Professional Documents
Culture Documents
AR 322S1 / AR32FA1
Building Technology 4
GENERAL SPECIFICATION
DIVISION 11 - DIVISION 16
Submitted by:
Treyes, Ma. Lailanie B.
Submitted to:
Ar. Feliciano
GENERAL SPECIFICATIONS
RESIDENTIAL SPECIFICATION
PROJECT TITLE:
PROPOSED TWO-STOREY RESIDENTIAL HOUSE
DIVISION 11 - EQUIPMENT
PART 1 – GENERAL
PART 2 – PRODUCTS
DIVISION 12 - FURNISHINGS
Housing and Dining Facilities (HDS) has adopted amendments for all HDS facilities.
Confirm applicable standards with University Representative on a per project basis.
DIVISION 12 - FURNISHINGS
12 10 00 - ART
A. Art & Architectural Artwork:
1. Artwork will only be included as part of capital construction projects. Artwork for all
other projects will be funded by the individual departments and is not likely to be part of
construction documents.
12 20 00 - WINDOW TREATMENTS
A. Window Coverings:
1. Blinds, shades and shutters will normally be furnished and installed by the contractor
and should be included in the A/E specifications. Drapes are not normally provided as
part of construction projects. Drapes must be approved by the University
Representative prior to specifying.
2. Where windows or other uncontrolled light sources exist, these sources must be
controlled through use of blackout drapes or other devices so that light level can be
controlled for adequate projection viewing.
B. Window Films:
1. Smoke and gray colors are acceptable. Silver and bronze colors are not desirable
and should not be used unless necessary to match existing films or because of unusual
requirements which will need approval of the University Representative.
2. Shading coefficient shall be 0.65 or less for all films.
3. Films shall be sputter-coated using a charged metal process. Dyes or pigments are
not acceptable. Films shall have an abrasion resistant coating.
4. Films shall be warranted for five years to maintain all solar properties without
cracking, crazing, fading or peeling. Defective films shall be replaced without charge.
5. Safety film may be considered where retrofitting safety glazing is not advisable due to
the configuration, construction and condition of existing doors and windows that are not
being replaced.
12 30 00 - CASEWORK
A. Laboratory Casework:
1. Acceptable types are as follows:
a. Metal Laboratory Casework
b. Plastic Laminate Casework
c. Wood Casework
2. New laboratory casework in existing buildings shall match existing style such as
wood, metal, or plastic laminate. Verify with the University Representative.
3. Wood casework shall not be installed where water or chemicals are used.
B. Counter Tops:
1. Furnish tops in maximum practicable lengths.
2. Acceptable types include:
a. Composition Stone
b. Impregnated Stone
c. Glazed Composition Stone
d. Plastic Laminate - with plywood underlayment or medium density industrial
particleboard
e. Stainless Steel
f. Epoxy Resin
3. Flexibility of casework should be considered due to multiple use of space over a
period of time. Providing excessive amounts of casework does not benefit the owner.
1. Every classroom, office, and conference room will contain trash and recycling
containers. Appropriate space for a 28 quart recycle bin and a Slim Jim container shall
be included in the drawings.
2. In hallways and corridors where appropriate, cabinets separating trash and recycling
materials shall be included in the drawings.
3. The cost and procurement of trash and recycling containers will be included into the
cost of the project.
B. Outdoor Trash and Recycling Containers:
1. The cost and procurement of outdoor trash and recycling containers, including the
building dumpster, will be included into the cost of the project.
C. Provide at least two coat hooks in offices.
A. Floor Mats:
1. Entry mats and walk-off carpets shall be provided as a part of the construction
contract. Type and location shall be approved by Facilities Management-Custodial
Section through the University Representative. They shall be a type that will not hinder
door operation.
2. Main entrance lobbies should have recessed floor mats 4 to 6 feet wide and 10 feet
long.
12 50 00 - FURNITURE
A. Furniture:
1. Movable furniture and equipment will normally be purchased and installed by the
University under a separate contract and should not be included in the A/E
specifications. Installation may be specified by the A/E depending upon circumstances.
2. Room dividers and screens (movable wall partitions) will normally be purchased and
installed as movable equipment, unless otherwise approved. The A/E will be expected
to coordinate with the client in this design and specification.
3. All furniture should have non-marking wheels or glides that will not rust.
4. Floor mats should be used under rolling office chairs.
5. Computer labs should have furniture that allows mounting of tower case computers
on the furniture keeping the computer off the floor. Desktop case computers are
preferred. Cables should be concealed in raceway where possible to avoid draping
cable on the floor.
6. Classrooms, conference rooms and similar rooms should have chair rails on the
walls.
7. See Division 32 – Exterior Improvements for requirements for Site Furnishings.
12 60 00 – MULTIPLE SEATING
A. Fixed classroom and auditorium seating should be rail mounted rather than individual
pedestal mounted unless otherwise directed by the University Representative. Use drop
arm writing surfaces with grained color and matte texture plastic laminate finish. Flip
seats are preferred.
RADIATION PROTECTION
DIVISION 14 - EQUIPMENT
A/E must provide heat load calculations with regards to additional equipment and
plan/revise HVAC system accordingly.
A. The Consultant must plan spaces, plumbing, HVAC, and electric to accommodate all
laboratory equipment. Be sure to provide for hook-ups and coordination of installation
sequences.
1. FUME HOOD AND EXHAUST SYSTEM: Shall be designed and installed in
accordance
with American National Standards Institute (ANSI) Z9.5 - 2012. Refer to Appendix A,
Environmental Health & Safety Design Guidelines, Section 8.2.
2. ALL NEW LABORATORY FUME HOODS: Shall use 100% exhaust with an average
face velocity of eighty to one-hundred (80-100) feet per minute (with sash fully open for
constant air volume hoods with a bypass feature) with no face velocity measurement
more than plus or minus twenty percent (20%) of the average. Auxiliary air type hoods
are not to be used.
3. IN LABORATORIES: At least one (1) station in each laboratory shall be provided for
the physically disabled. Said station shall have a low workbench with a clear minimum
height of 30 inches under the workbench and no apron. Aisles between the tray slides
and control railings shall be a minimum of 34 inches.
4. FITTINGS AND FIXTURES: Utility fittings and fixtures specified for laboratory
equipment shall be of quality at least equal to that specified for the Plumbing, HVAC,
and electrical contracts. This is critical. Consultant shall certify in writing to the
University that 1). The specification quality is equal, and 2). That the installation
conforms to specified quality.
a. AUTOMATIC SHUT-OFF VALVES: Specify that these must have a ten (10) year
written warranty.
2.4 MEDICAL EQUIPMENT
DIVISION 15 - MECHANICAL
Introduction
The work shall be in accordance with all rules, regulations, by-laws and requirements of
all authorities having jurisdiction..
Part 1 - General
• Codes
• The project shall comply with the latest edition of the following codes unless otherwise
stated:
• After inspection and approval of service lines in trenches, provide a continuous trace
wire and attach to service line directly. The Mechanical Contractor shall take ‘as-built’
measurements, including all depths, prior to commencement of backfilling operations. It
will not be sufficient to check off line locations. Definite measurements shall be taken for
each service line. The location of buried piping shall be shown on the drawings and
dimensioned from fixed points.
● Where piping, ductwork and equipment is indicated for use in future expansion of
the building and/or for future installations within the building, the Contractor shall
leave sufficient clear space and install the piping, ductwork and equipment in
such manner that connections to the future building expansion and/or future
installations within the building can be made without removing existing floors,
walls, ceilings. The Contractor shall consult with the Architect/U of A whenever
necessary for this purpose.
● Any piping stub-outs provided for future connections to domestic hot and cold
water piping systems shall be arranged so that “dead legs” (i.e., pipe sections
where there is no water circulation) are prevented. The termination point of any
piping stub-out shall be as close to the main piping flow as physically possible.
Where future branch lines must extend a distance greater than ten (10) branch
line pipe diameters from the main piping flow, a valved drain port or blind flange
with a valved drain shall be provided at the end of the branch piping to allow
periodic flushing.
● Abandonment of Domestic Water Piping
• Verify routing of existing domestic hot and cold water piping systems prior to their
being abandoned. Cap abandoned branch lines as close as physically possible to the
main piping flow to eliminate “dead legs”. Elimination of “dead legs” shall not hinder the
proper operation of any existing hot water return, i.e., recirculation, systems.
Introduction
Part 1 - General
● All piping and ductwork in finished areas shall be concealed in ceiling spaces,
shafts, or chases.
● Electrical conduits shall not touch or be supported via pipes or ducts.
● Ensure fire and smoke separation rating of walls and floors is maintained
following penetration.
● All electrical work associated with Division 15 shall comply with requirements of
Division 16.Part 2 - Products
● Valves
● Sizes 6" and above shall have gear operator ball chain if located more
than 7 ft. above floor.
● Provide isolation Ball valves - 100% full-port, full-line size, bronze-body,
threaded connections at all
equipment and on all main branch take-offs.
● Provide brass valve tags marked for the service. See pertinent service
specification for valve type.
● Butterfly valves shall be 100% bubble-tight shut-off. Lug type only. Iron
body with bronze disk. Valves to
have two year warranty. Use for throttling/balancing. Preferred
manufacturers are Norris, Centerline or UA approved equal.
● Piping Labels
● Provide at directional changes and/or each 20 ft. Labels to be
pre-manufactured snap-on plastic wrap- around type sized to cover entire
circumference of piping and insulation.
● Labels to have integral color identification as established by ANSI
Standard A13.1 - 1981.
● Lettering shall be sized to be easily legible. Directional arrows shall
indicate direction of flow and shall be
located to point away from lettering.
● Escutcheons
● Install in exposed locations, except in mechanical rooms.
● Escutcheons to be hinged, chrome-plated type.
● Pipe Sleeves / Concrete Walls & Floors Above Grade
● Shall be schedule 40 steel
● Sized for full dimensions of insulation and fire caulked where required
● Install in all exterior walls, fire walls and floors
● Floor sleeves to extend 1” above floor surface
● Pipe sleeves in non-rated, non-masonry walls or partitions. Provide 24 gage
galvanized steel.
● Pipe sleeves in rated non-masonry wall or partitions – provide manufactured,
pre-engineered fire-rated pipe sleeve kits.
● Pipe sleeves installed below ground through exterior walls shall have mechanical
type neoprene seals.
• Motors shall have minimum efficiency as tabulated below and in accordance with IEEE
Standard 112 test method B.
Part 3 - Execution
• Workmanship
• Equipment Installation/Removal
Provide a means of removing any valve that is larger than 2” and is mounted six feet or
more above floor level.
● Install to prevent the existence of sections of piping where water could stagnate,
i.e., where no water circulation occurs.
● Provide recirculating loops for all domestic hot water piping systems.
● Arrange piping in such a manner that there are no “transitory dead legs”, i.e.,
piping branch lines that
contain stagnant water.
● Refer to “Provisions For Future Expansion And/Or Installations” Section 15000 -
General Discussion
for the installation requirements of future connections.
Introduction
A listing of valves, their types and applications associated with the following mechanical
systems:
Specialty valves used only in a particular type of mechanical system may be found in
design standards for that system
Part 1 - General
● Install valves of type and service outlined in locations outlined in this standard
● Standard products - use same manufacturer for multiple units of same type
Gate valves to have non-rising stem and handwheel, inside screw and renewable
composition
Part 3 - Execution
Workmanship
- Valves 6" and over shall have gear operator ball chain fall if located more than
7 feet above floor
- Provide butterfly valves at all equipment and on all main branch take-offs
- Provide globe disc valves at all equipment and on all main branch take-offs in
steam piping
system
- Provide gate valves, ball valves and globe valves at all equipment and on all
main branch take-
offs
- Provide relief valves on piping and equipment as needed to meet code
requirements
- Provide plug cock valves at connections to gas-fired equipment and in all
branch piping.
End of Section 15100
Introduction
Equipment associated with the insulation and attenuation of airborne and impact sound.
Part 1 - General
Part 2 - Products
Part 3 - Execution
● Provide vibration isolation for all mechanical motor driven equipment and for all
horizontally suspended fan coil units.
● Provide neoprene side snubbers or restraining springs where side torque or
thrust may develop.
● Spring mounts for equipment with operating weight different from installed.
● Provide adjustable limit stops on spring mounts for equipment with operating
weights different from installed weight.
● Provide spring isolators on piping connected to isolated equipment as follows:
● Up to 4" diameter - first 3 points of support
● to 8" diameter - first 4 points of support
● diameter and larger - first 6 points of support
● First point of support shall have a static deflection of twice the deflection of the
isolated equipment.
● Isolators located outdoors or in a moist environment shall have 'hot-dipped'
galvanized housings and 2 coats
of neoprene on springs.
● Isolators shall not have less than 30% reserve capacity.
● Flex Connections
• PIPING, DUCTWORK
Part 1 - General
• Use wrapped supply ductwork, except in acoustically critical applications where liner
may be used only after written permission is given by the U of A. Lined ducts shall not
be used in medical areas, clean rooms, all high velocity supply ductwork.
Part 2 - Products
• Armaflex insulation which meets smoke developed/flame spread ratings of 50/25 shall
be used only for interior refrigerant service applications
Part 3 - Execution
● Provide fitted insulation which can be removed and reused around equipment,
valves, flanges, etc.
● Use Z-strips on all leading edges of duct liner, (when permitted).
● Insulated fittings, i.e., elbows, tees, Y’s to be packed and fitted with PVC covers.
● Install insulation per latest edition SMACNA Duct Construction Standards.
● Use welded pins for ductwork insulation attachment. No mechanical or glued
attachments allowed.
● For pipe sizes greater than 11⁄4” provide calcium silicate inserts and metal
shields to protect the insulation at
each support.
This work shall be in strict accordance with all rules, regulations, by-laws and
requirements of all authorities having jurisdiction including, but not limited to; NFPA
codes, Arizona State Fire Code, UA Department of Risk Management and Safety.
Part 1 - General
Part 2 - Products
Part 3 - Execution
Introduction
Part 1 - General
Part 2 - Products
Same as for above grade except use type "K" copper for below ground and 15% silver
brazed joints.
Same as for above grade with sealed coating. Same as for above grade.
Same as for above grade - install in concrete trough with metal plate cover.
Introduction
Fixtures and appurtenances associated with the use of plumbing system piping
including:
Part 1 - General
● Refer to Section 15000 “Provisions for Future Expansion and/or Installations and
Section 15050 Part 3 - Execution”.
● All fixtures shall be of the “water saving type”.
● Install fixtures as required for either standard or handicapped accessible service
per ADA.
● All fixtures shall be white.Part 2 - Products
● Water Closets, Wall Mount shall be/provided with:
● Vitreous china construction
● Elongated bowl
● 1 1⁄2” inlet spud
● Siphon jet action
● ANSI Standard A112.19.2
● Toilet Seats shall be:
• Manufactured by Sloan (Royal # 110 for water closets 1.6 gpf, Royal #186 for urinals,
1.0 gpf)
Introduction
Part 1 - General
● For energy conservation purposes, hot water shall not be provided to rest rooms
● Use central plant steam via heat exchangers for hot water. Consider impact of
summer shutdown of steam
service, (back up systems may be required) - consult with UA Facilities Design &
Construction..
● Where used, water heaters shall be placed as near point-of-usage location as
possible. Pumped recirculation
system is required for piping systems lengths exceeding 50 feet.
● Small clear water ejector systems may use drop-in submersible pump.
● Autoclaves shall be connected to campus steam system and not furnished with
individual steam generators. Verify adequate steam supply main pipe size and
available pressure. Provide timers with over-ride button to shut off steam and
water when not being used.
Part 2 - Products
● Water Softeners shall be dual automatic regenerating type to provide service
during routine maintenance, complete with fiberglass tanks
● Sewage Ejector Pumps shall be self-priming, base mounted pump with suction
line extended to sewage pit, high water alarm to U of A Campus EMCS.
Preferred manufacturer is G orman Rupp or UA approved e qual.
● Water Heaters - Gas fired preferred, although electric spot heaters may be used
where economically justified. Lined galvanized steel tanks. 80% minimum
efficiency.
● Water Pressure Booster System shall be Duplex pumping system, removable
bladder type hydropneumatic pressure tank.
● Drop-in Submersible Pumps - Fractional horsepower use only.
Part 3 - Execution
● All equipment shall be installed with isolation ball valves - 100% full-port, full line
size, bronze body at the equipment, drains, thermometers (on heat exchange
equipment) and pressure gauges.
● Provide drip pans with piped drain beneath water heaters placed in areas other
than in equipment rooms.
● Provide two sewage ejector pumps for stand-by service with lead/lag control for
building service application.
Provide vent bleed valve per manufacturers recommendation.
● Provide line size (2" maximum) full port ball valve blowdown on each side of plate
and frame heat exchangers (typically 4).
● pt and eliminate balancing devices for all banked coil application and wherever
practical.
● Use circuit setting devices in closed loop systems. Preferred design is a variable
flow pumping system controlling system differential pressure and using externally
adjustable pressure dependent circuit setters at each point of use.
● Design heating water systems with a 40°F temperature differential.
● Refer to meter requirements (attachment to Section 15970).
DIVISION 16 - ELECTRICAL
GENERAL
Basic Electrical Design shall insure that the building power factor is 0.9 or greater.
MATERIALS
All light switches and receptacles shall be specification grade, 20 Amp. Back or side
wired with tightening screws only. No push-on type connectors.
Electrical Panels:
Conduit:
E. Wire Colors
1. 120/208V
Phase A Phase B Phase C Neutral Ground
2. 277/480V
Phase A Phase B Phase C Neutral Ground
3. 12KV
Phase A Phase B Phase C
1. All motor controls have NEMA rated starter with HOA switch, running light,
EMS interlock, and smoke detector interlock.
1. Surface raceway shall be secured at 2’-0” intervals (raceway wider than 2” shall be
secured with 2 screws at each attachment point) with wood screws into wooden framing
or molly bolts into sheetrock or plastic inserts with pre-assembled drive screw for
concrete (ITT-HOLUB “HI-DRIVE” nail anchors, no known equal) Powder driven
anchors are not acceptable. The use of adhesives for fastening to any surface is not
allowed.
2 Screws used in fastening surface raceway shall be no less than 1" in length.
3. The proper support and joiner clips, as called for by the manufacturer, for securing
surface raceway to walls or floors are to be used per the manufacturer's instructions.
Control wiring shall be NEC Class 2 cabling. Coordinate with the University's
representative if conduit is required. Coordinate with Division 15.
EXECUTION
Interruption of Services:
1. Before making any high voltage connections, notify Owner in writing at least two
weeks in advance. Such work shall be performed at such times as designated by
Owner.
2. Before making any low voltage connections that require power interruption to
existing facilities, notify Owner at least one week in advance.
3. All service interruptions shall be performed by the Campus Electrical
Department.
Office power receptacles shall be 4 plex and shall be located on all 4 walls.
Emergency Power panel-boards shall have cover painted yellow; receptacles shall be
yellow.
Panelboards shall have a 2" conduit stubbed above ceiling level for future expansion.
Provide 4" high concrete equipment pad beneath switchboards, motor control centers,
transformers, etc.
Receptacles shall be marked with Panel and circuit # of origin via a transparent tape
lettering machine such as Kroy or Merlin.
Receptacles in areas likely to serve copy machines, laser printers, coffeemakers, etc.
shall be served by dedicated circuits.
Provide receptacles at all elevator lobbies and at every other stair landing.
Where cable trays are being installed, provide coordination between the mechanical
systems installation and cable tray space requirements such that the cable tray is
accessible from below and a minimum of 12” clear is provided over top and at least one
side of the cable tray to allow for future cables to be set in place.
All power and communications site wiring shall be routed underground in conduit. Refer
to Part III Site Requirements and Specification Section 01530 Tree Protection for
requirements affecting underground distribution.
All conduits shall be 4" schedule 40 PVC or P&C duct rated for concrete encasement.
Risers from below grade shall be rigid wrapped galvanized steel or schedule 80 PVC.
The number of conduits in each duct bank shall be determined by the requirements and
approved by the Project Manager.
Provide one spare power and one spare communication conduit in each duct bank.
Communications conduits will include three 4" conduits minimum as follows:
1. Telephone (T).
2. Computer / data (C) and cable TV (TV).
3. Fire alarm (FA).
All conduits, including those with new cables installed, shall have a nylon pull rope
installed.
CONCRETE PULLBOXES
Provide separate precast concrete pullboxes, with lids labeled "communications" (for
TV, telephone, data, fire alarm) or "power".
Pullboxes for site power and communications shall be inside dimensions 30" x 60" x 36”
deep, minimum. This dimension shall be increased if high voltage junctions are
installed. Install on gravel pad and provide drain. Pullboxes shall have concrete bottoms
and galvanized steel lids.
Pullboxes in traffic areas and along roads shall be designed and installed for H20-44
loading.
Pullboxes shall be located and provided with grade rings as necessary to ensure that
water is drained from conduits.
All cables in manholes and pullboxes shall be formed around the sides of the pullbox
and tie- wrapped to racks with rack arms and ceramic insulators attached to the sides of
the pullbox.
All underground conduit shall have a correctly sized mandrel pulled through it before
cables are installed.
Non-slip lids shall be provided for pullboxes in sidewalk areas. Use concrete or
fiberglass-no metal lids in sidewalks.
Contractor shall protect from damage existing UCSC and utility company cables and
facilities that are present underground and at cable closets. Damage to such cables
shall be promptly reported and repaired at no cost to the University. Splice cases shall
not be used as steps to enter/exit manholes. Contractor shall provide ladder for
manhole access.
GENERAL
Electrical Distribution System
MATERIALS
1. All high voltage cable shall be shielded single conductor rated MV-90, 15 KV,
ungrounded neutral. The conductor shall be copper size 4/0 AWG. Class B
concentric stranding and shall have a semi-conducting layer between conductor
and insulation. The insulation shall be ethylene propylene rubber, 220-mil
thickness, which shall be ozone, moisture and heat resistant. Insulation shielding
shall consist of a layer of semi-conducting material with either drain wire or
copper shielding tape overall. The outer jacket shall be PVC and be water, oil,
alkali, and sunlight resistant.
2. All cable shall be copper conductor and shall be manufactured, factory tested,
and field tested in full compliance with all applicable sections of I.P.C.E.A.,
N.E.M.A., A.S.T.M., U.S.A.S.I., I.E.E.E. and A.E.I.C. standards.
3. High Voltage Separable Connectors: Provide 600 amp ESNA-type connectors
with insulated bushings General Electric "Suremake", Elastimold or equal.
Provide capacitance test point. Connectors shall satisfy requirements of IEEE
386 and shall be designed for use with the specific cable and type of installation
required. The manufacturer shall provide all components and at least two copies
of complete directions for assembling, and putting the unit into service, (one of
which shall be submitted for record). All switch 600A terminations shall be
provided with a capacitance tap for voltage testing and a 200A grounding
terminal 15KV kits from Elastimold 656ETP-WOX-DRG-SG2 or SG3.
B. Building Substation:
1. The building substation will generally consist of: load interrupter switches,
transition bay, transformer, secondary junction box.
2. Load interrupter switches shall be outdoor (or indoor) type, metal clad, rated 13.8
KV (95 KV BIL) for use on a 12,000 volt, 3 phase primary service. The apparatus
shall consist of two air interrupter switches, a duplex switch arrangement, and
each switch shall consist of a stationary, 3 pole, group-operated air switch
mounted within a free-standing, weatherproof (indoor) enclosure. There shall be
mounted in the bottom compartment of one switch a set of three current limiting
fuses connected common to the load side of the switches. Each complete
assembly shall be rated 13,800 volts, 600 amperes continuous, 600 amps load
interrupting, not less than 40,000 amps momentary at 12,000 volts, and shall be
rated to close in on a fault of 40,000 amps asymmetrical at 12,000 volts. Provide
a spare set of fuses. Each section of outdoor switches shall be supplied with a
250 watt strip heater to reduce condensation. Incoming high voltage terminations
at these switches shall utilize stress cones.
3. Each switch shall be three-pole, single-throw, and shall be assembled using
NEMA standard components, spacing, arrangement and mounting. Live parts,
except contacts, shall be copper alloy totally free of aluminum. Contacts shall be
silver, silver coated, or silver alloy.
4. Each switch shall be group operated by a handle external to the switch
compartment. The operating handle shall have a spring-assisted mechanism that
provides quick-make, quick- break contact action totally independent of
manipulation by the individual actuating the mechanism.
5. Each switch operating mechanism shall be fitted with a Kirk-key interlock. The
key interlocks shall function to retain the key when the switch is closed, thereby
permitting switch operation, and shall release the key when the switch is open,
thereby preventing switch operating. The intent of this provision is that under
normal circumstances, only one switch can be operated at a time. A spare
Kirk-key shall be provided. The fuse compartment door will be Kirk-key
interlocked with each switch such that both switches must be opened before the
fuse compartment door can be opened.
6. The transformer shall be mineral oil filled 3 phase, 60 cycle, KVA rating as
required with a 12000 volt delta primary winding having two 2-1/2% taps above
and below normal voltage. The secondary winding will be 3 phase, 4 wire, wye
grounded. Provide accessories as listed for Pad Mounted Transformer.
7. Provide a set of 3 spare fuses to the Campus Facilities Electrical Department.
8. Provide flexible braid connection between transformer secondary connections
and
secondary distribution section.
9. Provide factory tests including the following: ratio, polarity, phase relation,
no-load loss, excitation current, impedance voltage, load loss, applied potential,
induced potential, leak, resistance measurement.
a. "Weak-link" primary fusing is not acceptable in lieu of current limiting primary fusing.
9. Provide factory tests including the following: ratio, polarity, phase relation, no-load
loss, excitation current, impedance voltage, load loss, applied potential, induced
potential, leak, resistance measurement.
Pad mounted air insulated switches shall be deadfront, 600 Amp continuous current on
switch side, 200 Amp on fuse side. 12,000 Amps asymmetrical; 19,000 Amps
asymmetrical momentary current. 600 Amp apparatus bushings. Side operated external
operating mechanism. Oversized viewing windows so that break is easily visible. Coal
tar undercoating. Chance AIS Series, S&C Electrical Equipment Co. or equal.
EXECUTION
After cables are installed, a high potential test shall be performed on each conductor.
An initial voltage shall be applied and increased in no less than 5 uniform steps up to
the maximum test voltage. The minimum time at each step shall be no less than
required for test current to stabilize. The high potential test shall be AC or DC. If an AC
test is performed, the applied voltage shall be 60 Hz. If the applied voltage is interrupted
at any time during the test on a conductor, the test shall be started again from the
beginning.
DC Test
15 KV 63 KV
15 KV 15 KV
Report of Test Results: Reports of voltage test results shall be submitted for review with
three copies of each report prepared in the following format and detail:
1. A separate 8-1/2 by 11 inch report sheet shall be prepared for each separately
tested section of high voltage cable.
2. Each report shall be headed with the project identification.
3. The following additional data shall appear on each report sheet:
Date
Name of operator performing test
Company operator is employed by
Section of cable tested
Type of cable insulation
Cable length
Nominal rating of cable
Cable manufacturer and product identification Size of conductor
Identification of test equipment
Whether AC or DC test
4. The test results shall be plotted on a log-log graph and shall have microamperes
on the left and kilovolts across the bottom. The graph shall also provide a current
vs. time test to be recorded in 1-minute intervals after final test voltage has been
reached.
5. Each test report shall be signed by the operator of the test equipment.
6. Each report sheet shall be endorsed by the contractor or his authorized
representative.
● Insulation Resistance Tests: Electrical insulation resistance tests shall be made
by the Contractor in the presence of the Architect for all new sectionalizing
switches using a constant voltage magneto generator capable of measuring
2,000 megohms. Tests shall be made between phase conductors and grounded
phase conductors. Insulation resistance shall not be less than 750 megohms.
The Contractor shall furnish the Project Manager with a record of all insulation
resistance measurements for distribution to UCSC Utilities Dept.
● Cable shall be looped and racked in all pull boxes and manholes.
● All outdoor terminations shall be covered with high-voltage silicone tape.
● Grounding
1. A #2 AWG copper ground wire shall be installed with each of the feeders and it shall
be connected to the existing grounding system in the manhole, the grounding system at
the pad mounted switches and the building grounding system. All cable shields shall be
connected to this ground.
All buildings shall be provided with a separate power/power quality meter at the service
2 Provide area metering at each building for the following building classifications: (Verify
with Project Manager.)
● Academic Buildings
● Housing
● Food Service
● Parking lots (verify with Project Manager)
● Other areas as determined for specific projects.
3. Provide separate metering for path and street lighting.
4. It is desirable to have the KWH meters grouped at the main distribution panel
within a
8. Design and specify Lantronix serial to Ethernet converter with power source,
preferably on generator power. Connection to campus SCADA via the closest ITS data
network closet shall be provided.
9. Meters shall be programmed to trend KW, KWH, Volts, Amps, KVA. MATERIALS
A. the power meter including it’s communication to the SCADA front end.
All hardware, power, terminations and programming shall be provided to fully
commission
B. The meter constant shall be printed on the faceplate (it shall include the effects of
potential and current transformers).
C. The meter shall be a multi-function electronic meter Power Measurement Co. #7350
to match existing networked metering equipment. Meter functions shall include: voltage,
current, KW, KVAR, PF, Frequency. Provide SCADA network connection using
Lantronix:
UDS1100 device server, US domestic power 120 VAC power supply Part Number:
UD1100001-01
DB25M to RS485 and 9-30 VDC power input screw terminal adapter Part Number:
500-171-R
GENERAL
All interior lighting shall utilize fluorescent or high intensity discharge sources.
Incandescent lighting may only be used if written justification is approved by the
Assistant Vice Chancellor.
Exterior Building Lights shall be fluorescent or high pressure sodium and shall be
controlled by the campus Energy Management System (EMS).
Minimal lighting with keyless fixtures and switching at the access opening should be
provided at those parts of crawl spaces where fire sprinklers are required or clear height
exceeds four feet.
Details shall be provided on the drawings to show seismic requirements for pendant
mounted light fixtures.
MATERIALS
Electronic high frequency ballasts shall be utilized for all classroom, office, living areas,
etc. to minimize noise and reduce energy consumption. Noise from the lighting system
in these areas shall not exceed 24 dbA for an installation with 50 footcandles nominal
light levels, 20 dbA background noise levels and enclosed fixtures.
Fluorescent lamps shall be energy saving type T-8, SP-35.
Lighting control panels that sweep interior lights off to comply with Title 24 energy
regulations shall use a BMS contact input to enable the start of the sweep off period and
to disable the end of this period. Wattstopper SWS panel with BMS interface option. NO
INTERNAL CLOCKS.
GENERAL
Lighting shall be provided for safety only. Decorative lighting shall be used only upon
approval by the Campus Architect of a written justification submitted early in the design
process. Such justification may include: lighting is necessary for public performances (in
this case, lights shall be switched separately from safety lighting) or to achieve a limited
effect at the building entrance. Refer to LRDP for lighting considerations and wildlife.
Emergency egress lighting with required backup power source shall be provided to
major roadways.
1. 70 watt, 120 volt, high pressure sodium lamps shall be used in path lights and
150 watt, 277 volt, high pressure sodium lamps shall be used in street lamps.
2. Each fixture shall be fused with a time delay fuse in a weatherproof holder. Fuse
shall be located in the base or in the base pull box.
3. Street and path light assignment numbers (based on sector map location) shall
be stenciled on the base of path and street lights. Numbers shall be determined
by the Project Manager and shall match the campus standard.
4. Lighting control circuits shall be on a circuit separate from the lighting branch
circuits to minimize lighting disruptions.
5. Site lighting shall be scheduled on and off by the campus energy management
system (EMS).
6. Site lighting shall be metered separately from other power.
7. Street lights shall have a concrete pull box installed adjacent to each fixture with
conduits and wiring terminating in this pullbox.
8. No tree mounted lights allowed.
9. Site lighting pullboxes shall include a concrete bottom with drain hole.
MATERIALS
Refer to Standard Details in Part VI of this Handbook for standard campus path and
street lights, including bases. Note that specific projects may specify lower level path
lighting or other special requirements at particular projects. Verify with the Project
Manager.
Street, and parking lot lights shall be die cast aluminum, 150 high pressure sodium,
bronze finish, glass lens, aluminum 4" x 4" x 20' pole, RUUD PR2515M to match
existing. Path light fixtures shall utilize globe type fixture as shown on attached detail or
70 watt version of RUUD fixture above.
EXECUTION
A.
● Provide auxiliary contacts on the transfer switch and utilize the EMS to monitor
and controls witch operation.
● Provide emergency power to the following equipment as a minimum:
EMS (Repeaters and Excel Plus panels at a minimum) & FA Panels Telephone
switch and associated air conditioning (if present) Egress lights including exterior
stairs.
Mech/electrical room lights and receptacles
Exterior substation lights and receptacles
Selected equipment and fume hood fans as identified in the program
● Provide two position maintained contact switch on the automatic transfer switch:
"Test" and "Automatic". The "Test" position simulates power failure with transfer
to "emergency" position. To prevent the unauthorized operation of exterior
mounted switches, test switch shall be either key operated or contained in a
locked area.
● Exterior mounted automatic transfer switches shall contain a thermostatically
controlled strip heater.
● Provide a four-hour full load field test of generator.
● Coordinate with mechanical engineer to provide required natural gas inlet
pressure of approximately 11" w.c. and gas meter.
● Provide seismic rated spring isolators at base attachment to pad.
● Provide remote start with status connection from the campus energy
management system.
● Submit heat rate, fuel consumption, and emissions data necessary for the
university to apply for and receive Authority to Construct and Permit to Operate
from Monterey Bay Unified Air Pollution Control District. Generator must include
BACT as determined by MBAPCD.
● Provide automatic transfer switch with a switched neutral and ground neutral as
required for “separately derived system”.
● Contractor to schedule with Project Manager load testing and training. After
successful operational test, Contractor shall schedule with Project Manager and
campus EH&S representative an inspection by Monterey Bay Air Pollution
Control District.