Professional Documents
Culture Documents
Properly gathering, recording information will pay off in the long run
between each pair 1-4,
2-5, 3-6. The resistance
from leads 7, 8 or 9 to lead 1
0 should all be the same
and should match that 4
of leads 1-4, 2-5, and 3-6.
There will be continuity 7
between leads 7, 8, 9 and 0
and the resistance between
leads 7-8, 8-9 and 9-7 will
9 85
be twice the values of the
previous test.
6
Many large alternators
3 0 2
have 12 or 24 external
By Tom Bishop, P.E. leads. For the purposes of
EASA Senior Technical Support Specialist using EASA’s internal con-
nection diagrams, these
We will begin this article by clarify- can be considered wye- Figure 1. Lead numbering for a 10-lead alternator.
ing the terms “alternator” and “gen- delta 12-lead connections.
erator.” Both terms refer to a machine The 24 leads consist of
that converts mechanical to electrical leads that will be paired
power. An alternator is a synchronous to result in 12 leads. Al-
machine that converts mechanical to though most alternators
AC electrical power. A generator is a utilize external wye con-
more general term and is a machine nections (to provide a neu-
that converts mechanical to electrical tral), there are cases where
power, either AC or DC. An alternator the alternator output is
is always a generator, but not vice- delta connected. These
versa. Our focus in this article will possibilities reinforce the
be on 3-phase alternators. However, need to carefully record
much of the information provided also the complete as-received
applies to single-phase alternators and connections. See Figure 2.
single- or three-phase generators. If there are leads in addi-
tion to the main winding
Identify the leads output, they may be taps Figure 2. Note the apparent random arrangement of leads
The initial step in the rewind data used to provide voltage for and connections, necessitating great care when
taking process is to determine the control circuits such as for recording the connections.
number of leads and their identifi- the voltage regulator. See
cation. Consider this example: The the section on determining the inter- size that would be determined from
main stator of an alternator has 10 nal connections for further guidance. a lead wire ampacity table. This is
leads, with numbers 0 through 9. See Note: Numerical lead labeling particularly the case with alternators
Figure 1. The “0” lead is probably the is common with North American rated for less than continuous, e.g.,
neutral; however, the lead identifica- alternators, and alphabetical (letter) standby duty. Record the as-received
tion should be verified. If that is the or alphanumeric lead identifications lead wire size if it is marked on the
case, the alternator has an internal are commonly found on alternators leads. If the leads are not marked, slip
wye or multiple internal wyes and the manufactured to IEC standards. a terminal lug that fits snugly onto the
lead coming from it is labeled “0.” To leads, thereby using the lug as sizing
confirm this, we need a low-resistance
Determining lead wire size guide to determine the correct lead
ohmmeter. There will be continuity The lead wire size used on an al-
between the four leads 7-8-9-0, and ternator is frequently smaller than the
Continued On Page 2
May 2010 • EASA CURRENTS Copyright © 2007-2010 Electrical Apparatus Services Association, Inc. 1
Taking winding connection data on alternators
Properly gathering, recording information will pay off in the long run
Continued From Page 1
wire size. Note: Lugs are not sized for ficult and frequently
lead cable, so the correct lug will be not possible. It is much
snug to very tight. better to carefully take
connection data rather
Determine the internal than have to purchase
connections a replacement stator
Prior to the burnout process, it is or complete alterna-
a good practice to lift and completely tor if the correct and
identify the connections. If there are complete connection
leads other than output power leads, information was not
such as main winding taps for a control obtained during the
circuit or leads for an auxiliary wind- data taking process.
ing, these need to be identified, and After identifying
their position in the winding located. and labeling all of the
See Figures 3 and 4. Label every lead: main external leads
main winding, taps, auxiliary, etc. with from the winding, pro-
identification that will withstand the ceed to do the same
burnout process. with any taps or aux-
Draw the winding connection be- iliary winding leads.
fore the burnout process and verify If there are taps, count
that it is correct. Most but not all al- the number of coils Figure 3. Example of an alternator with 10 main leads and
ternators are synchronous machines between the tap and
4 tapped connections (20, 22, 24 and X1).
having a rotor with wound poles the associated main
supplied by direct current (DC). A lead. Likewise, count
straightforward but important check the number of coils
is to confirm that the winding poles from the tap to the
match the number of wound poles on nearest non-output
the synchronous rotor. lead, most often a
Connection data for alternators is lead that is used to
frequently not available from the origi- form a wye connec-
nal manufacturer. In some cases the tion. In many cases
manufacturer name on the alternator the tap is within a coil.
nameplate is not the actual alternator Therefore, count the
manufacturer, making the task of ob- number of turns to the
taining original information more dif- tap. See the July 2004
Currents article titled
It is much better to “Powering Up: Deter-
mining Where To Tap
carefully take con- Stator Windings” for
nection data rather detailed instructions
than have to purchase to identify and locate
a replacement stator tap locations. Note: If Figure 4: An alternator with 12 main leads and 6 tapped
the winding is tapped, connections.
or complete alterna-
it may be prudent to
tor if the correct and Draw the connection diagrams of the
burn out the stator without first cut-
complete connection ting off the coil end. main and auxiliary windings referenc-
information was not If there is an auxiliary winding, ing coil and lead positions relative to
obtained during the data permanently label a slot as “slot #1.” A slot #1. Relative to the main winding,
taking process. good place to do this is the slot where and to slot #1, the auxiliary winding
the main winding lead #1 is located. Continued On Page 3
2 May 2010 • EASA CURRENTS Copyright © 2007-2010 Electrical Apparatus Services Association, Inc.
Taking winding connection data on alternators
Properly gathering, recording information will pay off in the long run
Continued From Page 2
May 2010 • EASA CURRENTS Copyright © 2007-2010 Electrical Apparatus Services Association, Inc. 3
Taking winding connection data on alternators
Properly gathering, recording information will pay off in the long run
Continued From Page 2
the original type of connection, which and current densities are maintained. CMA to a value that may be too low
is usually wye for the 3-phase line-to- One practical alternative solution is to even for standby duty. Voltage changes
line output. And check that the desired wind two sets of coils, each using half from a higher voltage such as 4160 volts
number of new circuits is possible. the needed wires in hand, lay them in to a lower voltage such as 480 volts
For example, if the original connec- exactly the same slots, then parallel may also be problematic. The theoreti-
tion of a 6-pole generator was 2 wye, the two sets. cal conversion often requires fractional
a doubling to 4 wye would require an turns such as a combination of 1 and 2
impossible connection.
Voltage changes turn coils that are not practical to use. A
It is a good practice to use the Proceed cautiously with requests to coil with 2 turns would have only about
EASA AC Motor Verification and change the voltage rating of an alterna- 50% of the CMA of the 1 turn coil and
Redesign Program when performing tor. If the machine is rated 600 volts or would probably overheat. In some cases
changes such as doubling the circuits less, a change to a higher voltage such as the conversion results in a fractional turn
to reduce wires in multiple. The pro- 4160 volts will probably not be feasible much less than 1, making it impossible
gram has built-in checks to prevent even if the original winding had formed to convert. n
selection of circuits that can’t be used. coils. The reason is that the higher volt-
It also confirms that the magnetic flux age rating requires much more coil to
ground insulation, thus reducing the
4 May 2010 • EASA CURRENTS Copyright © 2007-2010 Electrical Apparatus Services Association, Inc.