.

Discharge hood exhaust air


Discharge hood exhaust air
Discharge hood exhaust air for external installation. Includes protection guard.
Mounting via flange connection to the unit connector. Surface with weather-
resistant coating.

Dimensional drawing

X
R
T
W C

B
U
S
V

9
A 50

Dim. in mm
Maße (mm)
Art.-Nr. Type A B C R S T U V W X
Dimensions
06613 AIR1-AAHF XH 1000 375 270 235 343 238 315 210 - - -
Type Ref.XHno.
06643 AIR1-AAHF 1500/RH 1500 A B
410 370 C
338 378 R
338 350 310S - -T - U V W X
06646 AIR1-AAHF XH 2500/RH 2000 530 370 338 498 338 470 310 - - -
AIR1-AAHF XH 1500/RH 1500 06647 06643 410
AIR1-AAHF XH 3500-4500/RH 3000
370
640 470
338
375 608
378
438 580
338
410 -
350
- -
310 – – –
AIR1-AAHF XH 2500/RH 2000 06648 06646
AIR1-AAHF 530
XH 5500/RH 5000-6000 370
915 530 338
375 883 498 855
438 338 498
410 470
- - 310 – – –
06841 AIR1-AAHF XH 7000/RH 8000 1115 530 375 1083 438 1055 410 498 361,1 -
AIR1-AAHF XH 3500-4500/RH 3000 06647 640 470 375 608 438 580 410 – – –
06864 AIR1-AAHF XH 8500/RH 9500 1260 530 375 1228 438 1200 410 498 409,4 -
AIR1-AAHF XH 5500/RH 5000-6000
06865 06648
AIR1-AAHF RH 12000 915 530
1595 630 375
415 883 1475 510
1503 538 438 598 501,1
5801563 410 498 – –
AIR1-AAHF XH 7000/RH 8000 06866 AIR1-AAHF RH 15000
06841 1115 1720
530 830 566
375 1628 738 1600 710
1083 438 798 814,2 1688
1055 410 498 361 –
AIR1-AAHF XH 8500/RH 9500 06864 1260 530 375 1228 438 1200 410 498 409 –
AIR1-AAHF RH 12000 06865 1595 630 415 1503 538 1475 510 598 501 1563
AIR1-AAHF RH 15000 06866 1720 830 566 1628 738 1600 710 798 814 1688

112 Helios
Controller Eco
Controller Eco
Backlit display with 4 lines a 20 characters. The display menu system is operated
via seven buttons. There are two LEDs on the front side: One alarm LED and one
LED for the input mode. The controller is delivered with a 5 m cable as standard.
Cable lengths of 10 m and 20 m are optionally available. The maximum connec-
tion length is 100 m. The controller is designed for wall mounting. Alternatively,
it can also be attached to the unit casing using magnetic strips. Protection class
IP 40.

Technical data

Power Dimensions Ambient Ambient Connection Connection


Type Ref. no. Voltage
consumption (WxHxD) humidity temperature cable 10 m cable 20 m

(1) AIR1-SL 4/10 AIR1-SL 4/20


AIR1-BE ECO 06186 24 V DC 0.24 W 115 x 95 x 25 mm Max. 90 % RH +5 °C to +40 °C
Ref. no.: 07073 Ref. no.: 07121

Controller Touch
Controller Touch
Graphic user interface with intuitive menu structure and simple operation. The
display has a capacitive touch function and a size of 7”, incl. multi-colour colour
technology. Includes stainless steel casing for simple surface-mounting to the
wall. It is delivered with a 5 m cable as standard. Cable lengths of 10 m and 20
m are optionally available. The maximum connection length is 100 m. Protection
class IP 20.

Technical data

Power Dimensions Ambient Ambient Connection Connection


Type Ref. no. Voltage
consumption (WxHxD) humidity temperature cable 10 m cable 20 m

(1) AIR1-SL 4/10 AIR1-SL 4/20


AIR1-BE TOUCH 06187 24 V DC 6W 185 x 131 x 50 mm Max. 90 % RH -10 °C to +60 °C
Ref. no.: 07073 Ref. no.: 07121

Room sensors Room sensors


For measuring the CO2, mixed gas (VOC) concentration or relative humidity
and temperature. Control according to highest measured value. Includes
control cable KWL-SL 4/3 (3 m long), other lengths available upon request.
Dimensions (W x H x D) 95 x 97 x 30 mm.

Technical data
Type Ref. no. Measurement range
KWL-CO2 04272 400 ... 2000 ppm
(1)
KWL-FTF 04273 0 ... 99 % RH and 0 ... 40 °C
KWL-VOC 04274 450 ... 2000 ppm

(1) Non-condensing

Helios AIR1 Series RH 113


Accessories for the RH series.

Carbon dioxide sensor for duct installation


Carbon dioxide sensor for duct installation
Sensor for measuring the carbon dioxide concentration in the air. For installation
in the ventilation duct. Installation depth 40 – 180 mm.

Technical data
Type Ref. no. Measurement range
AIR1-CO2 K 07124 0 ... 2000 ppm

Signal converter Signal converter for sensors


Signal converter for the connection of up to six AIR1 room sensors of the same
sensor type. The AIR1-SK compares the connected inputs and forwards the
highest input signal to the max. output. Supplied pre-installed in the appropriate
terminal box incl. transformer 230 V / 24 V AC and terminal strip.
Dimensions terminal box (L x H x W): 218 x 149 x 97 mm

Technical data

Power Protection
Type Ref. no. Voltage Ambient humidity Ambient temperature
consumption class

(1) IP 20 / IP 66 in
AIR1-SK 06019 230 V, 50 Hz max. 15 VA Max. 90 % RH -40 °C to +50 °C
terminal box

Extension kit for CAP mode Extension kit for CAP mode
Differential pressure transmitter for constant pressure operation of the ventilation
unit. Vertical or horizontal installation possible.
Scope of delivery: Pressure transmitter, pressure hose and sensor.

Technical data
Type Ref. no. Voltage Ambient humidity Ambient temperature Protection class

(1)
AIR1-CAP 06756 24 V AC / DC ± 15 % Max. 95 % RH -25 °C to +50 °C IP 54

(1) Non-condensing

114 Helios
Spare air filter Spare air filter
Helios AIR1 units are supplied with the filter classes ePM1 55%/F7 (outside air)
and ePM10 50%/M5 (extract air) as standard. Depending on the unit size, the
(1) (2) (3)
air filter consists of multiple (separate) air filter inserts. This is taken into account
when ordering the spare air filter.
In case of increased air quality requirements, other filter classes are available for
the outside air and extract air (see table below). All air filters are pressure-loss-
optimised cassette filters with large filter surfaces.

(1) (2) (3)


Pre-filter outs. air Extract air filter Outs. or extract air filter ePM1 55% (F7)
ePM10 50% (M5) ePM10 50% (M5) Outside air filter ePM1 80% (F9)

Technical data
Type Ref. no. Filter class
ELF-AIR1 RH 1500/ePM10 50%/48 02192 ePM10 50% (M5)
ELF-AIR1 RH 2000/ePM10 50%/48 02193 ePM10 50% (M5)
Pre-filter outside air

ELF-AIR1 RH 3000/ePM10 50%/48 02194 ePM10 50% (M5)


ELF-AIR1 RH 5000/ePM10 50%/48 02196 ePM10 50% (M5)
ELF-AIR1 RH 6000/ePM10 50%/48 02220 ePM10 50% (M5)
ELF-AIR1 RH 8000/ePM10 50%/48 02199 ePM10 50% (M5)
ELF-AIR1 RH 9500/ePM10 50%/48 02200 ePM10 50% (M5)
ELF-AIR1 RH 12000/ePM10 50%/48 02201 ePM10 50% (M5)
ELF-AIR1 RH 15000/ePM10 50%/48 02202 ePM10 50% (M5)
ELF-AIR1 RH 1500/ePM10 50%/96 02211 ePM10 50% (M5)
ELF-AIR1 RH 2000/ePM10 50%/96 02212 ePM10 50% (M5)
ELF-AIR1 RH 3000/ePM10 50%/96 02213 ePM10 50% (M5)
Extract air filter

ELF-AIR1 RH 5000/ePM10 50%/96 02214 ePM10 50% (M5)


ELF-AIR1 RH 6000/ePM10 50%/96 02215 ePM10 50% (M5)
ELF-AIR1 RH 8000/ePM10 50%/96 02216 ePM10 50% (M5)
ELF-AIR1 RH 9500/ePM10 50%/96 02217 ePM10 50% (M5)
ELF-AIR1 RH 12000/ePM10 50%/96 02218 ePM10 50% (M5)
ELF-AIR1 RH 15000/ePM10 50%/96 02219 ePM10 50% (M5)
ELF-AIR1 RH 1500/ePM1 55%/96 02236 ePM1 55% (F7)
ELF-AIR1 RH 2000/ePM1 55%/96 02237 ePM1 55% (F7)
Outside or extract air filter

ELF-AIR1 RH 3000/ePM1 55%/96 02238 ePM1 55% (F7)


ELF-AIR1 RH 5000/ePM1 55%/96 02239 ePM1 55% (F7)
ELF-AIR1 RH 6000/ePM1 55%/96 02240 ePM1 55% (F7)
ELF-AIR1 RH 8000/ePM1 55%/96 02241 ePM1 55% (F7)
ELF-AIR1 RH 9500/ePM1 55%/96 02261 ePM1 55% (F7)
ELF-AIR1 RH 12000/ePM1 55%/96 02264 ePM1 55% (F7)
ELF-AIR1 RH 15000/ePM1 55%/96 02271 ePM1 55% (F7)
ELF-AIR1 RH 1500/ePM1 80%/96 02374 ePM1 80% (F9)
ELF-AIR1 RH 2000/ePM1 80%/96 02384 ePM1 80% (F9)
ELF-AIR1 RH 3000/ePM1 80%/96 02425 ePM1 80% (F9)
Outside air filter

ELF-AIR1 RH 5000/ePM1 80%/96 02446 ePM1 80% (F9)


ELF-AIR1 RH 6000/ePM1 80%/96 02451 ePM1 80% (F9)
ELF-AIR1 RH 8000/ePM1 80%/96 02460 ePM1 80% (F9)
ELF-AIR1 RH 9500/ePM1 80%/96 02463 ePM1 80% (F9)
ELF-AIR1 RH 12000/ePM1 80%/96 02471 ePM1 80% (F9)
ELF-AIR1 RH 15000/ePM1 80%/96 02479 ePM1 80% (F9)

Helios AIR1 Series RH 115


Helios AIR1 : ®

more than a product.

The innovative configuration, excellent quality


characteristics and clever system solutions –
Helios AIR1 is more than the sum of its parts.
This also includes a perfectly conceived control
concept, ideally matched accessories and an
A1 service offering. See for yourself.

116 Helios
All set?
Quick and easy – this also applies to the Helios AIR1
control system, be it during the commissioning or
operation. In this respect, there are various automatic
control options using sensors and different control
elements through to integration in modern central
building control systems.
More information can be found on page 118.

A strong unit needs


a strong partner.
Helios completes the Helios AIR1 system package with
the MultiZoneBox. These two perfectly coordinated
solutions combine maximum efficiency with maximum
individuality in multi-storey construction.
More information can be found on page 120.

Helios AIR1 System and Service 117


Control everything. Simply.
All Helios AIR1 compact ventilation units have an advanced control A Optimal indoor climate
system, which leaves nothing to be desired. The commissioning
Whether it is a school, office or theatre hall, an
and configuration is quick and easy due to the clever “step by optimal indoor climate is an important aspect for all
step” assistant. ventilation applications. With the option of connecting
various air quality sensors, there is the right unit
Modern standards, such as a high-quality touch control element for all requirements.
and the connection to common building management systems,
also guarantee extremely convenient operation. Completely auto-
mated operation using various air quality sensors is also possible.
Overall, this results in a control concept that could not be more
diverse, flexible and user-friendly.

B Various control types


The Helios AIR1 control system has various pre-pro-
grammed functions. All control types and parameters
can be simply set or changed via the external control
unit.

Constant
flow rate
Constant
pressure
Constant Demand- B
speed based

Time External Recirculation Temperature


signal

118 Helios
C Flexible communication
Various control elements are available for communication
with the Helios AIR1 ventilation units. The connection to
modern building management systems is also possible
with the integrated protocols BACnet and Modbus.

Control element TOUCH


The large 7” colour display is extremely user-friendly and
a perfect visualisation of all important system parameters.
Includes Commissioning Assistant.

Control element ECO


The control element ECO is the economical and functional
solution for controlling the Helios AIR1 ventilation units.
Includes Commissioning Assistant.

D Extended control options


With the high-performance Helios AIR1 control system,
all accessory components, such as heater and cooling
batteries, can also be controlled without complication.
Various control scenarios for a variety of applications are
available for this purpose.

Heating Heating Cooling Cooling


electric hot water cold water DX

Helios AIR1 Control system 119


The KWL® MultiZoneBox.
The flexible partner for
Helios AIR1®.
Central ventilation in multi-
storey construction is now
more individual than ever
with the KWL MulitZoneBox

120 Helios
It has more potential
for multi-storey construction.
Flow rate control, sound insulation, air distribution and system This process is even more efficient than ever in combination
control – you save on numerous individual components with with Helios AIR1: Thanks to the integrated fan-optimiser
the new KWL MultiZoneBox. The MultiZoneBox silently ensu- technology, the exact amount of air required for each moment
res the appropriate supply and extract ventilation of residential is provided. This reduces the energy consumption without
and commercial units in combination with a central building reducing the level of comfort.
ventilation unit with heat recovery.

Maintenance-free

Consumable and wear parts were comple-


tely avoided during the construction of the
KWL MultiZoneBox.

Super quiet

Large scale sound insulation elements


ensure silent operation. Ideal for noise-
sensitive environments.

All automatic

The optional room air sensor makes the


MultiZoneBox a ventilation-on-demand unit.

Unique

Revolutionary technology safely ensures the


pre-defined flow rate – independently and
continuously.

Quick assembly

Just one single, compact box is installed,


instead of numerous individual components.

Helios AIR1 and KWL MultiZoneBox 121


Both this and that.
More individuality for residential and
commercial units.

Both classic and modern.

The MultiZoneBox is compatible with all ducts. Spiral ducts can


be connected as easily as the flexible plastic ducting system
FlexPipeplus. There are no limits to the possibilities.

Both for work and at home.


The MultiZoneBox guarantees reliable air distribution for almost
all areas of application. Thus, it is the perfect solution for resi-
dential and commercial units – whether it is a single apartment
or maisonette – an office complex or loading area, or all
together.

Both now and tomorrow.

One box instead of multiple individual components reduces the


planning cost in advance and saves valuable installation space.
The maintenance-freedom, highest functional reliability and
silent operation are convincing in practical use.

Both high-performance and demand-based.


If multiple MultiZoneBoxes are used to ventilate a large unit,
such as e.g. a practice, different zones can be independently
supplied with different volumes of air based on demand.

Both inside and outside, above and below.

Whether the ventilation system is installed in the basement or on


the roof, inside or outside – the MultiZoneBox always ensures
the ideal air distribution with each ventilation unit.

122 Helios
Supply air
Extract air

Helios AIR1 and KWL MultiZoneBox 123


The KWL® MultiZoneBox range.

MultiZoneBox Right 90 degrees MultiZoneBox Left 90 degrees

KWL-MZB 6+1-75/125 R90 Ref. no. 04050 KWL-MZB 6+1-75/125 L90 Ref. no. 04051

200
61

200

61
1001

250
250

1001
Abluft

961

Abluft

961
Zuluft

Zuluft
722 722

400 125
125 400
44

44

Compact unit for the connection of supply and extract air DN 125 Compact unit for the connection of supply and extract air DN 125
and 2 sets of 7 single nozzles DN 75 with the supply air on the right and 2 sets of 7 single nozzles DN 75 with the supply air on the left
side. side.

MultiZoneBox Straight-through 75 MultiZoneBox Straight-through 125

KWL-MZB 6+1-75/125* Ref. no. 04052 KWL-MZB 125/125* Ref. no. 04053

722 200 722 200


61

100 ø75
61

100 Stutzen
87

Abluft

optional
Abluft
1040
1040

Zuluft

961
961
Zuluft

75 400

125 400 125


400

Compact unit for the connection of supply and extract air DN 125 Box with one connection for both supply and extract air on each side
and 2 sets of 7 single nozzles DN 75. DN 125.

* Supply and extract air direction optional.


All dimensions in mm.

124 Helios
Control element Eco Control element Touch Central controller

KWL-MZB-BE Ref. no. 04213 KWL-MZB-BET Ref. no. 04214 KWL-MZB-ZR Ref. no. 04215

Manual 4 stage operation or auto- Glass touch display for controlling and Central control, configuration and
matic mode. For flush-mounting. configuring the boxes. management of all connected boxes.
– Dim. (WxHxD) 80 x 80 x 10 mm – Dim. (WxHxD) 110 x 93 x 19 mm – Networking of up to 256 boxes
– 4-stage with LED, flush-mount. version – 3.9 inch display, including temperature – Fan-optimiser function
sensor, flush-mounted version

Connection plate Duct support set Duct support set

KWL-MZB-AP Ref. no. 04217 KWL-MZB-RH7 Ref. no. 04236 MZB-RH13 Ref. no. 04249

For installation in concrete ceilings. Duct support sets for bilateral connection Duct support sets for one-sided
– Dim. (WxHxD) 776 x 50 x 255 mm of FlexPipe® plus connection of FlexPipe® plus.
– 2 x 6 single nozzles DN75 – Set consists of 2 connection plates – consisting of 1 connection plate with
– for direct connection of box to the per 7 holders 13 holders
ducting system in the ceiling

Connection set Combi sensor Humidity sensor

KWL-MZB-VSAP Ref. no. 04219 KWL-MZB-VOC-F Ref. no. 04216 KWL-MZB-F Ref. no. 04250

For ceiling installation with connection Combi sensor (air humidity and VOC) Air humidity sensor for installation in
plate. Set with 12 single nozzles and for installation in the MZB. the MultiZoneBox.
mounting bracket. – VOC-humidity sensor
– including 12 single nozzles for – Installation in MultiZoneBox
connection plate

Plastic fittings DN75 Technical data

KWL-MZB KSS Ref. no. 04253 Area of application 40-220 m3/h

Measurement accuracy +/-10 m3/h

Voltage/frequency 230 V 1~, 50 Hz

Max. power consumption 6 Watt

Protection class IP 40

Weight 25 kg
Set consisting of 2 pcs, for optio-
nal, side-connection of a ventilation duct
DN75 to KWL-MZB 125/125 All details for the individual types:
(Ref. no.: 04053), included in scope of www.HeliosSelect.de
delivery for boxes 04050, 04051, 04052!

Helios AIR1 and KWL MultiZoneBox 125


Notes

126 Helios
Helios Ventilatoren GmbH + Co KG · Lupfenstraße 8 · 78056 Villingen-Schwenningen · Germany