STORAGE, OPERATING
AND MAINTENANCE INSTRUCTIONS
IS2470GB
V.le Suzzani, 229 - 20162 Milano (Italy)
Tel. 02-66122.1 (ra) - Fax 02-6470906 IS 2470GB
e-mail: info@passoni-villa.com Page 2 / 17
FABBRICA ISOLATORI E CONDENSATORI SpA
INDEX
1 DESCRIPTION ............................................................................................................................................3
1.1 GENERAL ............................................................................................................................................3
1.2 SAFETY ...............................................................................................................................................3
1.3 TECHNICAL CHARACTERISTICS ......................................................................................................3
2 PACKING AND STORAGE.........................................................................................................................5
2.1 PACKING .............................................................................................................................................5
2.2 ACCEPTANCE.....................................................................................................................................6
2.3 STORAGE............................................................................................................................................6
3 LIFTING AND TRANSPORTATION ...........................................................................................................6
3.1 PACKED BUSHING .............................................................................................................................6
3.2 UNPACKED BUSHING ........................................................................................................................6
3.3 SHIPMENT TO THE END USER..........................................................................................................8
4 INSTALLATION ON THE TRANSFORMER...............................................................................................8
4.1 DRAW LEAD CONNECTION...............................................................................................................8
4.2 DRAW ROD CONNECTION ................................................................................................................9
4.3 BOTTOM CONNECTION.....................................................................................................................9
4.4 OIL SIDE DEFLECTOR......................................................................................................................11
4.5 ICE AND SNOW DEPOSITS..............................................................................................................11
4.6 OIL FILLING OF THE TUBE OF THE BUSHING................................................................................11
4.7 OIL LEVEL REGULATION .................................................................................................................12
4.8 CONNECTION TO BUCHHOLZ RELAY ............................................................................................12
5 TEMPERATURE LIMITS ..........................................................................................................................12
PNO.525.1550.1250
1.2 SAFETY
This manual must be available to the personnel
responsible of the installation, operation and
maintenance of the bushings.
The installation, operation and maintenance of the
bushings present conditions of no safety and it is
necessary to follow carefully specific procedures and
instructions. No compliance with these procedures and
instructions can involve very severe and dangerous
conditions for the personnel and the property.
Please follow carefully all the instructions of the manual
and pay attention to the WARNING (severe hazard),
and CAUTION (minor hazard) signs.
During the winding a sequence of aluminium foils, 1.3.5. Head and oil level indication
cylindrical shape and coaxial disposition, is inserted
The metal components of the head are made of
between the layers of paper. These foils grade the
aluminium alloy casting and acts as oil reservoir.
best possible distribution of the radial and longitudinal
The bushing head operates as oil compensator and is
electrical gradient between the conductor and the
provided by an oil level indicator, prismatic glass type.
fixing flange, which is grounded.
Upon request a magnetic oil level indicator can be
The winding is made by computer controlled
supplied.
machines, with simultaneous machining to the final
shape. After the winding the bushing is assembled
1.3.6. Oil side shield
and placed into an oven at 105 °C, treated under
-2 The oil side is shielded by a suitable electrode, made of
vacuum (each bushing individually), kept at 4⋅10
mm Hg for some days and impregnated with oil aluminium sheet, with the function of reducing the
(having max. humidity content of 3 ppm and suitably dielectric strength in oil. The shield is removable in
degassed). The impregnation is made under pressure order to ease the lead connection operations.
in order to obtain the best impregnation and to test
the perfect tightness. 1.3.7. Flange
After impregnation the head of bushing is filled with The flange made of aluminium casting and is equipped
nitrogen cushion. All this process is automatic and with the following accessories:
computer controlled.
- Power factor tap;
- Buchholz relay connection;
1.3.2 Air side - Oil sampling valve;
The air side envelope is made of porcelain, brown - Lifting holes;
colour (upon request grey colour or resin fibre-glass
envelope covered with silicone sheds), with a - Potential device tap (voltage tap) – on request.
creepage distance normally for very high-polluted
atmosphere (VHP): 31 mm/kV. 1.3.8. Gaskets
The shed configuration is alternated type (small-large Made of Fluorcarbonium elastomer, o-ring type. They
sheds). This is the most effective solution as proved are compatible with impregnating oil of bushing and
by salt tests and the profile of sheds complies with hot mineral oil of the transformer.
the recommendations of Standards. Flat gaskets are fitted concentrically to o-rings, to
More pieces of porcelain are used, epoxy resin glued, prevent a direct contact from the metal parts and the
without using gaskets in between. porcelain envelope.
For special requirements regarding low ambient
temperatures (up to -55°C) special o-rings are
1.3.3 Oil side foreseen, made of nitrile mixtures.
The oil side envelope is made of moulded epoxy resin
for bushings up to 420 kV. This type of housing has 1.3.9. Assembling
been employed by PASSONI & VILLA for the first Mechanical coupling among all the components is
time in 1963, for the manufacturing of the transformer obtained by compression springs placed at the head
side envelope in the re-entrant type bushing. The of the bushing. Furthermore the air side porcelain is
epoxy resin is bi-components type, i.e. consists of a cemented to the flange, in order to have a stronger
resin base and a hardener, the charge material is mechanical resistance.
quartz sand. The epoxy resin envelopes have The cemented used is a monocalcic aluminized type,
shapes, thickness and dimension tolerance not curing quick. All the cement surfaces in contact with
possible to be achieved by porcelains, moreover they the external ambient are protected by means of a
can grant the possibility of making metal parts silicone sealing.
embedded in the mass itself.
For bushings greater than 420 kV the oil side 1.3.10. Type of dielectric
envelope is made of one piece porcelain.
Versions with under flange sleeve in oil side for CT The impregnation is made with synthetic oil
accommodation, are available upon request. dodecylbenzene (DDB). This is an oil with high
electrical and constant characteristics, long time
experienced in the cable field.
1.3.4. HV terminal DDB is made by a mixture of monoalkylbenzols, with
lateral saturated chains. It has an optimum stability to
The HV terminal can be removable in case of draw the electrical and thermal stresses and exceptional
lead or draw rod execution; it is coupled to the gas absorption capacity in presence of an electrical
conductor by means of multi-blades contacts, and it is field. Its pour point is lower than -55°C, so it can be
fixed on the head by means of four screws. In case of used also for special low ambient temperature
bottom connection execution it is fixed. requirements.
Terminal can be made of aluminium or copper, These characteristics together with physical-
depending from the rated current of the bushing; the chemical constancy make it better and preferable to
aluminium one can be without any surface treatment the mineral oil. Before the impregnation, oil is suitably
or silver plated; the copper one is always tinned.
V.le Suzzani, 229 - 20162 Milano (Italy)
Tel. 02-66122.1 (ra) - Fax 02-6470906 IS 2470GB
e-mail: info@passoni-villa.com Page 5 / 17
FABBRICA ISOLATORI E CONDENSATORI SpA
dried, degassed and filtered. DDB is fully compatible 2 PACKING AND STORAGE
and miscible with transformer mineral oil.
2.1 PACKING
1.3.11. Name plate
After the tests, before packing, the lower part of the
Each bushing is provided of two name plates, with bushing is cleaned from the oil and the porcelain from
serial number and all the electrical data, in accordance the dust. Thanks to a special device to prevent the
with the prescription of IEC Standards. diffusion of the nitrogen cushion of the head into the
The plates (fig. 2a and 2b) are made of stainless steel bottom part, bushings can be packed in horizontal
and are placed on the flange by nails. On the main position.
plate (fig. 2a) there are the following information: Remember to lay down the bushing following
1 - Type of bushing carefully the indication of the yellow label sticked in
the bushing’s head.
2 - Insulating voltages
The possibility of positioning bushings in horizontal
3 - Rated current grants that the dimensions of cases, containing one
4 - Max. mounting angle bushing, are smaller and the transportation less
costly.
5 - Weight
6 - Serial number
CAUTION
7 - Month and year of production
8 - (Available) When the bushing is positioned in horizontal
position, make sure to follow the indications written
MILAN in the yellow label of fig. 3, positioned on the head:
ITALY 7
the bushing has to be positioned with the oil level
PASSANTE- BUSHING- TRAVERSEE- DURCHFUHRUNG
1 indicator towards the bottom.
N░ 6
2 kV A
50- 60Hz Kg 3
4 5 8
Fig. 2a
Fig. 3
Fig. 2b
V.le Suzzani, 229 - 20162 Milano (Italy)
Tel. 02-66122.1 (ra) - Fax 02-6470906 IS 2470GB
e-mail: info@passoni-villa.com Page 6 / 17
FABBRICA ISOLATORI E CONDENSATORI SpA
2.3 STORAGE
Although there are no preclusion for the bushings Fig. 5
remaining in the open air, it is preferable to store them
in a closed location.
The bushings must be kept in their original packing and 3.2 UNPACKED BUSHING
in their initial position, that is with the oil level indicator To take the bushing out of the case, operate according
towards the bottom, as indicated by the yellow label put to the following suggestions:
on the head of the bushing and reproduced in fig. 4.
• Considering the weight and the dimensions it is
On request, for a long period storage (greater than advisable to use two tackles or two equivalent
one year) the bushings can also be shipped with the lifting systems.
V.le Suzzani, 229 - 20162 Milano (Italy)
Tel. 02-66122.1 (ra) - Fax 02-6470906 IS 2470GB
e-mail: info@passoni-villa.com Page 7 / 17
FABBRICA ISOLATORI E CONDENSATORI SpA
If the air side is film glass made, the rope has not to
be fixed between petticoats, because there is the
risk to damage them. So place the rope between
the head and the first petticoat
Fig. 7a
CAUTION
CAUTION
Inclined mounting
4 INSTALLATION ON THE TRANSFORMER
If the bushing has to be mounted in inclined position, it
will be still necessary to operate with two independent Before installation, keep the bushing in vertical position
tackles. for 24 hours and gently rock it to release any residual of
nitrogen gas, which may have been trapped in the
Apply a rope at the two lifting holes on the flange and insulation. In any case it is advisable to keep the
fasten it with a string around the upper petticoats of the bushing in a vertical position for about 48 hours prior to
porcelain (from second and third). electrically testing it.
Apply the second rope at the two lifting holes (fig. 7a). The installation of the bushing on the transformer and
the coupling with the insulated connection coming from
Lift the bushing (fig. 7d) and operate with the two the winding must be executed according to the
tackles in order to give the request inclination (fig. 7c). following information:
• Cut the connection at a right size Lcut plus 20 mm necessary to block the terminal before filling the
for the soldering of the lug; note that the size Lcut is transformer with oil. The gasket which is necessary
indicated on the “bushing overall dimensions” to assure the tightness between the oil of the
drawing, supplied with the bushing’s order bushing and the oil of the transformer, is not
confirmation; involved in this assembly. The connector to the HV
terminal must be of compatible material. Clean well
• Make a hole, in the lug, having sufficient diameter
the terminal and apply a specific grease for
for the connection but a maximum diameter 3 mm
electrical contact and then assembly the connector
lower than that of the lug;
to the terminal
• Make the connection, through brazing, of the draw
lead to the copper lug; For a better bushing’s tail insulation, it is advisable to
protect the lead coming from the winding of the
• Fix a thread to the lug, using the M12 hole (fig. 1); transformer with paper; it is suggested to insulate with
a minimum layer of 1,5 mm and a maximum diameter
• Place the gasket on the flange on the transformer;
of 2 mm smaller than the internal one of the tube (to
• Slide inside the central bushing’s tube from the permit the oil circulation).
bottom the lug with the lead;
2
1
1
Fig. 10
1 1
2
2
Fig. 13
Fig. 11 Hexagon type bottom terminal
Palm type bottom terminal
V.le Suzzani, 229 - 20162 Milano (Italy)
Tel. 02-66122.1 (ra) - Fax 02-6470906 IS 2470GB
e-mail: info@passoni-villa.com Page 11 / 17
FABBRICA ISOLATORI E CONDENSATORI SpA
CAUTION
Fig. 14
Clamping type bottom terminal
Fig. 15
5 TEMPERATURE LIMITS
CAUTION Bushings of the series PNO are designed for operation
at temperatures according to IEC 60137 Standard:
The characteristic of withstanding vacuum and Ambient temperature: Maximum: + 40°C
temperature refers to new bushings. In case of old
Max. daily mean: + 30°C
bushings it must be considered the natural derating
and ageing of the gaskets Minimum: - 25°C
Oil temperature: Maximum: +100°C
Max. daily mean: + 90°C
6 4 5
Fig. 18
Power factor tap (on request)
WARNING
Don’t unscrew the screws item 7 of fig. 17, that fix the
PF flange to the bushing.
If accidentally this operation happens some oil goes
out from the bushing and the electrical contact
between the internal condenser body and the flange
3 7 2 1 can be damaged.
WARNING
If not used the voltage tap can remain empty, but we Bushings with major chips or cracks which appreciably
recommend to fill it of mineral oil to prevent the decrease the creepage distance should be removed
entrance of moisture, that during the years can cause from service and replaced.
the corrosion of the tap connection contact, with Wash periodically the porcelain surfaces, on which
dangerous sparking problems. dust, saline compounds, combustion resituates, dirt, oil
and other deposits may easily collect and reduce
consequently the flashover value.
WARNING If the transformer has to be put in service during winter,
it is recommendable before to clean the bushing’s
If the potential device tap is not used, we porcelain from ice or snow that can reduce the
recommend to control if the cap of the oil filling dielectric withstand capability.
screw (fig. 19 item 8) have been properly applied
and screwed. On the contrary moisture entering can HV terminals
cause the corrosion of the tap connection contact, Check the connections in order to avoid poor contacts
with dangerous sparking problems. and consequent overheating.
Make particular attention on the air side connections,
more subject to oxidation than the oil side ones.
In case of connections surfaces very oxidised, clean
them slightly passing a fine sandpaper, paying
6.3 DISASSEMBLY OF THE BUSHING attention to not damage the tinned layer, if present.
To disassembly the bushing operate according to the After this operation, clean well the surfaces with a light
constructive solution adopted for the transformer, in solvent (for example alcohol).
parallel with the following suggestions:
Power factor tap
• Bring the oil until a level lower than the bushing
flange; Check the proper location of the tap cap and its
suitable complete screwing in order to prevent entrance
• For draw lead and draw rod type bushings of moisture (Fig. 17).
withdraw the terminal from the lug (fig. 9). For this
operation it is necessary to draw the terminal in Potential device tap (Voltage tap)
longitudinal way and, at the same time, rotating a
little in clockwise and counter clockwise direction. If present and not used, check the proper location and
For bottom connection bushings, loose the the suitable complete screwing either of the tap cap
terminal four screws, in order to let go down the and the oil filling screw, in order to prevent entrance of
transformer oil level inside the bushing central moisture (Fig. 19). Voltage tap If not used can remain
tube, and then remove the connection in the oil empty, but we recommend to fill it of mineral oil to
side. prevent the entrance of moisture, that during the years
can cause the corrosion of the tap connection contact,
• Secure a pulling device to the hole foreseen in the with dangerous sparking problems
top of the lug and remove the locking pin (not for
bottom connection execution); Metal parts
• Fix the bushing like indicated in par. 3 ; It is advisable after a period of 10 years for bushings
indoor installation and after 5 years for outdoor ones, to
• Remove the bolts that fix the flange and lift the give a further paint coating.
bushing following the indication given in par 3;
Oil level
Check the oil level of the bushing and add oil if
6.4 MAINTENANCE
necessary. The refilling can be done throughout the tap
The bushings PNO are hermetically sealed and positioned in the upper part of the head, near the HV
therefore an excellent preservation in time of the terminal (item 5 – fig. 9, item 3 - fig. 10), by using the
dielectric properties of the oil paper is ensured. same transformer mineral oil, accurately treated and
As for the preservation of the active part, these degassed. Mineral oil is fully compatible with the
bushings require no maintenance. impregnating DDB synthetic bushing’s oil.
It is recommended to perform every 5 years the Close the cap with a tightening torque of 100 Nm.
measurement of the dielectric losses (tgδ) following the The refilling of the gas cushion on the top head of the
instruction under par. 5. bushing with nitrogen or dry air is not strictly necessary.
As for the preservation of the external surfaces, In case the oil level would go down, check carefully if
PASSONI & VILLA suggest to undergo the following any external leakage is present. If nothing will be
inspections: detected then refill the bushing. If the oil level still go
down it is necessary to remove the bushing from the
Porcelain service and to repair it.
Check for chips, cracks and contamination. Minor chips
maybe painted with an insulating varnish to obtain a
glossy finish which will prevent dirt and moisture attack.
V.le Suzzani, 229 - 20162 Milano (Italy)
Tel. 02-66122.1 (ra) - Fax 02-6470906 IS 2470GB
e-mail: info@passoni-villa.com Page 15 / 17
FABBRICA ISOLATORI E CONDENSATORI SpA
6.5 MEASUREMENT OF DIELECTRIC LOSSES The old bushings are suitable for service if, as regards
the values of reception test, there are no increase
Test in the factory higher than (note: values only indicatives):
The Standard - IEC Publication 60137 - states that the • 1% for the capacitance C1 (this assure that there
-3
oil-paper bushings must have a tanδ less than 7x10 . isn’t a perforation between two layers)
The measurement is performed in our Test Laboratory
by means of a Schering bridge (Tettex type) at the • 30% for tgδ of capacitance C1.
voltages requested by the Standards. • 100% for tgδ of capacitance Co.
All values are shown in the Test Report.
Measurement at the voltage of 10 kV is carried out in An increase of the last value means a derating of the
order to have a reference value for comparison with dielectric characteristic of the external layers of the
measurements made at site during the service of the paper and/or of the oil in the interspace between the
bushing. condenser body of the bushing and the external
housing.
Test on the bushing installed on the transformer
With the bushing already installed on the transformer
and the HV terminal disconnected, the measurement
can be performed by means of a bridge, by applying a 6.7 EXTRAORDINARY CHECKS
voltage of 10 kV between the HV terminal and PF tap If the electric measurement detects a tgδ higher than
(or PD if present), maintaining grounded the flange (C1 the limits it is suggested to carry out an oil sampling
measurement). The bushing is considered good if a tgδ (See par. 6.8) and to perform the following tests:
less than the maximum one established by the
Standards is measured. • Humidity content
If a tgδ higher than the above one is measured, please
contact Areva-Passoni & Villa that will decide if it is Original value: ≤ 10 ppm
necessary to make other tests before removing the During working: ≤ 20 ppm
bushing from service or to ship it back, in order to make
a complete check and eventually to carry out an oil • Dielectric strength
treatment or eventually to replace the active part with
another of new manufacture. Original value: ≥ 62 kV/2,5 mm
In order to measure the Co value (capacitance between During working: ≥ 45 kV/2,5 mm
the PF tap and flange) the flange has to be supplied
with a voltage maximum of 2 kV and the PF tap has to • Dielectric losses (tgδ):
be connected to the bridge. Original value: ≤ 7*10-3
In case of presence of PD tap, this one can be supplied
During working: ≤ 12*10-3
with a max voltage of 10 kV and the PF tap has to be
connected to the bridge (C2 measurement). • Gas chromatography (DGE):
A field measurement of tgδ and capacitance can differ Make reference to Standards (IEC 60599,
from the measurements carried out in the factory due to IEC TR 61464)
the different conditions of test and relevant accuracy:
for this reason a light shifting (max 10% for tgδ) is If these checks give negative results, it is necessary to
acceptable. Furthermore the installation conditions, due ship back the bushing to PASSONI & VILLA which will
to stray capacitances, can affect the capacitance value. execute a complete set of electrical tests and
eventually will decide to make an oil treatment to the
For this it is advisable to measure capacitance and tgδ
bushing or to replace the active part with another one
upon the installation and use these values as base for
of new construction.
future comparison measurements.
V.le Suzzani, 229 - 20162 Milano (Italy)
Tel. 02-66122.1 (ra) - Fax 02-6470906 IS 2470GB
e-mail: info@passoni-villa.com Page 16 / 17
FABBRICA ISOLATORI E CONDENSATORI SpA
CAUTION
The operation is to be obviously carried out when
the line is off.
Equipment
To carry out oil sampling from a bushing, we need the
following (see fig. 20):
4
3 Second way
• A 150 cm oil syringe (item 4) (Lab. Type);
3
• A semi-rigid pipe (item 2);
First way Bushing flange
• An appropriate little flange suitable for fixing to the
sampling valve (having 4 holes positioned at 90°
each others, with a holes wheelbase of 50 mm; 1
the o-ring housing is positioned on the valve
body). This little flange will have a suitable con-
nection to the sampling semi-rigid pipe (item 1);
• A two-way cock (item 3) with a suitable 2
connection to the syringe;
• A syringe cap;
• Adhesive tape.
Preparation
Fig. 20
Operate as follows:
• Clean the plug zone accurately;
• Prepare all the syringe apparatus, with the cock
(item 3) and the tube (item 2);
• Dismantle the closing flange unscrewing the 4
screws M8 and fix the sampling flange, provided by
a suitable connection to the semi-rigid pipe (item 1);
• Wash the syringe with oil two times by repeating
the following operations:
- Open 2nd way of cock (item 3);
°7 0
Fig. 21
V.le Suzzani, 229 - 20162 Milano (Italy)
Tel. 02-66122.1 (ra) - Fax 02-6470906 IS 2470GB
e-mail: info@passoni-villa.com Page 17 / 17
FABBRICA ISOLATORI E CONDENSATORI SpA
The oil taken out has to be restored by adding the Wooden strips layer Rubber foam layer
same quantity of transformer mineral oil, accurately
treated and degassed, which is perfectly miscible with
the synthetic bushing oil. The refilling must be done
through the tap located on the top of the bushing’s
head (item 3, fig. 10), which must be closed
immediately after the end of the operations.
CAUTION Porcelain