Release 4.4.9
sadia VG FANCOIL SALA 5
Munters ICA--120
Prepared for :
Date : 27/set/07
,
Prepared by : ANTONIO FABIO
Reference No. : Quote
System Flow Diagram
Altitude 0 ft
Release 4.4.9
sadia VG FANCOIL SALA 5
ICA--120
Altitude 0 ft
Access/Removal side * From the LEFT looking in the direction of air flow
System FLA 65
Component Options:
Fan No No None
* See the system drawing for further details on component access and removal.
A27147
Release 4.4.9
sadia VG FANCOIL SALA 5
ICA--120
Altitude 0 ft
Equipment Schedule
Air Filter
Media Type Panel
Filter Thickness in 2.0
Filter Efficiency % 30%
Filter Class UL 1
Face Velocity FPM 403
Initial Resistance ''WC 0.19
Final Resistance ''WC 0.90
Filter Sizes 24 @ 24 in x 24 in
Cooling Coil - Chilled Water with Ethylene Glycol (2 coils - energy and flow values are totals)
Entering Conditions °F / gr/lb 54 / 31.6
Leaving Conditions °F / gr/lb 37 / 31.0
Capacity Btuh 737,170
Air Flow SCFM 39,942
Face Area ft² 2 Coils @ 48.0 each
Face Velocity FPM 416
Air Resistance ''WC 0.60
Water Consumption GPM 153.9
Percent Glycol % 20
Fluid Resistance feet 28.2
Connection Size Sweat 2.5
Rows 8
Tubes .625 dia x .035 thk Copper
Fins 12 FPI, .0075 thk Aluminium
Case GalvanizedSteel
Release 4.4.9
sadia VG FANCOIL SALA 5
ICA--120
Altitude 0 ft
Filter Specifications
Filter
COARSE FILTERS
1. Air is filtered through filters of 25% to 30% minimum efficiency with 90% to 92% arrestance minimum as rated by
ASHRAE Test Standard 52-76. Filters are disposable 2" deep, pleated disposable type with non-woven media held in
place by a welded wire grid. Filters are held in aluminum channels top and bottom with spacers and back-up plates to
minimize bypass. Filter channels are welded and sealed in place to eliminate air bypass.
FINE FILTERS
1. Air is filtered through 12 inch deep pleated disposable filter of efficiency show in the schedule. All filters are
constructed of a non-woven media held in a rigid frame with welded wire support grid. The 12 inch deep filter also contains
contour supports and is held in a specifically designed rigid frame using spring type clamping fasteners. Filter mounting
partitions are welded and sealed in place to eliminate air bypass.
Release 4.4.9
sadia VG FANCOIL SALA 5
ICA--120
Altitude 0 ft
Cooling Coil
Outlet
54 °F 37 °F
Inlet
Performance Data:
Physical Data:
Dimensions 48.0 in FH 144.0 in FL 96.0 ft²
8 Rows 12.0 fpi 0.625 in Tubes
Copper Tubes 0.625 in Diameter 0.035 in wall
Aluminum Fins 0.0075 in Thick Corrugated Fins
Galvanized Casing
2.5 Conn. Size Circuiting 3/4 Serpentine
(MPT)
A27147
Release 4.4.9
sadia VG FANCOIL SALA 5
ICA--120
Altitude 0 ft
1. Coils shall be sized to provide the full capacity scheduled. Coils shall be arranged to condition the full volume of
process air with bypass or balancing dampers as required. Tube water velocities are 7 fps or less and air face velocities
are 500 fpm or less. Coil circuiting provides for optimum performance with minimum pressure loss. Coil shall be designed
for 250 PSI working pressure and factory tested under water at 300-PSI air pressure.
2. Chilled water coils are fin and tube type, constructed of seamless copper tubes of .625 inch diameter with .035
inch wall thickness and aluminum plate type fins of .0075 inch thickness, mechanically bonded to tubes. Casing and tube
support sheets are 16 gauge galvanized steel formed to provide mounting flanges and structural support for the finned-tube
assembly. Supply and return headers are heavy wall copper pipe with vent and drain connections. Supply and return
connections are brazed in place with sweat connections for piping. Coils conform to ARI standard 410.
3. Chilled water coils shall be equipped with a drain pan for removal of condensate and to collect and remove coolant
in case of leaks. The drain pan is to be constructed of welded 304 SS and bolted in place. Cooling coil drain pans shall
extend the entire length of the coil and shall extend a minimum of 6 inches beyond the air leaving side of the coil. The drain
pan shall be a minimum of 2 inches deep and have a minimum pitch of 1 inch. The drain pan shall be triple sloped to ensure
zero standing water. Drain connection shall extend through unit base. Connection to be 1 inch male NPT.
A27147
Release 4.4.9
sadia VG FANCOIL SALA 5
ICA--120
Altitude 0 ft
Performance:
Component Initial Final
Mixing Box .20 .20
Med Eff Panel Filter .19 .90
Cooling Coil .60 .60
Supply Fan Diffuser .50 .50
Access Section .00 .00
Total 1.49 2.20
Fan Performance @ 37 °F
Design Point
9.0
8.0
7.0
Static Pressure ''WC
6.0
330 DWDI @
1577 rpm
5.0
4.0
3.0
2.0 System
Final
System
1.0
Initial