FOR
TECHNICAL SPECIFICATIONS
December 2017
For
Technical Specifications
1. CIVIL AND ARCHITECTURE WORKS
1.1 MATERIALS
(1) CEMENT
Cement shall be Ordinary Portland Cement or Portland Composite Cement conforming to
the requirements of the Standard Specifications for Portland Cement Type-I, ASTM C-150
unless otherwise specified.
Cement shall conform to the following standards as per ASTM C109, C191, C204.
a) Water for normal consistency : 26% to 33%
b) Fineness : Minimum 280 sqm/kg (by air
permeability method)
b-i) Initial setting time, ASTM C191 : Not less than 45 min.
b-ii) Final setting time, ASTM C191 : Not more than 375 min.
c) Minimum compressive strength
c-i) 3 days : 12.4 MPa (1,800 psi)
c-ii) 7 days : 19.3 MPa (2,800 psi)
c-iii) 28 days (optional) : 27.6 MPa (4,000 psi)
Cement shall be delivered in packages as packed by the Manufacturer with the brand name,
type of cement and weight of each bag marked on the bag. Sample test of cement must be
done from the laboratory designated by the Engineer. Two bags from each brand or each
consignment of supply of 50 metric tons of cement shall be selected for testing.
(2) BRICK
Size of Brick shall be 9”x4.5”x2.75”, molded and burnt in a Bull’s Kiln unless otherwise
specified by the terms of the contract.
Bricks shall be table molded with sand, thoroughly and equally burnt throughout without
being vitrified, good substance and shape, square and true and generally of deep red or
copper color, without flews or cracks or other blemishes and having a clear ring when struck.
The dimensions of burnt bricks, unless otherwise specified, shall be used Myanmar local
standard. Bricks shall not absorb more than 1/5th of its dry weight.
The Contractor shall submit enough sample bricks to the Engineer before transportation to
site for his approval. The approved samples shall be kept by the Engineer for the reference
of quality of bricks during construction time.
(3) SAND
Sand shall conform to ASTM C33.
Sand shall be either natural sand, composed of clean, hard, durable uncoated particles
resulting from the disintegration of siliceous and/or calcareous rocks; or manufactured sand
resulting from the crushing of boulders or shingle.
Sand shall be clean and free of injurious amounts of organic impurities; deleterious
substances shall not exceed the following percentages by weight:
Clay Lumps and friable particles - maximum - 3%
Coal and Lignite - 0.25%
Material passing the 0.075-mm (No. 200) sieve - 1%
Shale, coal, soft or flaky fragments - 1%
Sulfur compounds - 0.3%
Organic material content no organic material - (None)
Sand shall be well graded from coarse to fine and shall conform to the following
Fineness Modulus:
Concrete: 2 to 2.5 (Two to Two point five)
Mortar: 1.2 to 1.5
Filling sand : 0.8 to 1.0
Sand from different sources of supply shall not be mixed and stored in the same stockpile
nor used alternately in the work without permission from the Engineer.
The boulder shall be of uniform light color as approved and shall be free of thin laminations,
adherent coatings, and deleterious substances. The wear loss of coarse aggregate of all types
shall not exceed 35% by weight when tested by the Los Angeles Abrasion Test.
(6) WATER
The water for washing aggregate, mixing concrete and mortar shall be clean, potable and
free from objectionable quantities of silt, organic matter, alkali, salt, acids and other
impurities. Sufficient water storage facilities shall be provided to ensure the continuous
operation of concrete placing.
The methods of delivering and storing water shall be subject to the approval of the Engineer.
The water to be used for mixing concrete shall be tested prior to construction work.
The water used to mix concrete shall comply with the following criteria:
The nominal size and cross sectional area and mass are as follows:
Nominal Size Unit Weight per Foot Cross Sectional Area (in2)
(Diameter) (Lb)
3/8” (10 mm) 0.376 0.11
1/2” (12 mm) 0.668 0.20
5/8” (16 mm) 1.043 0.31
3/4” (20 mm) 1.502 0.44
7/8” (22 mm) 2.044 0.60
1” (25 mm) 2.670 0.79
All steel bars prior to its use shall be cleaned with wire brush to make it free from loose
scale, dirt, paint, oil, grease or other foreign substances.
All reinforcing steel shall be stored properly under shed not to be contaminated by oil,
grease or mud.
(2) Material
Fineness modulus of sand shall not be less than 0.8 (zero point eight), shall be clean and free
from organic and other deleterious materials.
(3) Construction Requirements
The fill materials shall be deposited and spread in successive uniform horizontal layers of
about 6” (150mm) thick and compacted by use of mechanical or other approved devices up
to a compaction that satisfy to the Engineer. In filling /back filling against a newly constructed
structure, precaution must be taken so that the structure is well matured to take the thrust of
filling and while filling that against a wall, the filling is done from both sides simultaneously.
1.4 HARDCORE
(1) Description
The work covered by this item shall consist of supplying and providing on top of the earth
to form a sub-base.
(2) Materials
Hardcore shall be broken brick or broken boulders comply with requirements unless
otherwise required by the Engineer.
The broken brick or boulders will have a required hardness in the judgment of the Engineer
so as to meet design requirement.
(3) Construction Requirements
The Hardcore shall be provided level and compacted, dewatered and cleared of all loose
materials.
Hardcore shall be provided flat in surface with sand grouting and shall be well rammed
under lean concrete or anywhere it is necessary in accordance with the drawings. Lean
concrete shall not be provided until the hardcore layer is inspected by the Engineer or the
Engineer’s representative.
The Contractor shall submit the test results to the Engineer for approval. No
reinforcement from a consignment or lot shall be placed in the work without approval
of the Engineer.
(d) Slump Test and Temperature Test of Fresh Concrete
Slump test shall be carried out by the Contractor once for casting day. Slump test shall
be taken in accordance with ASTM C 143-90a. Steel slump test equipment shall meet
with the requirement described in ASTM C 143-90a. Acceptable value of slump for
each part of structure is as shown in the drawing.
The temperature of fresh concrete shall be checked for each batch of fresh concrete by
the Engineer’s representative when concrete placement has been carried out.
(e) Strength Test of Concrete
Mix proportions for desired concrete strength shall be based sampling and strength test
requirements Clause 1.9 of the Technical Specifications shall apply.
[Sampling, Testing and Approval of Concrete Cast in Place]
Six (6) samples for strength tests of each class of concrete placed on major structure
shall be taken not less than
(i) Pile, Foundation, Columns, Beams and Floors
(ii) nor less than once for each 4058.35 Cuft (115 ㎥) casting
(iii) nor less than once for each 5003.4 Sft. (465 ㎡) of surface area for slabs or
walls.
Three (3) samples shall be tested at seven (7) days and other three (3) samples shall be
tested at twenty eight (28) days for compressive strength determinations.
Samples for strength tests shall be taken in accordance with “Method of Sampling
Freshly Mixed Concrete” (ASTM C 172).
The Concrete samples for strength tests shall be moulded by steel and laboratory cured
in accordance with “Practice for Marking and Curing Concrete Test Specimens in the
Field” (ASTM C 31) and tested in accordance with “Test Method for Compressive
Strength of Tube Concrete Specimens” (ASTM C 39).
The 6”samples shall be provided with identification marks (8 characters maximum) and
casting date installed with synthetic paint. The markings should be placed as soon as
the concrete hardens on the top of the Tube (about 18-24 hours after casting).
(i) Arithmetic average of strength of three samples equals or exceeds f ’c.
(ii) No individual strength falls below f ‘c by more than 500 psi.
Strength reduction factor of 85% shall be applied for strength evaluation of
concrete test due to sample shape effect between cylinder shaped and cubic
shaped samples. Therefore average strength of f’c/0.85 shall be necessary as
the required minimum strength of compression test of samples.
The 28 days strength (average of three Tubes) test shall be used as a basis for acceptance
of the concrete placed. Seven (7) days tests are made to obtain advance information on
the adequacy of strength development.
[Investigation of Low- strength test results]
If any strength test of concrete sample of laboratory-cured Tubes falls below specified
value of f’c by more than 500 psi, the Contractor at his own cost and under guidance
of the Engineer shall arrange tests of cores drilled from the area in question in
accordance with “Method of Obtaining and Testing Drilled Cores and Sawed Beams of
Concrete” (ASTM C 42) and the guidelines of ACI 318-95 shall also be applicable in
evaluation of strength of the member. Concrete in an area represented by core tests shall
be considered structurally adequate if the average of three cores is equal to at least 85
percent of f ’c and if no single core is less than 75 percent of f’c. If evaluation of strength
by concrete cores confirms that the structural adequacy of the portion of the structure
remains in doubt, that portion will be removed by the Contractor and fresh concreting
shall be made under the guidance of the Engineer. If, in contrary, the Engineer
determines that the said concrete is located where it will not create an intolerable
detrimental effect on the structure and the Contractor agrees to it, a reduced
Measurement to compensate the Employer for loss of durability and other lost benefits
shall be arranged. The Engineer’s decision in regard to the amount of compensation
shall be final.
(f) Test of Bricks
The bricks to be used shall have the properties as mentioned in Technical Specifications
under clause 7.1.1 and its sub-clauses.
For each consignment not exceeding 10,000 bricks at least six (6) bricks shall be tested
to ascertain the properties listed in Table 2-7.
2.1 FINE AND COARSE AGGREGATE FOR CONCRETE (Sand, Stone Chips)
At least one sample shall be tested for each consignment but not exceeding 275 cubic meter for
fine aggregate (Sand). At least one sample shall be tested for each consignment but not
exceeding 600 cubic meter for coarse aggregate (Stone Chips).
(1) Particle size distribution of fine and coarse aggregates by sieve analysis
(2) Clay lumps and friable particles in aggregates
(3) Organic impurities in fine aggregates
(4) Absorption of fine and coarse aggregates
(5) Unit weight and voids in fine and coarse aggregates
(6) Soundness of aggregates by use of 5 cycles of magnesium sulphate tests
(7) Mica content in fine aggregates
(8) Materials finer than 75 mm (No. 200) sieve in fine aggregates
(9) Sand equivalent value of fine aggregates
(10) Los Angeles abrasion value of coarse aggregates
2.2 BRICK
At least 6 bricks to be tested for each consignment not exceeding 50,000 of brick.
(1) Immersions and Unit weight
(2) Compressive strength
(3) Water absorption
(4) Dimensions (size and shape)
(5) Efflorescence, if necessary (10 bricks)
2.3 REINFORCEMENT
For each consignment not exceeding 20 metric tons at least three representative samples of
each size of reinforcement shall be tested.
(1) Actual Diameter (Cross Section Area)
(2) Unit Weight/ meter
(3) Yield or 0.2% Proof strength test
(4) Ultimate tensile strength test
(5) Percent Elongation
(6) Measurement of Deformation
2.4 CEMENT
At least 2 bags from each brand of cement shall be tested for each consignment but not
exceeding 50 metric tons.
(1) Compressive strength of hydraulic cement mortars using 2” or 50 mm cube specimens. (3,
7, 28 days)
(2) Initial time of setting of hydraulic cement by vicat needle
(3) Final time of setting of hydraulic cement by vicat needle
(4) Fineness of Portland cement by air permeability apparatus
2.5 CONCRETE
(1) Temperature for fresh concrete (For each batch)
(2) Slump Test for fresh concrete (Once for casting day)
(3) Compression Strength Test
(4) For all concrete work, at least 2 (two) sets of 3 (three) samples of concrete for each casting
day shall be preserved and tested to for 7 days and 28 days compressive strength.
3. PLUMBING WORKS
3.1 PIPING REQUIREMENT
All pipes shall be jointed with fittings compatible with the pipe and of the suitable type for
intended service.
Union joints shall be properly provided in piping to allow disassembly of the piping into
reasonable length for handling.
Flanges shall be provided for pipes. Full face rubber gasket shall be provided for all flanged
joints. All piping shall be fitted and assembled to introduce minimum stress to the pipe and
fittings. All pipe shall be supported where shown on the Drawings or as directed by the
Engineer.
All piping to be embedded shall be tested and approved by the Engineer prior to being
embedded.
Check-outs shall be provided where pipe passes through concrete structure, concrete block or
brick structure. The space shall be filled with suitable materials. Where pipe passes through a
wall or floor where water tightness is required, the space shall be filed with yarn and lead or
with approved expanding grout.
All embedded pipes in the ground.
(1) Materials: PVC Pipes
Polyvinyl chloride pipes shall conform to JIS K6742 and / or K6741 or Class 13.5
(Myanmar Standard) and be laid and jointed in accordance with the manufacturer’s
instructions and to the Engineer’s satisfaction.
After the pipes have been laid, they shall be left exposed, hunched or surrounded in concrete
or covered with spoil as required on the Drawings. Where covering with spoil is done, care
shall be taken to prevent damage due to large stone striking the pipe by removing large
stones from the layer of spoil immediately against the pipe or by other means.
(2) Plumbing Fixtures
Plumbing fixtures shall be obtained from a reputable supplier and the Contractor shall
submit catalogues for approval of the Engineer.
Generally, all fixtures except water closets shall have the water supply above the rim. Angle
stops, straight stops, stops integral with the faucets or concealed and installed type loose-
key pattern stops for supplies shall be furnished and fittings. Exposed fixtures trimmings
and fittings shall be chromium-plated or nickel-plated brass with polished, bright surfaces.
(3) Fixture connections
Where space conditions shall not permit standard fittings in conjunction with the cast iron
floor flange, special short-radius fittings shall be provided. Connections between
earthenware fixtures and flanges on soil pipe shall be made absolutely watertight with a
closet settings compound or with a neoprene gasket and seal.
Wall-hung fixtures shall be fastened to the wall by through bolts where practical. For solid
concrete or masonry and where through bolting are not practical, the fixtures shall be
fastened with machine-bolt expansion shields or stud-type expansion bolts. For concrete
masonry unit construction, fixtures shall be fastened with through bolts or toggle bolts as
required.
(4) Testing of Sewage and Waste Water Pipe
No pipe shall be cover before it is tested. Before the pipelines are to be tested the Contractor
shall obtain approval of the Engineer.
All openings and pipe ends shall be securely plugged and filled with water up to the top
highest opening. The water shall remain at the same level for 2 hours.
All pipes shall also be inspected visually to ensure that there is no projections in the pipe
and the pipeline is straight and void of abrupt kinks.
Exposed pipes shall further be subject to a leakage test. Leakage test shall be made only
after a minimum of 24 hours after the pipe has been filled with water. No leakage shall be
found for durations of another 2 hours on the pipe line.
4. ELECTRICAL WORKS
1. Myanmar local practices for electrical design and installation
2. CP5, Singapore code for electrical design of civil buildings
3. Code for lightning system design for building GB50057-95 (2000)
4. CP13, lpc and NFPA13
1 All electrical works carried out comply with the latest local standard code of practice code
of practice for the installation and maintenance of emergency evacuation lighting and
power supply in building.
2 Earthing installation system shall comply with the latest local standard code of practice.
All wiring shall be in concealed conduit/trunking unless otherwise approved by consulting
engineers.
3 The mounting height of all 13A switched socket outlet shall be at 4’6” from finished floor
and 15A switched socket outlet shall be at 1’6” under the ceiling or slab.
4 The positioning of all lighting luminaries, switch socket outlets distribution boards etc. As
shown in the drawings are approximate only. The exact positions shall be determined on
site.
5 The electrical contractor shall be responsible for the electrical load balancing and labeling
of all equipment and switchboards throughout the installation.
6 The electrical contractor shall be responsible to liaise with the local authority for all
clearance, cable jointing, testing and electricity metering for the installation.
7 The overall resistance for the earthing system (electrical) shall be less than 0.1 ohm and in
any case shall comply with the local authority’s latest requirements.
8 All discharge lighting luminaires shall be complete with built-in control gear, lamp, low-
loss ballast, etc.
9 The electrical contractor shall be responsible for sealing of all cable penetration openings
between floor slab and walls etc. With approved fire rating material/sealant to consulting
engineer’s approval.
10 Electrical contractor shall be responsible for sealing of all cable penetration openings
through roof wall with approved water-proof materials after the installation of cables.
11 Electrical contractor shall provide enclosures for electrical data services as when and where
to architects/consulting engineer’s approval.
Unless otherwise stated, all electrical installation as shown in the drawing are to be carried
out by the electrical contractor.
12 All fluorescent lighting luminaires shall be complete with low loss Ballast, color 84 tubes,
etc. Unless otherwise stated.
13 The electrical contractor shall backfill the manholes and draw pits with sand to comply
with technical specifications.
14 All cables to be laid in GI pipes with prevent paint encased in concrete when laid across
the driveway.
15 All electrical panel be completed with protection:
(i) Earth leakage circuit breaker shall be provided for distribution boards rated at
60amps and below
(ii) Incoming and outgoing indicating lights and earth leakage relay shall be provided
for distribution boards rated above 60amps
(iii) Incoming and outgoing indicating lights, earth leakage relay voltmeter shall be
provided for distribution rated 100amps and above
(iv) Incoming and outgoing indicating lights, earth fault relay, overcurrent relay,
ammeter and voltmeter shall be provided for distribution board rated 300amps and
above
(v) Ammeter shall be provided for all outgoing circuit.
16 Fire rated cable shall be used for all essential circuit wiring unless otherwise stated.
17 All underground wiring shall be of pvc/swa/pvc cable (in GI pipe for hard ground/
pavement).
18 It is the contractor’s responsibility to provide earth fault and overcurrent tripping
discrimination between the switch boards with the local authority incoming feeder to
comply with the local authority/consultants latest requirements.
19 Electrical contractor shall be responsible for the equipotential earthing bonding to all metal
parts completed by the other trades to the nearby electrical panel accordance with the latest
local standard code of practice.
20 All wiring to lighting luminaires shall comprise of approved floor slab and ceiling for
indoor installation and weatherproof junction box for outdoor installation. Connection to
light fixture shall be by means of PVC sheathed flexible cable for normal supply, fr cable
for emergency supply and armoured cable for outdoor installation.
21 All lighting pole specified shall comprise of rail mounted 10a mcb in the compartment.
22 Outdoor installation shall be in heavy duty UPVC pipes. (waisal)
23 MCB’s rated < 100a protecting cables supplying loads with high switch-on current (e.g.
motors, hid lamps, etc.) Shall have type “c” magnetic curve rating unless otherwise
indicated in the plans.
24 The electrical contractor shall furnish all necessary labor, materials and equipment for
satisfactory completion of the entire electrical installation as generally described in the
specification and/ or shown on drawings.
25 All locations of equipment and cable routes shown on the drawing are approximate. The
exact locations must be coordinated on site before installation. Fully co-ordinate shop
drawings must be submitted to the architect for approval before commencement of work.
26 All switchboards and distribution boards shall be constructed in accordance with the latest
local standard specifications and to the approval of local supply authority. They shall be
painted with a coat of anti-rust paint and two coats of semi-gloss teak paint of best quality
to the approval of the architect.
27 All conduit pipes which input in the floor slab and wall.
28 All conduits shall comply with the latest local code and minimum size shall not be less
than 20mm.
29 Phase segregation shall comply with the latest requirements of the iee wiring regulations.
Separate conduits shall be used for cables of different circuit categories. For 3 phase final
circuits, separate conduits shall be used for different circuits.
30 All lighting points shall be provided with circuit protective conductors and all metal parts
shall be continuously earthed throughout.
31 The electrical contractor shall supply and install all light luminaires as shown on the
drawings. Each fitting shall have its own independent support regardless of surface,
recessed or suspended mounting.
32 Each circuit shall be tested for grounds and shorts by means of a megger insulation
resistance testing instrument applying a voltage of not less than 500v d.c. upon circuit
under test.
33 Cables for essential circuits such as emergency lighting circuits and firefighting equipment
circuits etc shall not be drawn into the same conduit intended for normal circuits as per iee
wiring regulation.
34 Cables for extra low voltages circuits such as public address system circuits, security
system circuits shall not share the same conduit with normal circuits as per the latest iee
wiring & local regulation.
35 For single phase supply, circuits of different phases shall not share the same conduit.
36 All shunt trip releases of acb's in the main electrical switchboard shall be rated at 30v dc.
A battery supply of sufficient capacity shall be provided for the tripping of acb’s, capacity
of battery shall be submitted for the architect's approval prior to installation.
37 All earth tests shall be carried out with a 1000v megger test instrument and in accordance
with the latest requirements of the iee wiring regulations.
38 The lightning protection system shall comply with the requirements of the latest local code
of practice and installed to the satisfaction of the architect.
39 The electrical contractor shall ensure that power supply is adequately provided to suit the
system requirements.
40 All switched socket outlets in the room shall be metal clad unless otherwise stated.
41 Equipotential bonding shall be provided in all toilets.
42 All electrical works from the mains up to outlet points are to be executed by the electrical
contractor. For rough-ins, a 2m cable and waterproof conduit length is to be made available
by electrical contractor for purposes of connection to equipment.
43 Electrical contractor to furnish and install the following : all junction boxes, electrical
outlets, switches, etc, not built into fixtures or equipment. All electrical outlets, junction
boxes, etc, which are in close proximity (1.5m) of wet operational stations are to be
waterproof. B) all plugs and cords shall be rated as per the latest local codes for fabricated
equipment.
44 All power outlet, lighting, telephone, tv, data, etc, locations shown are approximate only
and the electrical consultant/contractor must coordinated with architect, interior designer,
kitchen and laundry equipment supplier.
45 As shown on drawing, the contractor shall supply and install the conduit pipe.
46 A copper tab of conductor shall be provided on the roof as form a mash network connected
to the structure column to earth. The impedance of the lightning system shall be not more
than 1 ohm.
47 The impedance of system earthing such as electrical earthing, lightning earthing, fire
protection system earthing, common earthing shall not more than 1 ohm.
48 All exposed conductive and metallic parts such as metallic pipework, door, window frame
and accessory shall be bonded with the earth conductor.
49 AC system, earthing system and earth conductor shall be comply with China code of
electrical regulation requirement.
50 The earthing system of new switchboard shall be connected to the existing earthing system.