Professional Documents
Culture Documents
There are FIVE significant components in a standalone system that is vital for the
system operation to run at its maximum power out-put
1. DC and AC Loads
2. Solar module
3. Battery bank
4. Inverter
5. Charge controller
Each of these components has its Formulae calculation to select the right .
The most important component to consider when designing a standalone system is the
total load that is to be used by the consumer.
Solar module
Charge Controller
The main function is to maintain the batteries at the proper
charging level and to protect them from overcharging.
Battery Bank:
The battery bank contains one or more deep-cycle batteries
connected in series and/or parallel depending on the voltage
and current capacity needed. The batteries store the power
produced by the solar array and discharge it when you need it.
Inverter
An inverter is required when you want to power AC devices.
The inverter converts the DC power, or direct current, from the
solar array and batteries into AC power
.
Solar PV system sizing
Location: Nai’ereka village, Solomon Islands
Peak Sun hours: 5 hrs
Days without sunlight: 2 days
Inverter efficiency: 85%
Inverter input voltage: 48v
Battery DOD: 80%
Battery capacity: 200Ah, 24v
Panel rating: BP SX3200B 200W,
Imp- 8.16A,
Vmp- 24.5v,
Isc- 8.7A,
Voc- 30.8v,
Type- Monocrystalline silicon
LOAD CALCULATION
AC loads
Lights – 360Wh
Refrigerators - 1600Wh
Laptop - 130Wh
Mobile - 9Wh
TV- 900Wh
= 2999Wh
DC loads
1.2 Calculate total Watt-hours per day needed from the PV modules.
= 144Wh + (2999/0.85)
= 144Wh + 3,528.23Wh
= 3,672.23Wh
= 3672.23Wh/48v
= 76.50 Ah
= 2 days x 76.50Ah
=153Ah/0.8
=191.25Ah
= 191.25/200Ah
= 0.956
Therefore: a minimum of 1 batteries of 200Ah (24v) will be required to supply the load
with rated current and voltage.
= 191.25 Ah/5hrs
= 38.25A
4.2 Solar panel required in PARALLEL
No. of panels required in PARALLEL
=38.25 A/8.16A
= 4.6875
= 48v/24.5
= 1.9
= 488.5 + 146.55
= 635.05W
Module specification
Pm- 200W
Vm – 24.5V
Im – 8.16A
Voc – 30.8V
Isc – 8.7A
= 5 x 8.7A x 1.25
= 54.375A
Therefore, the charge controller should be rated 60A (or greater) @ 24v
CABLE SIZING, CIRCUIT BREAKERS, SWITCHES & GPO’s
CABLE SIZE
6mm-10mm
6mm-10mm
6mm-10mm
CIRCUIT-BREAKERS
Mains
40A
Lights
10A
Power-point
15A
POSITIONING OF THE PV MODULE
All devices powered by solar cells are expected to operate under its maximum
power. The power incident on a PV module depends not only on the power
contained in the sunlight, but also on the angle between the module and the sun.
When the absorbing surface and the sunlight are perpendicular to each other, the
power density on the surface is equal to that of the sunlight (in other words, the
power density will always be at its maximum when the PV module is
perpendicular to the sun). However, as the angle between the sun and a fixed
surface is continually changing, the power density on a fixed PV module is less
than that of the incident sunlight.
Therefore, the BEST ANGLE for a PV module is when the solar cell is positioned
perpendicular to the direction of sun light
Discussion
Turbine Design
TURBINE BLADE DESIGN
The tip speed ratio is a very important factor in the different formulas of blade design. Generally,
slow running multi bladed wind turbine rotors operate with tip speed ratios like 1-4, while fast
runners use 5-7 as tip speed ratios.
To fit the known generator capacity and revolutions to the wind speed and to the swept rotor
area. Two formulas are needed
Power (W) = 0.6 x Cp x N x A x V3
Revolutions (rpm) = V x TSR x 60 / (6.28 x R),
2. REVOLUTION (rpm)
V x TSR x 60
Revolutions (rpm) = (6.28 x R)
10 m/ s x 7 x 60
= (6.28 x 2.5 m)
= 267.51 rpm
3. TURBINE CAPACITY
Thus Rotor efficiency can go as high as Cp = 0.48, but Cp = 0.4 is often used in this type of
calculations. This concept works without transmission. If transmission, a efficiency of 0.95 was
to be included.
Therefore Power output (Generator Capacity) = 0.6 x 0.4 x (0.95 x 0.6) x 19.625m2 x (12 m/s) 3
= 4.639KW
4. BLADE CHORD
The width of the blade is also called the blade chord. A good formula for computing this is:
5.6 x R2
Blade Chord (m) = (i x Cl x r x TSR 2)
Where;
R = Radius at tip,
r = radius at point of computation,
i = number of blades,
Cl = Lift coefficient,
TSR=Tip Speed Ratio.
Kinetic Energy = 0.5 x Mass x Velocity 2, where the mass is measured in kg, the velocity in m/s,
and the energy is given in joules. Air has a known density (around 1.23 kg/m 3 at sea level), so
the mass of air hitting our wind turbine (which sweeps a known area) each second is given by the
following equation:
Mass/sec (kg/s) = Velocity (m/s) x Area (m2) x Density (kg/m3).
Therefore, the power (i.e. energy per second) in the wind hitting a wind turbine with a certain
swept area is given by simply inserting the mass per second calculation into the standard kinetic
energy equation given above resulting in the following vital equation:
Scope block
Scope block can produce the waveform from the connection. By using this
scope, the magnitude of output power either real or reactance power can be
read and recorded.
10
12m/s
14m/s
11m/s
1.5 Discussion
Note that the wind turbine generator capacity that was calculated is rated at
4.639KW in 12m/s winds and the wind power that was calculated is 8.342KW.
Why the power of the wind is so much larger than the maximum power of the
turbine generator is because of the Betz Limit and inefficiencies in the system.
The Betz law means that wind turbines can never be better than 59.3% efficient.
The law can be simply explained by considering that if all of the energy coming
from wind movement into the turbine were converted into useful energy then the
wind speed afterwards would be zero. However, if the wind stopped moving at
the exit of the turbine, then no more fresh wind could get in - it would be
blocked. In order to keep the wind moving through the turbine, to keep getting
energy, there has to be some wind movement on the outside with energy left in
it. There must be a 'sweet spot' somewhere and there is, the Betz limit at 59.3%.
Pitch angle can be defined as the angle of attack of the wind with the blade.
Changing pitch angle means that the angle of attack of the wind is changed, this
can be done by changing the set of the wind turbine in Matlab-simulink in the
wind turbine parameters block as shown above. For example, when the pitch
angle is zero and wind speed is 12 m/sec we get maximum power but if we
change the pitch angle to 5 and 10 respectively for the same wind speed the
output power is decrease and this indicate the effect of pitch angle on the output
power as shown on the result. So the pitch angle value must be evaluated for
optimum wind speed in order to get best output power such as it change
automatically when the speed is high or low and this done by using proper
position control, the optimum pitch angle value is set as set point for the wind
turbine. This position control system change the pitch angle according to wind
speed, for example for high wind speed the pitch angle decrease and for low wind
speed the pitch angle increase to get constant speed and after that to obtain best
output power and for the safety of the blades structure.
On the result, one can see the effect of changing wind speed on the output power
(Active power) when the pitch angle is constant. The output power of the wind
turbine depend on wind speed, so the output power change when the wind speed
is change as shown in result. As noted from the simulation, output power of the
wind turbine depend on wind speed. Thus, the output power change when the
wind speed is change. The maximum power for our wind turbine when simulated
is 4.085KW when the wind speed is 12 m/sec.