ULS SHEAR CHECK FOR CIRCULAR PILE

SECANT PILE
Design BM
working moment 1100 KN-m/m
working moment per pile 1826 KN-m
FOS 1.5 Water level at actual level
uls design moment 2739 KN-m
Grade of concrete Fck= 40 Mpa
Reduce strength of concrete Fck= 32 Mpa
dia of pile 100 mm
Spacing In pile 1.66 m
clear cover 40 mm
yield strength of main steel 500 Mpa
yield strength of shear steel 415 Mpa
min percentage of r/f 0.4 % Min R/F is provided
min area of steel req 31.4159265359 mm2
pu/fckD2 0
Mu/fckD3 85.59375
d'/D
p/fck 0.125 Refer chart 60 SP 16
% of steel 4%
ast req 314.159265359 mm2 Spacing -20mm
bar dia 25 mm for bundled -41mm
no of bar 16 Nos
bar dia 32 mm
no of bar 16 Nos
ASTprovided 20721.94514308 mm2 ök 263.84%
Youngs modulus of Elasticity of RCC pile 28284271.24746
M.I. of pile 4.908738521E-06 m4
Moment of Inertia (M.I) per m Run of Wall 2.957071398E-06 m4
Input Cracked Momment of Inertia in wallap 58.54702667001 m4
Provide 16 Nos of 25 mm dia bar and 16 Nos of 32 mm dia bar as main R/F in pile
Design SHEAR FORCE
Horizontal shear force V= 160 kN/m
Design horizontal shear force Vu= 398.4 kN
Vertical force Pu= 0 kN #N/A
Dia of stirrups 12 mm
no of legs 2 mm
Dia of pile D= 100 mm
grade of steel for stirrups Fy= 415 Mpa
Ast Provided Ast= 20721.94514308 mm2
Clear cover 40 mm
Dia of main R/F 25 mm
Eff Area of tensile r/f 50% 10360.97257154 mm2
% of main steel provided 263.84 %

AS per clause 5.8.2.9-2 AASHTO LRFD Bridge Design Specification Effective depth to be
Consider in shear check

Dr= dia of circle passing through the centre of longitudinal R/F


Dr -29 mm
de 40.8 mm `
Dv 37 mm
% of tensile R/F 280.03 %
Horizontal shear stress Tv 107675.68 kN/m2
Ʈv=Vu/(bv.dv) 107.68 kN/mm2
Permissible shear force in concrete #N/A table 19 Is 456

= 1 + (3*0)/(area of
enhancement factor due to axial load pile*32) 1 cl 40.2.2 IS 456
Modified shear strength of concrete Ʈc #N/A MPA
final permissible stress #N/A kN/m2

CHECK: #N/A
Spacing of shear R/F Required
Vs #N/A
Asv 226.19
fy 415 MPA

Spacing of shear R/F Req SV sv #N/A mm cl 40.4 IS 456

#N/A

Design

Main R/F Provide 16 Nos of 25 mm dia bar and 16 Nos of 32 mm dia bar as main R/F in pile

Shear R/F #N/A


ULS SHEAR CHECK FOR CIRCULAR PILE

SYSTRA SECANT PILE UGC_1


Design BM
working moment 700 KN-m/m
working moment per pile 910 KN-m
uls design moment 955.5 KN-m
Grade of concrete Fck= 25 Mpa
Reduce strength of concrete Fck= 20 Mpa
dia of pile 800 mm
Spacing In pile 1.3 m
clear cover 50 mm
yield strength of main steel 500 Mpa
yield strength of shear steel 415 Mpa
min percentage of r/f 0.4 %
min area of steel req 2010.619 mm2
pu/fckD2 0
Mu/fckD3 0.074648
d'/D 0.09
p/fck 0.074648 As no axial load, Pu/FckD2 value is taken
% of steel 1.492969 %
ast req 7504.479 mm2
bar dia 25 mm
no of bar 11 Nos
bar dia 25 mm
no of bar 11 Nos
ASTprovided 10799.22 mm2 ök

Provide 11 Nos of 25 mm dia bar and 11 Nos of 25 mm dia bar as main R/F in pile
Design SHEAR FORCE
Horizontal shear force V= 559 kN/m
Design horizontal shear force Vu= 763.035 kN
Vertical force Pu= 0 kN
Dia of stirrups 16 mm
no of legs 2 mm
Dia of pile D= 800 mm
grade of steel for stirrups Fy= 415 Mpa
Ast Provided Ast= 10799.22 mm2
Clear cover 50 mm
Dia of main R/F 25 mm
Eff Area of tensile r/f 50% 5399.612 mm2
% of main steel provided 2.148438 %
AS per clause 5.8.2.9-2 AASHTO LRFD Bridge Design Specification Effective
depth to be Consider in shear check

Dr= dia of circle passing through the centre of longitudinal R/F


Dr 692 mm
de 620.4 mm `
Dv 558 mm
% of tensile R/F 1.21 %
Horizontal shear stress Tv 1709.31 kN/m2
Ʈv=Vu/(bv.dv) 1.71
Permissible shear force in concrete = 1 + (3*0)/(area of 0.66 table 19 Is 456
enhancement factor due to axial load pile*20) 1 cl 40.2.2 IS 456
Modified shear strength of concrete 0.66 MPA
final permissible stress 658.56 kN/m2

CHECK: SHEAR REINFORCEMTNT REQUIRED


Spacing of shear R/F Required
Vs 672477.6
Asv 402.12
fy 415 MPA

Spacing of shear R/F Req SV sv 170 mm cl 40.4 IS 456

Provide 2 legged 16 mm dia stirrups @170 mm c/c spacing as shear R/F in pile

Design

Main R/F Provide 11 Nos of 25 mm dia bar and 11 Nos of 25 mm dia bar as main R/F in pile

Shear R/F Provide 2 legged 16 mm dia stirrups @170 mm c/c spacing as shear R/F in pile
Calculation of Stiffness provided for outer station wall

b 1 considering per metre


d 1

Area = 3I/L^3 height


Area = 0.1878287 1.1
0.07407407 1.5
0.03125 2
0.016 2.5
0.00925926 3
0.0058309 3.5
0.00390625 4
0.00274348 4.5
0.002 5
0.00150263 5.5
0.00115741 6

308.8235294
1203.54227 1.243828352

Grade of steel 500


grade of concrete 20 25 30 35 40
bond stress 1.2 1.4 1.5 1.7 1.9
Defrom bar 1.6 1.92 2.24 2.4 2.72 3.04

LD* dia 56.64 48.55 45.31 39.98 35.77


Bar Dia 10 mm 570 mm 490 mm 455 mm 400 mm 360 mm

30 45.3125
32 43.18014706
35 39.98161765
mu due to slenderness 45.31749 2104 3156
0.8
17.175
248.2557
372.3835 2620.8

45.53