You are on page 1of 48

Why Mavili Elektronik?

Mavili Elektronik Sanayi ve Ticaret A.S., a holder of ISO


9001:2000 certificate, was established in 1987. Since then
due to its unwavering policy of unconditional customer
satisfaction, the company has grown into a professional,
making continuous investment in research and development
as well as new production lines. In May 2005 the company
moved to a new building of 5000 m2, which enabled the
Surface mount assembly
company to expand the production area. Today Mavili
employs a staff of 100, including highly qualified engineers
and technicians.

Unlike other manufacturers of detectors or control panels,


Mavili is a system manufacturer and thus enjoys the
invaluable advantage of accumulated experience and
technical know-how.
Surface mount
machines Why MaviGard?

The Quality Control, Research & Development and Fire


Testing departments lead Mavili to development of new
and superior products, complying with such standards as
EN 54, TSE (Turkish Standard), SSPB (Russian Fire Safety
Certification System), GOST R (Russian State Standard),
89/336/EEC EMC (Electromagnetic Compatibility) Directive.
The MaviGard products have been approved by Kazakhstan,
PCB surface mount Oman, Bahrain and United Arab Emirates Civil Defence
preparation authorities. MaviGard gas detectors are approved for use
by Russian Federal Department of Ecological, Technological
and Atomic Energy Supervision.

Mavili pays attention to training and offers training programs


to its customers on every new product.

In addition to standard products, Mavili can manufacture


special products to custom specifications if and when
PCB assembly needed. Any problem a customer faces is solved by Mavili’s
flexible production ability, technical support and training
as well as prompt supply of spare parts.

Selling Worldwide
Every year MaviGard products expand worldwide. Nowadays
Mavili exports to Latvia, Russia, Estonia, Italy, Romania,
Finland, Malta, Mauritius, Sri Lanka, Oman, Bahrain, United
Arab Emirates, Bulgaria, Syria, Greece, South Africa and
other countries. Mavili participates in domestic and
international exhibitions such as Intersec (Dubai), MIPS
(Moscow), Security Technologies (Moscow) and Security
Detector smoke test Expo. (Almaty)
chamber

What’s new in 2008-2009


Mavili introduces a completely new product line: multi-
loop analogue addressable fire alarm control panels
(MG-7800), printers for addressable control panels, new
addressable manual call point with isolator module and
resettable MG-8130, new addressable detector mounting
base MG-3510, ceiling type gas detector TGDR-1224M,
new conventional manual call point, wheather-proof (IP67)
WR4072 and new conventional repeater panel MGRP-64.
Stability test

1 www.mavigard.com
CONTENTS

CERTIFICATES AND APPROVALS 3

REFERENCES 4

Factory and Head Office

Harezmic Intelligent Analogue


Addressable Fire Detection
MG-7800 Multi-Loop Fire Alarm 5-6
Control Panels
MG-7100 Single Loop Fire Alarm 7-8
Control Panel
Mechanical
design MG-7200/MG-7400 Multi-Loop Fire 9-10
Alarm Control Panels
MG-9000 Series Fire Detectors 11-12

AGD Series Gas Detectors 13-14


MG-6000 Series Monitor and 15-16
Controller Modules
Analogue Addressable System 17-18
Accessories
Loop Manager 19-20

Supervisor 21-22
Research and Development PCB design
System Capabilities 23-24

Conventional Fire Detection


SD64+ Fire Alarm Control Panels
25-26
Detector and TP64+ Repeater Panels
test
MG-8 Fire Alarm Control Panels 27-28
MP-8 Fire Alarm Control Panels 29-30
MS-64 Fire Alarm Control Panels 31-32
MGRP-64 Repeater Panel 33-34
MG/MGR-2000 Series Fire Detectors 35-36

Quality control Environmental test Extinguishant Control System


chamber
MG-104 Extinguishant Control Panel 37-38

MaviGard Marine Fire Detection 39-40


Depot

Conventional Gas Detection


MG-400 Industrial Type Combined 41-42
Gas and Fire Alarm Control Panel
GD/GDR Series Gas Detectors 43-44

General Accessories 45-46


Meeting room & Show room Technical service traning

www.mavigard.com 2
CERTIFICATES APPROVALS

Mavili Elektronik has been approved EN ISO 9001:2000 All MaviGard products are approved by DGPS (State
standard by SWEDAC (Swedish Board for Accreditation Fire Prevention Service Department of Ministry for
and Conformity Assessment) accredited TURK LOYDU. Emergency Situations) of Kazakhstan.

All MaviGard products are approved by Directorate


General of Civil Defence of Sultanate of Oman.
MaviGard Harezmic series analogue addressable fire
alarm control panels, fire detectors and manual call
points; SD64+ conventional fire alarm control panels,
MG/MGR-2000 series fire detectors (standard and with
relay output) and manual call points are EN 54 certified.

Conventional fire alarm control panels, fire detectors


and Harezmic series analogue addressable fire alarm
control system are approved by General Directorate of
Civil Defence of Kingdom of Bahrain.

All MaviGard analogue addressable and conventional


fire detectors are EMC-CE (Electromagnetic
Compatibility) certified by KEMA Quality B.V. (The
Netherlands)

All MaviGard products are approved by General Civil


Defence Directorate of United Arab Emirates.

All MaviGard products have Russian SSPB (Fire Safety


Certification System) certificates given by ANO
Normatest.

MaviGard series gas detectors are approved by Russian


Federal Department of Ecological, Technological and
Atomic Energy Supervision.

All MaviGard products are GOST R (Russian State


Standard) certified.

All EN 54 certified MaviGard products are approved by


Civil Defence authority of the Bulgarian Ministry of the
Interior.

MaviGard Marine series fire alarm and extinguishant


systems are tested according to SOLAS 74 and FSS
(Fire Safety System) and have TURK LOYDU certificate.

Mavili Elektronik is a member of NFPA (National Fire


Protection Association).

3 www.mavigard.com
More than 30,000 sites around the world are protected by
MaviGard fire and gas alarm systems.

www.mavigard.com 4
OVERVIEW

HAREZMIC MG-7800
MULTI-LOOP INTELLIGENT
ANALOGUE ADDRESSABLE
FIRE ALARM CONTROL
PANELS
The latest MaviGard Multi-loop Intelligent
Analogue Addressable Fire Alarm Control
Panel. It has more flexibity and upgraded
features which operates on unique VIP
communication protocol. An easy way to
use in large sites up to 8 loops and 1016
addresses. SSPB and GOST R certified.

Highlights
Panel loop capacity can be extended
into 8 loops. MG-7800 Analogue Addressable Fire Alarm Control Panel

Operating in a network of 64 panels


and/or repeater panels

4 programmable and supervised


Harezmic series panels operate on unique be included into cause-effect configurations.
sounder outputs VIP (Very Intelligent Protocol), developed by
engineers of Mavili Elektronik. Harezmic panels Access levels
LCD (240 x 64 characters) with blue
backlight
use the most advanced microprocessor Panels have password-secured access levels,
technology to provide a control system of which prevent unauthorised changing of the
64 user-defined zones highest level of integrity. settings in the system.
Displaying detector measurements
Supported devices Panel outputs
The loop can host the whole range of The 4 sounder and 3 relay outputs are fully
Features Harezmic series devices (fire and gas programmable like any addressable device in
1000 event log memory detectors, monitoring and controlling the system. The outputs can be set to delay
modules, sounders). for up to 250sec. on reception of fire or fault
Detailed information about fire and
fault events
event by the control panel. Delay Active LED
Panel capacity illuminates on the front panel when outputs
Real-time clock Panels are available with 8 loops, each capable are set to delay.
Soft touch buttons of hosting up to 127 addresses. Fire protection
area can be enlarged with conventional zones Loop Manager & Supervisor
Switched mode power supply
by use of MG-6400 Series Zone Monitor Cause-effect configurations and other
Communication interrupt for fast fire Modules. advanced settings are made with Loop
alarm detection in 1.5 sec Manager, which allows full site automation
Microprocessor-controlled Networking and monitoring.
A total of 64 panels and/or repeater panels
3 programmable relay outputs
can be assembled into a network, thus Supervisor is used for fire and fault events
Protection from electromagnetic providing a fire protection system for large graphical monitoring and controlling fire alarm
interference sites. control panel(s). In case of fire and fault
Hosting up to 127 addresses on each events it is possible to send messages
loop Event indication automatically via Internet, WAN and/or LAN
Loop polling in 7.5 sec Panel LCD (240 x 64 characters) with blue by setting up a patch of the software to other
backlight provides detailed alarm, fault and computers.
Printer output
general system information. Front panel, LCD
and panel software (Loop Manager) are MG-Printer(7800) MaviGard Harezmic
available in three languages: English, Turkish, Analogue Addressable System
and Russian. The LCD shows real-time Panel is compatible with MG-Printer(7800)
analogue measurement of detectors. thermal printer. MG-printer can be added
later on to the control panel. It uses RS-232
User-defined zones communication protocol to communicate
Addresses in Harezmic system can be grouped with the panel. The event log can also be sent
into 64 zones. Each zone has a fire alarm to printer from the panel menu. The printed
signal indicator on the front panel. log has detailed information on fire and fault
events as well as passing access levels of the
Interface modules panel menu.
Interface modules provide building security
control automation. Analogue addressable
detectors, addressable manual call points,
addressable sounders and interface modules
are programmed by use of Loop Manager to
5 www.mavigard.com
SPECIFICATIONS

Auxiliary power supply output:


0.5 A 24 VDC, self-resetting fuse protected.
Alarm relay:
1A 30VDC, volt-free change over,
programmable, delay 250 sec. max. Sounder outputs:
4 x ( 0.5 A 24 VDC ), programmable and
Fire relay: supervised, self-resetting fuse protected, delay
Loops: 1A 30VDC, volt-free change over, 250sec max., end-of-line resistor 10 kW.
8 x 127 addresses, 64 user- programmable, delay 250 sec. max.
defined zones. All Harezmic PC - Loop Manager, Supervisor
series devices are supported. Fault relay:
1A 30VDC, volt-free change over, Printer with RS-232 input.
Circuit is protected by 0.5 A self- programmable, delay 250 sec. max.
resetting fuse.

ZONE LEDS ZONE LEDS


Power
On FIRE 1
1 2 3 4 33 34 35 36
General
Fault FIRE
5 6 7 8 37 38 39 40
Power Evacuate 4 2
Fault
9 10 11 12 41 42 43 44
System General
Fault Disablement
13 14 15 16 45 46 47 48
Resound Zone 3
Alarm Disablement Silence
17 18 19 20 Silence Resound Lamp Exit Enter 49 50 51 52
Evacuate Alarm Alarm Buzzer Test Reset
Sounder Buzzer Button
Fault Silenced More Control More
21 22 23 24 53 54 55 56
Fires Events
Sounder Alarm
Disabled Silenced
25 26 27 28 57 58 59 60
More More Analogue Addressable
Fires Events Fire Alarm Control Panel Enable
29 30 31 32 61 62 63 64
Disable

Zonal LEDs LED Indicators LCD screen (64x240 character) Controller Zonal LEDs
with adjustable blue backlight. Buttons

Menu Samples
Technical Specifications - MG-7800
FIRE!
Loops : 8 (1016 addresses) FIRE EVENT ACTIVATION 001/003
PANEL#01 ZONE:11 ADDRESS:080
Mains power supply : 220 VAC 50 Hz, 2 A glass type fuse protected MG-8100 MANUAL CALL POINT
Operating voltage : 24 VDC Left wing corridor, 1st floor
Headquarters building
Batteries : 2 x (12 V 7 Ah)

Construction : Panel cabinet: 1.2 mm sheet steel, front panel: 1.5 Fire event
mm sheet steel, plastic cover
Finish : Epoxy powder coat FAULT
FAULT EVENT ACTIVATION 002/003
Mounting : Surface PANEL#01 ZONE:12 ADDRESS:027
MG-6200 SWITCH MONITOR, 1-WAY IN
Standard colour : Panel cabinet: grey, front panel and cover: white
Extinguishant flow switch
Operating ambient temperature : (-10ºC)-(+55ºC) Headquarters building

Operating ambient humidity : 0-95% (non-condensing)


Fault event generated by input device
Programmable zones : 64
Size : 500 x 370 x 130 mm

MG-Printer(7800) Specifications
Panel Models
Operating voltage : 24 V DC
Product Loops Address Weight*
Code capacity capacity
Stand-by current : 20mA
MG-7800/100 1 127 9.1kg
Max. current : 150mA
MG-7800/200 2 256 9.5 kg
MG-7800/300 3 381 9.9 kg Size : 500 x 115 x 71 mm

MG-7800/400 4 508 10.4 kg Operating temperature : (-10ºC)-(+55ºC)


MG-7800/500 5 635 10.8 kg Operating ambient humidity : 0-95% (non-condensing)
MG-7800/600 6 762 11.2 kg
Weight(approx.) : 1.5 kg
MG-7800/700 7 889 11.6 kg
MG-7800/800 8 1016 12 kg The printer is mounted under
the panel cabinet.
*Approximately without batteries

www.mavigard.com 6
OVERVIEW

HAREZMIC MG-7100
SINGLE LOOP INTELLIGENT
ANALOGUE ADDRESSABLE
FIRE ALARM CONTROL
PANEL
Single loop structure, stylish exterior design
and enhanced programmability make the
MG-7100 an economical and
technologically top-level solution for small
and medium sites. EN 54 and SSPB (Russia)
and GOST R certified. Approved by
Kazakhstan, Oman, UAE, and Bahrain Civil
Defence authorities.

Highlights MG-7100 Analogue Addressable Fire Alarm Control Panel


Very Intelligent Communication
Protocol

Display priority to fire events Harezmic series panels operate on unique events when displaying many miscellaneous
VIP (Very Intelligent Protocol), developed by events simultaneously.
Polling interrupt for fast alarm
detection
engineers of Mavili Elektronik.
Panel menu
64 x 240 pixel LCD with adjustable Supported devices Panel menu has built-in tips to assist the user
blue backlight
The loop can host the whole range of while navigation. There are also 2nd and 3rd
Password-protected access levels Harezmic series devices (fire and gas level passwords to prevent unauthorised
Printer output detectors, monitoring and controlling access to the settings of the system.
modules, sounders). Loop capacity is 127
Displaying detector measurements addresses. Fire protection area can be enlarged Configuration by Loop Manager
with conventional zones by use of MG-6400 Cause-effect configurations and other
Features Series Zone Monitor Modules. advanced settings are made with Loop
Real-time clock
Manager, which allows full site automation
Sounder outputs and monitoring. Panel menu, front panel and
1000 event log memory The panel has 2 supervised and programmable Loop Manager have versions in three
Microprocessor-controlled sounder outputs, which can be included as languages: Turkish, English and Russian.
outputs in cause-effect configurations like an
PCBs made by use of Surface Mount
Technology
addressable device. Connecting MG-5000 Monitoring and controlling by Supervisor
series sounders and bells to the outputs is Supervisor is a specially developed PC
2 programmable and supervised recommended for best performance. Each software used for fire and fault events
sounder outputs
output can host 16 MG-5000 Sounders, 8 graphical monitoring and controlling fire alarm
3 programmable relay outputs MG-5200 Sounder Strobes or 20 MG-5400 control panel(s).In case of fire and fault events
16 user-defined zones Fire Alarm Bells. it is possible to send messages automatically
via Internet, WAN and/or LAN by setting up
Loop polling in 7.5 sec Relay outputs a patch of the software to other computers.
Protection against electromagnetic Programmable Alarm, Fire and Fault relay
Panel power supply
interference outputs can be used for controlling external
Power supply of the panel is under continuous
Auxiliary power supply output systems and devices. Like sounder outputs,
monitoring. Batteries are charged
they can be included in cause-effect
Soft-touch buttons automatically and charging is cut off when
configurations. An activation delay can be set
necessary level is reached. Power supply faults
Built-in silenceable buzzer to the outputs; it is indicated on the front
are displayed by related LEDs.
panel by Delay Active LED.
MG-Printer(7100) MaviGard Harezmic
Auxiliary power supply output
Analogue Addressable System
Panels are equipped with an auxiliary 24V
MG-Printer has been designed for MG-7100
power supply output for energising external
intelligent analogue addressable fire alarm
devices, such as telephone dialers or gas
control panels.
detectors.
Event log can be written either simultaneously
or entirely.MG-Printer(7100) is mounted just
Event indication
under the MG-7100 panel and operates with
A large (64 x 240 pixels) graphic LCD with
RS-232 communication protocol.
adjustable blue backlight can exhibit all
MG-printer is used for indoor use. It is not
information without serious abbreviations and
used in outdoor and hazardous areas.
shortenings. Each user-defined zone has a
fire LED on front panel to facilitate locating
fire alarm area. The LCD gives priority to fire

7 www.mavigard.com
SPECIFICATIONS

Alarm relay:
1A 30VDC, volt free change over, Auxiliary power supply output:
programmable, delay 250 sec. max. 0.5 A 24 VDC, self-resetting fuse protected.

Fire relay: Sounder outputs:


1A 30VDC, volt free change over, 2 x ( 0.5 A 24 VDC ), programmable and
programmable, delay 250 sec. max. supervised, self-resetting fuse protected, delay
Loop: 250sec max., end-of-line resistor 10 kW.
127 addresses, 16 user-defined zones. All Fault relay:
Harezmic series devices are supported. Circuit 1A 30VDC, volt free change over, PC - Loop Manager
is protected by 0.5 A self-resetting fuse. programmable, delay 250 sec. max. Printer with RS-232 input.

Zonal fire LEDs Controls


LCD, 64 x 240 pixels, with
System status and fault LEDs adjustable blue backlight

Event message examples

Technical Specifications - MG-7100 FIRE!


FIRE EVENT ACTIVATION 001/003
Mains power supply : 220 VAC 50 Hz, 2 A glass type fuse protected PANEL#01 ZONE:11 ADDRESS:080
MG-8100 MANUAL CALL POINT
Operating voltage : 24 VDC Left wing corridor, 1st floor
Headquarters building
Batteries : 2 x (12 V 7 Ah)

Construction : Panel cabinet: 1.2 mm sheet steel, front panel: 1.5 mm sheet Fire event
steel, plastic cover
Finish : Epoxy powder coat FAULT
FAULT EVENT ACTIVATION 002/003
Mounting : Surface PANEL#01 ZONE:12 ADDRESS:027
Standard colour : Panel cabinet: grey, front panel and cover: white MG-6200 SWITCH MONITOR, 1-WAY IN
Extinguishant flow switch
Operating ambient temperature : (-10ºC)-(+55ºC) Headquarters building
Operating ambient humidity : 0-95% (non-condensing)
Fault event generated by input device
Size : 400 x 300 x 100 mm

MG-Printer(7100) Specifications

Operating voltage : 24 V DC

Quiescent current : 20mA

Max. current : 150mA

Size : 400 x 115 x 71 mm

Operating temperature : (-10ºC)-(+55ºC)


MG-Printer(7100)
Thermal printer
Operating ambient humidity : 0-95% (non-condensing)

Weight(approx.) : 1.25 kg

The printer is mounted under


the panel cabinet.

www.mavigard.com 8
OVERVIEW

HAREZMIC MULTI-LOOP
MG-7200/MG-7400
INTELLIGENT ANALOGUE
ADDRESSABLE FIRE
ALARM CONTROL PANELS
Reliable fire alarm control panels
operating on unique VIP communication
protocol. EN 54 and SSPB (Russia) and
GOST R certified. Approved by Kazakhstan,
Oman, and Bahrain Civil Defense
authorities.

Highlights
MG-7200/MG-7400 Analogue Addressable Fire Alarm Control Panel
2 and 4 loop standard models

Operating in a network of 32 panels


and/or repeater panels

4 programmable and supervised Harezmic series panels operate on unique be included into cause-effect configurations.
sounder outputs VIP (Very Intelligent Protocol), developed by
engineers of Mavili Elektronik. Harezmic panels Access levels
LCD (2 x 40 characters) with backlight
use the most advanced microprocessor Panels have password-secured access levels,
48 user-defined zones technology to provide a control system of which prevent unauthorised changing of the
Displaying detector measurements highest level of integrity. settings in the system.

Features Supported devices Panel outputs


1000 event log memory The loop can host the whole range of The 4 sounder and 3 relay outputs are fully
Harezmic series devices (fire and gas programmable like any addressable device in
Detailed information about fire and
fault events detectors, monitoring and controlling the system. The outputs can be set to delay
modules, sounders). for up to 250sec. on reception of fire or fault
Real-time clock
event by the control panel. Delay Active LED
Soft touch buttons Panel capacity illuminates on the front panel when outputs
Switched mode power supply
Panels are available with 2 or 4 loops, each are set to delay.
capable of hosting up to 127 addresses. Fire
Communication interrupt for fast fire protection area can be enlarged with MG-Printer(7200-7400) MaviGard Harezmic
alarm detection in 1.5 sec
conventional zones by use of MG-6400 Series Analogue Addressable System
Microprocessor-controlled Zone Monitor Modules. MG-Printer has been designed for MG-7200
3 programmable relay outputs & MG-7400 intelligent analogue addressable
Networking fire alarm control panels.
Protection from electromagnetic A total of 32 panels and/or repeater panels Event log can be written either simultaneously
interference
can be assembled into a network, thus or entirely.
Hosting up to 127 addresses on each providing a fire protection system for large
loop sites. MG-printer is used for indoor use. It is not
Loop polling in 7.5 sec used in outdoor and hazardous areas.
Event indication
Printer output
Panel LCD (2 x 40 characters) with backlight Panel and printer communicate over RS-232
Repeater Panel Features provides detailed alarm, fault and general communication protocol. Printer comm. cable
system information. Front panel, LCD and is given with the printer. MG-Printer shall be
Replicates the status of the analogue panel software (Loop Manager) are available mounted next to the panel.
addressable fire alarm control system. in three languages: English, Turkish, and
Russian. The LCD shows real-time analogue Loop manager & Supervisor
Panels in network can be controlled
by repeater panels measurement of detectors. Cause-effect configurations and other
Detailed event information on panel
advanced settings are made with Loop
User-defined zones Manager, which allows full site automation
LCD
Addresses in Harezmic system can be grouped and monitoring.
RS-485 network communication into 48 zones. Each zone has a fire alarm
protocol
signal indicator on the front panel. Supervisor is used for fire and fault events
graphical monitoring and controlling fire alarm
Interface modules control panel(s). In case of fire and fault
Interface modules provide building security events it is possible to send messages
control automation. Analogue addressable automatically via Internet, WAN and/or LAN
detectors, addressable manual call points, by setting up a patch of the software to other
addressable sounders and interface modules computers.
are programmed by use of Loop Manager to

9 www.mavigard.com
SPECIFICATIONS

Event message
Device type Total event count
Event code Active event number
Location text Device address
Event name Loop number
Zone number Panel address

FIRE ALARM Z004 A:02.1.035 001/003


Floor 1: Meeting room
Event Code: 0021 – – – For details: ENTER
MG-9100 Photo-electric smoke detector
LCD (2 x 40 characters)
An event message has 4 lines as shown above. On event occurence
System status LEDs panel LCD shows first 2 lines - the event name and location text.
Controls Pressing the Enter button rolls the lines up to display the 2nd
and 3rd, 3rd and 4th lines respectively.
Zonal fire LEDs

Viewing device information


Panel name
Device type Device address
Analogue value Loop number
Zone number Panel address

Analogue value: 137 Z:006 A:28.1.118


MG-9300 Heat detector
HAREZMIC PANEL 28
Pressing the Enter button displays the 3rd line, showing panel
Technical Specifications - MG-7200- MG-7400 name.
Loops : 2 or 4 (0.5 A 24 VDC, self-resetting fuse protected) Temperature Analogue value
22ºC 137
Addresses : 254 or 508 43ºC 92
60ºC 67 Alarm threshold
User-defines zones : 48
76ºC 41
Sounder outputs : 4 x (0.5 A 24 VDC), programmable and supervised, self-resetting
fuse protected, end-of-line resistor 10 kW
Panel models
Fire relay : 1 A 30 VDC, programmable, volt free changeover, NO and NC
Product Loops Address Weight*
Alarm relay : 1 A 30 VDC, programmable, volt free changeover, NO and NC Code capacity capacity
Fault relay : 1 A 30 VDC, programmable, volt free changeover, NO and NC MG-7200 2 254 9.1 kg
Output delay : 250 sec. max. MG-7400 4 508 9.8 kg
Auxiliary power supply output : 0.5 A 24 VDC, self-resetting fuse protected MG-7000 0 - 9 kg
Controls : Alarm, Silence Alarm, Reset, Enter, More Events, Microprocessor * approx., without batteries.
Reset, Write Enable Switch
Accessories
Indicators : System On, Pre-Alarm, System Fault, General Fault, Sounder Fault,
Fire, Alarm Silenced, Disable, Delay Active, On Test, More Events, Product Description
2 x 40 character LCD, zonal Fire LEDs Code
00YS87 Loop extension card
Networking : Up to 32 panels
Optional printer : External with RS-232 input MG-7090 Network interface card
MG-Printer External printer
Mains power supply : 220 VAC 50Hz, 5 A glass type fuse protected

Operating voltage : 24 VDC

System fuse : 4 A, self-resetting


Batteries : 2 x (12 V 7Ah)

Construction : 1.7 mm sheet steel

Finish : Epoxy powder coat

Mounting : Surface

Standard colour : Two tone grey MG-Printer(7200-7400)


Thermal printer
Operating ambient temperature : (-10ºC)-(+55ºC)

Operating ambient humidity : 0-95% (non-condensing)


MG-Printer(7200-7400) Specifications
Size : 500 x 400 x 140 mm
Operating voltage: 24 V DC

Stand-by current: 20mA

Max. current: 150mA

Operating temperature : (-10ºC)-(+55ºC)

Operating humidity : 0-95% (non-condensing)

Weight: 1,20 kg (approx.)

Size: 200 x 150 x 85 mm

www.mavigard.com 10
OVERVIEW

MG-9100 Photo-Electric Smoke


Detector

Operating voltage 18-33 VDC


MG-9000 SERIES
Detection principle Optical chamber
INTELLIGENT ANALOGUE
ADDRESSABLE FIRE Quiescent current (max.) 600 µA

DETECTORS Remote indicator output 4 mA

2 transparent LEDs
VIP (Very Intelligent Protocol) compatible. Photo-electric smoke detector utilises the Indicators (red on alarm)
EN 54, EMC-CE and SSPB (Russia) and light scatter sensing principle. It has an
GOST R certified. Approved by Kazakhstan,
Oman, UAE and Bahrain Civil Defence
infrared light source, which emits signals Operating ambient temperature (-10 C)-(+50 C)
0 0

authorities. and a photo-diode, which senses the


Operating ambient humidity 0-95 %
scattering light with the effect of smoke (non-condensing)
entering the chamber. The chamber is
designed for protection from dust, insects Size (incl. base) Ø: 100 mm, h: 50 mm
and other external interferences. Detectors Weight (approx.) 143 g
are EN 54-7 and EMC Directive 89/336/EEC
Features
certified. Alarm threshold 0.10-0.15 dB/m
EN 54-5 ve EN 54-7 certified

Twin fire alarm indicators for 360°


viewing
MG-9200 Ionisation Smoke
‘Soft’ addressable by use of Address
Programmer Detector
Remote indicator output
Operating voltage 18-33 VDC
Communication interrupt for fast fire
alarm detection in 1.5 sec Detection principle Americium(241) 33.3 kBq
Stable sensitivity
Quiescent current (max.) 450 µA
PCB protected by metal case
Remote indicator output 4 mA
Protection from electromagnetic
interference 2 transparent LEDs
Indicators (red on alarm)
MG-3510 Addressable Mounting Base
Ionisation smoke detector has twin room
compatible
ionisation chamber to prevent the Operating temperature (-100C)-(+500C)
MG-3600 Recessed Mounting Base interference of excessive humidity and heat.
compatible Operating ambient humidity 0-95 %
One of the rooms functions as reference (non-condensing)
Microprocessor-controlled and the other as the sampling one. The
chamber is designed for protection from Size (incl. base) Ø: 100 mm, h: 50 mm
Clamp terminals to ensure firm contact
with the base dust, insects and other external Weight (approx.) 133 g
Produced by use of Surface Mount interferences. Detectors are EN 54-7 and
Technology EMC Directive 89/336/EEC certified. Alarm threshold Y value 0.7

MG-9300 Heat Detector


Operating voltage 18-33 VDC

Detection principle Thermistor

Quiescent current (max.) 450 µA

Remote indicator output 4 mA

2 transparent LEDs
Indicators (red on alarm)

Operating temperature (-100C)-(+500C)


Heat detector detects temperature
change by temperature-sensitive Operating humidity 0-95 %
thermistors. The detector can function (non-condensing)
either as a fixed heat or rate of rise heat Size (incl. base) Ø: 100 mm, h: 50 mm
detector. The design of the chamber
provides sensitive ambient temperature Weight (approx.) 123 g
measurement. Detectors are EN 54-5
300C/min temperature rise
and EMC Directive 89/336/EEC certified. Alarm threshold and/or 600C fixed temp.

Heat detector class A1 R

11 www.mavigard.com
OVERVIEW

MG-9400 Multi-sensor
(Photo-Electric Smoke + Heat Detector)

Operating voltage 18-33 VDC

Detection principle Optical chamber and thermistor

Quiescent current (max.) 600 µA

Remote indicator output 4 mA

Indicators 2 transparent LEDs (red on alarm)

Operating ambient temperature (-100C)-(+500C)

Operating ambient humidity 0-95 %


(non-condensing)
The multi-sensor has a photo-electric smoke
detection chamber and a temperature-sensitive Size (incl. base) Ø: 100 mm, h: 55 mm
thermistor. The chamber is designed for protection
Weight (approx.) 175 g
from dust, insects and other external interferences.
The design of the chambers provides maximum Alarm threshold 0.10-0.15 dB/m
sensitivity to smoke and temperature change.
Detectors are EMC Directive 89/336/EEC certified. Heat detector class A1 R

Upper cover
LED reflector plastics
Chamber cover
Sensor metal protector
Optical chamber
PCB (in all fire detectors surface-
mount technology is used)
Screening plate
Base plastics
Detector base

www.mavigard.com 12
OVERVIEW

AGD SERIES
INTELLIGENT
ADDRESSABLE GAS
DETECTORS
An addressable solution for gas leakage
detection. AGD series gas detectors are
connected to loops of Harezmic series fire
alarm control panels and operate on
Harezmic Very Intelligent Protocol. SSPB
(Russia) and GOST R certified.

Features
Compatible with MG-7000 series
MaviGard Harezmic intelligent
analogue addressable fire alarm control
panels

Built-in buzzer

Built-in relay output

Power On, Gas Alarm and Fault LED


indicators and buzzer test button

5 year sensor life under normal


operating conditions Outer cover
LED reflectors
Stable sensitivity and high operating
Test button
performance
Inner cover
12/24 VDC external power supply PCB
Max. 127 gas detectors per loop Detector base

Can be included in cause-effect


configurations as input devices by use
of Loop Manager

Microprocessor-controlled design

Loop in External power supply inpu

Loop out Relay output

System On LED
Alarm LED
Fault LED
Test button

13 www.mavigard.com
SPECIFICATIONS

Common Technical Specifications

Power consumption : 2 W
External power supply : 12/24 VDC
Relay output : 10 A 250 VAC / 8 A 30 VDC
Fuse : 0.5 A, self-resetting
Protection area (max.) : 50 m2
Operating ambient temperature : (-10ºC) - (+55ºC)
Operating ambient humidity : 0-95% (non-condensing)
Audible alarm : Piezzoelectric buzzer, 85 dB/1m
Indicators : System On LED (green), Alarm LED (red), Fault LED (yellow)
Controls : Test button
Construction : ABS
Ingress Protection class (IP) : 42
Size : 140 x 100 x 50 mm
Weight : 210 g
Sensor type : Semiconductor
Sensor life : 5 years
Colour : White

Gas Detector Models


AGD-1224L/VIP Addressable LPG (Propane+Butane) Detectors
LPG is an explosive hydrocarbon gas
Product Code AGD-1224L/VIP
consisting of butane and propane. It is
heavier than air and sinks to floor in case Gas Type Propane & Butane
of leakage. Therefore, an LPG detector must Warm-up time <1 min
be mounted 15-25 cm above floor and
within 1-2 m horizontally within the range Alarm response time <10 sec
of possible gas leakage. The MaviGard LPG Lower explosive limit 20%
detectors respond audibly and visually
before the leakage reaches 20% LEL.

AGD-1224M/VIP Addressable Natural Gas (Methane) Detectors


Methane is an explosive hydrocarbon gas.
Product Code AGD-1224M/VIP
It is lighter than air and rises to ceiling in
case of leakage. Therefore, a natural gas Gas Type Methane
detector must be mounted 5-15 cm below Warm-up time <1 min
ceiling and 1-2 m horizontally within the
range of possible gas leakage. The MaviGard Alarm response time <10 sec
natural gas detectors respond audibly and Lower explosive limit 20%
visually before the leakage reaches 20%
LEL.

AGD-1224C/VIP Addressable Carbon Monoxide (CO) Detectors


Carbon monoxide is a toxic and explosive Product Code AGD-1224C/VIP
gas with density nearly equal to air.
Therefore, a carbon monoxide detector Gas Type Carbon monoxide
must be mounted 1-1.5 m above floor and Warm-up time <30 sec
1-2 m horizontally within the range of
Alarm response time <2.5 min
possible gas leakage. Carbon monoxide
detectors should not be mounted outside Lower explosive limit 50 ppm (parts per million)
buildings, behind or inside cupboards, where
air circulation is low, in damp or humid
places, above fuel burning appliances and
places with low or high temperatures. The
MaviGard carbon monoxide detectors
respond audibly and visually when the gas
concentration reaches 50 ppm (parts of
gas per million parts of air).

www.mavigard.com 14
OVERVIEW
MG-6100 Relay Controller, 1-Way Output
MG-6108 Relay Controller, 8-Way Output
MG-6100 MG-6108

Power supply Loop-powered Loop-powered

Quiescent current 377 µA 650 µA

Alarm current 380 µA 1.8 mA


HAREZMIC SERIES Max. load 1 A 30 VDC* 1 A 30 VDC*
INTELLIGENT Operating ambient
0
(-10 C)-(+55 C)
0 0
(-10 C)-(+55 C)
0

temperature range
ADDRESSABLE
Operating ambient 0-95 % 0-95 %
MONITOR AND humidity (non-cond.)
CONTROLLER MODULES Size 120 x 85 x 50 mm 155 x 110 x 65 mm

VIP (Very Intelligent Protocol) compatible. Weight 90 g 315 g


SSPB (Russia) and GOST R certified. *Measured values from clamps,outputs are voltage-free contacts.
Approved by Kazakhstan, Oman, UAE and
Bahrain Civil Defence authorities.
The modules are used for activation of external equipment such as lifts, dampers etc. on fire
or fault event as defined in cause-effect configuration. The MG-6100 model has one relay
output with volt free changeover normally open and normally close contacts. The MG-6108
model has 8 outputs, each having a separate address. The modules are loop-powered and
have two indicators: Polling and Relay Active.
Features
Microprocessor-controlled MG-6200 Switch Monitor, 1-Way Input
‘Soft’ addressable by use of Address MG-6208 Switch Monitor, 8-Way Input
Programmer MG-6200 MG-6208

Easily programmable by Loop Manager Power supply Loop-powered Loop-powered

LED-indicated activation and fault Quiescent current 345 µA (NO) 650 µA (NO)
conditions
Alarm current 530 µA (NO) 4.2 mA (NO)
Loop-powered Switch Monitors and
Relay Controllers Operating ambient
temperature range (-100C)-(+550C) (-100C)-(+550C)
Power supply fault monitoring by volt-
free changeover contact Operating ambient
humidity (non-cond.) 0-95 % 0-95 %
8-way input and output module 120 x 85 x 50 mm 155 x110 x 65 mm
Size
models
Weight 90 g 315 g

The modules are used for monitoring of external devices such as sprinkler system, alarm inputs,
general purpose fire prevention devices, control contacts and other security outputs. The MG-
6200 model has one volt free input, which can monitor both normally open and normally close
contacts. The MG-6208 model has 8 inputs, each having a separate address. The modules are
loop-powered and have one indicator: Polling.
MG-6300 Sounder Controller, 1-Way Output
MG-6308 Sounder Controller, 8-Way Output
MG-6300 MG-6308
External power supply 24 VDC 24 VDC
Quiescent current 24.4 mA** 25.5 mA**
Alarm current 43 mA** 150 mA**
Max. load 0.5 A 24 VDC 8 x (0.5 A 24 VDC)
End-of-line resistor 10 kW 10kW
Operating ambient (-100C)-(+550C) (-100C)-(+550C)
temperature range
Operating ambient 0-95 % 0-95 %
humidity (non-cond.)

Size 120 x 85 x 50 mm 300 x 110 x 65 mm


Weight 135 g 540 g
** When there is no device connected into inputs or outputs, the current drawn by external
power supply.

The modules are used for activation of sounders, sounder strobes, fire alarm bells and other
audio-visual warning devices as defined in cause-effect configuration. Sounder circuit is
continuously monitored for open and short circuits. The MG-6300 model has one output.
The MG-6308 model has 8 outputs, each having a separate address. The modules have three
indicators: Polling, Sounder Active, and 24 V Fault.

The MG-6300 series modules require external 24V DC power supply. Each output can host 16
MG-5000 Sounders, 8 MG-5200 Sounder Strobes or 20 MG-5400 Fire Alarm Bells.
15 www.mavigard.com
OVERVIEW

MG-6400 Zone Monitor, 1-Way Input


MG-6408 Zone Monitor, 8-Way Input MG-6400 MG-6408
External power supply 24 VDC 24 VDC
Quiescent current 17.2 mA** 34.8 mA**
Alarm current 33.1 mA** 47.2 mA**
Max. load 20 detectors 160 detectors
End-of-line resistor 6.8 kW 6.8 kW
0 0
Operating ambient (-10 C)-(+55 C) (-100C)-(+550C)
temperature range

Operating ambient 0-95 % 0-95 %


humidity (non-cond.)

Size 120 x 85 x 50 mm 155 x 110 x 65 mm


Weight 135 g 435 g
** When there is no device connected into inputs or outputs, the current drawn by external
power supply.

The modules are used for expanding the fire alarm control system with conventional zones, each capable of hosting up to 20
detectors and unlimited number of manual call points. Zone circuits of the modules are continuously monitored for open and short
circuits. The MG-6400 model has one input. The MG-6408 model has 8 inputs, each having a separate address. The modules have
two indicators: Polling and 24 V Fault.

The MG-6400 series modules require external 24 VDC power supply.

For best performance, connecting MG-2000 series fire detectors and MG-5100 series manual call points is recommended.

MG-6700 Mains Relay Controller, 1-Way Output MG-6700


External power supply Loop-powered
Quiescent current 377 µA
Alarm current 380 mA
Max. load 8 A 250 V AC*
End-of-line resistor NA
Operating ambient (-100C)-(+550C)
temperature range
Operating ambient 0-95 %
humidity (non-cond.)

Size 120 x 85 x 50 mm
Weight 90 g
*Measured values from clamps,outputs are voltage-free contacts.
The module is used for activation of external equipment such as lifts, dampers etc. on fire and fault event as defined in cause-
effect configuration.The module has one relay output with volt-free, unipolar contacts with max. load of 8 A 250 VAC. The relay
can operate as normally open or normally close. The module is loop-powered and has two LED indicators: Polling and Relay Active.
The module does not require an external power supply.
Module models

Code Description

MG-6100 Relay Controller, 1-Way Output Power supply units


MG-6108 Relay Controller, 8-Way Output Code Description
MG-6200 Switch Monitor, 1-Way Input MG-7080 MSM-4 (SMPS) Switched Mode Power Supply Unit, 4 A
MG-6208 Switch Monitor, 8-Way Input MG-7050 MSM-4 (SMPS) Switched Mode Power Supply Unit, 2.5 A
MG-6300 Sounder Controller, 1-Way Output

MG-6308 Sounder Controller, 8-Way Output


MG-6400 Zone Monitor, 1-Way Input

MG-6408 Zone Monitor, 8-Way Input


MG-6700 Mains Relay Controller, 1-Way Output

www.mavigard.com 16
OVERVIEW

MG-8110 Addressable Manual Call Point, Resettable, and 2-Terminal


Red Back Box (MG-8101)
Power supply Loop-powered
The MG-8110 is a resettable manual
call point, which features flexible Quiescent current 60 µA
operating element. The resettable Alarm current 2 mA
HAREZMIC SERIES type MCP is the best solution where
Operating ambient (-100C)-(+550C)
INTELLIGENT ANALOGUE no break-glass type MCPs are temperature
applicable. The manual call points
ADDRESSABLE SYSTEM are equipped with a red LED, which
Operating ambient
humidity 0-95%
ACCESSORIES blinks on polling and illuminates Size 89 x 93 x 57.5 mm
continuously on activation.
Weight 160 g
VIP (Very Intelligent Protocol) compatible.
SSPB (Russia) and GOST R certified.
Approved by Kazakhstan, Oman, UAE, and
Bahrain Civil Defence authorities. MG-8110 Manual Call Point test and reset steps

Features
Microprocessor-controlled
1 2 3
‘Soft’ addressable by use of Address
Programmer

Easily programable by use of Loop


Manager MG-8120 Addressable Manual Call Point,
Able to integrate into the cause-effect Wheather-Proof (IP67)
scenarios.
The MG-8120 manual call point is
LED-indicated activation activated by breaking film-coated Power supply Loop-powered
glass. When the glass is broken, the
Monitoring analogue value Quiescent current 85 µA
switch, normally resting on glass
Mesuring contamination level edge, changes its position and Alarm current 4.2 mA
retains till new glass is mounted. Operating ambient (-10ºC)-(+50ºC)
Aesthetic design
Since the glass covered with the film, temperature
Production by surface-mount it does not harm the fingers. The Operating ambient 0-95%
technology manual call point is equipped with humidity
a red LED, which blinks on polling Protection Class IP67
and illuminates continuously on 124 x 124 x 60 mm
Size
activation.The MG-8120 addressable
manual call points are wheather- Weight 347 g
proof and placed in the IP67 ingress
protection class.

MG-8130 Addressable Manual Call Point with Isolator Module,


Resettable

MG-8130 Addressable manual call


points has 2 LEDs on it. Power supply Loop-powered
Quiescent current 4 mA
The red LED illuminates on
activation of manual call point and Alarm current 6 mA
the yellow LED illuminates on short Operating ambient (-100C)-(+500C)
circuit condition on loop. temperature

MG-8130 operates similar to MG- Operating ambient 0-95 %


humidity
8110. The module is used for
isolation of the loop sector affected Size 87.5 x 87.5 x 56,5 mm
by short circuit, thus preserving the Weight 347 g
healthy operating of the rest of the
loop.

17 www.mavigard.com
OVERVIEW

MG-6500 Short Circuit Isolator


Power supply Loop-powered
The module is used for isolation of the loop
Quiescent current 4 µA
sector affected by short circuit, thus
preserving the healthy operating of the rest Alarm current 30 mA
of the loop. Connecting one short circuit Operating ambient
isolator module per 20 addressable devices temperature (-100C)-(+550C)

is recommended. The module deactivates Operating ambient


humidity 0-95%
automatically as soon as short circuit
condition ends. The module is not Size 90 x 90 x 40 mm
addressable. Weight 110 g

MG-6600 Addressable Loop-Powered Sounder Power supply Loop-powered


Quiescent current 220 µA
The sounder gives single tone 100 dB(A)
Alarm current 10 mA
output at 1m and has low power
consumption, which allows connecting up Max. load per loop 10 pcs/loop
to 10 sounders per loop. Like other Operating ambient
addressable devices in the Harezmic fire temperature) (-100C)-(+550C)
alarm control system, the sounder is Operating ambient
addressed by use of Address Programmer humidity 0-95%
and fully programmable in Loop Manager Size 108 x 108 x 94 mm
for inclusion in cause-effect configurations.
Weight 270 g
The sounder is designed for indoor use and
holds IP42 rating.

MG-8200 Address Programmer


Analogue addressable detectors, manual Power supply 9V
call points, modules and addressable Operating ambient (-100C)-(+550C)
sounders are microprocessor-controlled, temperature
which allows ‘soft’ addressing from 1 to Operating ambient
0-95 %
127. The Address Programmer is used for humidity
both address setting and displaying the Size 150 x 85 x 35 mm
measured analogue value; this feature allows
Weight 270 g
detecting the pollution level in the smoke
detector chamber.

MG-3510 Addressable Mounting Base


Latest MG- 3510 analogue addressable Operating temperature (-100C)-(+500C)
mounting bases are compatible with MG-
Operating humidity
9000 series analogue addressable detectors. (non-condensing)) 0-95 %
Remote indicator output is standard for
MG series detectors. Addressable mounting Size Ø:99 mm, h:21 mm
base has Ni-Cd coated corrosion-proof Weight (approx.) 45 g
clamp type contacts.It is used for wall and
ceiling mounted applications.

Viewing analogue value on MG-8200 Address Programmer

1 2 1 Connect MaviGard addressable


device to the Address programmer
and press the Left button for about
5 seconds to turn the Address
Programmer on.

2 The address of the device will be


displayed on the display
automatically.

3 Press the Down button to display


3 4 the analogue value. Prior to
switching to analogue value, the
display will show “A” letter on the
screen.

4 Press the Left button for about 5


seconds to turn the Address
Programmer off.

www.mavigard.com 18
OVERVIEW

RS-232

MG-7100
Loop Manager
RS-232 PC

LOOP MANAGER
HAREZMIC SERIES
INTELLIGENT ANALOGUE Harezmic Intelligent Analogue Addressable Fire
ADDRESSABLE
Alarm Control System is configured on PC with
SYSTEM CONFIGURATION MG-7800
SOFTWARE specially designed software, Loop Manager.
The software has 3 language options: Turkish,
Used for making advanced settings in the English, and Russian. The program can work
Harezmic fire alarm control system, such under Windows operating system and has user-
as assigning location texts to addresses, friendly graphical interface. The connection
setting delays to outputs and creating RS-232
cause-effect algorithms for site automation. MG-7200 between PC and panel is held via RS-232
MG-7400

Main window
Loop, zone number, type and location text
Features
(if available) of an addressable device included
Allows defining cause-effect algorithms in the fire alarm system.
for site automation

Three language options: Turkish, New devices can be included in the system
English, and Russian by double-clicking a device in the list.
Up to 40 character location text for Tree-listed addressable devices of the fire
each address
alarm system.
Monitoring external systems and
devices’ operation as Fire or Fault
events

Assigning delays to zone monitor Device settings


modules and loop-powered
addressable sounders up to 300
Device type used in the configuration.
seconds Event type (Fire of Fault) as conveyed to the
Assigning up to 250 seconds delay to fire alarm system.
panel relay and sounder outputs.
Delay up to 250 seconds set to outputs on
Device- and event-based cause-effects interface modules.
System configuration print out Device address and zone number as used in
the configuration.
Location text displayed on panel LCD when an
event is received.

Fire alarm control panel settings


A 40 character text displayed on panel LCD in
quiescent condition.
Panel name.

Delay (up to 250 sec.) assignable to each relay


and sounder output of panel.
System operation mode.

Program settings
The option allows encrypting of the
configuration data to protect from opening the
file on PC where Loop Manager is not installed.
Language (English, Turkish, or Russian).
The option sets the program to ask panel
software version on each program launch.

19 www.mavigard.com
OVERVIEW

Selection of cause-effect inputs and logical principle.


When a cause-effect is created, first the inputs are selected.
All information of the inputs such as loop number, address,
device type etc. are displayed. This simplifies the selection
process. Totally, 254 addresses can be selected as inputs
in single cause-effect.
Cause-effect name.
In the second step, the logical principle, according to which
the cause-effect will operate, is selected:
“AND/All” - outputs activation from any of the selected
inputs.
“OR/Single” - outputs activation from any two of the
selected inputs.
“ANY TWO/Coincidence” - outputs activation from any
two of the selected inputs.
Number of selected inputs out of all available inputs.

Selection of cause-effect outputs.


A cause-effect can include up to 254 addresses as outputs.
Panel relay and sounder outputs can also be added.
Number of selected outputs out of all available outputs.

Visualisation of the cause-effect.


Inputs of cause-effect.
Outputs of cause-effect.
Cause-effect is editable.
Cause-effect can be deleted.

Configuration print out.


Print information:
The name and location of the configuration
folder
Supplier info
Panel name
Number of loops

Device data on loop

Total number of devices


System operation mode
Total number of cause-effects
Cause-effect name
Cause-effect inputs and outputs

www.mavigard.com 20
OVERVIEW
Internet

RS-232

RS-485
GPRS
TCP/IP
SUPERVISOR
GRAPHIC SOFTWARE FOR
MONITORING AND
MANAGING HAREZMIC
ANALOGUE ADDRESSABLE 64 panels network
SYSTEM

Up to 64 panels and/or repeaters operating


in a network can be graphically monitored
and managed on PC.

Features
All fire and fault events in the fire alarm Menu Devices and Maps tree
panels in a network can be graphically Changes the list order of the Maps tree Managing panel(s) using control
monitored buttons
Program access bar (green indicates
All networking fire alarm control panels session is active, red - off.) Map zoom in and out
can be controlled from the program Configuration can be tested by
by use of Alarm, Reset, Silence Alarm simulation
buttons

Automatic program start-up with the


PC operating system

Integrating building projects into the


monitoring program as maps

Switching between maps using


graphical links

Fire alarm system configuration based


on files created in the Loop Manager

Disabling Windows keyboard shortcuts.

10 different users can be defined.

Audible warning according to event


type.

RS-232 communication protocol.

Adjustable event effects.

Three language options: Turkish, Supplier name status bar Map name
English, and Russian.
Incoming events from fire Link used for switching
Event logging alarm control system between maps
Map
Sending alarm messages to remote Maps and System window
PCs in LAN/WAN by use of TCP/IP CPU usage
protocol. System clock

Software alarm settings according to event type


Event type (Fire, Fault, Info) for which settings to be done.
Standard audio or custom midi/mp3 sound file can be selected as alarm.
Alarm visual effect and colour; the setting can be previewed.

Program settings
PC communication port
Automatic launch with PC operating system
Alarm message sent to remote computers
PCs to which alarm message will be sent
Software language
Windows keyboard shortcuts disablement
Supplier Name continuously displayed on status bar

Option setting the alarm message to be sent by pressing


the button (Alarm, Silence Alarm, Reset) or automatically.

Log file name

21 www.mavigard.com
OVERVIEW

Users
Pasword of the users
Confirming which users will be enabled
Up to 10 different software users can be defined.

Link display details


Operation mode for which the link’s settings
are made
Border width and colour
Link colour
Transparency

Device details
Device type.
Panel number to which the device is connected.
Loop number, to which the device is connected.
Device address.
Zone number, to which the device is allocated.
Location text of the device (editable).
The name of the map, on which the device is located.
Icon size in pixels.
Link details
Link name
Source
Target
Target selection drop-
down menu
Event log Text displayed on link
Log print out
Saving log with custom file name
Clearing the active log
Filtering log according to event
type and date interval

Simulation
A simulation of a Fire, Fault or Info event
can be done by selecting panel address,
loop number and device address.
Supervisor and accessories
Product code Description
MHS-1001 Supervisor, graphic software for monitoring and managing of 1 panel
MHS-1004 Supervisor, graphic software for monitoring and managing of 4 panels
MHS-1008 Supervisor, graphic software for monitoring and managing of 8 panels
MHS-1016 Supervisor, graphic software for monitoring and managing of 16 panels
MHS-1032 Supervisor, graphic software for monitoring and managing of 32 panels
MHS-1064 Supervisor, graphic software for monitoring and managing of 64 panels
MHS-2100 USB Dongle
MHS-2200 Network alarm software for 10 users
MHS-2300 Network alarm software for 25 users
MHS-2400 Network alarm software for 50 users
MHS-2500 USB/RS-232 converter
MHS-2600 PC-panel extender kit for communication cable

www.mavigard.com 22
Protocol features Main capabilities
System works over VIP (Very Up to 64 panels/repeaters can be
Intelligent Communication protocol). assembled under network via RS-485
Entire address polling is accomplished communication protocol. Each loop
in 7.5 seconds regardsless of the number of has 127 address capacity. If 8 loop
devices connected to panel. In case the panels are used, 65024 occupied
HAREZMIC ANALOGUE analogue value exceeds the threshold level the addresses can run under the network.
polling interrupt features is activated and control Thus Harezmic series intelligent
ADDRESSABLE FIRE
panel checks several times the values that analogue addressable systems can be
ALARM CONTROL detector has just measured in 1.5 seconds. If used on large sites. MG-6400/MG6408
SYSTEM CAPABILITIES checked value is higher than the alarm threshold zone controller modules allow
value, the system switches to fire alarm integrating conventional zones to the
Harezmic provides reliable and user- condition and a fire event is generated. The system, extending the protection area.
friendly fire alarm control system for most same control mechanism is undergone for fault
complex sites, meeting all requirements
conditions. Loop polling process is protected
the protected area may have.
from interference by use of parity bit control.

MG-9300
Features Heat detector
MG-9100
64 control panels / repeater panels
Photo-electric
networking
smoke detector
Monitoring external devices and
systems AGD series
Controlling external devices and gas detector
systems

Full range of interface devices MG-7800 up to 8 loop fire alarm control panel
Integrating conventional zones

User-friendly software MG-8130


MG-8110
Manual
Programmable panel outputs Resettable MG-8120
call point
Device- and event-based cause-effects manual Weather-proof
with isolator MG-6600
call point manual
Integration with other security systems module, Loop-
Up to 64 fire Resettable call point, powered
Intelligent data processing alarm control / IP67 sounder
Polling data parity check repeater panels RS-485
in a network
Graphical system monitoring on PC

MG-7800 up to
8 loop fire alarm
control panel
Telephone
dialer

The printer is mounted


under the panel cabinet.
TCP/IP

RS-232 Alarm message to a


remote PC via TCP/IP
or network domain.
Internet Internet

PC
Loop Manager Supervisor
Files Maps Devices Links Log Settings Run

Loop Manager allows creating Graphical monitoring and control of


cause-effect algorithms for fire alarm control system network is
site automation. provided by specially developed
software, Supervisor.

23 www.mavigard.com
MG-6700 has single Peripheral systems An alarm signal from an
relay output with such as extingushant asprirating type smoke
volt-free contacts and control or ventilation detection system can be
max. load of 8A 250V AC. can be activated by use conveyed to the Harezmic
The relay is capable of of relay controllers fire alarm control system.
activating mains-rated included in cause-effect
otomation devices algortithms.
directly.

MG-6700 MG-6100
Mains relay Relay controller, MG-6108
MG-9400
controller, 1-way output Relay controller,
Multi-sensor
1-way output 8-way output MG-6208
Switch monitor,
8-way input

MG-6200 Switch monitor,


1-way input
MG-6308 Sounder controller,
8-way output
MG-6200 and MG-6208 can
MG-6300 monitor external devices to convey
Sounder controller, their operation as fire or fault
MG-6400 1-way output events.
MG-6408 Zone monitor,
MG-6500 Zone monitor, 1-way input
Short circuit 8-way input MG-6308 has 8 outputs,
isolator module
each having a max. load
of 500 mA 24V DC.

Sounder output (max. 500mA 24V DC)

A beam detector kit can


be integrated to loop
by use of a zone
monitor module.
Conventional zone (max. 500mA 24V DC)

Sounder output (max. 500mA 24V DC)

The MG-6300, The MG-8200


MG-6400, and Address programmer
MG-6408 require is used for ‘soft’
external power addressing the
supply. devices and reading
the analogue value of
fire detectors.

www.mavigard.com 24
OVERVIEW

SD64+ SERIES
CONVENTIONAL
FIRE ALARM CONTROL
PANEL AND TP64+ SD64+/082 Fire Alarm Control Panel SD64+/162 Fire Alarm Control Panel
SERIES CONVENTIONAL
REPEATER PANELS
Programmable and microprocessor-
controlled fire alarm control panels and
repeater panels. EN 54, SSPB (Russia) and
GOST R certified. Approved by Kazakhstan,
Oman, and UAE Civil Defence authorities.

Control panel features


8, 16, 32 or 64 zone capacity

Microprocessor-controlled

Compatible with all popular


conventional fire detectors

2 supervised sounder outputs SD64+/322 Fire Alarm Control Panel SD64+/642 Fire Alarm Control Panel

Fire and fault relay outputs


Control panels if required. Panels have an electronic charger
PCBs protected with metal case circuit limiting the ampere level, providing
Supported devices continuous monitoring of the charge level and
Protection from electromagnetic
interference A wide range of detectors and manual call points automatic cut facility, when charging is finished.
are supported by the equipment, ensuring that If the battery voltage falls under operating level,
Soft touch buttons the SD64+ series control panels can be used panel automatically switches off.
Zonal Fire and Fault LED indicators with existing installations without the need to
change field devices. For best performance, Networking
Button control key to prevent connecting MG-2000 series fire detectors and Up to 8 TP64+ conventional repeater panels
unauthorised access MG-5100 series manual call points is can be assembled into a network with a SD64+
recommended. series fire alarm control panel.
Piezzoelectric buzzer and 16 fault
indicators
Disable Mode Relay modules
Switched mode power supply Zones can be disabled. This may be required if A relay output can be assigned to every zone
there is work in progress in the building, which by installing an optional relay module.
Zone Test and Zone Disable functions
may cause faulty operation of the fire alarm
Delayable sounder output activation control system. Disable LED indicator on the Repeater panels
front panel illuminates when panel is on Disable
Repeater panels available Mode. Communication protocol
8 or 16 zone relay modules available TP64+ series repeater panels communicate with
Test Mode fire alarm control panels in network via RS-485
Communication with TP64+ and relay Test Mode allows the system to be tested single- communication protocol.
modules via RS-485 communication handed. On the Test Mode, fire alarm signal
protocol automatically resets after few seconds to Network cable length
eliminate the need for returning to the panel to If recommended standard cables are used,
reset the system. Test LED indicator illuminates network cable length between two panels can
Repeater panel features on the front panel during testing. be up to 500m.
Controlling fire alarm control panels
in a network Sounder delay Network capacity
A fixed delay of 2 minutes can be set for sounder Up to 8 repeater panels can be connected to a
EN 54-4 certified switched mode outputs. Delay Active LED indicator on the front single SD64+ series fire alarm control panel.
power supply panel illuminates when panel sounder outputs
Zonal Fire and Fault LED indicators are on the Delay Mode. Network panel control
Repeater panel buttons provide complete control
Network communication via RS-485 Controls and indicators of repeater as well as fire alarm control panels.
communication protocol Panel controls and LED indicators are kept to
Microprocesor-controlled
minimum to simplify user operation and to Conditions indication
maintain clarity of indication. Zonal Fire and Fault Row-organised LEDs on the front label indicate
Soft touch buttons indicators in rows are used on all SD64+ series fault and fire signals from fire alarm control
panel models. Panels also feature 16 fault panels and from other repeater panels in network.
Button control key to prevent
various LEDs.
unauthorised access
Both control panel and repeater panel menus
Indicator and buzzer test Power supply and serigraphies have versions in three languages:
Panels and TP64+ repeater panels are supplied Turkish, English and Russian.
with switched mode power supply and generous
battery space to give extended battery standby

25 www.mavigard.com
SPECIFICATIONS

Control panel features Repeater panel features

Zones : 8, 16, 32, or 64


Monitored zones : 8, 16, 32 or 64
Sounder outputs : 2 x ( 0.5 A 24 VDC), supevised, self-resetting Panel functions : Silence alarm, alarm, indicator and buzzer test, reset,
fuse protected replication of the status of the fire alarm system
Auxiliary power supply output : 0.5 A 24 VDC, self-resetting fuse protected Control buttons : Reset, Alarm, Silence Alarm, button control key
Fault relay : 1 A 30 VDC, volt free changeover, NO and NC Indicators : Fire, Communication Fault, Power Fault, Delay Active,
Sounder OC, Sounder SC, System On, Silence Alarm,
Fire relay : 1 A 30 VDC, volt free changeover, NO and NC System Fault, Battery Fault, Disable, Test, 24V DC Fault,
Earth Fault, Processor Fault, zonal Fire and Fault LEDs
Zone circuit end-of-line resistor : 6.8 kW
Mains power supply : 220 VAC 50 Hz, 5 A glass type fuse protected
Sounder circuit end-of-line resistor : 10 kW
Operating voltage : 24 VDC
Controls : Reset, Alarm, Silence Alarm, button control System fuse : 2.5 A (8 and 16 zone panels) or 4 A (32 and 64 zone
key panels), self-resetting
Indicators : Fire, Program Input, Power Fault, Delay Active, Batteries : 2 x ( 12 VDC 7 Ah )
Sounder OC, Sounder SC, System On, Silence
Alarm, System Fault, Battery Fault, Disable, Construction : 1.2 mm sheet steel
Test, 24 VDC Fault, Earth Fault, Processor Fault,
zonal Fire and Fault LEDs Finish : Epoxy powder coat

Networking : Up to 8 TP64+ series repeater panels Mounting : Surface

Mains power supply : 220 VAC 50 Hz, 5 A glass type fuse protected Colour : Two tone grey

Operating ambient
Operating voltage : 24 VDC temperature : (-10°C) – (+55°C)
System fuse : 2.5 A (8 and 16 zone panels) or 4 A (32 and Operating ambient
64 zone panels) self-resetting humidity : 0-95% (non-condensing)
Batteries : 2 x ( 12 VDC 7 Ah )

Construction : 1.2 mm sheet steel

Finish : Epoxy powder coat

Mounting : Surface

Standard colour : Two tone grey

Operating ambient temperature : (-10°C) – (+55°C)

Operating ambient humidity : 0-95% (non-condensing)


SD64+/162 internal view

Panel models
Product Zones Power Quiescent Weight* Size
Code supply current
SD64+/082 8 2.5 A 80 mA 6.5 kg 421 x 323 x 138 mm
SD64+/162 16 2.5 A 90 mA 6.65 kg 421 x 323 x 138 mm
SD64+/322 32 4A 150 mA 14.57 kg 500 x 598 x 140 mm
SD64+/642 64 4A 280 mA 16.33 kg 500 x 598 x 140 mm

*approx., without batteries

SD64+/642 internal view


Repeater panel models
Product Zones Power Weight* Size
Code supply
TP64+/083 8 2.5 A 5.5 kg 421 x 323 x 138 mm
TP64+/163 16 2.5 A 5.65 kg 421 x 323 x 138 mm
TP64+/323 32 4A 13.57 kg 500 x 598 x 140 mm
TP64+/643 64 4A 15.33 kg 500 x 598 x 140 mm

*approx., without batteries


TP64+ Series Conventional Repeater Panels

Relay module models


Relay modules Specifications
Product Description
Code
Operating voltage : 24 VDC
Y42030.40 8-way relay output module for SD64+ series panels
Relay output : 1 A 30 VDC, volt free changeover, NO and NC
Y42031.40 16-way relay output module for SD64+ series panels
Communication protocol : RS-485
Max. cable length : 500 m, provided suitable cable is used
Size : 102 x 82 mm
Operating ambient temperature : (-10°C) – (+55°C)
Operating ambient humidity : 0-95% (non-condensing) Y42030.40 Y42031.40

www.mavigard.com 26
OVERVIEW

MG-8 SERIES
CONVENTIONAL
FIRE ALARM
CONTROL PANELS
Stylish exterior design and programmability
make the MG-8 series a top-level panel
among conventional panels for small sites.
SSPB (Russia) and GOST R certified.
Approved by Kazakhstan and Oman Civil
Defence authorities.

Highligts
MG-8 Fire Alarm Control Panel
2, 4 or 8 zone models

Configurable latching/non-latching
zones

Configurable detection of short circuit


as fire alarm

Delayable zone fire alarm Panel capacity 24 V power supply output for energising
Each zone of the MG-8 series panel can external devices, such as telephone dialers
Distinguished detector/MCP alarm
host 160 fire detectors and unlimited or gas detectors.
detection
number of manual call points, thus allowing
2 x 16 character LCD with adjustable the system to have a protection area The LCD and menu
backlight consisting of 160 fire detectors. The zones 2 x 16 character LCD with backlight and
Remote control are monitored for open and short circuits, LED indicators for faults and system
indicated on front panel. The panels support conditions allow comprehensive
Delayable sounder output activation
all standard conventional fire detectors. presentation of information on operating
Password-protected access levels For best performance, MaviGard MG-2000 of the system. Each zone has separate
Zone Test and Zone Disable modes
series fire detectors are recommended. LED indicators for Fire and Fault, which
facilitates locating alarm area.
Zonal Fire and Fault LED indicators Zone programmability
Zone location text on front panel Zones are latching by default. Zones can Advanced menu and navigation buttons
be set to non-latching, which enables make programming of the panel an easy
automatic reset after fire alarm condition task. Menu levels are password-protected
Features ends. Zonal fire alarm indication can be to prevent unauthorised access to the
Microprocessor-controlled delayed by 30sec. Panels can distinguish settings of the panel.
detector/manual call point alarm. Zones
PCBs made by use of Surface Mount
can be set to detect short circuits as fire Panel menu and front panel have versions
Technology
alarms. Zones can be set to Disable and in three languages: Turkish, English and
2 programmable and supervised Test modes. On the Test Mode, manually Russian.
sounder outputs initiated fire alarm is reset automatically
3 relay outputs after a few seconds; this allows testing Power supply
zones by one person without need for Panel power supply is under continuous
Compatible with all popular
conventional fire detectors
returning to the panel for reset. monitoring. Batteries are charged
automatically and charging is cut off when
Protection against electromagnetic Panel output programmability necessary level is reached. Power supply
interference Panels are equipped with 2 supervised and faults are displayed by related LEDs.
Optional repeater panels programmable sounder outputs, which can
be disabled or set to delay for up to 10min. Networking and relay modules
Optional relay modules
Connecting MG-5000 series sounders and Optional repeater panels allow full
Auxiliary power supply output bells to the outputs is recommended for replication of system information and
LED test by use of single button
best performance. Each output can host control by integrating addional network
16 MG-5000 Sounders, 8 MG-5200 card . By use of optional relay modules, a
Soft-touch buttons Sounder Strobes or 20 MG-5400 Fire Alarm relay output can be assigned to each
Built-in silenceable buzzer Bells. zone.

Alarm, Fire and Fault relays enable wide Remote control


applicability for remote control and signaling User can put the system into Fire Alarm or
on various system conditions. System Fault conditions as well as silence
alarm and reset the panel by use of remote
The panels are equipped with an auxiliary control inputs.

27 www.mavigard.com
SPECIFICATIONS

Alarm relay:
Networking: 1 A 30 VDC, volt-free change over
Repeater panels and relay modules
Fire relay:
Remote controls: 1 A 30 VDC, volt-free change over
Silence Alarm
Sound Alarm Fault relay: Zones:
Day/Night 1 A 30 VDC, volt-free change over Up to 8 inputs, 24 VDC,
Reset supervised, end-of-line resistor
Fault Sounder outputs: 6.8 kW, connecting MG-2000
2 x ( 0.5 A 24 VDC ), supervised, self-resetting series fire detectors and
Auxiliary power supply output: fuse protected, delay 10min max., end-of-line MG-5100 series MCPs is
0.5 A 24 VDC, self-reseting fuse protected resistor 10 kW recommended

Controls System status and fault LEDs Zone location text

LCD 2 x 16 characters, Zonal Fire and Fault LEDs


with adjustable backlight Menu item examples

Mains power supply : 220 VAC 50 Hz, 2 A glass type fuse protected

Operating voltage : 24 VDC


Zone 1 Test
Batteries : 2 x (12 VDC 7 Ah)

Construction : Panel cabinet 1.2 mm sheet steel, front panel: 1.5 mm sheet
Function On
steel, plastic cover Setting a zone to the Test Mode

Finish : Epoxy powder coat

Mounting : Surface Z1 Input Delay


Standard colour : Panel cabinet: grey, front panel and cover: white Function Off
Operating ambient Setting delay to zone alarm
temperature : (-10°C) - (+55°C)
Operating ambient humidity : 0-95% (non-condensing) Sounder Disable
Size : 400 x 300 x 100 mm Function On
Weight : 5.5 kg (approx., without batteries)
Disabling sounder outputs

Panel models
Product
Code Zones
MG-802 2
MG-804 4
MG-808 8

Additional Equipment
Product
Code Descripton
MG-SR Network card for communicating with MGRP-64 repeater panel.

www.mavigard.com 28
OVERVIEW

MP-8 SERIES
CONVENTIONAL FIRE
ALARM CONTROL PANELS

Economical solution for small sites, where


simple and reliable fire alarm system is
required.SSPB (Russia) and GOST R
certified. Approved by Kazakhstan and
Oman Civil Defence authorities.

Highlights
2, 4 or 8 zone models

Zonal Fire and Fault LED indicators

Button control key MP-8 Fire Alarm Control Panel

Zone Test and Zone Disable modes

Zone location text on front panel

Features
Panel capacity Panels have an auxiliary 24 V power supply
Soft-touch buttons Each zone can host max. 20 fire detectors output for energising external devices, such
Microprocessor-controlled
and unlimited number of manual call points, as telephone dialers or gas detectors.
thus allowing the system to have a
PCBs made by use of Surface Mount protection area consisting of max. 160 (in Conditions indication
Technology
8 zone models) fire detectors. The zones Zonal Fire and Faults are displayed by
1 supervised sounder output are monitored for open and short circuits, separate LEDs located on the front panel.
2 relay outputs indicated on the front panel. The panel
Compatible with all popular
supports all standard conventional fire Controls
conventional fire detectors detectors. For best performance, MaviGard Panels have 4 buttons, including Lamp Test,
MG-2000 series fire detectors are which allows single-push testing of all LEDs
Protection against electromagnetic
interference recommended. on the front panel. Button Control Key
prevents unauthorised control of the panel.
Optional repeater panels
Zone programmability
Optional relay modules Zones can be set to Disable and Test Panel menu and front panel have versions
Auxiliary power supply output Modes. On the Test Mode, manually in three languages: Turkish, English and
initiated fire alarm is reset automatically Russian.
LED test by use of single button
after a few seconds; this allows testing
Built-in silenceable buzzer zones by one person without need for Power supply
returning to the panel for reset. Panel power supply is under continuous
monitoring. Batteries are charged
Panel outputs automatically and charging is cut off when
Panels are equipped with 1 supervised necessary level is reached. Power supply
sounder output. Connecting MG-5000 faults are displayed by related LEDs on
series sounders and bells to the output is front panel.
recommended for best performance. The
output can host 16 MG-5000 Sounders, 8 Networking
MG-5200 Sounder Strobes or 20 MG-5400 Optional repeater panels allow full
Fire Alarm Bells. replication of system information and
control. By use of optional relay modules,
Fire and Fault relays enable wide applicability a relay output can be assigned to each
for remote control and signaling on various zone.
system conditions.

29 www.mavigard.com
SPECIFICATIONS

Auxiliary power supply output:


0.5 A 24 VDC, self-reseting fuse
protected

Sounder output:
0.5 A 24 VDC, supervised, self-
resetting fuse protected, end-of-line
resistor 10 kW
Fire relay: Zones:
1 A 30 VDC, volt free change over up to 8 inputs, 24 VDC, supervised, end-of-line
resistor 6.8 kW, connecting MG-2000 series fire
Fault relay: detectors and MG-5100 series MCPs is
1 A 30 VDC, volt free change over recommended

Controls System status and fault LEDs Zone location text


Zonal Fire and Fault LEDs

Mains power supply : 220 VAC 50 Hz, 2 A glass type fuse protected

Operating voltage : 24 VDC

Power supply : 1.5A


Batteries : 2 x (12V DC 7Ah)

Construction : Panel cabinet: 1.2mm sheet steel, front panel: 1.5mm sheet
steel, plastic cover

Finish : Epoxy powder coat

Mounting : Surface

Standard colour : Panel cabinet: grey, front panel and cover: white

Operating ambient
temperature : (-10°C) - (+55°C)
Panel models
Operating ambient humidity : 0-95% (non-condensing)
Product
Code Zones Size : 400 x 300 x 100 mm
MP-82 2 Weight : 3.8 kg (approx., without batteries)
MP-84 4

MP-88 8

Additional Equipment
Product
Code Descripton
MG-SR Network card for communicating with MGRP-64 repeater panel.

www.mavigard.com 30
OVERVIEW

MS-64 SERIES
CONVENTIONAL
FIRE ALARM
CONTROL PANEL
Economical solution for medium and large
sites, where simple and reliable fire alarm
system is required. SSPB (Russia) and GOST
R certified. Approved by Kazakhstan and
Oman Civil Defence authorities.

Highlights
8, 16, 32 or 64 zone models

Sounder test

2-digit display MS-64 Fire Alarm Control Panel

Button control key

Zone Test and Zone Disable Modes


Panel capacity Conditions indication
Each zone of the panel can host 20 fire Zonal indications are exhibited by 2-digit
Features
detectors and unlimited number of manual display, which shows zone numbers, where
Microprocessor-controlled
call points, thus allowing the system to fire and faults have been detected in
PCBs made by use of Surface Mount have a protection area consisting of max. sequence of their reception by the panel,
Technology 1280 fire detectors (in 64 zone models). and type of condition.
2 supervised sounder outputs The panels support all standard
2 relay outputs conventional fire detectors. For best Controls
performance, MaviGard MG-2000 series Panels have 6 buttons, including Lamp Test
Compatible with all popular
conventional fire detectors
fire detectors are recommended. The zones and Sounder Test, which allow single-push
are monitored for open and short circuits, testing of all LEDs on the front panel and
Optional repeater panels
indicated on the front panel. sounder outputs respectively. Button
Optional relay modules Control Key prevents unauthorised control
Auxiliary power supply output Zone programmability of the panel.
Zones can be set to Disable and Test
Display and LED test by use of single
button
modes. On the Test Mode, manually Panel menu and front panel have versions
initiated fire alarm is reset automatically in three languages: Turkish, English and
Soft-touch buttons
after a few seconds; this allows testing Russian.
Built-in silenceable buzzer zones by one person without need for
returning to the panel for reset. Power supply
Panel power supply is under continuous
Panel outputs monitoring. Batteries are charged
Panels are equipped with 2 supervised automatically and charging is cut off when
sounder outputs. Connecting MG-5000 necessary level is reached. Power supply
series sounders and bells to the outputs is faults are displayed by related LEDs on
recommended for best performance. Each front panel.
output can host 16 MG-5000 Sounders, 8
MG-5200 Sounder Strobes or 20 MG-5400 Networking
Fire Alarm Bells. Optional repeater panels allow full
replication of system information and
Fire and Fault relays enable wide applicability control.
for remote control and signaling on various
system conditions. Relay modules
By use of optional relay modules, a relay
Panels have an auxiliary 24 V power supply output can be assigned to each zone.
output for energising external devices, such
as telephone dialers or gas detectors.

31 www.mavigard.com
SPECIFICATIONS

Auxiliary power supply output:


0.5 A 24 VDC, self-reseting fuse protected
Sounder outputs:
2 x ( 0.5 A 24 VDC ), supervised, self-resetting
fuse protected, end-of-line resistor 10 kW

Fire relay: Zones:


1 A 30 VDC, volt-free change over up to 64 inputs, 24 VDC, supervised, end-of-
line resistor 6.8 kW, connecting MG-2000 series
Fault relay: fire detectors and MG-5100 series MCPs is
1 A 30 VDC, volt-free change over recommended

System Status and fault LEDs Controls Zone location text

2-digit display

Mains power supply : 220 VAC 50 Hz, 2 A glass type fuse protected

Operating voltage : 24 VDC


Mains power supply fuse : 2 A

Batteries : 2 x ( 12 VDC 7 Ah)

Construction : Panel cabinet: 1.2mm sheet steel, front panel: 1.5mm sheet
steel, plastic cover

Finish : Epoxy powder coat


Mounting : Surface
Standard colour : Panel cabinet: grey, front panel and cover: white

Panel models Operating ambient


temperature : (-10°C) - (+55°C)
Product
Code Zones Weight* Operating ambient
humidity : 0-95% (non-condensing)
MS-6408 8 4.5 kg
MS-6416 16 4.6 kg Size : 400 x 300 x 100 mm
MS-6432 32 4.7 kg
MS-6464 64 4.8 kg

*approx., without batteries

Additional Equipment
Product
Code Descripton
MG-SR Network card for communicating with MGRP-64 repeater panel.

www.mavigard.com 32
OVERVIEW

MGRP-64 CONVENTIONAL
COMMON REPEATER
PANEL
Using at least one MGRP-64 repeater panel
enables to configure up to 32 fire alarm
control panels and/or repeater panels in
large site conventional fire alarm
applications. MGRP-64 series repeater
panels has a stylish exterior appearance
and produced by using surface mount
technology. SSPB (Russia) and GOST R
certified.

Features
High and stable operation performance
64 repeater zone capacity
MGRP-64 Repeater Panel
24 VDC operation voltage
PCB produced using Surface Mount
Technology
Stylish exterior design
Microprocessor-controlled design
Compatibility is automatically detected and included in
Compatible with MP-8, MS-64, and network structure.
MG-8 model conventional fire alarm MGRP-64 series conventional repeater
control panels panels can work with MP-8, MS-64, and If any control panel is removed from the
By using at least one MGRP-64, a large MG-8 conventional fire alarm control network, repeater panel displays
network system can be formed which panels. It replicates fire alarm control “Disconnected Panel” fault.
has 32 conventional fire alarm control
panels and/or repeater panels. panels’ events and enables controlling all
panels in the network. Conditions indication
Polling entire network in every 0.5
seconds Communication protocol LCD (2 x 16 character) and LEDs in front
of the repeater panel enable easy
RS-485 communication protocol MGRP-64 repeater panels communicate representation of the details of fire and
Network cable length up to 1200 with fire alarm control panels in network fault alarm status from other fire alarm
metres via RS-485 communication protocol. control panels in the network.
Automatic detection and inclusion of Network Power supply
new panels into network
Automatic detection and exclusion of Using at least one MGRP-64 repeater panel, Panel power supply is under continuous
removed panels from network 32 conventional fire alarm control panels/ monitoring. Batteries are charged
Storage of latest 50 events in the
repeater panels can be assembled in one automatically and charging is cut off when
memory. system. necessary level is reached. Power supply
Display priority to fire events Fire alarm control panels require MG-SR faults are displayed by related LEDs.
Detailed information on fire and fault network card to communicate with each
events from each control panel on other in the network. Panel functions
repeater LCD
Provided “Ftp Cat6” network cable is used, Using MGRP-64 repeater panel, all fire
Single-button test of LEDs and LCD network cable length can be up to 1200 alarm control panels can be reset, put to
Button enable/disable key to prevent m. alarm and silenced alarm condition by use
unauthorised access of the repeater panel buttons.
All fire alarm control panels in network are
polled by repeater panel every 0.5 seconds. Repeater panel keeps latest 50 events in
All events in fire alarm control panel are its memory. Fire condition has a priority to
kept in network card till next polling. If the other events when displayed on panel LCD.
predetermined respond time exceeds,
repeater panel shows fault status. LCD and all LEDs can be tested by pressing
single button.
A control panel newly added to the network

33 www.mavigard.com
SPECIFICATIONS

Conventional sounder line

Conventional zone line

Conventional sounder line

Conventional zone line

Conventional sounder line

Conventional zone line

RS-232 port:
PC connection for
configuring MGRP-64.
Shows the devices and
panels in the network.
Allows assigning 16
character vacation text to
panels and zones.

MS-64, Node 1 MP-8, Node 2 MG-8, Node 32

Network Cable; Ftp Cat6 up to 1200 m distance.

Networking:
Auxiliary power supply Max. 32 alarm
output control/repeater panels
500 mA 24 VDC, self- Fire relay: MG-RP

resetting fuse protected 1 A 30 VDC, volt free


change over
Sounder output:
500 mA 24 VDC, self- Fault relay:
resetting fuse protected, 1 A 30 VDC, volt free
supervised, end-of-line change over
resistor 10 kW RS-232

Controls System status LEDs 2 x 16 characters LCD with Location text


adjustable backlight

Mains power supply : 220 VAC 50 Hz


Menu item examples
Operating voltage : 24 VDC

Mains fuse : 2 A

Battery : 2 x ( 12 VDC 7 Ah )
Mavili Elektronik SC p4 z5
Construction : Panel cabinet: 1.2 mm metal sheet,
front panel: 1.5 mm metal sheet 0216 466 45 05 Production dept
Finish : Epoxy powder coat Quiescent condition Ground floor
Mounting : Surface Short circuit on zone 5 (Location
text: Ground floor) of Panel 4 (Panel
Standard colour : Grey metal cabinet, white front
panel and cover
FIRE p8 z3 name: Production dept).

Headquarters
Operating ambient temperature : (-10°C) - (+55°C)
Sound flt p9 s1
Operating ambient humidity : 0-95% (non-condensing) Floor 3
Fire alarm on zone 3 (Location text:
Office A
Size : 400 x 300 x 100 mm Floor 3) of Panel 8 (Panel name:
Headquarters). The location text Sounder 1 fault of Panel 9 (Panel
Weight : 3.97 kg (approx., without batteries) and panel name are editable on PC. name: Office A).

www.mavigard.com 34
OVERVIEW

Superior design and excellent functional features of the MaviGard detectors are the result
of the Research & Development work done using latest technological achievements in the
fire alarm industry. Detectors are produced with Surface Mount Technology (SMT). Detector
PCB is protected against electromagnetic interference and corrosion by minimizing contact
with external medium. MG series detectors are compatible with all fire alarm control panels,
MGR series detectors are compatible with all security alarm control panels. All detectors are
provided with blue plastic cover, which protects detector from dust, dirt etc. during construction
and paint. Detectors are produced in white as standard but, according to customer's choice,
MG/MGR-2000 SERIES various colours are available. Detectors can be provided with magnet-testing feature on
CONVENTIONAL customer's demand.
FIRE DETECTORS
Designed and produced according to EN
54 by use of Surface Mount Technology
STANDARD AND RELAY OUTPUT MODELS
providing stable sensitivity. EN 54, EMC-
CE and SSPB (Russia) and GOST R certified.
Approved by Kazakhstan, Oman, UAE and
MG-2100 Photo-Electric Smoke Detector
Bahrain Civil Defence authorities.. MGR-2100 Photo-Electric Smoke Detector with Relay Output
MG-2100 MGR-2100
Operating voltage 10-30V DC 12V DC
Quiescent current (max.) 100µA 100µA
Alarm current (max.) 30mA 50mA
Remote indicator output 100mA 100mA
Features Operating ambient temperature (-10ºC)-(+50ºC) (-10ºC)-(+50ºC)
Stable sensitivity Size (incl. base) Ø: 100mm, h: 50mm Ø: 100mm, h: 50mm

Microprocessor-controlled Weight (approx.) 148g 135g


Relay Output Condition - Normally close*
MGR models with relay output
Relay Output Rating - 0.5A 220V AC
Twin fire alarm indicators for 360° 2A 24V DC
viewing * NO option for special orders

PCB protected by metal case Photo-electric smoke detector utilises the light scatter sensing principle. It has an infrared
Protection from electromagnetic light source which emits signals and a photo-diode which senses the scattering light with
interference the effect of smoke entering the chamber. The chamber is protected from dust, insects and
Clamps terminals to ensure firm
other external interferences. The detectors are EN 54-7 and EMC Directive 89/336/EEC
contact with the base certified.
MG-3500 Universal Mounting Base
compatible MG-2200 Ionisation Smoke Detector
MG-3600 Recessed Mounting Base MGR-2200 Ionisation Smoke Detector with Relay Output
compatible
MG-2200 MGR-2200
Remote indicator output Operating voltage 12V DC
10-30V DC
In MGR series normally close relay Quiescent current (max.) 30µA 30µA
output as standard (normally open
Alarm current (max.) 30mA 50mA
also available)
Remote indicator output 100mA 100mA
Operating ambient temperature (-10ºC)-(+50ºC) (-10ºC)-(+50ºC)
Size (incl. base) Ø: 100mm, h: 50mm Ø: 100mm, h: 50mm
Weight (approx.) 143g 130g
Relay Output Condition - Normally close*
Relay Output Rating - 0.5A 220V AC
2A 24V DC
* NO option for special orders

Ionisation smoke detector has twin room ionisation chamber to prevent the interference of
excessive humidity and heat. One of the rooms functions as a reference and the other as
the sampling one. The chamber is protected from dust, insects and other external interferences.
The detectors are EN 54-7 and EMC Directive 89/336/EEC certified.

MaviGard conventional and analogue


addressable detectors are produced
in white as standard and coloured on
demand: red, dark blue, black, green,
brown, pink, orange, yellow, metallic
silver and metallic gold.

35 www.mavigard.com
OVERVIEW

STANDARD AND RELAY OUTPUT MODELS


MG-2300 Rate of Rise Heat Detector
MGR-2300 Rate of Rise Heat Detector with Relay Output
MG-2300 MGR-2300
Operating voltage 10-30V DC 12V DC
Quiescent current (max.) 30µA 30µA
Alarm current (max.) 30mA 50mA
Remote indicator output 100mA 100mA
Operating ambient temperature (-10ºC)-(+50ºC) (-10ºC)-(+50ºC)
Size (incl. base) Ø: 100mm, h: 50mm Ø: 100mm, h: 50mm
Weight (approx.) 123g 110g
Relay Output Condition - Normally close*
Relay Output Rating - 0.5A 220V AC
2A 24V DC
* NO option for special orders

Rate of rise heat detector detects temperature change by two temperature-sensitive thermistors. The detector can function either
as a fixed heat or rate of rise heat detector. Fire alarm signal is generated in case of 300C /min or higher heat rise and/or on reaching
the threshold of 600C. The design of the chamber provides sensitive ambient temperature measuring. Design of the detector
provides fast response to heat rise. The detectors are EN 54-5 and EMC Directive 89/336/EEC certified.

MG-2400 Fixed Heat Detector


MGR-2400 Fixed Heat Detector with Relay Output
MG-2400 MGR-2400
Operating voltage 10-30V DC 12V DC
Quiescent current (max.) 30µA 30µA
Alarm current (max.) 30mA 50mA
Remote indicator output 100mA 100mA
Operating ambient temperature (-10ºC)-(+50ºC) (-10ºC)-(+50ºC)
Size (incl. base) Ø: 100mm, h: 50mm Ø: 100mm, h: 50mm
Weight (approx.) 123g 110g
Relay Output Condition - Normally close*
Relay Output Rating - 0.5A 220V AC
2A 24V DC
* NO option for special orders

Fixed heat detector detects temperature change by one temperature-sensitive thermistor. The fire alarm signal is generated on
reaching the threshold of 600C. The design of the chamber provides sensitive ambient temperature measuring. Design of the
detector provides fast response to heat rise. The detectors are EN 54-5 and EMC Directive 89/336/EEC certified.

MG-2500 Multi-sensor (Photo-Electric Smoke + Heat Detector)


MGR-2500 Multi-sensor (Photo-Electric Smoke + Heat Detector) with Relay Output
MG-2500 MGR-2500
Operating voltage 10-30V DC 12V DC
Quiescent current (max.) 130µA 130µA
Alarm current (max.) 30mA 50mA
Remote indicator output 100mA 100mA
Operating ambient temperature (-10ºC)-(+50ºC) (-10ºC)-(+50ºC)
Size (incl. base) Ø: 100mm, h: 55mm Ø: 100mm, h: 55mm
Weight (approx.) 143g 175g
Relay Output Condition - Normally close*
Relay Output Rating - 0.5A 220V AC
2A 24V DC
* NO option for special orders

Multi-sensor series fire detector has features of both photo-electric smoke and fixed heat detector. It has an infrared light source
which emits signals and a photo-diode which senses the scattering light with the effect of smoke entering the chamber. The chamber
is protected from dust, insects and other external interferences. The detector measures the temperature change by one thermistor.
Design of the detector provides fast response to smoke and heat rise. Detectors are EN 54-5, EN 54-7 and EMC Directive 89/336/EEC
certified.

www.mavigard.com 36
OVERVIEW

MG-104 SERIES
CONVENTIONAL
EXTINGUISHANT
CONTROL PANEL
MG-104 Series operates on cross-zone
principle, has 4 detection zones and one
extinguishant release output which
can be programmed according to site
needs. SSPB (Russia) and GOST R certified.
Approved by Kazakhstan and Oman Civil
Defence authorities.

Highlights
4 zones, 1 extinguishant release output MG-104 Extinguishant Control Panel

Configurable latching/non-latching
zones Zone functions ends for gas extraction.
The 1st and 2nd zones are used for The panel has an auxiliary 24 V power
Configurable detection of short circuit extinguishant output control based on supply output for energising external
as fire alarm
cross-zone principle. The 3rd and 4th zones devices, such as telephone dialers or gas
Distinguished detector/MCP alarm are for fire alarm control only. Each zone detectors.
detection can host max. 20 fire detectors and
Programmable 1st Stage sounder unlimited number of manual call points. Conditions indication and menu
output delay Connecting MG-2000 series fire detectors 2 x 16 character LCD with adjustable
and MG-5100 series manual call points is backlight facilitates monitoring the operating
Programmable extinguishant release
duration
recommended for best performance. of the system and configuring system
settings. The LCD features extinguishant
Extinguishant release countdown timer Extinguishant feature release countdown timer after the 2nd
Manual and Automatic/Manual The panel can be set to Manual or Stage alarm. Extinguishant-related front
extinguishant modes Automatic/Manual extinguishant modes. panel LEDs provide full information on
Extinguishant status can be controlled by extinguishant control status.
1st and 2nd Stage relay outputs supervised Extinguishant Release,
Solenoid valve and actuator compatible Extinguishant Abort and Extinguishant Mode Panel menu and navigation buttons make
remote buttons. The Extinguishant Release programming of the panel an easy task.
Remote control
output can control valves and actuators. Menu levels are password-protected to
6 programmable relay outputs Extinguishant release duration is prevent unauthorised access to the settings
configurable. Extinguishant gas status is of the panel.
Features monitored by supervised Low Pressure and
Gas Release inputs. Power supply
Soft-touch buttons Panel power supply is under continuous
Microprocessor-controlled
Zone programmability monitoring. Batteries are charged
Zones are latching by default. Zones can automatically and charging is cut off when
PCBs made by use of Surface Mount be set to non-latching, which enables necessary level is reached. Power supply
Technology automatic reset after fire alarm condition faults are displayed by related LEDs.
3 programmable and supervised disappears. Zonal fire alarm indication can
sounder outputs be delayed by 30 sec. Zones can also be Networking
Compatible with all popular
set to detect short circuits as fire alarms. Optional repeater panels allow full
conventional fire detectors Panels can distinguish detector/manual call replication of system information and
point alarm. Zones can be set to Disable control. By use of optional relay modules,
Protection against electromagnetic and Test modes. On the Test Mode, a relay output can be assigned to each
interference
manually initiated fire alarm is reset zone.
Optional repeater panels automatically after a few seconds.
Remote control
Optional relay modules
Output programmability User can put the system into Fire Alarm or
Auxiliary power supply output The panel has 3 programmable and System Fault conditions as well as silence
Display and LED test by use of single
supervised sounder outputs, one of which alarm and reset the panel by use remote
button is activated on the 2nd Stage fire alarm. control inputs. Sounder outputs, 1st and
Each output can be disabled and set to 2nd Stage relays, Extinguishant Release
Built-in silencable buzzer delay. The panel is equipped with 6 relays: output and Extinguishant Release button
3 standard (Alarm, Fire and Fault), 2 related can be disabled.
to extinguishant control: 1st Stage and 2nd
Stage, which can be disabled. The 6th relay
activates fan after extinguishant process

37 www.mavigard.com
SPECIFICATIONS

1st stage relay:


Low pressure monitor: 1 A 30 VDC, volt free
end-of-line resistor 6.8 kW changeover
Supervised remote
Networking: controls: Exting. release monitor: 2nd stage relay:
repeater panels and relay Exting. hold end-of-line resistor 6.8 kW 1 A 30 VDC, volt free
modules Exting. manual release 1st stage sounder outputs: changeover
Auxiliary power supply Exting. mode Gas extraction relay: 2 x ( 0.5 A 24 VDC ), Fault relay:
output: 1A 30V DC, volt-free supervised, self-resetting 1 A 30 VDC, volt free
0.5 A 24 VDC, self- Zones 1 and 2: changeover fuse protected, end-of-line change over
resetting fuse protected trigger exting. control output resistor 10 kW
on cross-zone principle, 24 Alarm relay:
Exting. control output: 1 A 30 VDC, volt free
Remote controls: VDC, supervised, end-of- 0.5 A 24 VDC, self-resetting 2nd stage sounder output:
Silence Alarm line resistor 6.8 kW 0.5 A 24 VDC, supervised, change over
fuse protected, end-of-line Fire relay:
Sound Alarm element 1N 4001 diode self-resetting fuse protected,
Fault Zones 3 and 4: end-of-line resistor 10 kW 1 A 30 VDC, volt free
Reset fire detection only change over

Extinguishant mode control key

System status and fault LEDs Extinguishant-related LEDs


Controls Zone location text
LCD, 2 x 16 characters, Zonal Fire and Fault LEDs
with adjustable backlight
MG-5300 Extinguishant Abort MG-5310 Extinguishant
Extinguishant
Button (latching) Release process can be
Menu item examples Button manually started
or held/aborted

Zone 1 Disable

Mains power supply : 220 VAC 50 Hz, 2 A glass type


Function On
Cross-zone
fuse protected Setting zone to the Disable Mode EXTINGUISHANT AREA principle has
been applied in
extinguishant
Access Level 3
MG-2100 Photo-
Operating voltage : 24 VDC Electric Smoke
areas
MG-2300 Rate

Detector
of Rise Heat

Batteries : 2 x ( 12 VDC 7 Ah )
Detector

Extinguishant
Construction : Panel cabinet: 1.2 mm sheet Enter Password system

steel, front panel:1.5 mm sheet Entering Access Level 3


steel, plastic cover 2x0.8+0.8 JY(st)Y

Finish : Epoxy powder coat Exting. Delay


MG-2100 Photo-

Mounting : Surface
27
Electric Smoke

MG-2300 Rate
Detector

of Rise Heat
Detector

Standard colour : Panel cabinet: grey, front panel


and cover: white Extinguishant release countdown
Operating
ambient temperature : (-10ºC) – (+55ºC)
2x0.8+0.8 JY(st)Y
Remote
Operating Dialer controls
MG-2300 Rate of MG-2100 Photo-electric MG-2500 Multisensor
ambient humidity : 0-95% (non-condensing) Rise Heat Detector Smoke Detector

Size : 400 x 300 x 100 mm


Weight : 5.3 kg (approx., without
batteries)
2x0.8+0.8 JY(st)Y

MG-5120
Manual Call Point
2x1.5 NYM/NYY (Resettable)

Extinguishant output

Remote Control Buttons 1st Stage MG-5000


Sounder Output Electronic
Product sounder MG-5200
Sounder
Code Description strobe
2 x 1.5 NYM/NYY
MG-5300 Extinguishant Abort Button Unit (latching)
2nd Stage MG-5400
Sounder Output Fire Alarm Bell
MG-5310 Extinguishant Release Button Unit System diagram

www.mavigard.com 38
OVERVIEW

MARINE APPROVED
FIRE ALARM
CONTROL SYSTEMS
All marine products are Lloyd certified.
They can be used in all sea vehicles.

MaviGard Marine series analogue addressable fire alarm systems have been tested
according to SOLAS 74 and FSS (Fire Safety System) for compliance with marine
Conventional System Features conditions. The marine systems are TURK LOYDU certified.
8, 16, 32 or 64 zone capacity

Microprocessor-controlled

Protection from electromagnetic


interference

Stable sensitivity of detectors

Twin fire alarm indicators for 360°


viewing

2 sounder outputs, 1 fire relay, 1 fault


relay

Microprocessor-controlled switched
mode power supply

Clamp terminals on detector bases to


ensure firm contact
MaviGard Marine series conventional fire alarm systems have been tested according
to SOLAS 74 and FSS (Fire Safety System) for compliance with marine conditions.
Analogue Addressable The marine systems are TURK LOYDU certified.
System Features
1, 2, 4 or 8 loops.

Up to 1016 x 32 address capacity. All MaviGard Marine series products


have been designed and produced to
Up to 64 programmable zones.
provide corrosion-proof feature.
Microprocessor controlled design.

1000 event log memory.

Programmable and supervised sounder


outputs.

Analogue value display measured by


detectors.

PCBs are protected by metal case.

Protection from electromagnetic


interference

Communication interrupt for fast fire


alarm identification in 1.5 sec.
MG-3700/M Marine Back Box
Loop polling in 7.5 seconds.

LCD with backlight. Specially designed for marine applications, marine


Cause-effect programming.
back box is used at media with harsh weather
conditions. Marine back box is surface-mounted.
The box is compatible with all MaviGard Marine
conventional and analogue addressable fire
detectors.

39 www.mavigard.com
SPECIFICATIONS

Marine Conventional Marine Addressable


Fire Alarm Control System Fire Alarm Control System

SD64+ series fire alarm control panels & Repeaters Harezmic Series Fire Alarm Control Panels & Repeaters
Product code Description Product code Description

SD64+/082/M FACP, 8 Zones, 24 VDC MG-7100/M FACP, 1 loop, 127 Addresses

SD64+/162/M FACP,16 Zones, 24 VDC MG-7200/M FACP, 2 Loops, 254 Addresses

SD64+/322/M FACP, 32 Zones, 24 VDC MG-7400/M FACP, 4 Loops, 508 Addresses

SD64+/642/M FACP, 64 Zones, 24 VDC MG-7800/M FACP, 8 Loops, 1016 Addresses

TP64+/083/M Repeater Panel, 8 Zones, 24 VDC MG-7000/M Repeater Panel

TP64+/163/M Repeater Panel, 16 Zones, 24 VDC


Repeater Panel, 32 Zones, 24 VDC
Harezmic Series Analogue Addressable Fire Detectors
TP64+/323/M
Product code Description
TP64+/643/M Repeater Panel, 64 Zones, 24 VDC
MG-9100/M Photo-Electric Smoke Detector

MG-2000 Series Fire Detectors MG-9200/M Ionisation Smoke Detector

Product code Description MG-9300/M Heat Detector

Photo-Electric Smoke Detector MG-9400/M Multi-sensor


MG-2100/M

MG-2200/M Ionisation Smoke Detector


Harezmic series interface modules
MG-2300/M Rate of Rise Heat Detector
Product code Description
MG-2400/M Fixed Heat Detector
MG-6100/M Relay Controller
MG-2500/M Multi-sensor (Smoke+Heat)
MG-6200/M Switch Monitor
MGR-2100/M Photo-Electric Smoke Detector with Relay Output
MG-6300/M Sounder Controller
MGR-2200/M Ionisation Smoke Detector with Relay Output
MG-6400/M Zone Monitor
MGR-2300/M Rate of Rise Heat Detector with Relay Output
MG-6700/M Mains Relay Controller, 250V AC, 8A
MGR-2400/M Fixed Heat Detector with Relay Output

Multi-sensor (Smoke+Heat) with Relay Output


MGR-2500/M Harezmic series accessories
Product code Description
Conventional Manual Call Point MG-6500/M Short Circuit Isolator
Product code Description MG-6600/M Loop-powered Addressable Sounder

MG-5100/M Manual Call Point with Break-Glass MG-7080/M MSM-4 (SMPS) Switched Mode Power Supply

MG-5120/M Manual Call Point, resettable MG-7090/M Network Interface Card


MG-8110/M Addressable Manual Call Point,(resetable)
MG-8120/M Addressable Manual Call Point, Wheather-proof (IP67)
Lloyd Certified, Marine Type
Fire Extinguishant System

Fire Extinguishant Control Panel & Accessories


Product code Description

MG-104/M Fire Extinguishant Control Panel,


2 detection zone, 1 extinguishant zone

MG-5300/M Extinguishant abort button (Latching)

MG-5310/M Extinguishant release button

Marine accessories
Product code Description

MG-3500/M* Universal Mounting Base

MG-3600/M Recessed Mounting Base

MG-3700/M Marine Back Box

MG-4000/M Remote Indicator

MG-5000/M Electronic Sounder

MG-5200/M Sounder Strobe, Red, 24V DC

MG-5400/M Electronic Alarm Bell (6 inch)


*Compatible with MaviGard conventional and analogue addressable detectors

www.mavigard.com 40
OVERVIEW

MG-400 SERIES
INDUSTRIAL TYPE
COMBINED GAS
AND FIRE ALARM
CONTROL PANEL
Advanced programmability and high
performance make the panel widely
applicable for both industrial and home
use. SSPB (Russia) and GOST R certified.
Panels are approved by Kazakhstan and
Oman Civil Defence authorities.

Highlights
4 channels

Industrial gas detectors compatible MG-400 Combined Gas and Fire


Alarm Control Panel
4-20 mA converter compatible

2- and 3-wire gas detectors compatible

Adjustable High and Low Alarm


thresholds

Configurable latching/non-latching
Panel capacity
relays The panel has 4 channels, each capable of The panel is equipped with 4 relay outputs:
hosting max. 1 gas detector or 20 High Alarm, Low Alarm, OverRange and
Configurable latching/non-latching conventional fire detectors and unlimited Fault. All relays can be tested from the
sounder outputs
number of manual call points. The channels panel menu command. Each relay can be
Sink and Source option for channels are monitored for open and short circuits. set for operation in either latching or non-
Remote control
Channels can be inhibited from the panel latching mode.
menu or remotely.
Delayable sounder output activation The auxiliary 24 V power supply output can
Password-protected access levels Enhanced gas leakage detection be used for energising external devices,
Channel measurement unit can be set to such as telephone dialers.
Sounder and relay test ‘%LEL’, ‘PPB’, ‘PPM’, ‘%VOL’ or ‘FIRE’. Panels
64 x 240 pixel LCD with adjustable can be set to ignore channel measurements The LCD and menu
blue backlight made just after energising of the panel for Large graphic 64 x 240 pixel LCD with
Channel location text on the front certain time. The time is adjustable from adjustable blue backlight facilitates
panel the panel menu. This feature prevents false displaying system information, including
alarms during the first minute of panel gas detector measurements, alarm
operation, when gas detectors do not make conditions and faults.
Features stable measurements yet.
Soft-touch buttons The menu has password-protected levels
Microprocessor-controlled High and Low Alarm dependence on either to prevent unauthorised access to the
rise or decrease of gas density and settings of the system. Panel menu and
PCBs made by use of Surface Mount threshold levels are adjustable from the front panel have versions in three languages:
Technology
panel menu. Gas detectors can be zeroed Turkish, English and Russian.
2 programmable and supervised and calibrated.
sounder outputs Power supply
4 programmable relay outputs Output programmability Panel power supply is under continuous
The panel has 2 sounder outputs, which monitoring. Batteries are charged
Compatible with all popular can be disabled, tested and set either for automatically and charging is cut off when
conventional fire detectors
operation in latching or non-latching mode. necessary level is reached.
Protection against electromagnetic Connecting MG-5000 series sounders and
interference bells to the outputs is recommended for Remote control
Optional repeater panels best performance. Each output can host User can silence alarm and inhibit channels
16 MG-5000 Sounders, 8 MG-5200 by use of remote control inputs.
Optional relay modules Sounder Strobes or 20 MG-5400 Fire Alarm
Auxiliary power supply output Bells.
Lamp test by use of single button

Built-in silenceable buzzer

41 www.mavigard.com
SPECIFICATIONS

IR³ Flame Detector


Infra-red (IR) fixed flame-proof flame detector with BG3
4-20 mA output Intrinsically safe manual call
ATEX ExII 2G, EExd IIB T5, FM/CSA
3x1,5 RE-2Y(St)2YQY-fl point
ATEX Ex II 1G,
EEx ia IIC T4

Xgard Type 5
Fixed flame-proof gas detector with 4-20 mA output 2x1,5+1,5 JY (st) Y
for flammable gases
ATEX Ex II 2G, EExd IIC T6 3x1,5 RE-2Y(St)2YQY-fl SLR-E-IS
Intrinsically safe photo-electric
smoke detector
BASEEFA
EEx ia IIC T5

Xgard IR
Flame-proof infra-red (IR) gas detector with 4-20
mA output for explosive gases
ATEX Ex II 2G, EExd IIC T6 3x1,5 RE-2Y(St)2YQY-fl
DCD-1E-IS
Low alarm relay: Intrinsically safe heat detector
8 A 30 VDC/10 A 250 VAC, volt BASEEFA
EEx ia IIC T5
free change over 3x2,5 RE-2Y(St)2YQY-fl DB1
Flame-proof sounder
ATEX ExII 2G, EExd IIB T3
High alarm relay:
8 A 30 VDC/10 A 250 VAC, volt DANGEROUS AREA
free change over
Networking: RoLP SOLISTA LED Z 728.F
repeater panels Sounder strobe Zener barier
Over range relay:
8 A 30 VDC/10 A 250 VAC, volt Auxiliary power supply output:
free change over 0.5 A 24 VDC, self-reseting fuse Sounder outputs: Chanels:
protected 2 x ( 0.5 A 24 VDC ), supervised, self- 4 inputs, supervised, self-resetting fuse
Fault relay: resetting fuse protected, end-of-line protected, end-of-line resistor 1.8 kW (for
Remote controls: resist or 10 kW fire detectors), industrial gas detectors
8 A 30 VDC/10 A 250 VAC, volt
Silence Alarm compatible, 2- and 3-wire gas detectors
free change over Inhibit compatible

Channel location text Controls LCD: 64 x 240 pixel


with adjustable blue backlight
System status and fault LEDs
Menu Samples

Panel models SIGNAL LEVEL


Product Code Capacity CHANNEL 1: 00.0 mA
CHANNEL 2: 05.5 mA
MG-400 4 CHANNEL 3: 10.7 mA
CHANNEL 4: 25.5 mA
Mains power supply: 220 VAC 50 Hz, EXIT-BACK
2 A glass type fuse protected
Displaying channel signal levels
Operating voltage: 24 VDC
System fuse: 5 A ***CHANNELS***
CHANNEL 1 SET-UP
Batteries: 2 x ( 12 V DC 7 Ah )
> DETECTOR MEASUREMENT RANGE: 9999
Construction: Panel cabinet: 1.2 mm sheet steel, FORCE ZERO: ACTIVE
front panel:1.5 mm sheet steel, 2mA CONDITION: FAULT
plastic cover OPENING DELAY: 120SEC
Finish: Epoxy powder coat ENTER-CONFIRM EXIT-BACK
Mounting: Surface Channel set-up

Standard colour: Panel cabinet: grey, front panel


and cover: white COMMON RELAY PROPERTIES
LOW ALARM RELAY: LATCHING/NO
Operating ambient (-10ºC) – (+55ºC) HIGH ALARM RELAY: NON-LATCHING/NC
temperature: OVER RANGE RELAY: LATCHING/NO
Ambient humidity: 0-95% (non-condensing) FAULT RELAY: NON-LATCHING/NO
Size: 400 x 300 x 100 mm EXIT-BACK
Weigth: 5.3 kg (approx., without batteries) Setting relay properties

www.mavigard.com 42
OVERVIEW
TGDR-1224M
Ceiling Type
Gas Detector

Wall Mounted
Gas Detector

GD/GDR SERIES Wall Mounted GD-220L


Gas Detector GD-220M
CONVENTIONAL GD-220C
GAS DETECTORS GDR-1224L
GDR-220L
User-friendly MaviGard gas detectors GDR-1224M
provide wide applicability and reliable gas
GDR-220M
safety. GOST R and SSPB (Russia) certified.
GDR-1224C
Approved by Kazakhstan, Oman, UAE and
Bahrain Civil Defence authorities and by GDR-220C
Russian Federal Department of Ecological,
Technological and Atomic Energy
Supervision.
LPG (Butane + Propane) detectors
LPG is an explosive hydrocarbon gas consisting of butane and propane. It is heavier than
air and sinks to floor in case of leakage. Therefore, an LPG detector must be mounted 15-
25 cm above floor and within 1-2 m horizontally within the range of possible gas leakage.
Features The MaviGard LPG detectors respond audibly and visually before the leakage reaches 20%
LEL(Lower Explosive Limit).
Power On, Gas Alarm and Fault LED
indicators Models
LED and buzzer test button
GDR-1224L LPG (Butane+Propane) Detector, 12/24 VDC, with Relay
Built-in buzzer
GD-220L LPG (Butane+Propane) Detector, 220 VAC
Microprocessor-controlled

5 year sensor life under normal GDR-220L LPG (Butane+Propane) Detector, 220 VAC, with Relay
operating conditions

Stable sensitivity

Compatible with MaviGard


conventional fire and gas alarm control
panels

Models with relay output are GDR-1224L GD-220L GDR-220L


compatible with most of fire alarm
Power supply 12/24 VDC 220 VAC 220 VAC
and security control panels
Relay output 10 A 250 VAC 8 A 30 VDC NA 10 A 250 VAC 8 A 30 VDC
220 VAC standard models operate
autonomously Weight
(approx.) 240 g 290 g 290 g
Easy mounting Warm-up
time <1 min <1 min <1 min
Alarm <10 sec <10 sec <10 sec
response time

Natural Gas Detectors (Methane)


Methane is an explosive hydrocarbon gas. It is lighter than air and rises to ceiling in case of
leakage. Therefore, a natural gas detector must be mounted 5-15 cm below the ceiling and
1-2 m horizontally within the range of possible gas leakage. The MaviGard natural gas
detectors responds audibly and visually before the leakage reaches 20% LEL (Lower Explosive
Limit).
Models
GDR-1224M Methane (Natural Gas) Detector, 12/24 VDC, with Relay

GD-220M Methane (Natural Gas) Detector, 220 VAC

GDR-220M Methane (Natural Gas) Detector, 220 VAC, with Relay

GDR-1224M GD-220M GDR-220M


Power supply 12/24 VDC 220 VAC 220 VAC
Relay output 10 A 250 VAC 8 A 30 VDC NA 10 A 250 VAC 8 A 30 VDC
Weight
(approx.) 240 g 290 g 290 g
Warm-up <1 min <1 min <1 min
time
Alarm <10 sec <10 sec <10 sec
response time

43 www.mavigard.com
OVERVIEW
Carbon Monoxide(CO) detectors
Carbon monoxide is a toxic and explosive gas with density nearly equal to air. Therefore, a carbon monoxide detector must
be mounted 1-1.5 m above floor and 1-2 m horizontally within the range of possible gas leakage. Carbon monoxide detectors
should not be mounted outside buildings, behind or inside cupboards, where air circulation is low, in damp or humid places,
above fuel burning appliances and places with low or high temperatures. The MaviGard carbon monoxide detectors respond
audibly and visually when the gas concentration reaches 50 ppm (parts of gas per million parts of air).

Models
GDR-1224C Carbon Monoxide (CO) Detector, 12/24 VDC, with Relay

GD-220C Carbon Monoxide (CO) Detector, 220 VAC

GDR-220C Carbon Monoxide (CO) Detector, 220 VAC, with Relay

GDR-1224C GD-220C GDR-220C


Power supply 12/24 VDC 220 VAC 220 VAC
Relay output 10 A 250 VAC 8 A 30 VDC NA 10 A 250 VAC 8 A 30 VDC
Weight
(approx.) 240 g 290 g 290 g
Warm-up <30 sec <30 sec <30 sec
time
Alarm <2,5 min <2,5 min <2,5 min
response time

Wall Mounted Gas Detectors

Specifications
System On LED
Power consumption : 2 W
Alarm LED
Operating ambient temperature : (-10ºC) - (+55ºC) Fault LED
Operating ambient humidity : 0-95% (non-condensing) Test button

Audible alarm : Piezzoelectric buzzer, 85 dB/1m Mounting holes

Indicators : System On LED (green), Alarm LED (red), Connection


Fault LED (yellow) (varies according
Cover to the model)
Controls : Test button
Construction : ABS

Ingress Protection class (IP) : 42


Fuse : 0.5 A, self-resetting

Size : 140 x 100 x 50 mm


Sensor type : Semiconductor
Sensor life : 5 years

Colour : White

TGDR-1224M Ceiling Type Gas Detector

TGDR-1224M Specifications

Power consumption : 2 W Supply Voltage 24V DC

Operating ambient temperature : (-10ºC) - (+55ºC) Relay Output 10A 250V AC, 8A 30V DC

Operating ambient humidity : 0-95% (non-condensing) Weight (approx.) 240g

Audible alarm : Piezzoelectric buzzer, 85 dB/1m Warm-up Time <1 min.

Indicators : System On LED (green), Alarm LED (red), Alarm response <10 sec.

Construction : ABS
Ingress Protection class (IP) : 42
Accessories
Fuse : 0.5 A, self-resetting
Product Code Description
Size : ø: 100 h: 50 mm
TGDR-1224M Methane (NaturalGas) detector, 24V DC, with relay
Sensor type : Semiconductor
MG-3500 Universal detector base
Sensor life : 5 years
MG-3600 Recessed Mounting Kit
Colour : White

www.mavigard.com 44
OVERVIEW

MG-5100 Conventional Manual Call Point with Break-Glass


Supply voltage 12/24 VDC
The MG-5100 MCP is activated by
manual breaking of the film-coated Operating temperature (-25ºC)-(+55ºC)
glass. When the glass is broken, the
switch, normally resting on glass edge, Operating humidity 0-95%
(non-condensing)
changes position and retains it till new
ACCESSORIES FOR glass is installed. The glass does not Size 87 x 87 x 52 mm
FIRE AND GAS harm fingers because of the film.
Weight (approx.) 165 g
ALARM CONTROL Ingress Protection class 31
SYSTEMS

The products are SSPB(Russia) and GOST


R certified and approved by Kazakhstan,
MG-5120 Conventional Manual Call Point, Resettable
Oman and Bahrain Civil Defense authorities.
The MG-5120 is a resettable manual Supply voltage 12/24 VDC
call point, which features flexible plastic Operating temperature
cover. The resettable type MCP is the (-10ºC)-(+55ºC)
best solution where no break-glass Operating humidity 0-95%
type MCPs are applicable. (non-condensing)

Features The manual call points are EN 54-11 Size 87.5x87.5x56.5 mm


and SSPB (Russia) certified and Weight (approx.) 110 g
EN 54-11 certified manual call points. approved by Kazakhstan, Oman and
Universal mounting base compatible
UAE Civil Defence authorities. Ingress Protection class 24
for all addressable and conventional
fire detectors.

Recessed mounting bases allow


creating more aesthetic interiors.
WR4072 Conventional Manual Call Point, Wheather-Proof
EN 54-4 certified power supply units.
(IP67)
The WR40072 MCP is activated by Supply voltage 12/24 VDC
Electronic sounders and sounder manual breaking of the film-coated
strobes provide 105 dB(A) @ 24 VDC Operating temperature (-10ºC)-(+55ºC)
glass. When the glass is broken, the
max. audible signal power. switch, normally resting on glass edge, Operating humidity 0-95%
Electronic fire alarm bells have 150 changes position and retains it till new (non-condensing)
mm diameter gong provide strong glass is installed. The glass does not
harm fingers because of the film. Size 124x124x60mm
audio power.
This call point is wheather-proof and Weight (approx.) 110 g
can be used in outdoor applications.
Ingress Protection class 67

MG-3500 Universal Mounting Base


The bases are compatible with 0 0
Operating temperature (-25 C)-(+55 C)
MG/MGR-2000 series conventional
detectors. Remote indicator output is Operating humidity
standard for MG series detectors. (non-condensing)) 0-95 %
Universal mounting base has Ni-Cd
coated corrosion-proof clamp type Size Ø:100 mm, h:10mm
contacts. Weight (approx.) 50 g

MG-4000 Remote Indicator


Supply voltage 12/24 VDC
Operating temperature (-250C)-(+550C)
Remote indicators facilitate identifying
the alarm location by matching the Operating humidity
0-95 %
triggered detector placed above false (non-condensing))
ceiling or rooms. Size 85x85x40 mm
Weight (approx.) 85 g
Ingress Protection class IP44

MG-IO General Purpose Input/Output Module


0 0
Operating temperature (-25 C)-(+55 C)
This is an input output module used
for general purpose.It has 3 input and Operating humidity 0-95 %
(non-condensing))
3 outputs connected these inputs
respectively. Size 60 x 60 x 15 mm
Weight (approx.) 95 g

45 www.mavigard.com
OVERVIEW

MG-3600 Recessed Mounting Base


Recessed mounting base is used for mounting
Operating ambient temperature (-250C)-(+550C)
conventional as well as analogue addressable
detectors on false ceilings of various types Operating humidity (non-condensing) 0-95 %
(metal, plaster etc.). The base allows creating Size Ø: 140 mm, h: 44 mm
more aesthetic architectural applications. Weight (approx.) 175 g
Bases are produced from ABS and have the
same colour as detectors. Bases are flush-
mounted into ceiling with two clamps and
stainless steel screws.

MG-3700 Back Box


Specially designed for marine applications,
Operating ambient temperature (-250C)-(+550C)
back box is used at media with harsh weather
Operating humidity (non-condensing) 0-95 %
conditions. Back box is surface-mounted.
Size Ø: 100 mm, h: 55 mm
The box is compatible with all MaviGard
Weight (approx.) 210 g
conventional and analogue addressable fire
detectors.This device has also marine
certificate.

MG-7050 / MG-7080 Power Supply Units


MG-7050 MG-7080
Max. Current 2,5 A 4A
MG-7050 and MG-7080 switched mode Continuos Current 2A 3,5 A
power supplies have 2.5 A and 4 A 24 VDC Weight (approx.) 4,8 kg 5,4 kg
output current respectively. The power supplies Load Voltage 24 VDC
perform continuous fault monitoring (earth,
Power supply 220 V AC 50 Hz
batteries, 24 VDC, 220 V mains fail etc.).
Power supplies are microprocessor-controlled. Usage 2 units of 12 V 7 A
Operating ambient temperature (-250C)-(+550C)
Operating humidity (non-condensing) 0-95 %
Size 400 x 300 x 100 mm

MG-5000 Electronic Sounder


Supply voltage 12/24 VDC
Supply current 13/30 m A
Sounder is mounted so that an audible alarm Operating temperature (-250C)-(+550C)
of 75 dB can be heard at every part of the Operating humidity (non-condensing) 0-95 %
protected area. The maximum audible signal Size Ø: 123, h: 60 mm
power of the sounder is 105 dB(A) 24 VDC
at 1 m. Weight (approx.) 85 g
Ingress Protection class IP44
Audible signal power 105 dB(A)/1m

MG-5200 Electronic Sounder Strobe


Supply voltage 12/24 VDC
The strobe has both audible and visual alarm
Supply current 17/50 mA
features. The sounder is mounted 2 m above
the floor and so that the audible alarm of 75 Operating temperature (-250C)-(+550C)
dB can be heard at every part of the protected Operating humidity (non-condensing) 0-95 %
area. The maximum audible signal power of Size Ø: 123, h: 55mm
the sounder is 105 dB(A) 24 VDC at 1 m. The Weight (approx.) 95 g
strobe has 3 W power and a flash rate of Ingress Protection class IP44
150/min.
Audible signal power 105 dB(A)/1m

MG-5400 Fire Alarm Bell (6 inches)


The bell is designed to meet requirements of Supply voltage 24 VDC
superior performance with low current Supply current 25 mA
consumption. It can be installed directly onto
Operating temperature (-250C)-(+550C)
a wall or by use of any standard mounting
box. A built-in varistor suppression element Operating humidity (non-condensing) 0-95 %
is incorporated to micro-motor unit of the Size Ø: 152.4 mm
bell to reduce EMI and RFI effects. The bell is Weight (approx.) 527 g
well-suited to various indoor and outdoor Ingress Protection class IP51
applications, where strong audible warning is 105 dB(A)/1m
Audible signal power
required, such as schools, apartments,
hospitals, office buildings, and hotels.

www.mavigard.com 46
Mavili Elektronik Ticaret ve Sanayi A.S. reserves the right to alter the specifications of
its products presented in this catalogue without prior notice. (08/v9)