Introduction 1
______________________________________________________________________________
SICAM RTUs
2
Interoperability of SICAM RTUs using
balanced mode according to IEC 60870-5-
101 (BPP)
______________________________________________________________________________
3
Interoperability of SICAM RTUs using
IEC 60870-5-101/104 unbalanced mode according to IEC 60870-5-
101 (UMP)
______________________________________________________________________________
Interoperability
Interoperability of SICAM RTUs using
IEC 60870-5-104 (ETx4) 4
______________________________________________________________________________
5
Interoperability of SICAM MIC using
unbalanced slave mode according to
IEC 60870-5-101
______________________________________________________________________________
Literature
______________________________________________________________________________
• SICAM RTUs
This manual describes the interoperability of SICAM RTUs using protocol element according
to IEC 60870-5-101/104 and essentially contains
The document you are reading right now is addressed to users, who are in charge of the
following tasks:
1 Introduction ........................................................................................................................7
Contents
In this documentation, all definitions are described that are necessary for communication
between automation units as per IEC 60870-5-101 and between automation units or
automation units and control room process computer systems as per IEC 60870-5-104.
Syntax:
strike-through the text descriptions of parameters which are not applicable to this
companion standard
Definition:
SICAM AK
SICAM AK3
SM-2551/BPPA0
SICAM BC
SM-0551/BPPA0 IEC 60870-5-101 Controlling-/Controlled
SICAM TM
Station“Balanced“- “Point-to-Point“
Standard protocol elements for communication as
BPP BPPT0 SICAM EMIC per IEC-60870-5-101 with point to point
configuration for the link between the SICAM RTUs
CP-8000 or SICAM RTUs and outside systems that support
BPPT0 CP-8021 these parameters.
CP-8022
BPPI0 CP-8050
SICAM AK
SICAM AK3
SM-2551/UMPMA0
SICAM BC
SM-0551 UMPMA0 IEC 60870-5-101 Controlling-/Controlled Station
SICAM TM
“Unbalanced Master“
Standard protocol elements for communication as
UMP
(Master) UMPMT0 SICAM EMIC per IEC-60870-5-101 with multipoint configuration
for the link between the SICAM RTUs or
CP-8000 SICAM RTUs and outside systems that support
UMPMT0 CP-8021 these parameters.
CP-8022
UMPMI0 CP-8050
SICAM AK
SICAM AK3
SM-2551/UMPSA0
SICAM BC
SM-0551 UMPSA0 IEC 60870-5-101 Controlling-/Controlled Station
SICAM TM
“Unbalanced Slave“
Standard protocol elements for communication as
UMP
(Slave) UMPST0 SICAM EMIC per IEC-60870-5-101 with multipoint configuration
for the link between the SICAM RTUs or
CP-8000 SICAM RTUs and outside systems that support
UMPST0 CP-8021 these parameters.
CP-8022
UMPSI0 CP-8050
SICAM AK
SICAM AK3
SM-2558/ETA4
SICAM BC
SICAM TM IEC 60870-5-104 Controlling-/Controlled Station
Standard protocol elements for communication as
ETx4 ET24 SICAM AK3 per IEC-60870-5-104 for linking SICAM RTUs or
CP-8000 SICAM RTUs and 3rd party systems which support
ET84 CP-8021 these parameters.
CP-8022
ETI4 CP-8050
Contents
This companion standard presents sets of parameters and alternatives from which subsets
must be selected to implement particular telecontrol systems. Certain parameter values, such
as the number of octets in the COMMON ADDRESS of ASDUs represent mutually exclusive
alternatives. This means that only one value of the defined parameters is admitted per
system. Other parameters, such as the listed set of different process information in command
and in monitor direction, allow the specification of the complete set or subsets, as appropriate
for given applications. This clause summarizes the parameters of the previous clauses to
facilitate a suitable selection for a specific application. If a system is composed of equipment
stemming from different manufacturers it is necessary that all partners agree on the selected
parameters.
Note:
In addition, the full specification of a system may require individual selection of certain
parameters for certain parts of the system, such as the individual selection of scaling factors
for individually addressable measured values.
The possible selection (blank, X, R, or B) is specified for each specific clause or parameter.
(system-specific parameter, indicate the system’s or station’s function by marking one of the
following with ‘X’)
X System definition
Controlling Station (Master)
Controlled Station (Slave)
(network-specific parameter, all configurations that are used are to be marked ‘X’)
(network-specific parameter, all interfaces and data rates that are used are to be marked ‘X’)
(network-specific parameter, all options that are used are to be marked ‘X’. Specify the
maximum frame length. If a non-standard assignment of class 2 messages is implemented for
unbalanced transmission, indicate the Type ID and COT of all messages assigned to class 2.)
Frame format FT 1.2, single character 1 and the fixed time out interval are used exclusively in
this companion standard.
Frame length
Maximum length L (number of octets, possible 9-255)
When using an unbalanced link layer, the following ASDU types are returned in class 2
messages (low priority) with the indicated causes of transmission:
Note: In response to a class 2 poll, a controlled station may respond with class 1 data when
there is no class 2 data available.
Mode 1 (Least significant octet first), as defined in clause 4.10 of IEC 60870-5-4, is used
exclusively in this companion standard.
X 1 Octet X 2 Octets
X 1 Octet X structured
X 2 Octets X unstructured
X 3 Octets
Cause of transmission
(system-specific parameter, all configurations that are used are to be marked „X“)
Either ASDUs of the set <2>, <4>, <6>, <8>, <10>, <12>, <14>, <16>, <17>, <18>, <19> or of
the set <30 –40> are used.
6) Reception possible, thereby the blocked single-point information is deblocked and further
individually processed as TI = 30 (address translation occurs algorithmic).
Either the ASDUs of the set <45> - <51> or of the set <58> - <64> are used.
+
… secondary application function only
4) … Not used in IEC 60870-5-101 Edition 2. No use case.
File transfer
(station-specific parameter, mark each Type ID „X“ if it is only used in the standard direction,
„R“ if only used in the reverse direction, and „B“ if used in both directions)
<1> M_SP_NA_1 B B B B B
<2> M_SP_TA_1 B B B
<3> M_DP_NA_1 B B B B B
<4> M_DP_TA_1 B B B
<5> M_ST_NA_1 B B* B* B* B*
<6> M_ST_TA_1 B* B* B*
<7> M_BO_NA_1 B B* B*
<8> M_BO_TA_1 B*
<9> M_ME_NA_1 B B B B
<10> M_ME_TA_1 B
<11> M_ME_NB_1 B B B B
<12> M_ME_TB_1 B
<13> M_ME_NC_1 B B B B
<14> M_ME_TC_1 B
<15> M_IT_NA_1 B B
<16> M_IT_TA_1 B B
<17> M_EP_TA_1 B
<18> M_EP_TB_1 B
<19> M_EP_TC_1 B
<20> M_PS_NA_1 6) 6)
<21> M_ME_ND_1
<30> M_SP_TB_1 B B B
<31> M_DP_TB_1 B B B
<32> M_ST_TB_1 B* B* B*
<33> M_BO_TB_1 B*
<34> M_ME_TD_1 B
<35> M_ME_TE_1 B
<36> M_ME_TF_1 B
<37> M_IT_TB_1 B B
<38> M_EP_TD_1 B
<39> M_EP_TE_1 B
<40> M_EP_TF_1 B
<45> C_SC_NA_1 B B B B B B B B B
<46> C_DC_NA_1 B B B B B B B B B
<47> C_RC_NA_1 B B B B B B B B B
<48> C_SE_NA_1 B B B B B* B B B B
<49> C_SE_NB_1 B B B B B* B B B B
Station initialization
(station-specific parameter, mark „X“ if function is used)
Read procedure
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
Read procedure
Spontaneous transmission
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
B Spontaneous transmission
The following type identifications may be transmitted in succession caused by a single status
change of an information object. The particular information object addresses for which double
transmission is enabled are defined in a project-specific list.
Station interrogation
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
B global
B group 1 B group 7 B group 13
B group 2 B group 8 B group 14
B group 3 B group 9 B group 15
B group 4 B group 10 B group 16
B group 5 B group 11
B group 6 B group 12
Information Object Addresses assigned to each group must be shown in a separate table.
Clock synchronization
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
B Clock synchronization
Command transmission
(object-specific parameter, mark „X“ if function only used in standard direction, „R“ if only used
in the reverse direction, and „B“ if used in both directions)
B No additional definition
B Short pulse duration (duration determined by a system parameter in the outstation)
B Long pulse duration (duration determined by a system parameter in the outstation)
B* Persistent output
B Counter read
B Counter freeze without reset
B Counter freeze with reset
B Counter reset
Parameter loading
(object-specific parameter, mark „X“ if function only used in standard direction, „R“ if only used
in the reverse direction, and „B“ if used in both directions)
X Threshold value
X Smoothing factor
X Low limit for transmission of measured value
X High limit for transmission of measured value
Parameter activation
(object-specific parameter, mark „X“ if function only used in standard direction, „R“ if only used
in the reverse direction, and „B“ if used in both directions)
Test procedure
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
B Test procedure
File transfer
(station-specific parameter, mark each used function „X“)
X* Transparent file
X* Transmission of disturbance data of protection equipment
X Transmission of sequences of events
X* Transmission of sequences of recorded analog values
Transparent file
X* … Data can be transparently transported by the system but not generated or evaluated.
A maximum of 220 bytes user data can be transported.
Background scan
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
B Background scan
Note: used for data which are transmitted caused by a self-initiated general interrogation
Contents
Note
Not valid for SICAM MIC.
For SICAM MIC see Interoperability of SICAM MIC using unbalanced slave mode according to IEC 60870-
5-101
This companion standard presents sets of parameters and alternatives from which subsets
must be selected to implement particular telecontrol systems. Certain parameter values, such
as the number of octets in the COMMON ADDRESS of ASDUs represent mutually exclusive
alternatives. This means that only one value of the defined parameters is admitted per
system. Other parameters, such as the listed set of different process information in command
and in monitor direction, allow the specification of the complete set or subsets, as appropriate
for given applications. This clause summarizes the parameters of the previous clauses to
facilitate a suitable selection for a specific application. If a system is composed of equipment
stemming from different manufacturers it is necessary that all partners agree on the selected
parameters.
Note:
In addition, the full specification of a system may require individual selection of certain
parameters for certain parts of the system, such as the individual selection of scaling factors
for individually addressable measured values.
The possible selection (blank, X, R, or B) is specified for each specific clause or parameter.
(system-specific parameter, indicate the system’s or station’s function by marking one of the
following with ‘X’)
System definition
X Controlling Station (Master)
X Controlled Station (Slave)
(network-specific parameter, all configurations that are used are to be marked ‘X’)
(network-specific parameter, all interfaces and data rates that are used are to be marked ‘X’)
(network-specific parameter, all options that are used are to be marked ‘X’. Specify the
maximum frame length. If a non-standard assignment of class 2 messages is implemented for
unbalanced transmission, indicate the Type ID and COT of all messages assigned to class 2.)
Frame format FT 1.2, single character 1 and the fixed time out interval are used exclusively in
this companion standard.
Frame length
Maximum length L (number of octets, possible 9-255)
When using an unbalanced link layer, the following ASDU types are returned in class 2
messages (low priority) with the indicated causes of transmission:
parametrizable all
Note: In response to a class 2 poll, a controlled station may respond with class 1 data when
there is no class 2 data available.
Mode 1 (Least significant octet first), as defined in clause 4.10 of IEC 60870-5-4, is used
exclusively in this companion standard.
X 1 Octet X 2 Octets
X 1 Octet X structured
X 2 Octetst X unstructured
X 3 Octets
Cause of transmission
(system-specific parameter, all configurations that are used are to be marked „X“)
Either ASDUs of the set <2>, <4>, <6>, <8>, <10>, <12>, <14>, <16>, <17>, <18>, <19> or of
the set <30 –40> are used.
6) Reception possible, thereby the blocked single-point information is deblocked and further
individually processed as TI = 30 (address translation occurs algorithmic).
Either the ASDUs of the set <45> - <51> or of the set <58> - <64> are used.
File transfer
(station-specific parameter, mark each Type ID „X“ if it is only used in the standard direction,
„R“ if only used in the reverse direction, and „B“ if used in both directions)
<1> M_SP_NA_1 B B B B B
<2> M_SP_TA_1 B B B
<3> M_DP_NA_1 B B B B B
<4> M_DP_TA_1 B B B
<5> M_ST_NA_1 B B* B* B* B*
<6> M_ST_TA_1 B* B* B*
<7> M_BO_NA_1 B B* B*
<8> M_BO_TA_1 B*
<9> M_ME_NA_1 B B B B
<10> M_ME_TA_1 B
<11> M_ME_NB_1 B B B B
<12> M_ME_TB_1 B
<13> M_ME_NC_1 B B B B
<14> M_ME_TC_1 B
<15> M_IT_NA_1 B B
<16> M_IT_TA_1 B B
<17> M_EP_TA_1 B
<18> M_EP_TB_1 B
<19> M_EP_TC_1 B
<20> M_PS_NA_1 6) 6)
<21> M_ME_ND_1
<30> M_SP_TB_1 B B B
<31> M_DP_TB_1 B B B
<32> M_ST_TB_1 B* B* B*
<33> M_BO_TB_1 B*
<34> M_ME_TD_1 B
<35> M_ME_TE_1 B
<36> M_ME_TF_1 B
<37> M_IT_TB_1 B B
<38> M_EP_TD_1 B
<39> M_EP_TE_1 B
<40> M_EP_TF_1 B
<45> C_SC_NA_1 B B B B B B B B+ B
<46> C_DC_NA_1 B B B B B B B B+ B
<47> C_RC_NA_1 B B B B B B B B+ B
<48> C_SE_NA_1 B B B B B* B B B+ B
<49> C_SE_NB_1 B B B B B* B B B+ B
B* can be used only when the COT is generated via a function-plan application (CAEx)
+ nur UMPS
6) Reception possible, thereby the blocked single-point information is deblocked and further
individually processed as TI = 30 (address translation occurs algorithmic).
*) blank or X only
+ UMPS only
5) … transparent transmission by system
Station initialization
(station-specific parameter, mark „X“ if function is used)
X+ Remote initialization
Read procedure
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
Read procedure
Spontaneous transmission
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
B Spontaneous transmission
The following type identifications may be transmitted in succession caused by a single status
change of an information object. The particular information object addresses for which double
transmission is enabled are defined in a project-specific list.
Station interrogation
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
B global
B group 1 B group 7 B group 13
B group 2 B group 8 B group 14
B group 3 B group 9 B group 15
B group 4 B group 10 B group 16
B group 5 B group 11
B group 6 B group 12
Information Object Addresses assigned to each group must be shown in a seperate table.
Clock synchronization
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
B Clock synchronization
Command transmission
(object-specific parameter, mark „X“ if function only used in standard direction, „R“ if only used
in the reverse direction, and „B“ if used in both directions)
B No additional definition
B Short pulse duration (duration determined by a system parameter in the outstation)
B Long pulse duration (duration determined by a system parameter in the outstation)
B* Persistent output
B Counter read
B Counter freeze without reset
B Counter freeze with reset
B Counter reset
Parameter loading
(object-specific parameter, mark „X“ if function only used in standard direction, „R“ if only used
in the reverse direction, and „B“ if used in both directions)
X Threshold value
X Smoothing factor
X Low limit for transmission of measured value
X High limit for transmission of measured value
Parameter activation
(object-specific parameter, mark „X“ if function only used in standard direction, „R“ if only used
in the reverse direction, and „B“ if used in both directions)
Test procedure
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
X Test procedure
File transfer
(station-specific parameter, mark each used function „X“)
X* Transparent file
X* Transmission of disturbance data of protection equipment
X Transmission of sequences of events
X* Transmission of sequences of recorded analog values
Transparent file
X* … Data can be transparently transported by the system but not generated or evaluated.
A maximum of 220 bytes user data can be transported.
Background scan
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
B Background scan
Note: used for data which are transmitted caused by a self-initiated general interrogation
Contents
This companion standard presents sets of parameters and alternatives from which subsets
must be selected to implement particular telecontrol systems. Certain parameter values, such
as the choice of “structured“ or “unstructured“ fields of the INFORMATION OBJECT ADDRESS of
ASDUs represent mutually exclusive alternatives. This means that only one value of the
defined parameters is admitted per system. Other parameters, such as the listed set of
different process information in command and in monitor direction allow the specification of
the complete set or subsets, as appropriate for given applications. This clause summarizes
the parameters of the previous clauses to facilitate a suitable selection for a specific
application. If a system is composed of equipment stemming from different manufacturers it is
necessary that all partners agree on the selected parameters.
The interoperability list is defined as in IEC 60870-5-101 and extended with parameters used
in this standard. The text descriptions of parameters which are not applicable to this
companion standard are strike-through (corresponding check box is marked black).
Note:
In addition, the full specification of a system may require individual selection of certain
parameters for certain parts of the system, such as the individual selection of scaling factors
for individually addressable measured values.
The possible selection (blank, X, R, or B) is specified for each specific clause or parameter.
A black check box indicates that the option cannot be selected in this companion standard.
(system-specific parameter, indicate the system’s or station’s function by marking one of the
following with ‘X’)
X System definition
Controlling Station (Master)
Controlled Station (Slave)
(network-specific parameter, all configurations that are used are to be marked ‘X’)
(network-specific parameter, all interfaces and data rates that are used are to be marked ‘X’)
(network-specific parameter, all options that are used are to be marked ‘X’. Specify the
maximum frame length. If a non-standard assignment of class 2 messages is implemented for
unbalanced transmission, indicate the Type ID and COT of all messages assigned to class 2.)
Frame format FT 1.2, single character 1 and the fixed time out interval are used exclusively in
this companion standard.
Frame length
Maximum length L (number of octets, possible 9-255)
When using an unbalanced link layer, the following ASDU types are returned in class 2
messages (low priority) with the indicated causes of transmission:
Note: In response to a class 2 poll, a controlled station may respond with class 1 data when
there is no class 2 data available.
Mode 1 (Least significant octet first), as defined in clause 4.10 of IEC 60870-5-4, is used
exclusively in this companion standard.
1 Octet X 2 Octets
1 Octet X structured
2 Octets X unstructured
X 3 Octets
Cause of transmission
(system-specific parameter, all configurations that are used are to be marked „X“)
Length of APDU
(system-specific parameter, specify the maximum length of the APDU per system)
The maximum length of the APDU is 253 (default). The maximum length may be reduced per
system.
In this companion standard only the use of the set <30> – <40> for ASDUs with time tag is
permitted.
6) Reception possible, thereby the blocked single-point information is deblocked and further
individually processed as TI = 30 (address translation occurs algorithmic).
Either the ASDUs of the set <45> - <51> or of the set <58> - <64> are used.
File transfer
(station-specific parameter, mark each Type ID „X“ if it is only used in the standard direction,
„R“ if only used in the reverse direction, and „B“ if used in both directions)
<1> M_SP_NA_1 B B B B B
<2> M_SP_TA_1
<3> M_DP_NA_1 B B B B B
<4> M_DP_TA_1
<5> M_ST_NA_1 B B* B* B* B*
<6> M_ST_TA_1
<7> M_BO_NA_1 B B* B*
<8> M_BO_TA_1
<9> M_ME_NA_1 B B B B
<10> M_ME_TA_1
<11> M_ME_NB_1 B B B B
<12> M_ME_TB_1
<13> M_ME_NC_1 B B B B
<14> M_ME_TC_1
<15> M_IT_NA_1 B B
<16> M_IT_TA_1
<17> M_EP_TA_1
<18> M_EP_TB_1
<19> M_EP_TC_1
<20> M_PS_NA_1 6) 6)
<21> M_ME_ND_1
<30> M_SP_TB_1 B B B
<31> M_DP_TB_1 B B B
<32> M_ST_TB_1 B* B* B*
<33> M_BO_TB_1 B*
<34> M_ME_TD_1 B
<35> M_ME_TE_1 B
<36> M_ME_TF_1 B
<37> M_IT_TB_1 B B
<38> M_EP_TD_1 B
<39> M_EP_TE_1 B
<40> M_EP_TF_1 B
<45> C_SC_NA_1 B B B B B B B B B
<46> C_DC_NA_1 B B B B B B B B B
<47> C_RC_NA_1 B B B B B B B B B
<48> C_SE_NA_1 B B B B B* B B B B
<49> C_SE_NB_1 B B B B B* B B B B
6) Reception possible, thereby the blocked single-point information is deblocked and further
individually processed as TI = 30 (address translation occurs algorithmic).
*) blank or X only
B* can be generated by the PLC
5) transparent transmission by system
7) not supported; reply sent with COT=45 „unknown cause of transmission“
Station initialization
(station-specific parameter, mark „X“ if function is used)
X Remote initialization
Read procedure
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
Read procedure
Spontaneous transmission
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
B Spontaneous transmission
The following type identifications may be transmitted in succession caused by a single status
change of an information object. The particular information object addresses for which double
transmission is enabled are defined in a project-specific list.
Station interrogation
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
B global
B group 1 B group 7 B group 13
B group 2 B group 8 B group 14
B group 3 B group 9 B group 15
B group 4 B group 10 B group 16
B group 5 B group 11
B group 6 B group 12
Information Object Addresses assigned to each group must be shown in a separate table.
Clock synchronization
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
Command transmission
(object-specific parameter, mark „X“ if function only used in standard direction, „R“ if only used
in the reverse direction, and „B“ if used in both directions)
B No additional definition
B Short pulse duration (duration determined by a system parameter in the outstation)
B Long pulse duration (duration determined by a system parameter in the outstation)
B* Persistent output
B* … can be used only when the COT is generated via a function plan application (CAEx)
X Supervision of maximum delay in command direction of commands and set point commands
0-65535s Maximum allowable delay of commands and set point commands
B Counter read
B Counter freeze without reset
B Counter freeze with reset
B Counter reset
Parameter loading
(object-specific parameter, mark „X“ if function only used in standard direction, „R“ if only used
in the reverse direction, and „B“ if used in both directions)
X Threshold value
X Smoothing factor
X Low limit for transmission of measured value
X High limit for transmission of measured value
Parameter activation
(object-specific parameter, mark „X“ if function only used in standard direction, „R“ if only used
in the reverse direction, and „B“ if used in both directions)
Test procedure
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
B Test procedure
File transfer
(station-specific parameter, mark each used function „X“)
X* Transparent file
X* Transmission of disturbance data of protection equipment
X Transmission of sequences of events
X* Transmission of sequences of recorded analog values
Transparent file
X* … Data can be transparently transported by the system but not generated or evaluated.
A maximum of 220 bytes user data can be transported.
Background scan
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
B Background scan
Note: used for data which are transmitted caused by a self-initiated general interrogation
Portnumber
Redundant Connections
X Ethernet 802.3
Serial X.21 interface
Other selection from RFC 2200
1. ………………………………………
2. ………………………………………
3. ………………………………………
4. ………………………………………
5. ………………………………………
6. ………………………………………
7. etc.
Contents
This companion standard presents sets of parameters and alternatives from which subsets
must be selected to implement particular telecontrol systems. Certain parameter values, such
as the number of octets in the COMMON ADDRESS of ASDUs represent mutually exclusive
alternatives. This means that only one value of the defined parameters is admitted per
system. Other parameters, such as the listed set of different process information in command
and in monitor direction, allow the specification of the complete set or subsets, as appropriate
for given applications. This clause summarizes the parameters of the previous clauses to
facilitate a suitable selection for a specific application. If a system is composed of equipment
stemming from different manufacturers it is necessary that all partners agree on the selected
parameters.
Note:
In addition, the full specification of a system may require individual selection of certain
parameters for certain parts of the system, such as the individual selection of scaling factors
for individually addressable measured values.
The possible selection (blank, X, R, or B) is specified for each specific clause or parameter.
(system-specific parameter, indicate the system’s or station’s function by marking one of the
following with ‘X’)
X System definition
Controlling Station (Master)
X Controlled Station (Slave)
(network-specific parameter, all configurations that are used are to be marked ‘X’)
(network-specific parameter, all interfaces and data rates that are used are to be marked ‘X’)
(network-specific parameter, all options that are used are to be marked ‘X’. Specify the
maximum frame length. If a non-standard assignment of class 2 messages is implemented for
unbalanced transmission, indicate the Type ID and COT of all messages assigned to class 2.)
Frame format FT 1.2, single character 1 and the fixed time out interval are used exclusively in
this companion standard.
Frame length
255 Maximum length L (number of octets, possible 9-255) in control direction
255 Maximum length L (number of octets, possible 9-255) in monitor direction
When using an unbalanced link layer, the following ASDU types are returned in class 2
messages (low priority) with the indicated causes of transmission:
9,10,11,12,13,14 <3>
Note: In response to a class 2 poll, a controlled station may respond with class 1 data when
there is no class 2 data available.
Mode 1 (Least significant octet first), as defined in clause 4.10 of IEC 60870-5-4, is used
exclusively in this companion standard.
X 1 Octet X 2 Octets
X 1 Octet structured
X 2 Octets X unstructured
X 3 Octets
Cause of transmission
(system-specific parameter, all configurations that are used are to be marked „X“)
Either ASDUs of the set <2>, <4>, <6>, <8>, <10>, <12>, <14>, <16>, <17>, <18>, <19> or of
the set <30 –40> are used.
File transfer
(station-specific parameter, mark each Type ID „X“ if it is only used in the standard direction,
„R“ if only used in the reverse direction, and „B“ if used in both directions)
<1> M_SP_NA_1 B X X X*
<2> M_SP_TA_1 B X X
<3> M_DP_NA_1 X X X X*
<4> M_DP_TA_1 X X X
<5> M_ST_NA_1
<6> M_ST_TA_1
<7> M_BO_NA_1
<8> M_BO_TA_1
<9> M_ME_NA_1 X X*
<10> M_ME_TA_1 X
<11> M_ME_NB_1 X X*
<12> M_ME_TB_1 X
<13> M_ME_NC_1 X X*
<14> M_ME_TC_1 X
<15> M_IT_NA_1 X X
<16> M_IT_TA_1 X X
<17> M_EP_TA_1
<18> M_EP_TB_1
<19> M_EP_TC_1
<20> M_PS_NA_1
<21> M_ME_ND_1
<30> M_SP_TB_1 B X X
<31> M_DP_TB_1 X X X
<32> M_ST_TB_1
<33> M_BO_TB_1
<34> M_ME_TD_1 X
<35> M_ME_TE_1 X
<36> M_ME_TF_1 X
<37> M_IT_TB_1 X X
<38> M_EP_TD_1
<39> M_EP_TE_1
<40> M_EP_TF_1
<45> C_SC_NA_1 X X X X X
<46> C_DC_NA_1 X X X X X
<47> C_RC_NA_1
<48> C_SE_NA_1 X X
<49> C_SE_NB_1 X X
*) … blank or X only
Station initialization
(station-specific parameter, mark „X“ if function is used)
X Remote initialization
Read procedure
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
Read procedure
Spontaneous transmission
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
B Spontaneous transmission
The following type identifications may be transmitted in succession caused by a single status
change of an information object. The particular information object addresses for which double
transmission is enabled are defined in a project-specific list.
Station interrogation
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
B global
group 1 group 7 group 13
group 2 group 8 group 14
group 3 group 9 group 15
group 4 group 10 group 16
group 5 group 11
group 6 group 12
Information Object Addresses assigned to each group must be shown in a separate table.
Clock synchronization
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
X Clock synchronization
Command transmission
(object-specific parameter, mark „X“ if function only used in standard direction, „R“ if only used
in the reverse direction, and „B“ if used in both directions)
X No additional definition
X Short pulse duration (duration determined by a system parameter in the outstation)
X Long pulse duration (duration determined by a system parameter in the outstation)
X* Persistent output
X Counter read
X Counter freeze without reset
X Counter freeze with reset
X Counter reset
Parameter loading
(object-specific parameter, mark „X“ if function only used in standard direction, „R“ if only used
in the reverse direction, and „B“ if used in both directions)
Threshold value
Smoothing factor
Low limit for transmission of measured value
High limit for transmission of measured value
Parameter activation
(object-specific parameter, mark „X“ if function only used in standard direction, „R“ if only used
in the reverse direction, and „B“ if used in both directions)
Test procedure
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
X Test procedure
File transfer
(station-specific parameter, mark each used function „X“)
Transparent file
Transmission of disturbance data of protection equipment
X Transmission of sequences of events
Transmission of sequences of recorded analog values
Transparent file
X* … Data can be transparently transported by the system but not generated or evaluated.
A maximum of 220 bytes user data can be transported.
Background scan
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
Background scan
Note: used for data which are transmitted caused by a self-initiated general interrogation
Contents
This companion standard presents sets of parameters and alternatives from which subsets
must be selected to implement particular telecontrol systems. Certain parameter values, such
as the choice of “structured“ or “unstructured“ fields of the INFORMATION OBJECT ADDRESS of
ASDUs represent mutually exclusive alternatives. This means that only one value of the
defined parameters is admitted per system. Other parameters, such as the listed set of
different process information in command and in monitor direction allow the specification of
the complete set or subsets, as appropriate for given applications. This clause summarizes
the parameters of the previous clauses to facilitate a suitable selection for a specific
application. If a system is composed of equipment stemming from different manufacturers it is
necessary that all partners agree on the selected parameters.
The interoperability list is defined as in IEC 60870-5-101 and extended with parameters used
in this standard. The text descriptions of parameters which are not applicable to this
companion standard are strike-through (corresponding check box is marked black).
Note:
In addition, the full specification of a system may require individual selection of certain
parameters for certain parts of the system, such as the individual selection of scaling factors
for individually addressable measured values.
The possible selection (blank, X, R, or B) is specified for each specific clause or parameter.
A black check box indicates that the option cannot be selected in this companion standard.
(system-specific parameter, indicate the system’s or station’s function by marking one of the
following with ‘X’)
X System definition
Controlling Station
Controlled Station
(network-specific parameter, all configurations that are used are to be marked ‘X’)
(network-specific parameter, all interfaces and data rates that are used are to be marked ‘X’)
(network-specific parameter, all options that are used are to be marked ‘X’. Specify the
maximum frame length. If a non-standard assignment of class 2 messages is implemented for
unbalanced transmission, indicate the Type ID and COT of all messages assigned to class 2.)
Frame format FT 1.2, single character 1 and the fixed time out interval are used exclusively in
this companion standard.
Frame length
Maximum length L (number of octets, possible 9-255)
When using an unbalanced link layer, the following ASDU types are returned in class 2
messages (low priority) with the indicated causes of transmission:
Note: In response to a class 2 poll, a controlled station may respond with class 1 data when
there is no class 2 data available.
Mode 1 (Least significant octet first), as defined in clause 4.10 of IEC 60870-5-4, is used
exclusively in this companion standard.
1 Octet X 2 Octets
1 Octet X structured
2 Octets X unstructured
X 3 Octets
Cause of transmission
(system-specific parameter, all configurations that are used are to be marked „X“)
Length of APDU
(system-specific parameter, specify the maximum length of the APDU per system)
The maximum length of the APDU is 253 (default). The maximum length may be reduced per
system.
In this companion standard only the use of the set <30> – <40> for ASDUs with time tag is
permitted.
Either the ASDUs of the set <45> - <51> or of the set <58> - <64> are used.
File transfer
(station-specific parameter, mark each Type ID „X“ if it is only used in the standard direction,
„R“ if only used in the reverse direction, and „B“ if used in both directions)
<1> M_SP_NA_1 B B B B B
<2> M_SP_TA_1
<3> M_DP_NA_1 B B B B B
<4> M_DP_TA_1
<5> M_ST_NA_1 B B B* B* B*
<6> M_ST_TA_1
<7> M_BO_NA_1 B B B*
<8> M_BO_TA_1
<9> M_ME_NA_1 B B B
<10> M_ME_TA_1
<11> M_ME_NB_1 B B B
<12> M_ME_TB_1
<13> M_ME_NC_1 B B B
<14> M_ME_TC_1
<15> M_IT_NA_1 B B
<16> M_IT_TA_1
<17> M_EP_TA_1
<18> M_EP_TB_1
<19> M_EP_TC_1
<20> M_PS_NA_1
<21> M_ME_ND_1
<30> M_SP_TB_1 B B B
<31> M_DP_TB_1 B B B
<32> M_ST_TB_1 B* B* B*
<33> M_BO_TB_1 B*
<34> M_ME_TD_1 B
<35> M_ME_TE_1 B
<36> M_ME_TF_1 B
<37> M_IT_TB_1 B B
<38> M_EP_TD_1 B
<39> M_EP_TE_1 B
<40> M_EP_TF_1 B
<45> C_SC_NA_1 B B B B B B B B B
<46> C_DC_NA_1 B B B B B B B B B
<47> C_RC_NA_1 B B B B B B B B B
<48> C_SE_NA_1 B B B B B* B B B B
<49> C_SE_NB_1 B B B B B* B B B B
B* can be generated by the PLC
Station initialization
(station-specific parameter, mark „X“ if function is used)
X Remote initialization
Read procedure
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
Read procedure
Spontaneous transmission
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
B Spontaneous transmission
The following type identifications may be transmitted in succession caused by a single status
change of an information object. The particular information object addresses for which double
transmission is enabled are defined in a project-specific list.
Station interrogation
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
B global
B group 1 B group 7 B group 13
B group 2 B group 8 B group 14
B group 3 B group 9 B group 15
B group 4 B group 10 B group 16
B group 5 B group 11
B group 6 B group 12
Information Object Addresses assigned to each group must be shown in a separate table.
Clock synchronization
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
Command transmission
(object-specific parameter, mark „X“ if function only used in standard direction, „R“ if only used
in the reverse direction, and „B“ if used in both directions)
B No additional definition
B Short pulse duration (duration determined by a system parameter in the outstation)
B Long pulse duration (duration determined by a system parameter in the outstation)
B* Persistent output
X Supervision of maximum delay in command direction of commands and set point commands
0-255s Maximum allowable delay of commands and set point commands
B Counter read
B Counter freeze without reset
B Counter freeze with reset
B Counter reset
Parameter loading
(object-specific parameter, mark „X“ if function only used in standard direction, „R“ if only used
in the reverse direction, and „B“ if used in both directions)
X Threshold value
X Smoothing factor
X Low limit for transmission of measured value
X High limit for transmission of measured value
Parameter activation
(object-specific parameter, mark „X“ if function only used in standard direction, „R“ if only used
in the reverse direction, and „B“ if used in both directions)
Test procedure
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
B Test procedure
File transfer
(station-specific parameter, mark each used function „X“)
X* Transparent file
X* Transmission of disturbance data of protection equipment
X Transmission of sequences of events
X* Transmission of sequences of recorded analog values
X* Transparent file
X* … Data can be transparently transported by the system but not generated or evaluated.
A maximum of 220 bytes user data can be transported.
Background scan
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
B Background scan
Note: used for data which are transmitted caused by a self-initiated general interrogation
15
Maximum range of value k: 1 to 32767 (2 – 1) APDUs, accuracy 1 APDU
Portnumber
Redundant Connections
RFC 2200 is an official Internet Standard which describes the state of standardization of
protocols used in the Internet as determined by the Internet Architecture Board (IAB). It offers
a broad spectrum of actual standards used in the Internet. The suitable selection of
documents from RFC 2200 defined in this standard for given projects has to be chosen by the
user of this standard.
X Ethernet 802.3
Serial X.21 interface
Other selection from RFC 2200
1. .......................................................
2. .......................................................
3. ..………………………………………
4. ..………………………………………
5. ..………………………………………
6. ..………………………………………
7. etc.
Contents
This companion standard presents sets of parameters and alternatives from which subsets
must be selected to implement particular telecontrol systems. Certain parameter values, such
as the choice of “structured“ or “unstructured“ fields of the INFORMATION OBJECT ADDRESS of
ASDUs represent mutually exclusive alternatives. This means that only one value of the
defined parameters is admitted per system. Other parameters, such as the listed set of
different process information in command and in monitor direction allow the specification of
the complete set or subsets, as appropriate for given applications. This clause summarizes
the parameters of the previous clauses to facilitate a suitable selection for a specific
application. If a system is composed of equipment stemming from different manufacturers it is
necessary that all partners agree on the selected parameters.
The interoperability list is defined as in IEC 60870-5-101 and extended with parameters used
in this standard. The text descriptions of parameters which are not applicable to this
companion standard are strike-through (corresponding check box is marked black).
Note:
In addition, the full specification of a system may require individual selection of certain
parameters for certain parts of the system, such as the individual selection of scaling factors
for individually addressable measured values.
The possible selection (blank, X, R, or B) is specified for each specific clause or parameter.
A black check box indicates that the option cannot be selected in this companion standard.
(system-specific parameter, indicate the system’s or station’s function by marking one of the
following with ‘X’)
System definition
Controlling Station (Master)
X Controlled Station (Slave)
(network-specific parameter, all configurations that are used are to be marked ‘X’)
(network-specific parameter, all interfaces and data rates that are used are to be marked ‘X’)
(network-specific parameter, all options that are used are to be marked ‘X’. Specify the
maximum frame length. If a non-standard assignment of class 2 messages is implemented for
unbalanced transmission, indicate the Type ID and COT of all messages assigned to class 2.)
Frame format FT 1.2, single character 1 and the fixed time out interval are used exclusively in
this companion standard.
Frame length
Maximum length L (number of octets, possible 9-255)
When using an unbalanced link layer, the following ASDU types are returned in class 2
messages (low priority) with the indicated causes of transmission:
Note: In response to a class 2 poll, a controlled station may respond with class 1 data when
there is no class 2 data available.
Mode 1 (Least significant octet first), as defined in clause 4.10 of IEC 60870-5-4, is used
exclusively in this companion standard.
1 Octet X 2 Octets
1 Octet X structured
2 Octets X unstructured
X 3 Octets
Cause of transmission
(system-specific parameter, all configurations that are used are to be marked „X“)
Length of APDU
(system-specific parameter, specify the maximum length of the APDU per system)
The maximum length of the APDU is 253 (default). The maximum length may be reduced per
system.
In this companion standard only the use of the set <30> – <40> for ASDUs with time tag is
permitted.
Either the ASDUs of the set <45> - <51> or of the set <58> - <64> are used.
File transfer
(station-specific parameter, mark each Type ID „X“ if it is only used in the standard direction,
„R“ if only used in the reverse direction, and „B“ if used in both directions)
<1> M_SP_NA_1 B X X X
<2> M_SP_TA_1
<3> M_DP_NA_1 X X X X
<4> M_DP_TA_1
<5> M_ST_NA_1
<6> M_ST_TA_1
<7> M_BO_NA_1
<8> M_BO_TA_1
<9> M_ME_NA_1 X X
<10> M_ME_TA_1
<11> M_ME_NB_1 X X
<12> M_ME_TB_1
<13> M_ME_NC_1 X X
<14> M_ME_TC_1
<15> M_IT_NA_1 X X
<16> M_IT_TA_1
<17> M_EP_TA_1
<18> M_EP_TB_1
<19> M_EP_TC_1
<20> M_PS_NA_1
<21> M_ME_ND_1
<30> M_SP_TB_1 B X X
<31> M_DP_TB_1 X X X
<32> M_ST_TB_1
<33> M_BO_TB_1
<34> M_ME_TD_1 X
<35> M_ME_TE_1 X
<36> M_ME_TF_1 X
<37> M_IT_TB_1 X X
<38> M_EP_TD_1
<39> M_EP_TE_1
<40> M_EP_TF_1
<45> C_SC_NA_1 X X X X X
<46> C_DC_NA_1 X X X X X
<47> C_RC_NA_1
<48> C_SE_NA_1 X X
<49> C_SE_NB_1 X X
B* … can be used only when the COT is generated via a function-plan application (CAEx)
*) blank or X only
Station initialization
(station-specific parameter, mark „X“ if function is used)
X Remote initialization
Read procedure
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
Read procedure
Spontaneous transmission
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
B Spontaneous transmission
The following type identifications may be transmitted in succession caused by a single status
change of an information object. The particular information object addresses for which double
transmission is enabled are defined in a project-specific list.
Station interrogation
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
B global
group 1 group 7 group 13
group 2 group 8 group 14
group 3 group 9 group 15
group 4 group 10 group 16
group 5 group 11
group 6 group 12
Information Object Addresses assigned to each group must be shown in a separate table.
Clock synchronization
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
X Clock synchronization
optional, see clause 7.6
Command transmission
(object-specific parameter, mark „X“ if function only used in standard direction, „R“ if only used
in the reverse direction, and „B“ if used in both directions)
X No additional definition
X Short pulse duration (duration determined by a system parameter in the outstation)
X Long pulse duration (duration determined by a system parameter in the outstation)
X* Persistent output
X Supervision of maximum delay in command direction of commands and set point commands
X Counter read
X Counter freeze without reset
X Counter freeze with reset
X Counter reset
Parameter loading
(object-specific parameter, mark „X“ if function only used in standard direction, „R“ if only used
in the reverse direction, and „B“ if used in both directions)
Threshold value
Smoothing factor
Low limit for transmission of measured value
High limit for transmission of measured value
Parameter activation
(object-specific parameter, mark „X“ if function only used in standard direction, „R“ if only used
in the reverse direction, and „B“ if used in both directions)
Test procedure
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
X Test procedure
File transfer
(station-specific parameter, mark each used function „X“)
Transparent file
Transmission of disturbance data of protection equipment
X Transmission of sequences of events
Transmission of sequences of recorded analog values
Transparent file
X* … Data can be transparently transported by the system but not generated or evaluated.
A maximum of 220 bytes user data can be transported.
Background scan
(station-specific parameter, mark „X“ if function only used in standard direction, „R“ if only
used in the reverse direction, and „B“ if used in both directions)
Background scan
Note: used for data which are transmitted caused by a self-initiated general interrogation
15
Maximum range of value k: 1 to 32767 (2 – 1) APDUs, accuracy 1 APDU
Portnumber
RFC 2200 is an official Internet Standard which describes the state of standardization of
protocols used in the Internet as determined by the Internet Architecture Board (IAB). It offers
a broad spectrum of actual standards used in the Internet. The suitable selection of
documents from RFC 2200 defined in this standard for given projects has to be chosen by the
user of this standard.
X Ethernet 802.3
Serial X.21 interface
Other selection from RFC 2200
1. .......................................................
2. .......................................................
3. ..………………………………………
4. ..………………………………………
5. ..………………………………………
6. ..………………………………………
7. etc.