Sr. no 23, in addition to 4-20mA DC, a digital o/p for failure status shall be
provided as mentioned in tender specification.
CH2M 2nd Comment (Dated 11.1019): - Please indicate the same in Data Sheet
(in the row of output)
Annexure Sheet – Add the following columns – Max flow, Min flow, Fluid
Pressure, Fluid temperature, location (Outdoor/Indoor)
CH2M 2nd Comment (Dated 11.1019): - Noted
Refer to data sheet Sr. no. 16, its showing that transmitter is 2- wire and power
supply is mentioned in the data sheet is 230V AC so please correct the same and
considered the transmitter 2- wire only as per tender specification.
CH2M Comment (12 Dec 19): According to data sheet point number 17, Two
wire transmitter is considered hence power supply should be 24VDC but
considered power supply is 230VAC 50 Hz (Refer the point number-
27) therefore contractor to review the same and considered the power supply as
per tender clause 6.18.6.2- D pH/ORP Analyser.
CH2M Comment (01 Jan 2020): 2 wire systems means, power and signal are
carried on the same set of wires and also known as loop powered devices so
contractor to change it 2 wire to 4 wire (if power supply 230VAC has been
considered) or 2 wire transmitter shall be deleted from the point number-17.
Contractor to revise the data sheet and same shall be submitted for the scrutiny.
Consultant (CH2M)
Contractor Reply Descision
(Open/Closed)
For pH sensor, flow does not require. It is to be installed in the tank. Closed