SECTION 6 • INSTALLATION .................................................................................................................. 6-1
General .................................................................................................................................................. 6-1
Hardware ................................................................................................................................................ 6-1
Mounting ................................................................................................................................................ 6-1
Connections ........................................................................................................................................... 6-3
Terminations ....................................................................................................................................... 6-3
Operating Power ............................................................................................................................. 6-3
Generator Current Sensing............................................................................................................. 6-3
Generator Voltage Sensing ............................................................................................................ 6-4
Bus Voltage Sensing ...................................................................................................................... 6-4
Analog Engine Sender Inputs ......................................................................................................... 6-5
Emergency Stop Input .................................................................................................................... 6-5
Magnetic Pickup Input .................................................................................................................... 6-7
Contact Sensing Inputs ................................................................................................................... 6-7
Output Contacts .............................................................................................................................. 6-8
USB Interface ................................................................................................................................. 6-8
RS-485 Communication Port .......................................................................................................... 6-9
CAN Bus Interface .......................................................................................................................... 6-9
Modem .......................................................................................................................................... 6-10
RDP-110 Connections .................................................................................................................. 6-10
Connections for Typical Applications ............................................................................................... 6-11
Three-Phase Wye Connections for Typical Applications ............................................................. 6-12
Three-Phase Delta Connections for Typical Applications ............................................................ 6-13
Single-Phase A-B Connections for Typical Applications .............................................................. 6-14
Single-Phase A-C Connections for Typical Applications .............................................................. 6-15
Connections with AEM-2020, CEM-2020, and LSM-2020 ............................................................... 6-20
Installation for CE Systems .................................................................................................................. 6-20
Installation in a Salt Fog Environment ................................................................................................. 6-20
Installation in an Ungrounded System Application .............................................................................. 6-20
Figures
Figure 6-1. Panel Cutting and Drilling Dimensions .................................................................................... 6-1
Figure 6-2. Overall Dimensions ................................................................................................................. 6-2
Figure 6-3. Emergency Stop Input Connections ....................................................................................... 6-5
Figure 6-4. Interposing Relay Diagram ..................................................................................................... 6-6
Figure 6-5. Emergency Stop Input Connections (Optional Wiring Method) .............................................. 6-6
Figure 6-6. Interposing Relay Diagram (Optional ESTOP Wiring Method) ............................................... 6-7
Figure 6-7. CAN Bus Interface with DGC-2020 providing One End of the Bus ...................................... 6-10
Figure 6-8. CAN Bus Interface with Optional AEM-2020 providing One End of the Bus ........................ 6-10
Figure 6-9. Three-Phase Wye Connections for Typical Applications (Hardware Version 3) .................. 6-12
Figure 6-10. Three-Phase Delta Connections for Typical Applications (Hardware Version 3) ............... 6-13
Figure 6-11. Single-Phase A-B Connections for Typical Applications (Hardware Version 3) ................. 6-14
Figure 6-12. Single-Phase A-C Connections for Typical Applications (Hardware Version 3) ................. 6-15
Figure 6-13. Three-Phase Wye Connections for Typical Applications (Hardware Versions 1 and 2) .... 6-16
Figure 6-14. Three-Phase Delta Connections for Typical Applications (Hardware Versions 1 and 2) ... 6-17
Figure 6-15. Single-Phase A-B Connections for Typical Applications (Hardware Versions 1 and 2) ..... 6-18
Figure 6-16. Single-Phase A-C Connections for Typical Applications (Hardware Versions 1 and 2) ..... 6-19
Figure 6-17. DGC-2020, AEM-2020, CEM-2020, LSM-2020 CAN Bus Connections ............................. 6-20
Tables
Table 6-1. Operating Power Terminals ..................................................................................................... 6-3
Table 6-2. Generator Current Sensing Terminals ..................................................................................... 6-4
Table 6-3. Generator Voltage Sensing Terminals ..................................................................................... 6-4
Table 6-4. Bus Voltage Sensing Terminals ............................................................................................... 6-4
9400200990 Rev Z DGC-2020 Installation i
Table 6-5. Sender Input Terminals ............................................................................................................ 6-5
Table 6-6. Emergency Stop Input Terminals ............................................................................................. 6-5
Table 6-7. Magnetic Pickup Input Terminals ............................................................................................. 6-7
Table 6-8. Contact Sensing Inputs ............................................................................................................ 6-7
Table 6-9. Programmable Output Contact Terminals ................................................................................ 6-8
Table 6-10. RS-485 Communication Port Terminals ................................................................................. 6-9
Table 6-11. CAN Bus Interface Terminals ................................................................................................. 6-9
Table 6-12. RDP-110 Interface Terminals ............................................................................................... 6-11
Table 6-13. Typical Connection Diagram Cross-Reference .................................................................... 6-11
Hardware
DGC-2020 controllers are packaged for mounting in any top-mount enclosure. The front panel is resistant
to moisture, salt fog, humidity, dust, dirt, and chemical contaminants. DGC-2020 controllers are mounted
using the four permanently attached 10-24 studs. The torque applied to the mounting hardware should
not exceed 25 inch-pounds (2.8 Newton meters).
Mounting
Panel cutting and drilling dimensions are shown in Figure 6-1. The horizontal drilling measurement of
10.75 inches has a tolerance of +0.01/–0.01 inches. The horizontal cutout measurement of 10.38 inches
has a tolerance of +0.04/-0 inches. The vertical drilling measurement of 7.25 inches has a tolerance of
+0.01/-0.01 inches. The vertical cutout measurement of 6.88 inches has a tolerance of +0.04/-0. Overall
dimensions are shown in Figure 6-2. All dimensions are shown in inches with millimeters in parenthesis.
NOTES
Be sure that the DGC-2020 is hard-wired to earth ground with no smaller than
12 AWG copper wire attached to the chassis ground terminal (terminal 1) on
the rear of the controller.
Operating power from the battery must be of the correct polarity. Although
reverse polarity will not cause damage, the DGC-2020 will not operate.
For the DGC-2020 to correctly meter power factor, the generator must be
rotating clockwise (A-B-C).
Terminations
All DGC-2020 terminals are located on the rear panel of the controller. There are three types of interface
terminals: a mini-B USB socket, plug-in connectors with screw-down compression terminals, and quarter-
inch, male, quick-connect terminals. DGC-2020 hardware version 3 controllers with style number
xxxxxExxx are equipped with an RS-232 port. This port allows communication with an external, user-
supplied modem with dial-in and dial-out capability. DGC-2020 hardware versions 1 and 2 with style
number xxxxxMxxx are equipped with an internal modem with dial-in and dial-out capability.
The mini-B USB socket mates with a standard USB cable and provides local communication between the
DGC-2020 and a PC running BESTCOMSPlus® software.
The majority of DGC-2020 connections are made with 15-position connectors with screw-down
compression terminals. These connectors plug into headers on the DGC-2020. The connectors and
headers have a dovetailed edge that ensures proper connector orientation. Each connector and header is
uniquely keyed to ensure that a connector mates only with the correct header. Connector screw terminals
accept a maximum wire size of 12 AWG. Maximum screw torque is four inch-pounds (0.45 N•m).
Connections to the DGC-2020 starter, fuel solenoid, and glow plug output contacts are made directly to
each relay through quarter-inch, male, quick-connect terminals. Amp part numbers 154718-3 (positive-
lock receptacle) and 154719-1 (nylon housing) are the recommended components for making
connections at these terminals.
DGC-2020 terminal groups are described in the following paragraphs.
Operating Power
The DGC-2020 operating power input accepts either 12 Vdc or 24 Vdc and tolerates voltage over the
range of 6 to 32 Vdc. Operating power must be of the correct polarity. Although reverse polarity will not
cause damage, the DGC-2020 will not operate. Operating power terminals are listed in Table 6-1.
To follow UL guidelines, a 5A maximum, 32 Vdc supplementary fuse must be implemented in the battery
input circuit to the DGC-2020.
NOTE
Unused current sensing inputs should be shorted to minimize noise pickup.
ESTOP (46)
DGC-2020
ESTOP (47)
P0066-19
NOTE
Units with a board number (located on back of the unit) lower than
9400201139 may experience problems associated with ESTOP wire lengths
greater than 2 feet (0.6 m). An interposing relay, connected as shown in Figure
6-6, alleviates potential problems.
ESTOP (46)
Relay
DGC-2020
ESTOP (47)
P0066-18
Figure 6-4. Interposing Relay Diagram
The relay is the type that when the coil is NOT energized, the contacts are
open. When the coil is energized, the relay contacts are closed. The ESTOP
button is normally closed (i.e. closed when it is NOT pushed). The relay coil is
always energized when the ESTOP switch is closed (NOT pushed), so relay
contacts are closed in normal operation. When the ESTOP button is pushed,
the ESTOP switch opens, so relay contacts open, shutting down the unit.
ESTOP (46)
DGC-2020
ESTOP (47)
P0066-20
NOTE
Units with a board number (located on back of the unit) lower than
9400201139 may experience problems associated with ESTOP wire lengths
greater than 2 feet (0.6 m). An interposing relay, connected as shown in Figure
6-6, alleviates potential problems.
ESTOP (46)
Relay
DGC-2020
ESTOP (47)
P0053-93
Figure 6-6. Interposing Relay Diagram (Optional ESTOP Wiring Method)
The relay is the type that when the coil is NOT energized, the contacts are
open. When the coil is energized, the relay contacts are closed. The ESTOP
button is normally closed (i.e. closed when it is NOT pushed). The relay coil is
always energized when the ESTOP switch is closed (NOT pushed), so relay
contacts are closed in normal operation. When the ESTOP button is pushed,
the ESTOP switch opens, so relay contacts open, shutting down the unit.
Output Contacts
The DGC-2020 has three sets of fixed-function output contacts: Pre, Start, and Run. The Pre contacts
supply battery power to the engine glow plugs, the Start contacts supply power to the start solenoid, and
the Run contacts supply power to the fuel solenoid. Connections to the three sets of contacts are made
directly at each relay using female, quarter-inch, quick-connect terminals. Amp part numbers 154718-3
(positive-lock receptacle) and 154719-1 (nylon housing) are the recommended components for making
connections at each relay. For the location of the Pre, Start, and Run relays refer to Figure 2-2.
Depending on the style number of the DGC-2020, either 4 or 12 sets of programmable output contacts
are provided. Four programmable outputs are provided on DGC-2020 controllers with a style number of
xxAxxxxxx. Twelve programmable outputs are provided on controllers with a style number of xxBxxxxxx.
Programmable output contact terminals are listed in Table 6-9.
USB Interface
A mini-B USB socket enables local communication with a PC running BESTCOMSPlus software. The
DGC-2020 is connected to a PC using a standard USB cable equipped with a type A plug on one end
(PC termination) and a mini-B plug on the other end (DGC-2020 termination).
NOTES
1. If the DGC-2020 is providing one end of the J1939 bus, a 120 Ω, ½ watt
terminating resistor should be installed across terminals 48 (CANL) and 49
(CANH).
2. If the DGC-2020 is not part of the J1939 bus, the stub connecting the
DGC-2020 to the bus should not exceed 914 mm (3 ft) in length.
3. The maximum bus length, not including stubs, is 40 m (131 ft).
4. The J1939 drain (shield) should be grounded at one point only. If
grounded elsewhere, do not connect the drain to the DGC-2020.
CAN-H
DGC-2020 Engine
CAN-L
P0053-95
120 ohm 120 ohm
Termination Termination
Other LSM-2020
Devices (Optional)
Figure 6-7. CAN Bus Interface with DGC-2020 providing One End of the Bus
CEM-2020
DGC-2020
(Optional)
Bus
Stub
CAN-H
AEM-2020
Engine
(Optional)
CAN-L
P0053-94
120 ohm 120 ohm
Termination Termination
Other LSM-2020
Devices (Optional)
Figure 6-8. CAN Bus Interface with Optional AEM-2020 providing One End of the Bus
Modem
DGC-2020 hardware version 3 controllers with style number xxxxxExxx are equipped with an RS-232
port. This port allows communication with an external, user-supplied modem with dial-in and dial-out
capability. DGC-2020 hardware versions 1 and 2 with style number xxxxxMxxx are equipped with an
internal modem with dial-in and dial-out capability. The modem connects to a standard-device telephone
line through a USOC RJ-11C jack.
RDP-110 Connections
Terminals are provided for connection with the optional RDP-110 remote display panel. These terminals
provide dc operating power to the RDP-110 and enable communication between the DGC-2020 and
RDP-110. Twisted-pair conductors are recommended for connecting the communication terminals of the
DGC-2020 and RDP-110. Communication may become unreliable if the connection wires exceed 4,000
feet.
Table 6-12 lists the DGC-2020 terminals that connect to the RDP-110.
Figure 6-9. Three-Phase Wye Connections for Typical Applications (Hardware Version 3)
Figure 6-10. Three-Phase Delta Connections for Typical Applications (Hardware Version 3)
Figure 6-11. Single-Phase A-B Connections for Typical Applications (Hardware Version 3)
Figure 6-12. Single-Phase A-C Connections for Typical Applications (Hardware Version 3)
GND
CANH DGC-2020
CANL
GND/SHIELD
GND
CANH
CANH AEM-2020
CANL
CANL
GND
CANH CEM-2020
CANL
GND
CANH LSM-2020
CANL
P0053-57