STRUCTURAL

Str DESIGN AND ANALYSIS


Proposed 3.2-meter
Proposed Concrete
3-m Concrete HollowBlock
Hollow Block Firewall
Wall

PREPARED FOR:

Urbaneast Developments, Inc.

PREPARED BY:

Katherine Shayne D. Yee


Civil Engineer
PRC No. 0137378
PTR No.: 8125160
Date Issued: January 07, 2020
Placed Issued: Makati City

October 7, 2020
Project Name: Arista Firewall
Location: Catalunan Grande, Davao City
Subject: Analysis of 3.2-meter CHB Wall Frame
Designed by: Katherine Shayne D. Yee

I. Structural Parameters

H= 3.2 m Height of CHB Wall


L= 7 m Length of CHB Wall
S= 2.3 m Column Span
y= 2 m Height of Beam from NGL
ϒchb = 16.5 kN/m3 Density of CHB Wall
ϒc = 23.6 kN/m3 Density of Concrete
t= 100 mm Thickness of CHB Wall
f'c = 3000 psi Compressive Strength of Concrete
fy = 414 Mpa Yield Strength of Steel

i. Beam Sizes
b= 0.2 m Width of Beam
h= 0.2 m Depth of Beam
NOB = 2 No. of Top/Bottom Bars
db = 10 mm Diameter of Main Bars
dbt = 8 mm Diameter of Stirrups

ii. Column Sizes


b= 0.2 m Width of Column
h= 0.2 m Depth of Column
NOB = 2 No. of Top/Bottom Bars
db = 10 mm Diameter of Main Bars
dbt = 8 mm Diameter of Stirrups
Pw = 0.44 kPa Min. Wind Pressure (As per NSCP 2015)

II. Loadings

i. Beam Calculations
W DL = 0.944 kN/m
WSDL = 1.98 kN/m
Mmax = 1.17691 kN/m Factored Maximum Moment of Beam
Vmax = 4.70764 kN Factored Maximum Shear of Beam

a. Flexure check
d= 147 mm Effective Depth of Beam
a= As fy
0.85 f'c d
a= 25.16 mm

φMc = 10.70 kN-m Ultimate Moment Capacity of Beam

DCR = 0.11 kN-m SAFE!


b. Shear check
Vc = 17.85 kN Shear Capacity of Concrete
Vu= 4.70764 Factored Maximum Shear of Beam
DCR = 0.26 Demand Capacity Ratio

Vc > Vu! Therefore, minimum reinforcement is needed.

ii. Column Calculations


Pbeam = 4.71 kN Axial Load due to the Beam
PDL = 2.832 kN Axial Load due to the Self Weight of Column
Pu = 10.56 Total Axial load

Mw = 5.18144 kN Moment of Column due to Wind


MDL = 1.18 kN Moment due to Beams
Project Information

Project Arista Firewall


Job No 001
Company Urbaneast Development Inc.
Designer KSDY
Remarks Located @ Catalunan Grande, Davao City

Software CSICOL (Version: 8.4 (Rev. 0))


File Name E:\Struct Works\Engr. Ronan Cua \Column

Working Units SI (mm, KN, KN-m, N/mm^2)


Design Code ACI-318-02

Column:Column1

Basic Design Parameters

Caption = Column1
Default Concrete Strength, Fc = 30.0 N/mm^2
Default Concrete Modulus, Ec = 26000.0 N/mm^2
Maximum Concrete Strain = 0.003 in/in

Rebar Set = User


Default Rebar Yeild Strength, Fy = 400.0 N/mm^2
Default Rebar Modulus, Es = 200000.0 N/mm^2
Default Cover to Rebars = 38.2 mm
Maximum Steel Strain = Infinity

Transverse Rebar Type = Ties

Total Shapes in Section =1


Consider Slenderness = No

Section Diagram

Result Summary

Sr.No Combination Pu (kN) Cap. Ratio-Bot Cap. Ratio- Remarks


Top
1 LOAD COMBO 9.81 0.586 0.586 Capacity OK

NOTE: THE CAPACITY RATIO IS LESS THAN 1.0.


THEREFORE, THE COLUMN IS STRUCTURALLY
ADEQUATE.

E:\Struct Works\Engr. Ronan Cua\Column.CDB Page 1


SQUARE FOOTING DESIGN
STRUCTURE Proposed 3-m CHB Firewall (Arista Firewall)FILE NUMBER:
LOCATION: Catalunan Grande, Davao City REVISION: 0
COMPANY Urbaneast Developments, Inc. PREPARED BY: KSDY
ARCHITECT: - DATE PREPARED: 7-Oct-20

I. Parameter
fy= 228 Mpa Reinforcing Steel Yield Stress,
f'c= 20.7 MPa Concrete Compressive Strength,
qa= 75 kPa Input Allowable Soil Pressure,
df= 1.5 m Depth of Column
B= 200 mm Width of Column
L= 200 mm Length of Column
t= 250 mm thickness of Footing
db= 12 mm 113.0973 Bar Diameter
γc= 24 kn/m3 Unit Weight of Concrete
γs= 18 kn/m3 Unit Weight of Soil
PDL= 10.092 kN Dead Load, DL
PLL= 0 kN Live Load, LL
PEL= 0 kN Seismic Load, EL
MDL= 0 kN-M Dead Load, DL x
MLL= 0 kN-M Live Load, LL x
MEL= 7.92 kN-M Seismic Load, EL x
MDL= 1.82 kN-M Dead Load, DL z
MLL= 0 kN-M Live Load, LL z
MEL= 0 kN-M Seismic Load, EL z
II. Calculate for Pu
Ps= 10.09 kN DL + LL + EL
Pu= 12.11 kN 1.2DL + 1.6LL
Pu= 12.11 kN 1.2DL + 1.0LL + 1.0EL
Pu= 12.11 kN 1.2DL + 1.0LL + 1.0WL
use Pu max. = 12.11 kN
Mu= 0.00 1.2DL + 1.6LL
Mu= 7.92 1.2DL + 1.0LL + 1.0EL
Mu= 0.00 1.2DL + 1.0LL + 1.0WL
use Mu max. = 7.92 kN
Mu= 2.18 1.2DL + 1.6LL
Mu= 2.18 1.2DL + 1.0LL + 1.0EL
Mu= 2.18 1.2DL + 1.0LL + 1.0WL
use Mu max. = 2.18 kN
III. Dimensions of Footing & Ultimate Bearing Capacity
i .Footing Dimension, B=L
qe= 46.5
B= 0.47 mm Pw / (qanet )
B= 500 mm
L= 500 mm
quMAX= -533.43 kPa Ultimate Soil Pressure, Pu / BL
quMIN= 436.55 kPa
ii. if QuMIN= (-) (OPTIONAL)
Note: Should the stress at the other end is (+) tension, the value of L must be computed using the following
procedure. (Since soil pressure cannot be tension)
e= 0.65 mm
a= 1.04 m 260.4387097 B= 140 m
L/2= 1.00 m 140 L= 2010 m
L= 2.00 m
III. Checking of One Way Shear
de = 163 mm Depth of Footing Assumed
y= -510.21 kPa
x1= 263 mm
B-x1= -263 mm
z= -73.66 kPa
Vu= 38.39 kPa
Vc = 61.80 kPa
ϕVc= 52.5 kPa
CHECKING OF ϕVc>Vu PASSED
IV. Checking of Two Way Shear
x1= 68.5 mm
x2= 181.5 mm
y1= -132.89 kPa
y2= -352.10 kPa
z1= 303.66 kPa
z2= 84.45 kPa
bo= 363 mm
Vu= 25.57 kPa
Vc = 123.60 kPa
ϕVc= 105.06 kPa
CHECKING OF ϕVc>Vu PASSED
V. Steel Requirements
x= 350 mm
B-x= 150 mm
y= -678.99 kPa
z= -242.44 kPa
Mu= 2.45 kN-m
Ru= 0.21 MPa
ρ= 0.00091
ρmin= 0.0061
USE: 0.0061
As = 500.44 mm2
n= 6 pcs BOTTOM BARS

Conclusion: The footing size provided is 800mm x 800mm x 250mm compared to 500mm x 500mm x 250mm
required. And the provided reinforcement is 7 pcs - 12mm dia bottom bars bothways compared to 6 pcs- 12mm dia
required reinforcement. Therefore, the provided footing is safe!