Professional Documents
Culture Documents
𝑉 𝐼 𝐿
⇒ = √𝑋𝐿 𝑋𝐶 = √𝑗𝜔𝐿 = √ = 𝑍𝑆 known as surge impedance.
𝐼 𝑗𝜔𝐶 𝐶
𝑧
𝑍𝐶 = √
𝑦
Multiply length of the line 𝑙 on both numerator and denominator, we will get total impedance of
the line.
𝑧. 𝑙 𝑍
𝑍𝐶 = √ =√
𝑦. 𝑙 𝑌
We can say, the characteristic impedance of the transmission line is independent of length of the
line as it is common in both numerator and denominator. However, it depends very much on the
parameters/characteristics of the transmission line i.e., R, X, G and B by holding the following
relations,
𝑍 = 𝑅 + 𝑗𝑋
𝑌 = 𝐺 + 𝑗𝐵
When we consider practical heavy well insulated conductors, the R and G values are neglected
mostly. We can write,
𝑍 = 𝑗𝑋
𝑌 = 𝑗𝐵
As R and G are absent, we can say the line to be a loss less line. Therefore, 𝑍𝑜 becomes the surge
impedance of the transmission line.
𝑗𝑋 𝜔𝐿 𝐿
𝑍𝑜 = √ =√ =√
𝑗𝐵 𝜔𝐶 𝐶
In the above expression, we can say L and C are independent of the frequency as they are cancelling
out. So, 𝑍𝑜 becomes pure resistive and the respective load is called as a pure resistive load.
𝐵 𝑧𝐶 sinh( 𝛾𝑙)
⇒ 𝑍𝑂𝐶 𝑍𝑆𝐶 = =
𝐶 1
sinh( 𝛾𝑙)
𝑧𝐶
⇒ (𝑍𝐶 )2 = 𝑍𝑂𝐶 𝑍𝑆𝐶
⇒ 𝑍𝐶 = √𝑍𝑂𝐶 𝑍𝑆𝐶
In practice R and G are neglected on a transmission line. So surge impedance and characteristics
impedance are same.
Surge impedance loading
It is defined as the load (having unity power factor) that can be delivered by the line of negligible
resistance. mathematically,
(𝑉𝑅𝐿 )2
𝑃𝑅 = MW
𝑍𝑜
𝛾 = 𝑗𝜔√𝐿𝐶 = 𝑗𝛽
𝛽 determines the torque angle 𝛿 between VS and VR. Therefore, if 𝛽 increases the stability of the system
decreases.
Now the second parameter which affects the power transfer capacity is 𝑍𝑜 . Controlling 𝑍𝑜 to get more
𝑃𝑅 is naturally not possible as it depends on the value of L and C parameters of the transmission
line, which are fixed once the line is designed. It can be done artificially through compensation
techniques.
1. Shunt capacitor:
Adding shut capacitor will increase the value of C.
This decreases the value of 𝑍𝑜 , as
𝐿
𝑍𝑜 = √
𝐶
That makes the power system unstable. So adding shunt capacitor is not a feasible solution for
increasing PR.
2. Series Capacitor:
Adding series capacitor, L , as effective reactance reduces.
𝐿
𝑍𝑜 = √
𝐶
𝑒 𝑗𝛽𝑙 −𝑒 −𝑗𝛽𝑙
B = zC sinh( γl) = zC = zC jsin(𝛽𝑙) = 𝑗zC sin(𝛽𝑙)
2
1 1 1
C= sinh( γl) = sinh( 𝑗𝛽𝑙) = j sin(𝛽𝑙)
zC zC zC
⇒ |V(x)| = 𝑉𝑅
This implies that voltage at any point x has a magnitude of VR. Only phase displacement will be
there.
1 1
I(x) = sinh( γx)VR + cosh( γx)IR = 𝑗 sin(𝛽𝑥)VR + cos(𝛽𝑥)IR
zC zC
1 VR VR VR
⇒𝑗 sin(𝛽𝑥)VR + cos(𝛽𝑥) = (cos(𝛽𝑥) + 𝑗sin(𝛽𝑥)) = 𝑒 𝑗𝛽𝑥 = 𝐼𝑅 ∠(𝛽𝑥)
zC ZC ZC ZC
⇒ |I(x)| = 𝐼𝑅
This implies that the magnitude of the current at any point of the line is constant and has a
magnitude of IR.
𝑉𝑆
𝑉𝑅(𝑛𝑙) =
cos(𝛽𝑙)
𝑉𝑅(𝑆𝐼𝐿) = 𝑉𝑆
𝑉𝑅(𝐹.𝐿)
𝑉𝑅(𝑆𝐶) = 0
𝑆(𝑥) remains constant from the sending end to the receiving end and as 𝑍𝐶 is resistive there is no
reactive power flows in the line and
𝑄𝑅 = 𝑄𝑆 = 0
𝐿
𝜔𝐿|𝐼𝑅 |2 = 𝜔𝐶|𝑉𝑅 |2 ⇒ 𝑍𝐶 = √
𝐶
𝑉𝑅2 (𝑟𝑎𝑡𝑒𝑑)
𝑆𝐼𝐿 =
𝑍𝐶
In practice the load on the line may be only fraction of SIL under no load condition. For loads
higher than SIL, shunt capacitance is needed to minimize the voltage drop and shunt inductance is
needed to compensate the line charging current.