You are on page 1of 31

Q#1 to Q#15 (Project No. 01) Situation 2 - Project No.

01
<<ALL ANSWERS AND ANNOTATIONS BY ARCH.
RAI BASSIG>> Q#6. D. NorthEast (NE)
<<REVIEWER/QUESTIONNAIRE - SOURCE: Similar to Q#36!
UNKNOWN>> Note that the choices given are the actual orientation
where the Amihan wind will originate. If you plot the
*****PROJECT NO. 01***** project site and face the property from the main
RROW, the wind will be coming from the lower right
Situation 1 - Project No. 01 corner of the lot.

Q#1. C. 3 Q#7. D. West, SouthWest (SW) and South perimeters


Refer to IRR of PD1096, Table VII.2, under R-1, Similar to Q#37!
Number of allowable storeys/floors above established Note that the choices given are the actual orientation
grade to buffer the Habagat wind at the direction such wind
will originate (i.e., Southwest). If you plot the project
Q#2. A. 10 site and face the property from the main RROW, the
Refer to IRR of PD1096, Table VII.2, under R-1, BHL wind will be coming from the upper left corner of the
meters above highest grade lot.

Q#3. C. 11 Q#8. C. North and South


Width of 6 lots = TLA of 6 lots (Given) / Depth of 6 lots The cluster street is given at the direction from west
(Given) to east and intersects the main RROW at right angles
Width of 6 lots = 132 sqm / 12m (perpendicular).
Width of 6 lots = 11m
Q#9. A. Right and Left side yards
Q#4. B. deck roof level parapet wall, if introduced Similar to Q#39!
Refer to IRR of PD1096, Glossary, "Height of If you plot the project site, the individual lots will have
Building/Structure - The vertical distance from the its right and left side yards facing the eastern and
established grade elevetion to the highest point of the western directions.
coping of a flat roof, to the average height of the
highes gable, pitch or hip roof, OR TO THE TOP OF Q#10. C. SE to SW and NE to NW
THE PARAPET, IF THE ROOF IS PROVIDED WITH Similar to Q#40!
A PARAPET...xxx..." See Figure VII.1 for illustration. The sun rises in the east and sets in the west,
Refer also to IRR of PD1096, Sec. 707, Item 2, Sub- therefore, the dominant path is east TO west. In the
Item a, Paragraph 2, "BHL EXCLUDES the height of Philippine setting, since the country is located just
permitted/allowed projections above the roof of the above the equator (northern hemisphere), the sun's
building/structure, e.g. SIGNAGE, MAST, ANTENNA, solar angle for most of the year is at the southern
telecom tower, beacons and the like. direction, while some months (around August-
November) the solar angle is slightly angled coming
Q#5. A. 1 to 5 from the northern direction. Therefore the dominant
Refer to IRR of PD1096, Glossary, under Height of path is SE to SW and NE to NW.
Buildings/Structure, "Low-Rise - ONE-STOREY UP
TO 5-STOREYS IN HEIGHT,...xxx..." Situation 3 - Project No. 01
Q#11. B. Homeowners' association office
The other given choices (gameroom, swimming pool,
and clubhouse) can be considered as amenities as it
will increase the value of the property and the living
conditions of the occupants. A homeowners'
association office is considered as a general facility
and does not directly uplift the land value of the
project. Moreover, there are only 10 individual lots
(with 1 lot assuming to be used exclusively for this
amenity provision), so, only 9 single-family dwellings
will comprise the association. 

With this logic, a homeowners' association office will


be too impractical to be built on that individual lot. If
such an office is indeed a necessity, it would be a
better option if such office will be included inside the
clubhouse or on a separate development project
(when the number of clusters have increased).

Q#12. D. Homeowners' association office


See my explanation above (Q#11).

Q#13. D. Overhead Water Tank


Similar to second Q#102 and Q#133!
The Overhead Water Tank pertains to a utility
provision (Plumbing).

Q#14. D. Guest Parking


Similar to Q#103 and Q#134!
The other choices, Generator Room, Domestic Water
Cistern, and STP all pertain to utility provisions
(Electrical, Plumbing and Sanitary Utilities,
respectively).

Q#15. D. Cistern and Sewage Treatment Plant, if


introduced
Similar to Q#104 and Q#135!
A Sewage Treatment Plant (STP) would be required
to be at a certain distance from buildings, trees, and
water sources to avoid contamination as per National
Plumbing Code of the Philippines and the Sanitation
Code of the Philippines. Placing a cistern (water
source) close to the STP would violate this provision.
Q#16 to Q#20 (Project No. 01)
<<ALL ANSWERS AND ANNOTATIONS BY ARCH. On the other hand, choice a. (recreational) can be
RAI BASSIG>> safely applied to the property as MOST of the
<<REVIEWER/QUESTIONNAIRE - SOURCE: PRINCIPAL/ACCESSORY/CONDITIONAL USES
UNKNOWN>> outlined in the NBCP is allowed for an A-1/R-1
development. Since in the design problem, the
Situation 4 - Project No. 01 developer wants to maximize his/her profit, the
recreational facilities in the cluster housing would
Q#16. A. Residential and recreational increase land values of the property.
Although the question might be subjective, I analyzed
the answer based on the 1) Design Problem and 2) Q#17. D. Warm, safe and comfortable
Use and Occupancy permitted as per IRR of PD Another subjective question as all choices can be
1096, Table VII.1. The design problem is located in a correct depending on the person looking at it.
municipality (i.e., low market) of Taytay on a 10% However, I will base my answer on the data given. It
slope (i.e., probable views of nature). The problem states in the design problem that the project is a
also states that the TGFA of the housing units is only CLOSELY-KNIT CLUSTER development. Having a
at 77 sqm. (this will play a factor in eliminating cluster street (i.e., dedicated access road for certain #
choices): of lots) would mean more security. The problem also
states that the project would be EXCLUSIVE - and
Choice d. (Retail) can be safely eliminated since the this would add to the safety of the property. The
use of the property is A-1 and the zone is R-1. As per orientation of the property and sizing of lot cuts
Table VII.1., NONE of the other principal uses or even contribute to the warmth and comfort that will be
accessory or conditional uses of the property allow for experienced by the occupants. Since the zone is R-1,
a commercial/retail structure. In fact, the A-1/R-1 all structures are detached creating air spaces around
use/zone is very specific that structures shall NOT be the building for the natural air to circulate. The yards
used for COMMERCIAL GAIN. would also be a good place to provide vegetation and
shading. The slope of the whole property (at 10%)
Choice b. (business/home office) may be applied BUT means that the end of the lot is elevated at approx.
ONLY FOR ACCESSORY USE and with CERTAIN 6m from the main RROW. This means that each lot is
LIMITATIONS. If one sets up a home office, the code approx. 1.2m higher than the one in front, creating
limits the practice of the professional to have a max. visual connectivity to other parts of the vicinity
of 20% of the floor area of the building to be used as (especially in front).
office. Since the TGFA of a unit is only 77 sqm, 20%
is only 15.4 sqm which is too cramped. Another Q#18. C. Modern with clean but textured lines
limiting factor is the number of assistants that can use All other choices given are detail-intensive, which will
the office which is not more than 3. The code also bring up the cost for design, fabrication, construction,
restricts the number of guests/customers in the and installation. On the other hand, choice C can be
access of the R-1 property. So, given these achieved by using very minimal details and therefore
limitations, the home office setup might not be viable. the most economical among the choices.

Choice c. (entertainment), despite its broad term as to Q#19. C. Horizontal


what type of entertainment facility will be provided, Another very subjective question as all choices can
are NOT found in the principal uses in so far as the A- be correct depending on the taste of the person
1/R-1 property is concerned. viewing it. Again, I will answer the question based on
data given.

On the average, the total buildable footprint of a unit


(considering 4.5m front setback and 2m side and rear
setbacks) would only be 38.5 sqm (i.e., 7m wide x
5.5m deep). At the given TGFA of a unit at 77 sqm,
this means that the proposed unit will be at 2 storeys.
Assuming a floor-to-floor height of about 3m plus
about 2m for roofing/decks/other elevation features,
the building mass of 1 house would be approximately
7m(W) x 5.5m(D) x 8m(H). As seen from the main
RROW (in front of the development), the SHORT
DEPTH of 5.5m of each house will be the main
emphasis. The whole development slopes up from
the RROW towards the end of the property: from 0.00
@ sidewalk to 6.0m @ end. This means that due to
the site's topography even the sides of the houses
behind the other house may be seen in front.
Therefore, with the visible short depths,
HORIZONTAL lines must be emphasized to CREATE
BALANCE based on the bulk of the prototype houses.

Q#20. C. 441
The question might have been phrased out-of-context
as it did not specify if the ceramic tiles will be or will
not be provided for the whole ground floor (including
or excluding the given bathroom dimensions). After
exploring all possible equations given the choices, my
answer was based on the premise that the
BATHROOM FLOORING will be a DIFFERENT tile
than the 0.30m x 0.30m ceramic tile to be used for the
other spaces of the ground floor. So,
Tile Qty. = TGFA (given in the problem) - Area of
Bathroom (given in the problem) / Area of 1 Tile
(given in the problem)
Tile Qty. = [(42.0 sqm) - (1.35m * 1.7m)] / (0.30m *
0.30m)
Tile Qty. = [(42.0 sqm) - (2.295 sqm)] / (0.09 sqm)
Tile Qty. = 39.705 sqm / 0.09 sqm
Tile Qty. = 441.11 or ABOUT 441 PCS
Q#21 to Q#30 (Project No. 01) firewalls are prohibited. Since the perimeter property
<<ALL ANSWERS AND ANNOTATIONS BY ARCH. wall's (i.e., the FENCE) purpose is just to
RAI BASSIG>> divide/delineate the adjacent property, it is logical to
<<REVIEWER/QUESTIONNAIRE - SOURCE: use the minimum thickness of CHB available. This
UNKNOWN>> way, there will be more open spaces at the property's
yards as compared to using thicker CHB's that will
Situation 5 - Project No. 01 serve no other purpose.

Q#21. C. 0.10 Q#23. A. Steep, gable-shaped metal roof on welded


Similar to Q#142! steel frame
There is insufficient data to answer the given Similar to Q#112!
question. Wall thicknesses are governed by Fire- Choice c. and choice d. have both low-sloped roof
Resistive Time Period Ratings (see IRR of PD1096, which, given the heavily forested site, will
Rule VI). Wall thickness are also dependent on the gather/collect leaves, twigs, and other undesirable
thermal and noise reduction the occupant would want materials that will impact the maintenance of such
to achieve. Then, there is also the factor if the CHB roofing. Providing a steep roofing will eliminate this
being asked is load bearing or non-load bearing. problem. This leaves us with choice a. and choice b.
Preferences might also play a factor, for example, if Since the question states that the budget is a
the occupant would want a lighter load on the upper concern, choice b. will not be a good option.
floors, the exterior CHB can be 4" thick for those Constructing a "very steep" roof will add more costs
floors while the ground floor can be 6" thick. on the roof framing. The asphalt shingle will also be
requiring an underlayment (i.e., the marine plywood)
However, for purposes of answering the given which will be more expensive and time-consuming to
question DESPITE the limited DATA given, the install. The best answer will be choice a. as the steep
COMMON PRACTICE (not a rule or a provision in the roof solves the site problems and the material
law) is to use 6" thick CHB for the exterior walls and (including the welded gable-shaped framing) solves
to use 4" thick CHB for the interior walls. A 6" CHB the budgetary concerns.
would be approx. 0.15m; while a 4" CHB would be
approx. 0.10m. The primary reason for this Q#24. C. Balconies
"COMMON PRACTICE" is the AVAILABILITY OF Similar to Q#113 and Q#144!
CHB PRODUCED LOCALLY. Most suppliers only Since all of the other choices does not pertain to
offer 4" and 6" thick CHB's. In "COMMON usable floor areas, balconies may pose a hazard to
PRACTICE", the 4" thick CHB is used for the interior the occupant accessing/using it if it is near a high-
because it would only occupy less space (creating a voltage transmission line.
larger interior floor area), while the 6" thick CHB is
used at the exterior perimeter walls since there is a Q#25. D. 0.15
sufficient space at the property's yards and as the Similar to Q#141!
perimeter walls are exposed to environmental factors See my explanation above (Q#21).
(noise, thermal, wind, etc), the thicker CHB would be
the better option to use. Situation 6 - Project No. 01

Q#22. D. 0.10 Q#26. A. 1.155


See also my explanation above (Q#21). Similar to Q#86!
The project is located in an R-1 zone wherein Refer to the IRR of BP 344, Appendix A, Sec. C, Item
3, Sub-Item 3.8, "DOORKNOBS AND OTHER acrylic painting can both be categorized under Sub-
HARDWARE should be located BETWEEN 0.82 M. Division 12.10.00-Art/Wall Decoration, while the
AND 1.06 M. ABOVE THE FLOOR; 0.90 is preferred." freestanding indoor sculpture can be categorized
under Sub-Division 12.14.00-Sculptures. On the other
Q#27. A. 0.3 hand, the Ceiling fan with lights is considered to be an
Similar to Q#87! EQUIPMENT or an ELECTRICAL EQUIPMENT,
This is a very subjective question as no data is given which can be classified under Sub-Division 11.34.00-
as to what purpose will the fixed countertop be used. Residential Ceiling Fan under Division 11.00.00-
Standard countertop depths are usually at the vicinity EQUIPMENT or can be classified under Sub-Division
of about 600mm (or 0.60m), while semi-countertops 26.50.00-Lighting (since it also functions as a lighting
have a larger range from as low as 13" (330.2mm or fixture) under Division 26.00.00-ELECTRICAL.
0.33m) to 18" (457.2mm or 0.46m). It all depends on
the use of the countertop. Analyzing the question, the
best answer would be the smallest (i.e., not a good
countertop depth).

Q#28. D. Soap Dispenser


Note that there might be a typographical error in
choice d. as it mentions "Soup Dispenser".

All the other choices are types of equipment (either


ventilation equipment, appliance, electrical equipment
or security equipment). Choice d. SOAP dispenser is
a type of Bathroom Accessory.

Q#29. C. Wall-mounted flat TV


Choice C. IS NOT a furniture; it IS an EQUIPMENT
(more specifically, an APPLIANCE or A
COMMUNICATION EQUIPMENT). As per the CSI
MasterFormat Specifications, choices a. Sofa, b.
coffee table, and d. dresser are all under Sub-Division
12.50.00-Furniture, which is categorized under
Division 12.00.00-FURNISHINGS. On the other hand,
choice c. wall-mounted flat TV may be categorized
either under Sub-Division 11.30.00-Residential
Equipment, which is under Division 11.00.00-
EQUIPMENT; or under Sub-Division 27.40.00-Audio-
Video Communications, which is under Division
27.00.00-COMMUNICATIONS.

Q#30. A. Ceiling fan with lights


As per the CSI MasterFormat Specifications, the
other choices are all under Division 12.00.00-
FURNISHINGS. The life-size wall mirror and the
Q#31 to Q#45 (Project No. 02)
<<ALL ANSWERS AND ANNOTATIONS BY ARCH. Situation 8 - Project No. 02
RAI BASSIG>>
<<REVIEWER/QUESTIONNAIRE - SOURCE: Q#36. B. NorthEast (NE)
UNKNOWN>> Similar to Q#6!
Note that the choices given are the actual orientation
*****PROJECT NO. 02***** where the Amihan wind will originate. If you plot the
project site and face the property from the main
Situation 7 - Project No. 02 RROW, the wind will be coming from the lower left
corner of the lot.
Q#31. B. 7.1 to 8.1
Refer to IRR of PD1096, Table VII.G.1, under Max. R- Q#37. A. West, SouthWest (SW) and South
3 perimeters
Similar to Q#7!
Q#32. B. 48,600 Note that the choices given are the actual orientation
GFA = TLA (Given) * FLAR (Q#31) to buffer the Habagat wind at the direction such wind
GFA = 6,000 sqm * 8.1 will originate (i.e., Southwest). If you plot the project
GFA = 48,600 sqm site and face the property from the main RROW, the
wind will be coming from the upper right corner of the
Q#33. D. 58,320 lot.
Refer to IRR of PD1096, Table VII.G.2, multiplier
under Max. R-3 Q#38. D. East and West
TGFA = GFA (Q#32) * Multiplier (Table VII.G.2) The project site, which is an interior lot, has a vacant
TGFA = 48,600 sqm * 1.2 lot in front that faces north where the vacant lot's
TGFA = 58,320 sqm frontage abuts the sidewalk of the RROW.

Q#34. D. Lobby Q#39. A. Right and left side yards


Refer to IRR of PD1096, RULE VII Guidelines, Similar to Q#9!
Application of Development Controls, Item f.i., which If you plot the project site, the lot will have its right
reads, and left side yards facing the eastern and western
"Gross Floor Area (GFA) - the total floor directions (i.e., dominant sun path).
space...xxx...such as office areas, residential areas,
corridors, LOBBIES and mezzanine level/s...xxx" Q#40. B. SE to SW and NE to NW
Similar to Q#10!
Q#35. A. Basement parking area, if introduced The sun rises in the east and sets in the west,
Refer to IRR of PD1096, RULE VII Guidelines, therefore, the dominant path is east TO west. In the
Application of Development Controls, Item f.i., which Philippine setting, since the country is located just
reads, above the equator (northern hemisphere), the sun's
"...and the GFA EXCLUDES the following: solar angle for most of the year is at the southern
(a) COVERED AREAS USED FOR PARKING AND direction, while some months (around August-
DRIVEWAYS, services and utilities; November) the solar angle is a slightly angled coming
(b) VERTICAL PENETRATIONS in PARKING from the northern direction. Therefore the dominant
FLOORS WHERE NO RESIDENTIAL OR OFFICE path is SE to SW and NE to NW.
UNITS ARE PRESENT; and...xxx"
Situation 9 - Project No. 02 access during maintenance/sorting/clearing - all of
which must not be seen in the project lobby (which is
Q#41. D. Basement level considered as the "front-of-the-house").
Similar to Q#71!
Refer to IRR of PD1096, Sec. 802, Item 1, "The Q#45. C. Enclosures for electronic equipment
measurement of site occupancy or lot occupancy Similar to Q#75!
shall be taken AT THE GROUND LEVEL and shall be Although it is a toss-up between Choices b. and c.,
exclusive of courts, yards, and light wells." the electronic equipment is a graver concern than the
Also, refer to IRR of PD1096, Glossary, under solid waste storage when water seepage and flooding
Allowable Maximum Building Footprint (AMBF), "The occurs in the basement levels.
maximum portion of the lot that may be occupied by
the building/structure AT GRADE LEVEL after
satisfying setback, yard and court
requirements...xxx..."

Q#42. B. Garden mall at ground floor


Similar to Q#72!
Refer to IRR of PD1096, Sec. 802, Item 1, "The
measurement of site occupancy or lot occupancy
shall be taken at the ground level and shall be
EXCLUSIVE of COURTS, YARDS, and light wells."
Also, refer to IRR of PD1096, Glossary, under
Allowable Maximum Building Footprint (AMBF), "The
maximum portion of the lot that may be occupied by
the building/structure at grade level AFTER satisfying
setback, YARD and COURT requirements...xxx...The
AMBF is the true buildable area on which a FULLY
ENCLOSED BUILDING/STRUCTURE can be
erected. The AMBF shall EXCLUDE provisions for
COURTS AT GRADE LEVEL."

Q#43. A. Executive lounge


Since the project is an apartment building with only 2
unit-types (Studio and 1BR), the target market
strategy would be budgeted and affordable. An
executive lounge, if any, would best suit target
markets in the "executive class" level. A better
alternative for a "lounge" is choice c., which is a
clubhouse or social area. The other choices, b.
elevator lobby and service stairs, and d. utility rooms
are all necessities for the project to function.

Q#44. A. Garbage Chute


The most obvious reasons are odor, noise, and
Q#46 to Q#50 (Project No. 02) Q#50. B. Glass of operable windows
<<ALL ANSWERS AND ANNOTATIONS BY ARCH. This question is highly subjective as most
RAI BASSIG>> suppliers/manufacturers of all of the given choices
<<REVIEWER/QUESTIONNAIRE - SOURCE: offer different periods of warranties for these products
UNKNOWN>> (ranging from 5-year, 10-year, to limited lifetime
warranties). I will answer based on the data in the
Situation 10 - Project No. 02 question where it states "in terms of operating and
maintenance costs". 
Q#46. A. Substantial use of masonry and some glass
In the Philippines, where construction is labor- Among the choices only the windows are "operable"
intensive, masonry works (regular CHB, concreting, (one cannot 'operate' a waterproofing nor 'operate' a
and plastering) will be more economical than the laminate flooring). Waterproofing also came in two
specialized fabrication and installation of glass panels choices (deck and indoor toilet), wherein choosing
and other specialty materials. one over the other would defeat the purpose that
waterproofing should have a warranty. The best
Q#47. A. Transparent glass and dark color-painted answer to the question would be windows as they are
masonry definitely maintained from time-to-time and as stated
Since the southern side is one of the hottest in the choice the windows are "operable".
orientation in the Philippine setting, the use of
transparent glass will allow direct sunlight to enter the
building, creating glare, while the dark color-paint
masonry will absorb a considerable amount of
thermal radation, both of which will lead to discomfort
of the building occupants, respectively.

Q#48. D. Dark gray and black


Depending on the material used for the deck, the
given choices of colors have the % of solar radiation
absorption:
Light Gray - Less than 40%
Medium Gray - 40% to 50%
Medium Blue - 70% to 80%
Dark Gray and Black - 80% to 100%
Source: DoE Guidelines

Q#49. D. Medium Blue Metal Roofing


Percentage of solar radiation absorption:
Light Red Polycarbonate Panels - Approx. 28% (Data
from Product Brochure)
Light Brown Metal Roofing - Approx. 30%
Dark Green Metal Roofing - Approx. 45%
Medium Blue Metal Roofing - Approx. 52%
Source: DoE Guidelines
Q#51 to Q#60 (Project No. 02) "instability". My answer refers to maximized structural
<<ALL ANSWERS AND ANNOTATIONS BY ARCH. stability or minimized structural instability, similar to
RAI BASSIG>> Q#83.
<<REVIEWER/QUESTIONNAIRE - SOURCE: In terms of design economy, if the beam is positioned
UNKNOWN>> near the column interior face so that the beam's
interior face is flushed with the column's interior face,
Situation 11 - Project No. 02 the effect would be:
1. Lesser and more re-usable formworks
Q#51. A. 7.25 x 8.0 2. Walls can be aligned so that plastering will be
Similar to Q#52, Q#81 and Q#82! easier to apply in terms of equal thickness
The question did not specify what type of vehicle will 3. Lesser baseboard/cornice/trim cutting in so far as
park, it also did not specify if the parking will be working around protruding columns
perpendicular/diagonal or parallel. I answered the 4. Lesser tile/ceiling cutting in so far as working
question with the assumption that a car will park around protruding columns
perpendicularly as this is the most common parking 5. Lesser surface area for painting works
configuration. In terms of structural stability, since the exterior
Refer to IRR of PD1096, Sec. 707, Item 4, Sub-Item columns are at the outer edges of the building,
b., "The size of an average automobile (car) parking supplying the beams at the interior side will shift the
slot must be computed at 2.50 METERS by 5.00 load eccentricity towards the interior of the structrual
meters for perpendicular or diagonal parking...xxx..." frame, where interior columns are all positioned. The
Since the question is asking for the bay measurement shift will also decrease the actual beam span to the
that will fit 3 vehicles (i.e., cars), then, next interior column, thereby creating lesser concrete
Total Min. Clear Width of Parking Bay = Width of volume (if there is a concrete slab above) or lesser
Parking Slot (Sec. 707.4.b) * No. of Vehicles (Given) lengths of structural trusses (if roofed above).
Total Min. Clear Width of Parking Bay = 2.50m * 3
Total Min. Clear Width of Parking Bay = 7.50m Q#54. D. At the building perimeter
Therefore, among the choices, the one with the Similar to Q#84!
measurement that falls below the min. clear width The question is too subjective because the answer is
should not be recommended. dependent on the design of the roof. If the roof is
designed with a 1-slope/shed-type roofing and it
Q#52. A. 6.6 slopes from the front towards the back, the best
Similar to Q#51, Q#81 and Q#82! position of the downspouts would be at the rear of the
See explanation in Q#51 above. building. If the building has a large central courtyard
and the roof all slopes towards the center, then the
Q#53. A. Positioned near the column interior face best position of the downspouts would be at the
Similar to Q#83! center of the building. If the building has a firewall and
Note that there might be a typographical error in the all roofing slopes towards that firewall, then the best
question as it states "overall design economy" but position of the downspouts would be along the
mentioned "minimized" structural stability. Checking property wall.
the similar question in Q#83, it states "overall design However, for purposes of answering the given
economy and maximized structural stability". The question in GENERAL TERMS, I would have to
"minimized" in the question should have been choose D. At the Building Perimeter. The main reason
"maximized" or the is, assuming whatever roof design and roof slope a
word "stability" should have been changed to given building mass has, the downspouts will be
located GENERALLy along the building walls which will be more expensive to produce.
(whichever location - front, side, or rear).
Q#57. B. Vinyl Strips
Q#55. A. 1.5 x 1.8 All other choices are non-resilient materials (brittle).
Similar to Q#85! Vinyl can be deformed elastically, to a certain degree,
There is NO provision in BP 344 regarding the without creating a permanent deformation or rupture.
minimum dimensions of an ELEVATOR SHAFT; only
the ELEVATOR CAR is provided which is 1.10m (W) Q#58. A. cornice moulding
x 1.40m (D) as per the IRR of BP 344, Appendix A, Millwork generally means profile sections of wood
Sec. C, Item 10, Sub-Item 10.2. Analyzing the given (but now available in plastics/synthetics) produced in
choices, the following clearances from the car to the a lumber mill. These are all generally categorized as
shaft are obtained: "Trims".
A. 1.5 x 1.8 will have 0.2m clearance all-around
B. 1.2 x 1.5 will have 0.05m clearance all-around Q#59. D. Door casing
C. 2.1 x 2.4 will have 0.5m clearance all-around Door Casings are categorized as Trims while the rest
D. 1.8 x 2.1 will have 0.35m clearance all-around of the choices are categorized as Hardware.
Also, looking at the same question in Q#85, we find
the following choices, and their corresponding Q#60. B. Halogen lamps
clearances from the car to the shaft: Halogen lamps consume considerable amount of
A. 1.5 x 1.8 will have 0.2m clearance all-around wattage as compared to the other choices, thereby
B. 1.7 x 2.0 will have 0.3m clearance all-around increasing electricity cost of the tenant/leasee.
C. 1.3 x 1.6 will have 0.15m clearance all-around
D. 1.9 x 2.2 will have 0.4m clearance all-around
Since only "1.5 x 1.8" appears on both questions, it
seems that the correct answer is 1.5 x 1.8 for the
minimum shaft dimensions (despite it not appearing in
the BP 344 as the question suggests). Therefore, the
shaft clearance from the car should be 0.2m by using
the 1.10m x 1.40m car inside the 1.5m x 1.8 shaft
dimension.

Situation 12 - Project No. 02

Q#56. C. Local marble slabs


The answer is based on economic principles. All
choices are imported materials. As such, the cost of
production, transportation, including tariffs, taxes and
importation, plus local taxes, distributor's profits and
overhead, etc., will be passed on to the consumer for
the original supplier to profit. On the other hand, if the
material to be used is sourced locally, the cost will be
cheaper than if it was produced abroad. There also is
the consideration of the material availability in case of
defects, replacement, and other occurrences, all of
 Q#61 to Q#75 (Project No. 03)
<<ALL ANSWERS AND ANNOTATIONS BY ARCH. Q#66. C. 5%
RAI BASSIG>> Refer to IRR of PD1096, Table VIII.1. Min. USA,
<<REVIEWER/QUESTIONNAIRE - SOURCE: under Commercial C-3
UNKNOWN>>
Q#67. C. 100 sqm
*****PROJECT NO. 03***** Min. USA = TLA (Given) * Min. % USA (Table VIII.1)
Min. USA = 2,000 sqm * 0.05
Situation 13 - Project No. 03 Min. USA = 100 sqm

Q#61. D. 1 parking slot : 2 units Q#68. C. 15%


Refer to IRR of PD1096, Table VII.4. Division E-2 for Refer to IRR of PD1096, Table VIII.1. Max. ISA,
18sqm-40sqm units under Commercial C-3, without firewalls

Q#62. D. 1 parking slot : 1 unit Q#69. D. 300 sqm


Refer to IRR of PD1096, Table VII.4. Division E-2 for Max. Allow. ISA = TLA (Given) * Max. % ISA (Table
41sqm-70sqm units VIII.1)
Max. Allow. ISA = 2,000 sqm * 0.15
Q#63. C. 3.7 Max. Allow. ISA = 300 sqm
Refer to IRR of BP344, Appendix A, Sec. B, Item 1,
Sub-Item 1.4, "Accessible parking slots should have a The question did NOT specify if with or without
minimum width of 3.70M." firewall. IRR of PD1096, Table VIII.1 under C-3 shows
15% ISA if without firewalls and 5% ISA if with
Q#64. A. 0.80 firewalls. I chose 15% because of 2 reasons: 1) this
Refer to IRR of BP344, Appendix A, Sec. C, Item 3, question MIGHT be related to Q#68 wherein the
Sub-Item 3.1, "ALL DOORS shall have a minimum question specifically asks for the Max. ISA WITHOUT
clear width of 0.80M." firewalls; and, 2) if I will compute the next question
Also, refer to IRR of BP344, Illustrations of Min. (Q#70) assuming there is a firewall (i.e., I will be
Requirements, Sec. C, Item 10, Sub-Item 10.2, using 5% as Max. ISA and 10% as Min. USA for a
showing a detailed plan of an accessible elevator with total of 15% ISA + USA), none of the given choices
minimum dimensions of 1.10m x 1.40m and an corresponds to that percentage.
elevator door min. width of 0.80M.
Q#70. C. 400 sqm
Q#65. C. 1.70 Max. Allow. ISA + Min. USA = TLA (Given) * TOSL %
Refer to IRR of BP344, Appendix A, Sec. C, Item 8, (Table VIII.1)
Sub-Item 8.2, "Accessible water closet stalls shall Max. Allow. ISA + Min. USA = 2,000 sqm * 0.20
have a minimum area of 1.70 x 1.80 MTS...xxx..." Max. Allow. ISA + Min. USA = 400 sqm
Also, refer to IRR of BP344, Illustrations of Min. Note that choices A, B, and D are 135 sqm, 535 sqm,
Requirements, Min. Water Closet Stall Dimensions and 270 sqm, respectively. The percentage would be
showing a detailed plan of an accessible water closet 6.75%, 26.75%, and 13.5% - all of these values are
stall with minimum WIDTH of 1.70M and minimum not found in Table VIII.1 of the IRR of PD1096.
DEPTH of 1.80m.
Situation 14 - Project No. 03
Situation 14 - Project No. 03 (Note there are 2 Situation #14)
could shy away higher offers for rent rates of the
Q#71. B. Basement level units).
Similar to Q#41!
Refer to IRR of PD1096, Sec. 802, Item 1, "The Q#74. B. Driver lounge
measurement of site occupancy or lot occupancy Since the project requirements is given that the
shall be taken AT THE GROUND LEVEL and shall be podium level will have covered parking, it is best that
exclusive of courts, yards, and light wells." the driver lounge be located near said parking area
Also, refer to IRR of PD1096, Glossary, under for quick access and visual security of the vehicle.
Allowable Maximum Building Footprint (AMBF), "The The ground floor level of the podium usually houses
maximum portion of the lot that may be occupied by the main lobby and the reception, while the parking
the building/structure AT GRADE LEVEL after spaces are usually
satisfying setback, yard and court located either at the basement or the upper levels of
requirements...xxx..." the podium.

Q#72. C. Patio at ground floor Q#75. C. Enclosures for electronic equipment


Similar to Q#42! Similar to Q#45!
Refer to IRR of PD1096, Sec. 802, Item 1, "The Although it is a toss-up between Choices c. and d.,
measurement of site occupancy or lot occupancy the electronic equipment is a graver concern than the
shall be taken at the ground level and shall be solid waste storage when water seepage and flooding
EXCLUSIVE of COURTS, YARDS, and light wells." occurs in the basement levels.
Also, refer to IRR of PD1096, Glossary, under
Allowable Maximum Building Footprint (AMBF), "The
maximum portion of the lot that may be occupied by
the building/structure at grade level AFTER satisfying
setback, YARD and COURT requirements...xxx...The
AMBF is the true buildable area on which a FULLY
ENCLOSED BUILDING/STRUCTURE can be
erected. The AMBF shall EXCLUDE provisions for
COURTS AT GRADE LEVEL."

Q#73. C. Workshop and carpentry room


Choice c. is a service area and should be located on
other parts of the project (such as the podium parking
or basement levels) due to access, noise, and spatial
concerns. A workshop/carpentry room will take up a
considerable amount of space due to storage of
materials. Note that the tower component will house
the Office-Condominium Units. If a large service area
(which is non-saleable) will be located at the tower
component, a large amount of space for
saleable/leasable units will have to be sacrificed.
Consider also that Office-Condo units adjacent to the
workshop/carpentry room will have to deal with noise
and unsightly delivery of materials (which in turn
Q#76 to Q#80 (Project No. 03) accordion doors given in the choices that will take
<<ALL ANSWERS AND ANNOTATIONS BY ARCH. more effort to operate and might result in
RAI BASSIG>> bottlenecking). The glass material will also
<<REVIEWER/QUESTIONNAIRE - SOURCE: complement the structure as the use of the building is
UNKNOWN>> office-condominium.

Situation 16 - Project No. 03 Q#80. B. 2.70


(Note there are no Situation #15 probably due to 2 Similar to Q#139 and Q#140!
Situation #14's) In this question, there MIGHT be a typographical error
as the sought distance from the FFL is not specified
Q#76. C. Construction timetable as to where it will be measured. I can safely assume
Similar to Q#136! that it is seeking for the distance from the FFL to the
Choice c., although a concern in the construction "ceiling" since a similar question appears in Q#139
stage of the project in so far as the use of materials, and Q#140.
operations, and sustainability (i.e., the longer the time Refer to IRR of PD1096, Sec. 805, Item 1, "Habitable
schedule of construction, the higher the energy rooms provided with artificial ventilation shall have
consumed), it is the best answer among the given ceiling heights not less than 2.40 meters measured
choices as it does not directly affect the operation of from floor to the ceiling...xxx...Above-stated rooms
the actual building AFTER it has been constructed. WITH NATURAL VENTILATION shall have ceiling
heights of NOT LESS THAN 2.70 METERS."
Q#77. C. Hand-cut natural stone
Similar to Q#137!
The embodied energy in producing the listed choices
are as follows:
High-Pressure Laminate Flooring - 11 to 12 MJ/kg
Baked Clay Tile - 6.5 MJ/kg
Hand-Cut Natural Stone - 0.1 to 2.0 MJ/kg
Ceramic Tiles - 12 MJ/kg

Q#78. C. Polycarbonate Sheet


Similar to Q#138!
The embodied energy in producing the listed choices
are as follows:
Plywood - 15 MJ/kg
Recycled cardboard egg crate - 23 MJ/kg
Polycarbonate Sheet - 113 MJ/kg
Gypsum Board - 6.75 MJ/kg

Q#79. D. Quadruple leaf swing/glass


Since the project is a medium-rise building having a
large Gross Floor Area (i.e., high traffic with high
occupancy volume), the quadruple leaf swing door
will be the most suitable considering ease of access
and fire safety (as compared to sliding, revolving, and
Q#81 to Q#90 (Project No. 03) Similar to Q#53!
<<ALL ANSWERS AND ANNOTATIONS BY ARCH. In terms of design economy, if the beam is positioned
RAI BASSIG>> near the column interior face so that the beam's
<<REVIEWER/QUESTIONNAIRE - SOURCE: interior face is flushed with the column's interior face,
UNKNOWN>> the effect would be:
1. Lesser and more re-usable formworks
Situation 17 - Project No. 03 2. Walls can be aligned so that plastering will be
easier to apply in terms of equal thickness
Q#81. B. 7.25 x 8.0 3. Lesser baseboard/cornice/trim cutting in so far as
Similar to Q#51, Q#52 and Q#82! working around protruding columns
The question did not specify what type of vehicle will 4. Lesser tile/ceiling cutting in so far as working
park, it also did not specify if the parking will be around protruding columns
perpendicular/diagonal or parallel. I answered the 5. Lesser surface area for painting works
question with the assumption that a car will park In terms of structural stability, since the exterior
perpendicularly as this is the most common parking columns are at the outer edges of the building,
configuration. supplying the beams at the interior side will shift the
Refer to IRR of PD1096, Sec. 707, Item 4, Sub-Item load eccentricity towards the interior of the structrual
b., "The size of an average automobile (car) parking frame, where interior columns are all positioned. The
slot must be computed at 2.50 METERS by 5.00 shift will also decrease the actual beam span to the
meters for perpendicular or diagonal parking...xxx..." next interior column, thereby creating lesser concrete
Since the question is asking for the bay measurement volume (if there is a concrete slab above) or lesser
that will fit 3 vehicles (i.e., cars), then, lengths of structural trusses (if roofed above).
Total Min. Clear Width of Parking Bay = Width of
Parking Slot (Sec. 707.4.b) * No. of Vehicles (Given) Q#84. B. At the exposed exterior faces of columns
Total Min. Clear Width of Parking Bay = 2.50m * 3 (and positioned farthest outside the architectural
Total Min. Clear Width of Parking Bay = 7.50m cladding)
Therefore, among the choices, the one with the Similar to Q#54!
measurement that falls below the min. clear width In terms of maintenance of downspouts, all concealed
should not be recommended. downspouts are impossible to replace without
demolishing the portion that conceals the pipe.
Q#82. C. 4.6 Therefore, among the choices, choice c. Enclosed by
Similar to Q#51, Q#52 and Q#81! CHB, and choice d. Inside the columns, can be
Since the question is asking for the bay measurement immediately eliminated.
that will fit 2 vehicles (i.e., cars), then, Between choice a. and b., which are both exposed,
Total Min. Clear Width of Parking Bay = Width of choice a. At the exposed sides of columns (and
Parking Slot (Sec. 707.4.b) * No. of Vehicles (Given) positioned nearest but outside the architectural
Total Min. Clear Width of Parking Bay = 2.50m * 2 cladding) will have longer pipe lengths coming from
Total Min. Clear Width of Parking Bay = 5.00m the leaders of the gutter towards the downspouts.
Therefore, among the choices, the one with the Therefore, in terms of design economy, choice b. is
measurement that falls below the min. clear width the best answer as the downspout distance from the
should not be recommended. gutter is shorter (and, consequently, the distance from
See explanation in Q#81 above. the downspout to the underground catch basin, if any,
or drainage pipe, will also be shorter).
Q#83. C. Positioned near the column interior face
Q#85. A. 1.5 x 1.8 0.33m) to 18" (457.2mm or 0.46m). It all depends on
Similar to Q#55! the use of the countertop. Analyzing the question, the
There is NO provision in BP 344 regarding the best answer would be the smallest (i.e., not a good
minimum dimensions of an ELEVATOR SHAFT; only countertop depth).
the ELEVATOR CAR is provided which is 1.10m (W)
x 1.40m (D) as per the IRR of BP 344, Appendix A, Q#88. C. 7.5 and D. 7.5
Sec. C, Item 10, Sub-Item 10.2. Analyzing the given Since it is given that the smallest office unit is 30 sqm
choices, the following clearances from the car to the in area, then,
shaft are obtained: Depth = Area (given in problem) / Width (given in
A. 1.5 x 1.8 will have 0.2m clearance all-around question)
B. 1.7 x 2.0 will have 0.3m clearance all-around Depth = 30 sqm / 4.0 m
C. 1.3 x 1.6 will have 0.15m clearance all-around Depth = 7.5m
D. 1.9 x 2.2 will have 0.4m clearance all-around
Also, looking at the same question in Q#55, we find Q#89. B. 334
the following choices, and their corresponding Note that the question may contain typographical
clearances from the car to the shaft: error as the size of the vinyl tile reads "0.30m by
A. 1.5 x 1.8 will have 0.2m clearance all-around 2.5mm thick". Since "tiles" and not "strips" are used,
B. 1.2 x 1.5 will have 0.05m clearance all-around the 0.30m measurement in the question MIGHT refer
C. 2.1 x 2.4 will have 0.5m clearance all-around to BOTH the tile's length and width (i.e., the tile is
D. 1.8 x 2.1 will have 0.35m clearance all-around square-shaped). Also, Q#90 mentions the same tile at
Since only "1.5 x 1.8" appears on both questions, it 0.30m x 0.30m x 2.5mm thick.
seems that the correct answer is 1.5 x 1.8 for the In relation to Q#88,
minimum shaft dimensions (despite it not appearing in Tile Qty. = Area of Unit (given in problem) / Area of
the BP 344 as the question suggests). Therefore, the Tile (given in question)
shaft clearance from the car should be 0.2m by using Tile Qty. = 30 sqm / (0.3m * 0.3m)
the 1.10m x 1.40m car inside the 1.5m x 1.8 shaft Tile Qty. = 30 sqm / 0.09 sqm
dimension. Tile Qty. = 333.33 or 334 PCS.

Situation 18 - Project No. 03 Q#90. B. 331


In relation to Q#89,
Q#86. A. 1.17 Tile Qty. = Area of Unit (given in question) / Area of
Similar to Q#26! Tile (given in question)
Refer to the IRR of BP 344, Appendix A, Sec. C, Item Tile Qty. = (3.5m * 8.5m) / (0.3m * 0.3m)
3, Sub-Item 3.8, "DOORKNOBS AND OTHER Tile Qty. = 29.75 sqm / 0.09 sqm
HARDWARE should be located BETWEEN 0.82 M. Tile Qty. = 330.55 or 331 PCS.
AND 1.06 M. ABOVE THE FLOOR; 0.90 is preferred."

Q#87. A. 0.35
Similar to Q#27!
This is a very subjective question as no data is given
as to what purpose will the fixed countertop be used.
Standard countertop depths are usually at the vicinity
of about 600mm (or 0.60m), while semi-countertops
have a larger range from as low as 13" (330.2mm or
Q#91 to Q#104 (Project No. 04) conditioning condensing unit (ACCU) balconies,
<<ALL ANSWERS AND ANNOTATIONS BY ARCH. overhead water tanks,...xxx"
RAI BASSIG>>
<<REVIEWER/QUESTIONNAIRE - SOURCE: Situation 20 - Project No. 04
UNKNOWN>>
Q#96. B. General Institutional
*****PROJECT NO. 04***** Refer to IRR of PD1096, Table VII.1, under Group C
and Group D Use/Occupancy
Situation 19 - Project No. 04
Q#97. NONE OF THE CHOICES (i.e., ALL ARE
Q#91. C. 2.5 ZONED AS G.I.)
Refer to IRR of PD1096, Table VII.G.1, under As per the IRR of PD 1096, Table VII.1, there are 2
Institutional types of G.I. zones:
1) FOR GROUP C, "GI (General Institutional) - a
Q#92. C. 20,000 community to national level of institutional use or
GFA = TLA (Given) * FLAR (Q#91) occupancy, characterized mainly as low-rise,
GFA = 8,000 sqm * 2.5 medium-rise or high-rise building/structure for
GFA = 20,000 sqm EDUCATIONAL, TRAINING and related activities,
e.g., SCHOOLS and RELATED FACILITIES and the
Q#93. B. Not Stated like."
Refer to IRR of PD1096, Table VII.G.2 2) FOR GROUP D, "GI (General Institutional) - a
There is no mention of the conversion of GFA to community to national level of institutional use or
TGFA for Institutional Use/Occupancy. Among the occupancy, characterized mainly as low-rise,
other given choices, 33% are for R-1, C-3, I-2, I-3 and medium-rise or high-rise building/structure for
UTS only; 25% are for C-2 and I-1 only; and, 20% are MEDICAL, government service, administrative and
for Basic R-2, Basic R-3, R-4 and C-1 only. related activities, e.g., HOSPITALS and RELATED
HEALTH CARE FACILITIES, government offices,
Q#94. C. Lobby military, police and correctional buildings and the
Similar to Q#34! like."
Refer to IRR of PD1096, RULE VII Guidelines,
Application of Development Controls, Item f.i., which Choice a. (Children's hospital) falls under the
reads, Principal Group D-2 Use/GI-Zone
"Gross Floor Area (GFA) - the total floor Choice b. (Orphanage) falls under the Principal Group
space...xxx...such as office areas, residential areas, D-3 Use/GI-Zone and the Accessory Group D-1
corridors, LOBBIES and mezzanine level/s...xxx" Use/GI-Zone
Choice c. (Dance School) falls under the Principal
Q#95. A. Cooling tower area, if introduced Group C-2 Use/GI-Zone
Similar to Q#35! Choice d. (Kindergarten School) falls under the
Refer to IRR of PD1096, RULE VII Guidelines, Principal Group C-1 Use/GI-Zone
Application of Development Controls, Item f.i., which
reads, Therefore, ALL of the given choices ARE PRINCIPAL
"...and the GFA EXCLUDES the following: USES permitted for a GI Zoning Classification!
...xxx...(c) Uncovered areas for helipads, AIR-
CONDITIONING COOLING TOWERS or air- Q#98. C. Vocational training center
Refer to IRR of PD1096, Table VII.1, under Group C- worship room is actually a perk in a government
2, Accessory Use, Item 2, "Colleges, universities, building as the LGU acknowledges the needs of its
professional business schools, VOCATIONAL AND diverse demographics (in so far as religion is
TRADE SCHOOLS, technical schools and other concerned) that everyone should have a fair share
institutions of higher learning" and under Group D-1, and equal rights, despite differences in faith, in
Accessory Use, Item 2, "Rehabilitation and working towards a common goal in the service of the
VOCATIONAL TRAINING CENTER for ex-convicts, community under God (as promulgated in the
drug addicts, unwed mothers, physically, mentally Philippine Constitution). 
and emotionally handicapped, ex-sanitaria inmates,
and similar establishments." Unlike the executive lounge which is exclusive, all the
other choices are diverse and inclusive.
Q#99. B. Institutional
Refer to IRR of PD1096, Table VII.1. Although it is Q#102. A. Gym
important to note that GI Zoning, apart from Group D Note that there are two Q#102's.
(Institutional - Government and Health Services), also Both Covered Parking and Multi-Purpose Rooms are
includes Group C (Education and Recreation). Among required for the Government Building to function as
the given choices, A. Recreational MAY also be a both areas are a necessity in the general use of the
correct answer. However, I selected B. Institutional for structure (the covered parking for
2 reasons: 1) The description of GI related to Group C transportation/accessibility and the multi-purpose
are "characterized mainly...xxx... for EDUCATIONAL, rooms for meetings/events/etc.). Daycare centers are
training and related activities...xxx"; and, 2) The given required in every baranggay as per law and they are
problem of the project is a low-rise national operated by the LGU through DSWD. The inclusion of
GOVERNMENT office. a daycare center in the project would also
acknowledge the LGU's commitment in providing for
Q#100. C. Turn court lot the basic education of children (especially for the
Refer to IRR of PD1096, Figure VIII.8, Table VIII.G.6, poor). The best answer among the given choices is
and Table VIII.G.7. The rest of the choices are all the gym, which is geared only to a select few, while
typical lot types. not serving as a basic requirement when compared
with the other choices.
Situation 21 - Project No. 04
Q#102. A. Electrical room
Q#101. A. Executive Lounge Note that there are two Q#102's. Similar to Q#13 and
An executive lounge, although an amenity by itself, Q#133!
would not be appropriate as an amenity for this The Electrical room pertains to a utility provision
particular project (Government Building). Executive (Electrical).
lounges cater to a select few, usually the so-called
"elite" or "upper-classes", which would be unfair to the Q#103. C. Guard locker and shower
rest of the community whose tax money also Similar to Q#14 and Q#134!
contributed to the construction of the building. A multi- The other choices, Cistern, Transformer Room, and
purpose room would be more appropriate to be used STP all pertain to utility provisions (Plumbing,
as a lounge room or for other purposes in case Electrical, and Sanitary Utilities, respectively).
dignitaries or special guests would visit the LGU.
Mini-conference rooms are also suitable for meetings, Q#104. C. Covered parking slots and fire reserve
discussions, hearings, etc. The interdenominational tanks
Similar to Q#15 and Q#135!
Although the choices are very subjective, the main
reason why choice C was selected as the best
answer is due to accessibility and maintenance
concerns. All of the other choices are suitable to be
located close to each other. Although a case can be
made regarding choice A that has the words "service
stairs" and "fire escapes" leading to a false conclusion
that there will be "2 stairs close to each other" and will
be redundant. However, the term "fire escapes" are
not limited to stairs alone. Fire escapes can be either
exit balconies, exit openings, exit corridors, and any
other form of egress during the occurrence of fire.
Choice C is the most uncommon spatial
interrelationship. If the fire reserve tanks are located
at the roof deck of a high-rise building, it is impractical
and illogical that covered parking slots will be located
there. In case the tanks are located in a basement or
a low-rise building, access during servicing would be
hindered when vehicles are parked close to the
reserve tanks.
Q#105 to Q#114 (Project No. 04) Q#109. C. Wall Hangings
<<ALL ANSWERS AND ANNOTATIONS BY ARCH. Wall Hangings are forms of furnishing/decoration
RAI BASSIG>> (under CSI Master Specification Division 12.00.00-
<<REVIEWER/QUESTIONNAIRE - SOURCE: FURNISHINGS) that ONLY INDIRECTLY AFFECTS
UNKNOWN>> the architectural design consideration for the project
as compared to the other given choices.
Situation 22 - Project No. 04
Situation 23 - Project No. 04
Q#105. A. Space planning and operations survey
Since the project is a national government office, prior Q#110. B. 1.3 x 1.3
to drafting the schematic designs, an analysis of the The question cannot be directly answered without
operational component must be performed for the accepting assumptions (which are risky). In sizing
said office. This is usually part of the Pre-Design columns, factors such as the height of the column, the
Services wherein Space Management Studies based total # of storeys, the total loads per area, and the
on ORGANIZATIONAL STRUCTURE and column material must be considered as a minimum.
FUNCTIONAL SET-UP will serve as basis for the None of these factors are given in the problem.
development of the architectural plan/design (refer to However, based on PRELIMINARY SIZING and
SPP Doc. 201, Item 2.9). In space planning, the calculated ASSUMPTIONS, a very rough sizing can
adequate sizes and appropriate configuration and be achieved.
assemblage for a proposed project is determined. Since the problem is a LOW-RISE government
However, this can only be done mainly through building, the # of storeys will be assumed at the
PRIMARY DATA GATHERING such as maximum permitted by the NBCP, which is 5 storeys
INTERVIEWS, CONSULTATIONS, INTERFACES, @ 15 meters total BHL (refer to IRR of PD 1096,
FOCUS GROUP DISCUSSIONS, SPACE PLANNING Glossary, under Height of Building, Low-Rise, and
SURVEYS, SPACE AUDITS, etc. (refer to SPP Doc. IRR of PD 1096, Table VII.2).
201, Item 2.8). The tributary area that the column will be supporting
including the floors above it can be computed on the
Q#106. A. Zoning ordinance basis of the given beam span of 8.5m to 10.0m.
The Zoning ordinance is the local law SPECIFIC to Based on preliminary column sizing studies
the Local Government Unit. PD 1096 and its IRR are considering seismic factors by U.Ersoy, the minimum
national laws. column cross-sectional area can be determined
using:
Q#107. A. Technical Specifications
The Technical Specifications is done during Contract Cross-Sectional Column Area > 0.0015*(Sum of
Documentation of the project, i.e., AFTER all designs Tributary Area Over All Floors)
have been finalized in preparation for the construction
of the project. Since beam spans are given, the tributary areas
(assuming all columns are interior columns) would be
Q#108. B. Drainage canal slope and direction from (8.5m * 8.5m = 72.25 sqm) to (10m * 10m =
Choice b. is a form of Civil Work that ONLY 100sqm) per floor.
INDIRECTLY AFFECTS the architectural design Assuming that the government building will have 5
consideration for the project as compared to the other floors (with basement as given in the problem), this
given choices. means that the ground floor column will be carrying
5x the tributary areas of the floors above it.
So, the minimum column area for the ground floor Similar to Q#24 and Q#144!
(using the max. beam span of 10m) will be: A very subjective question with very vague choices.
Cross-Sectional Column Area > 0.0015*(Sum of The question does not mention of other data such as
Tributary Area Over All Floors) location of the structure in the hillside, the orientation,
Cross-Sectional Column Area > 0.0015*(5 floors * slope, etc. All of the choices seems to be feasible.
100 sqm) However, since an answer should be chosen, I will
Cross-Sectional Column Area > 0.0015*(500 sqm) analyze based on certain assumptions.
Cross-Sectional Column Area > 0.75 sqm Choice a (1.2m deep balconies) might be unsuitable if
Among the choices, the corresponding cross- it is oriented towards the hillside (view is blocked and
sectional column areas are as follows: debris from the hill's sloped might fall directly into the
Choice a (1.7m x 1.7) is 2.89 sqm balcony which is accessible to occupants. However, if
Choice b (1.3m x 1.3m) is 1.69 sqm the balcony is oriented outwards the hill, there will be
Choice c (0.7m x 0.7m) is 0.49 sqm good vista and no danger from falling debris.
Choice d (1.9m x 1.9m) is 3.61 sqm Choice b (2.4m deep eaves) will be benefitial
Therefore, the best answer among the given choices especially if the eaves are oriented outwards the hill
would be B. 1.3m x 1.3m for the G/F columns. and if the sunpath is located in that direction.
However, the benefits of having deep eaves is more
Q#111. B. 0.8 x 0.8 geared toward protecting window openings from
See my explanation in Q#110 above (assuming the rainwater. The 2.4m depth would be easily carried by
government building is 5 storeys in height). the structural framing of the roofing, as the eave
Cross-Sectional Column Area > 0.0015*(Sum of framing is supposedly continuous to the structural
Tributary Area Over All Floors) trusses above.
Cross-Sectional Column Area > 0.0015*(2 floors * Choice c (2.4m deep canopy) might be unsuitable
100 sqm) considering that a canopy is generally defined as a
Cross-Sectional Column Area > 0.0015*(200 sqm) roofed structure attached to the building (i.e.,
Cross-Sectional Column Area > 0.30 sqm UNSUPPORTED/CANTILEVERED). Although deep
Among the choices, the corresponding cross- canopies provide a lot of advantages in so far as
sectional column areas are as follows: weatherproofing and sun-breaking are concerned, the
Choice a (1.2m x 1.2m) is 1.44 sqm 2.4m unsupported depth might pose danger during
Choice b (0.8m x 0.8m) is 0.64 sqm soil movement/earthquakes.
Choice c (1.5m x 1.5m) is 2.25 sqm Choice d (0.3m deep sun-breaker) might seem to be
Choice d (0.5m x 0.5m) is 0.25 sqm too shallow but it will depend on the installation and
Therefore, the best answer among the given choices orientation (vertical or horizontal). If one calculates
would be B. 0.8m x 0.8m for the 4/F columns. the correct sun-path, even the shallowest of sun-
breakers will be effective if such are angled correctly
Q#112. D. Steep gable roof to block the direct sun angle.
Similar to Q#23! So, with the above observations, the best answer to
All the other given choices have low-sloped roof the very subjective question would have to be the
which, given the forested site, will gather/collect 2.4m deep canopy (as NOT suitable for hillside
leaves, twigs, and other undesirable materials that will project).
impact the maintenance of such roofing. Providing a
steep roofing will eliminate this problem. Q#114. D. Windbreakers and sun-breakers
Similar to Q#145!
Q#113. C. 2.4 meter deep canopy Windbreakers and sun-breakers should be introduced
due to the high altitude and presence of high wind
velocities at the location of the project.
Q#115 to Q#119 (Project No. 04) 3/8" single glass in heavy frame - TL @ 30.13
<<ALL ANSWERS AND ANNOTATIONS BY ARCH. 5/8" single glass in heavy frame - TL @ 33.38
RAI BASSIG>> 1" single glass in heavy frame - TL @ 36.25
<<REVIEWER/QUESTIONNAIRE - SOURCE: 1/2" laminated glass - TL @ 41.14
UNKNOWN>> Source: Engineering Noise Control: Theory and
Practice by D.A. Bies and C.H. Hansen
Situation 24 - Project No. 04
Q#116. D. 0.2 and 0.25
Q#115. A. Wood or wood substitutes Refer to IRR of PD1096, Sec. 1207, Item 5, Sub-Item
The question is very subjective since sound/noise b., "Rise and Run. The rise of every step in a stairway
control of materials are dependent on the material's shall not exceed 200 MILLIMETERS and the run shall
mass/thickness and assembly. The given choices not be less than 250 MILLIMETERS...xxx"
offer no data as to how thick the materials are and
how many layers will it have, including its framework Q#117. A. 1.2
or cavity wall, if any. The sound transmission is also Refer to IRR of PD1096, Sec. 1207, Item 3, Sub-Item
dependent on the frequency of the sound, which is d., "Door Leaf Width. No leaf of an exit door shall
also not given in the question. However, I answered exceed 1.20 METERS in width."
the question using the average transmission loss of
all possible materials that would fit the description of Q#118. D. 28
the given choices. Acoustic Ceiling Board Qty. = [Area of Room (given) /
Area of Board (given)] - Area of Light Troffers (given)
The transmission loss (TL), at an average TL of Noise Acoustic Ceiling Board Qty. = [(4.0m * 6.1m) / (0.61m
Frequencies from 63Hz to 8,000Hz, of the given * 1.22m)] - 6 * (0.61m * 1.22m)
choices: Acoustic Ceiling Board Qty. = [24.4 sqm / 0.7422
sqm] - 6 * 0.7422 sqm
"WOOD OR WOOD SUBSTITUTES" Acoustic Ceiling Board Qty. = 32.8752 pcs - 4.4532
3/4" chipboard sheet on wood framework - TL @ 25 pcs
1/4" plywood sheets on wood framework - TL @ Acoustic Ceiling Board Qty. = Approx. 28 PCS
19.25
1/2" plywood sheets on wood framework - TL @ Q#119. C. 20.2
17.83 The question might have some typographical error
2" hardwood (mahogany) panel - TL @ 29.63 since a "T-runner angle section" would imply the use
of the MAIN T-RUNNERS across the grid of the
"TEXTURED-PAINTED MASONRY" whole ceiling surface. This means that the quantity of
4" CHB, painted - TL @ 41.38 Main T-Runners would be greater than the given
choices. Since all the choices are low in quantity, it
"METAL WITH TEXTURED SURFACE" may be possible that the question is asking for the
1.2mm thk. fluted steel panels, stiff edges, joints "Wall Angles" which are "L-shaped" and installed only
sealed - TL @ 27.13 along the perimeter walls where the T-Runner-
1.2mm thk. galvanized steel sheet - TL @ 26.25 Framed Ceiling will be mounted. 
0.9mm thk. galvanized steel sheet - TL @ 22.63
Therefore,
"SMOOTH GLASS" "T-runner angle section" (i.e., WALL ANGLES) Qty. =
1/4" single glass in heavy frame - TL @ 26.63 Room Perimeter (all side lengths are given)
"T-runner angle section" (i.e., WALL ANGLES) Qty. =
4.0m + 4.0m + 6.1m + 6.1m
"T-runner angle section" (i.e., WALL ANGLES) Qty. =
20.2 LINEAR METERS.
Q#120 to Q#130 (Project No. 05)
<<ALL ANSWERS AND ANNOTATIONS BY ARCH. Q#124. D. 65m x 107m = 6,955sqm
RAI BASSIG>> In plotting the lot and using the appropriate setbacks
<<REVIEWER/QUESTIONNAIRE - SOURCE: as per Table VIII.3 and my answers in Q#121, Q#122,
UNKNOWN>> and Q#123, the direct answer to the question about
the footprint dimensions would be B. 70m x 112m =
*****PROJECT NO. 05***** 7,840 sqm. This was computed with the given lot
dimensions of 80m(W) x 125m(D) then subtracting
Situation 25 - Project No. 05 the required setbacks of 8m (front) and 5m (sides and
rear): 80m(W) - 5m - 5m = 70m(Bldg. Width) and
Q#120. C. 70% of TLA 125m(D) - 8m - 5m = 112m(Bldg. Depth).
Refer to IRR of PD1096, Table VIII.1, under
Industrial-3, without firewall. However, referring to Figure VII.7. (illustration of a
Corner Lot Abutting 3 or More Streets, Alleys, Rivers,
Q#121. C. 8 etc.), it is mentioned in the code that "5% open space
Refer to IRR of PD1096, Table VIII.3, under 30.00 & for all group occupancies" must be provided. This
above RROW Width. means that according to Figure VII.7, the maximum
buildable area would be 95% for this particular type of
Q#122. B. 5 lot. 
Refer to IRR of PD1096, Table VIII.3, under 30.00 &
above RROW Width AND under Below 10.00 RROW Since the given total lot area (TLA) is 10,000 sqm,
Width. then the maximum buildable area to comply with the
Since the lot is bounded by 3 roads, the "side 5% open space is: 10,000 sqm * 0.95 = 9,500sqm.
setback" the question pertains to is technically
ANOTHER FRONT SETBACK/YARD in respect to On the other hand, referring to Table VIII.1 and my
the 6-m Minor RROW's. This means that the front answer in Q#120, it is found that the Maximum
setback of the 6-m RROW is the same as the "side Allowable Percentage of Site Occupancy (PSO) is
setback" of the 30-m RROW. Therefore, the 70% of the Total Lot Area (TLA) for this particular
appropriate setback should be used in accordance building occupancy/zone (I-3). This means that as per
with Table VIII.3. If there are discrepancies, then, as Table VIII.1, the maximum buildable area would be:
always, the more stringent shall prevail. 10,000 sqm * 0.70 = 7,000sqm.
As per code, the "side setback" with respect to the 30-
m RROW must be 5m, while the "front setback" with Now, we have computed 3 different values all in
respect to the 6-m RROW must be 5m. Since the accordance with the IRR of PD 1096 (as per Table
values are the same, we use 5m as the appropriate VIII.3, as per Figure VII.7, and as per Table VIII.1).
setback to answer the question.
According to Sec. 803, Item 2, "...xxx... In case of
Q#123. D. 5 DISCREPANCY between the SPECIFIED MAXIMUM
Refer to IRR of PD1096, Table VIII.3, under 30.00 & ALLOWABLE PSO and the OTHER LIGHT AND
above RROW Width. VENTILATION PROVISIONS under this Rule, the
See also my explanation in Q#122 as the same resulting LESSER building/structure footprint or gross
situation applies for the "side" which may also be floor area at the ground floor (or at grade level) MUST
treated as the "rear" depending on the reference PREVAIL." Also, according to Sec. 804, Item 11, "In
RROW of the particular project. case of CONFLICT in the provisions on lighting and
ventilation under this Rule or under the Code, the computed,
MORE STRINGENT restriction MUST PREVAIL." Rise/Run = Slope in Percentage
Moreover, according to Sec. 704, Item 4, Sub-Item a, Rise/125m = 0.04
"The following rules shall be observed in the Rise = 0.04 * 125m
determination of the Allowable Maximum Building Rise = 5m
Footprint (AMBF) for buildings and related habitable
structures. If the rules are COMPARED with (1) Rule Q#128. A. 4
VIII Table VIII.1 - Reference Table on Percentage of An average spatial width occupied by an adult person
Site Occupancy and Maximum Allowable would be approx. 0.60m (measured from shoulder-to-
Construction Area (MACA); (2) Rule VIII Tables VIII.2 shoulder with allowance for elbow and arm
and VIII.3 (setbacks, yards, and courts); OR (3) with movement). As the given width of the sidewalk is 2.40
the applicable stipulations under this Rule and with meters, then, the maximum number of adult persons
the applicable stipulations of the FIRE CODE, the that can walk side-by-side along the sidewalk is
MORE STRINGENT BUT APPLICABLE 2.40m / 0.60m = 4 persons.
REGULATION out of the aforementioned rules
SHOULD BE OBSERVED." Q#129. D. Perimeter
The RROW starts from the Property Line (or
So, with the 3 different values I have computed Perimeter), continues on to a Sidewalk (with Planting
above, the least footrpint area or the most stringent Strips, if any), then the Curb, then the Carriageway
shall govern. Therefore, the maximum building and onto another Curb, Sidewalk, and the Property
footprint sought by the question should be 7,000 sqm Line (or Perimeter) at the other side. Choice b. can be
as per Table VIII.1 (NOT 7,840 sqm as per Table eliminated immediately as a Front Yard is INSIDE the
VIII.3 NOR 9,500 sqm as per Figure VII.7). project site. Choice c. might be an option but only for
specific properties that have canopies projecting
Among the given choices in the question, since 7,000 beyond the perimeter into the public land (projecting
sqm is the maximum footprint, only choice A. 64m x 3m high above the sidewalk up to a maximum of
109m = 6,796sqm and choice D. 65m x 107m = 6,955 300mm distance before the Curb as per IRR of PD
sqm CONFORMS WITH THE NBCP. Choice B. and 1096).
Choice C. VIOLATES THE CODE.
Q#130. C. West yard
Situation 26 - Project No. 05 Since the problem already states that the main
access for container vans/trucks on a 24-hour basis is
Q#125. D. 125 along the 30-m RROW that is located at the western
Lot Depth = TLA (given in problem) / Lot Width (given portion of the lot (the frontage), then the best location
in problem) for the loading dock would be the west yard (in front
Lot Depth = 10,000 sqm / 80 m of the 30-m RROW). The other access roads (6-m
Lot Depth = 125 m RROW) are too narrow for container trucks to
maneuver.
Q#127. A. 5.0
Note that Q#126 is missing (probably due to two
Q#102's).
Since the Slope is 4% (as given in the problem) and
the Run (or property depth) is at 125m (as solved in
Q#125 above), the Rise/Depression can be
Q#131 to Q#140 (Project No. 05) receiving of materials, production, packaging to direct
<<ALL ANSWERS AND ANNOTATIONS BY ARCH. shipping out). Although a business center would not
RAI BASSIG>> hurt the factory, it is the least among the given
<<REVIEWER/QUESTIONNAIRE - SOURCE: choices to be considered as a service provision to
UNKNOWN>> cater the needs of the occupants.

Situation 27 - Project No. 05 Q#133. D. Overhead water tank


Similar to Q#13 and the second Q#102!
Q#131. A. Executive Lounge An Overhead Water Tank is a utility provision
Although an executive lounge is considered an (Plumbing Utilities).
amenity, it might not be appropriate for this particular
project. The project, as stated, is a factory serving Q#134. C. Covered parking
200 workers who are housed at a new facility and Similar to Q#14 and Q#103!
away from their families/residences. Choice c. would The other choices, Cistern, Generator Room, and
be a very appropriate recreational amenity for the STP all pertain to utility provisions (Plumbing,
workers as it would counter the workers' Electrical, and Sanitary Utilities, respectively).
boredom/depression and increase their productivity (it
might even shy them away from going at the videoke Q#135. B. Solid waste holding area and sewage
bars/drinking establishment located across the treatment plant
street). A worker's union office would also be Similar to Q#15 and Q#104!
benefitial for the firm-employee relationship as the Although the choices are very subjective, the main
office is a symbol that the rights of the workers are reason why choice B was selected as the best
highly respected by their employer. The video answer is due to maintenance/safety and by process
conference room would be appropriate for the type of of elimination of other choices. All of the other choices
business the firm has as described in the problem, are suitable to be located close to each other.
since the management cannot only talk to their clients Although a case can be made regarding choice A that
and suppliers but also show the actual has the words "service stairs" and "fire escapes"
products/packaging/materials during discussion leading to a false conclusion that there will be "2
meetings. An executive lounge, as compared with the stairs close to each other" and will be redundant.
other choices, would be very rarely used in the However, the term "fire escapes" are not limited to
factory. stairs alone. Fire escapes can be either exit
balconies, exit openings, exit corridors, and any other
Q#132. B. Business center for clients form of egress during the occurrence of fire. 
All the other given choices pertain to service
provisions for the main occupants of the structure Choice B is the most uncommon spatial
(factory). Gym and gameroom are both provisions to interrelationship. In the National Plumbing Code and
serve the recreational and physical needs of the 200 Sanitary Code, certain distances must be observed
stay-in workers (especially during breaks or day-offs). from Sewage Treatment Systems. Although a case
The cafeteria is another provision that would serve can also be made that both items in choice B are
the food requirements of the occupants. Choice b. wastes/disposal, the sewage treatment plant must be
Business center would only cater for selected segregated due to use of chemicals and other
occupants (clients) which rarely hold meetings in the substances used for the treatment and possible re-
factory. It has been stated in the problem that the use of the water. Hence, a solid waste holding area
operations of the factory will be an "in-and-out" (from (i.e., a garbage area) would be hazardous if placed
near the water/sewage water treatment area.
Q#140. D. 2.70
Situation 28 - Project No. 05 Similar to Q#80 and Q#139!
Refer to IRR of PD1096, Sec. 805, Item 1, "Habitable
Q#136. D. Relocation of informal settlers on the rooms provided with artificial ventilation shall have
Project Site, if any ceiling heights not less than 2.40 meters measured
Similar to Q#76! from floor to the ceiling...xxx...Above-stated rooms
Choice d., although it will still contribute to the WITH NATURAL VENTILATION shall have ceiling
proliferation of urban sprawl (which affects heights of NOT LESS THAN 2.70 METERS."
sustainability), it is the best answer among the given
choices as it does not directly affect the given project
site.

Q#137. D. Baguio stone


Similar to Q#77!
The embodied energy in producing the listed choices
are as follows:
High-Pressure Laminate Flooring - 11 to 12 MJ/kg
Vigan Tiles - 6.5 MJ/kg
Baguio Stone - 0.1 to 2.0 MJ/kg
Mariwasa Tiles - 12 MJ/kg

Q#138. B. Polycarbonate Sheet


Similar to Q#78!
Cement Bonded Board (CBB) - 11 MJ/kg
Recycled cardboard egg crate - 23 MJ/kg
Polycarbonate Sheet - 113 MJ/kg
Gypsum Board - 6.75 MJ/kg

Q#139. D. 2.10
Similar to Q#80 and Q#140!
Refer to IRR of PD1096, Sec. 805, Item 1, "Habitable
rooms provided WITH ARTIFICIAL VENTILATION
shall have ceiling heights not less than 2.40 meters
measured from floor to the ceiling; PROVIDED that
for buildings of MORE THAN ONE (1) STOREY, the
minimum ceiling height of the first storey shall be 2.70
meters and that for the second storey 2.40 meters
and the SUCCEEDING STORIES shall have an
UNOBSTRUCTED TYPICAL HEAD-ROOM
CLEARANCE of NOT LESS THAN 2.10 METERS
ABOVE THE FINISHED FLOOR. Above-stated rooms
WITH NATURAL VENTILATION shall have ceiling
heights of NOT LESS THAN 2.70 METERS."
Q#141 to Q#150 (Project No. 05)
<<ALL ANSWERS AND ANNOTATIONS BY ARCH. Q#143. C. Composite deck roof
RAI BASSIG>> Note that there might be a typographical error with
<<REVIEWER/QUESTIONNAIRE - SOURCE: choice c as it reads "Composible" deck roof, where it
UNKNOWN>> should have been written as "Composite" deck roof.

Situation 29 - Project No. 05 All of the other choices contain metal elements that, if
located near a coastal area, will be proned to
Q#141. D. 0.15 increased rusting due to presence of saline (sea
Similar to Q#25! salts) in the atmosphere. Choice b. is a better choice
There is insufficient data to answer the given than choice a. and choice d. because the steel rebars
question. Wall thicknesses are governed by Fire- are embedded in the concrete. However, during the
Resistive Time Period Ratings (see IRR of PD1096, fabrication and construction, the steel rebars are
Rule VI). Wall thickness are also dependent on the prone to oxidation. Choice c. is the best among the
thermal and noise reduction the occupant would want given choices as composite decking offers the beauty
to achieve. Then, there is also the factor if the CHB of wood without the drawbacks of potential corroding,
being asked is load bearing or non-load bearing. splintering or termite damage.
Preferences might also play a factor, for example, if
the occupant would want a lighter load on the upper Q#144. A. 3.0m deep eaves
floors, the exterior CHB can be 4" thick for those Similar to Q#24 and Q#113!
floors while the ground floor can be 6" thick. Another very subjective question with very vague
choices. All of the choices (eaves, balconies, sun-
However, for purposes of answering the given breakers, and canopies) may be introduced to a
question DESPITE the limited DATA given, the structure located at a lakeside vicinity. All will help
COMMON PRACTICE (not a rule or a provision in the with the sun-shading and rain-water protection of the
law) is to use 6" thick CHB for the exterior walls and building. However, to answer the question, I will
to use 4" thick CHB for the interior walls. A 6" CHB consider the vague measurements that appear in the
would be approx. 0.15m; while a 4" CHB would be choices (without any actual relation to the site where
approx. 0.10m. The primary reason for this the property is located as the question suggests).
"COMMON PRACTICE" is the AVAILABILITY OF Among the choices, the 3.0m deep eaves have the
CHB PRODUCED LOCALLY. Most suppliers only longest projection as compared with 1.5m, 0.3m, and
offer 4" and 6" thick CHB's. In "COMMON 1.8m for the balconies, sun-breakers, and canopy,
PRACTICE", the 4" thick CHB is used for the interior respectively. This lengthy projection, although
because it would only occupy less space (creating a beneficial for the total sun/rain protection, may be too
larger interior floor area), while the 6" thick CHB is impractical to be built without any supports at the
used at the exterior perimeter walls since there is a eaves' end. An eave is defined as a projection or
sufficient space at the property's yards and as the extension of the roofing WITHOUT ANY SUPPORTS.
perimeter walls are exposed to environmental factors Therefore, the best answer is a. due to impracticality
(noise, thermal, wind, etc), the thicker CHB would be and structural costs as compared to the other given
the better option to use. choices.

Q#142. B. 0.10 Q#145. D. Windbreakers and sun-breakers


Similar to Q#21! Similar to Q#114!
See my explanation above (Q#141). Windbreakers and sun-breakers should be introduced
due to the high altitude and presence of high wind Q#148. C. Daylight
velocities at the location of the project. Since work areas must be illuminated to represent the
light of day. The only choice would be to use Daylight
Situation 30 - Project No. 05 lamp colors. Although a case can be made if the work
area is designed for a "cozy" and "dramatic"
Q#146. C. Low-wattage track light atmosphere, wherein a warm-white lamp may be
We can safely eliminate all the other choices because used, the GENERAL choice would be the brightest for
choice a, b, and d are NOT devices but actual GENERAL WORKING.
lamps/bulbs. However, the main reason for choosing
c. is due to it's low-wattage (compared with halogen Q#149. B. Indirect lighting at the base of the curved
lamps and high-output spot lamps) which may affect ceiling
the surface of the watercolor painting due to its Choice a. and choice d. can be immediately
thermal levels. A CFL may be used, although as said, eliminated since both are down-light illumination
the given choice only supplies the bulb itself. A track (towards the floor) and will not emphasize the ceiling
light is the device to use for such purpose since the above it. Choice c. directly illuminates the ceiling,
lighting will be adjustable.  however, since a spotlight is used, a "circular beam"
will only highlight the parts of the curved ceiling the
In case another set of painting/s will be hung, beam hits - creating an imbalanced effect. Putting
whatever the size or the quantity, the track light can additional spotlights to cover up the other areas will
be adjusted to suit the illumination requirements. create overlapping of light beams and thus have
areas that are too bright and areas that are not. An
Q#147. B. Cool White indirect lighting at the base of the curved ceiling is the
This is another subjective question as there are no best among the given choices as the cove lighting
hard-and-fast rule in using lamp colors for any creats a soft but dramatic effect from the ceiling's
illumination requirements. This would depend on the base all the way up to it's curved surface. The lighting
preference and concerns of the actual user. Some will then be gradual and balanced.
people have eye-conditions that are strained when
the lights used are above 4000K (i.e., White, Cool Q#150. B. Industrial lighting (suspended fluorescent
White, and Daylight), so, they prefer warm lighting of lamps with reflectors)
about 2700K to 3000K. However, to answer the The general production area would require the most
subjective question, a Cool White color would be illumination, and among the given choices, only
GENERALLY suitable for task lighting. Daylight color choice b. offers high illuminance due to using
would be too bright (although some prefer this) for fluorescent lamp (i.e., tubes) with reflectors. Choice a.
task lighting since the distance between the lamp and will have the least brightness due to the diffusers and
the surface being illuminated is lesser than that if the will have the most difficulty in maintaining/lamp
lamp is located above the ceiling (as a general replacement (the mounting is directly on the slab soffit
lighting). A case can also be made for using Warm high above the ceiling and the diffuser has to be
White, however, GENERALLY SPEAKING, this would removed). Choice c. has a low angle of light
have a yellowish hue that may not be suitable for emittance due to it being a pendant-type lighting
drawing (or even writing/reading), especially if the using only compact fluorsecent lamps (CFL's), which
user is drawing using colored media. The cool white would mean having to provide a large amount of
will be a balanced choice in-between the Warm and quantity to fully illuminate the whole production area.
Day lighting effects. Choice d. has the same disadvantage of choice c.
plus an additional burdgen in electrical cost (due to it
being incandescent bulbs).

You might also like