Replies to comments on Datasheet for pH Meter R2

Item Doc.Page/Clause Referencew No.


No

5 Datasheet for pH meter C-1624-01-


IC- GEN-1001-03
eet for pH Meter R2

Consultant (CH2M) Comments

Mention IP rating of pH sensor.


CH2M 2nd Comment (Dated 11.1019): - Please indicate in the data sheet.

Sr. no 23, in addition to 4-20mA DC, a digital o/p for failure status shall be
provided as mentioned in tender specification.
CH2M 2nd Comment (Dated 11.1019): - Please indicate the same in Data Sheet
(in the row of output)

Provide details of mounting kit for sensor.


CH2M 2nd Comment (Dated 11.1019): - Noted, in case sensor will installed on
line so contractor to provide the flow through assembly for the same. Hence
Closed
Mention Make and model no, attach GA drawing and catalogs.
CH2M 2nd Comment (Dated 11.1019): - Noted

Annexure Sheet – Add the following columns – Max flow, Min flow, Fluid
Pressure, Fluid temperature, location (Outdoor/Indoor)
CH2M 2nd Comment (Dated 11.1019): - Noted

Refer to data sheet Sr. no. 16, its showing that transmitter is 2- wire and power
supply is mentioned in the data sheet is 230V AC so please correct the same and
considered the transmitter 2- wire only as per tender specification.
CH2M Comment (12 Dec 19): According to data sheet point number 17, Two
wire transmitter is considered hence power supply should be 24VDC but
considered power supply is 230VAC 50 Hz (Refer the point number-
27) therefore contractor to review the same and considered the power supply as
per tender clause 6.18.6.2- D pH/ORP Analyser.

CH2M Comment (01 Jan 2020): 2 wire systems means, power and signal are
carried on the same set of wires and also known as loop powered devices so
contractor to change it 2 wire to 4 wire (if power supply 230VAC has been
considered) or 2 wire transmitter shall be deleted from the point number-17.
Contractor to revise the data sheet and same shall be submitted for the scrutiny.
Consultant (CH2M)
Contractor Reply Descision
(Open/Closed)

Attaching the datasheet of manufacturer Closed


Replies to comment : Ok Added
OK noted and done Closed
Replies to comments: Ok Added

Dip pipe for mounting of the sensor Closed

GA drawings shall be provided later. Closed

For pH sensor, flow does not require. It is to be installed in the tank. Closed

We didn’t get your query. Open


Reply to comment : 2 wire transmitter means here transmitter can take
input signal from two different sensors (ph/ ORP, pH/DO etc.
This is multiparameter transmitter. 2 wire does not have any
resemblance with power supply.
Power supply to transmitter is 230VAC only.

Reply to 3rd Comment: Ok, changes done in the datasheet. 4 wire


system.