You are on page 1of 7

IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 29, NO.

1, JANUARYFEBRUARY 1993 195

All Amperes Are Not Created Equal: A Comparison


of Current Ratings of High-Voltage Circuit Breakers
Rated According to ANSI and IEC Standards
Baldwin Bridger, Jr., Fellow, IEEE

Abstract- The internationalization of the electrical power ratings in both the ANSI and the IEC systems, but this
equipment market has required engineers to apply equipment is unlikely to happen for at least two reasons. First, the
designed and built to unfamiliar standards. For high-voltage required testing is very expensive. Since both the ANSI and
circuit breakers, the two best-known standards are the ANSI
and the IEC standards. Since ratings with similar names have the IEC standards require testing to demonstrate conformity
different meanings in the two series of standards, it is vital with assigned ratings, there is no good way to use a single
that application engineers understand the differences.This paper set of tests to demonstrate ratings that conform with both
examines the continuous current, interrupting, short-time, and sets of standards. The testing of a single rating of medium-
closing current ratings and compares these ratings in the two voltage circuit breaker (of the type used in 15-kV metal-clad
series of standards.
switchgear) can cost upwards of $50 000 or even more if the
manufacturer has to purchase test laboratory services for all
INTRODUCTION of the required testing. Regardless of which set of standards is

T HERE ARE TWO well-known systems of standards used


to describe the rating and testing of high-voltage (includ-
ing medium-voltage) circuit breakers. The first set of standards
used for the original testing, most manufacturers find it difficult
to justify the added expense of a second round of testing. The
second reason is that a design that is optimized for the rating
is that issued by the American National Standards Institute structure of one set of standards is seldom optimal for the
(ANSI) and generally used in North America [1]-[3]. The other set, leading to a reduction in ratings when moving from
second set is that issued by the International Electrotechnical one set of requirements to the other.
Commission (IEC) and generally used in Europe [4], [ 5 ] . There are differences between the two sets of standards in
Other parts of the world may use either or both of these sets the definitions of various ratings. These differences, if not
of standards. The purpose of these standards is to establish understood by the application engineer, can lead to errors in
definitions, test procedures, and rating structures to allow the the application of circuit breakers. This paper will examine
comparison of one circuit breaker with another on an equitable the various current ratings assigned to high-voltage circuit
basis. breakers, including continuous current, short-circuit current,
In addition to the rating and testing standards, the ANSI C37 short-time current, and closing current, comparing the ANSI
series of standards includes several standards [6]-[8] designed and IEC rating methods and suggesting ways of converting
to help an application engineer choose the proper rating of circuit breaker ratings from one system to the other. The effects
circuit breaker for the particular set of system conditions likely of dc offset, voltage range factors, and interrupting time on the
to be encountered at the installation site in question. These rating structures will also be examined.
conditions may vary from the standard conditions upon which
the rating and testing standards are based. CONTINUOUS CURRENT
The electrical power equipment business is becoming Both ANSVIEEE C37.04 [l] (in Section 5.4) and IEC 694
increasingly internationalized, with both equipment suppliers [5] (in Section 4.4.1) define the continuous current rating of
and users operating on a worldwide basis. Because of this, a circuit breaker as the rms current the breaker can carry
application engineers familiar with one of these two sets of continuously without exceeding certain temperature rise limi-
circuit breaker standards may find themselves required to apply tations. Both standards base the limiting temperature rises on
circuit breakers rated and tested according to the other set of a maximum ambient of 40" C. Each standard includes tables
standards. of allowable temperature rise for various parts of a circuit
Of course, it is possible for a circuit breaker manufacturer breaker, and these values of allowable temperature rise are
to test a breaker to both sets of standards and establish different in the two standards.
Paper ICPSD 91-2, approved by the Power Systems Protection Committee Allowable Temperature Rise
of the IEEE Industry Applications Society for presentation at the 1991
Industrial and Commercial Power Systems Conference, Memphis, TN, May Table I lists a number of the parts of circuit breakers and the
6-9. Manuscript released for publication April 29, 1992. allowable temperature rises under the two standards. It can be
The author is with Powell Electrical Manufacturing Co., Houston, Tx
11211. seen from this table that the IEC standard is less stringent
IEEE Log Number 9204194. than the ANSI standard in several areas. A point-by-point
0093-9994/93$03.00 0 1993 IEEE
196 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 29, NO. 1, JANUARYFEBRUARY 1993

TABLE I
SELECTED TEMPERATURE RISE VALUES A
Allowable Temperature
Rise
Circuit Breaker Component
ANSI(1) IEC(2) C
Contacts, silver or silver plated, in air 65” C 65’ C

Connections, silver or silver plated, in air 65’ C 75O c


B X
Insulating material and metal parts in
contact with insulation
Class A 550 c 60’ C

Class B 80‘ C 90’ C


Fig. 1. Short circuit current wave. *} is the envelope of current
NOTES: (1) Refer to ANSYIEEE C37.04 [l], Tables 2, 3, and 4; (2) wave, BX is the normal zero line, CC’ ??the displacement of current wave
Refer to IEC 694 [ 5 ] ,Table V. zero line at any instant, DD’ is the rms value of the ac component of current
at any instant, measured from CC’, EE’ is the instant of contact separation
(initiation of the arc), IMCis the making current, IAC is the peak value of
comparison of the test results with either standard would be ac component of current at instant EE’, k is the ms value of the ac
Jz
necessary to determine whether or not a circuit breaker meets component at instant EE’, IDC is the dc component of current at instant
the temperature rise requirements of that standard. EE’, and l D ~ A ~ l is
o athe percentage value of the dc component.

Effect of an Enclosure
Section 4.4.1(2) of ANSUIEEE C37.09 requires enclosed
breakers to be tested in their enclosures. In North American SHORT CIRCUIT CURRENT
practice, breakers designed for use in enclosures are seldom The short circuit current a circuit breaker can interrupt is
if ever used without enclosures. Section 6.3.2 of IEC 694 probably its most important single rating. The current that
requires the circuit breaker to be mounted in all significant determines this rating is the current at the moment of contact
respects as in service, including all normal covers of any part separation. Before examining the standards to see how this
of the switching device. Since, however, European practice current is defined in each of the two standards systems, let us
may involve the use of the same circuit breaker in both open review the basics of short circuit current wave forms.
and enclosed installations, it is common practice to test and
rate the circuit breaker without an enclosure. The nameplate Review of Basics
continuous current rating may be for open-air application. It Fig. which is taken from Fig. of IEC 56 ,41, shows a
may be necessary to derate the circuit breaker for enclosed use. typical short circuit current waveform and defines the various
No general rule for derating can be given; the manufacturer component of this wave. At the moment of initiation
needs to be consulted in each case. of a short circuit, the ac current wave, which is normally
symmetrical about the zero axis (BX in Fig. l), is offset by
Effect of Frequency some value, creating a waveform that is symmetrical about
Section 5.3 of ANSVIEEE C37.04 specifies a rated fre- another axis (CC’ in Fig. 1). The degree of asymmeQ is a
quency of 60 Hz for circuit breakers. Section 4.3 of IEC 694 function of several variables, including the parameters of the
specifies a rated frequency of either 50 or 60 Hz. Section 5.4 power system up to the point of the short circuit and the point
of ANSUIEEE C37.04 states that the rated continuous current on the ac wave at which the short circuit was initiated. In a
is at the rated frequency. Section 6.3.2 of IEC 694 calls for three-phase circuit, there is usually one phase that is offset
continuous current tests to be made at rated frequency with significantly more than the other two phases.
a tolerance of +2% and -5%. Section 4.3 of ANSVIEEE It is convenient to analyze this asymmetrical waveform as
C37.09 [3] states “Tests demonstrating current carrying ability consisting of a symmetrical ac wave superimposed on a dc
which are not made at rated frequency may need correction current. In Fig. 1, CC’ represents the dc current, and the value
factors because the heat released varies with the frequency of that current at any instant is represented by the ordinate
of the current, the relation depending on dc resistance, skin of CC’. The dc component of the current normally decays
effects, eddy currents, and hysteresis losses.” No guidance is quite rapidly and reaches an insignificant value within 0.1 s
given for making these corrections, but it is known that higher in most power systems. The rate of decay is a function of the
frequencies cause higher heat losses. Therefore, a continuous system parameters. When the initial value of the dc current is
current carrying test made at 50 Hz may give temperature equal to the initial peak value of the ac current, the resulting
rise results that are less than would be experienced if the waveform is said to be fully offset or to have a 100% dc
same apparatus were tested at 60 Hz. Since the standards component. It is possible, in some power systems, to have an
give no mathematical model for correcting these test results, offset in excess of loo%, which may result in a waveform that
the continuous current test should be made at the highest has no current zeros for one or more cycles of the ac power
frequency at which the circuit breaker will be applied. frequency.
BRIDGER: ALL AMPERES ARE NOT CREATED EQUAL 197

The ac component of the short circuit current will also decay


at a rate dependant on the system parameters. In general, if the
fault is closer to generators or other large rotating machinery, ...
RICAL INTERRUPTING CAPABlLlM = S X SYMMETRICAL INTER-
the decay will be faster.
1.6

Short Circuit Current Rating


1.5
The ANSI definition of rated short-circuit current is found in
ANSIOEEE C37.04. Per Section 5.10.1 of this standard, “The 1.4

rated short-circuit current of a circuit breaker is the highest


2Vl
s 1.3
value of the symmetrical component of the polyphase or phase-
to-phase short-circuit current in rms amperes measured from
1.2
the envelope of the current wave at the instant of primary
arcing contact separation which the circuit breaker shall be 1.1
required to interrupt at rated maximum voltage and on the
standard operating duty.” This rated short-circuit current is the 1 .o
value from which the required symmetrical and asymmetrical
interrupting capabilities are derived. 3.0 4.0 CYCLES
0.5 1.0 2.0
The IEC definition of rated short-circuit current is found ,008 0.017 0.033 0.050 0.087 SECONDS

in Section 4.101 of IEC 56, which reads, in part, as follows: CIRCUIT BREAKER CONTACT PARTING TIME
SUM OF 1/2 CYCLE TRIPPING DElAY PLUS THE OPENING TIME
“The rated short-circuit breaking current is characterized by OF THE INDNIDUAL BREAKER

two values: Fig. 2. Ratio of circuit breaker asymmetrical to symmetrical interrupting


capabilities.
I . the rms value of its ac component, termed “rated short-
circuit current” for shortness, and
Section 5.10.2.2 of ANSVIEEE C37.04 specifies that the
2. the percentage dc component.”
required asymmetrical interrupting capability shall be the
From these two definitions, the rated short-circuit current required symmetrical interrupting capability multiplied by a
is seen to be defined as an rms ac current in both sets of factor S , which is determined from Fig. 2 of that standard,
standards. However, the rated short-circuit current does not which is reproduced as Fig. 2 of this paper.
define the current the circuit breaker is required to interrupt. The ANSI standard is further complicated by the require-
That value is further defined as follows. ment that the contact parting time be considered as the sum
In Section 5.10.2.1 of ANSIAEEE C37.04, the required of the one-half cycle relay delay plus the lesser of the actual
symmetrical interrupting capability at rated maximum voltage opening time of the particular circuit breaker or 1.0, 1.5,2.5, or
is defined as being the same as the rated short-circuit current. 3.5 cycles for breakers having a rated interrupting time of 2, 3,
There is a variation with voltage, which is discussed further 5 , or 8 cycles, respectively. In many instances, this will require
later in this paper. In Section 5.10.2.2, the required asymmetri- using a contact parting time less than the actual contact parting
cal interrupting capability is defined as being the highest value time of the circuit breaker. In addition, note that the times
of the total short-circuit current rms amperes, which includes are all given in cycles, which must be related to the 60-Hz
the rated short-circuit current plus a dc component. rated frequency of the circuit breaker under ANSI standards.
Section 4.101 of IEC 56 goes on to state that “The circuit For purposes of comparison with the IEC standards, which
breaker shall be capable of breaking any short-circuit current give times in milliseconds, these times should be converted
up to its rated short-circuit breaking current containing any ac to milliseconds.
component up to the rated value and associated with it any ANSI standards also require a certain percentage asymmetry
percentage dc component up to that specified....” in various test duties of Table 1 of ANSVIEEE C37.09. Some
This, of course, is an asymmetrical current. Note also that test duties require a percentage asymmetry of less than 20,
there is a subtle difference in definition between two very but many of the tests require a percentage asymmetry of
similar terms. The “rated short-circuit current” is only the ac 50 to 100. Percentage asymmetry is defined as a percent-
component of the asymmetrical “rated short-circuit breaking age of the peak value of the ac symmetrical component,
current.” which makes it equivalent to the percentage dc used in IEC
56.
Assigning a Value to the dc Component The IEC standard is somewhat simpler. The rated short
Both sets of standards recognize the rapid decay of the circuit breaking current includes a dc component whose value
dc component of the short-circuit current and therefore base is determined by reference to Fig. 8 of IEC 56, which is
their value on the expected time from the initiation of the reproduced here as Fig. 3 of this paper.
fault to contact parting. Both standards add one half of a Section 4.101.2 of IEC 56 requires the dc component of the
cycle of relaying time to the expected operating time of the short-circuit breaking current to be determined using a value of
circuit breaker to determine the contact parting time. From this T equal to the sum of the one-half-cycle relaying time and the
point, however, the method of determining the value of the dc shortest opening time of the circuit breaker obtainable under
component varies between the two sets of standards. any service conditions.
-

198 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 29, NO. 1, JANUARYIEBRUARY 1993

Voltage Range Factor K


The ANSI standards include a rated voltage range factor K ,
which is defined in Section 5.2 of ANSI/IEEE C37.04. The
effect of this K factor is to establish a voltage range in which
the breaker's interrupting capabilities are a constant value
of MVA, with current increasing proportionally as voltage
decreases. The numerical values of K are established in
the rating tables of ANSI C37.06 [2]. In the latest (1987)
edition of this standard, all outdoor circuit breakers, including
circuit breakers used in gas-insulated substations, have a rated
voltage range factor of 1. These circuit breakers are listed in
Tables I1 and 111. Indoor oilless circuit breakers, which are
commonly used in metal-clad switchgear, are listed in Table
I. These have assigned rated voltage range factors varying
Time interval from initiation of short-circuit current T (ms)
from 1.0 to 1.65, depending on the rating of the circuit
Fig. 3. Percentage dc component in relation to time interval 7.
breaker.
Section 4.101 of IEC 56 states that a standard circuit
Asymmetrical Value of Test Current breaker will be capable of breaking its rated short-circuit
The rms value of the asymmetrical current I existing at the breaking current at voltages below the rated voltage. The
moment of contact part may be calculated as follows (from IEC standards do not include a concept similar to the voltage
Fig. 9 of ANSVIEEE C37.09): range factor, although a footnote in Section 4.101 of IEC 56
allows breakers with proven short-circuit breaking currents at
two different voltages to assign intermediate characteristics
based on a straight line drawn between these two points on
a log-log display. This gives results within a few percent of
where IAC and IDC are as defined in Fig. 1 of this paper. those obtained using the formula found in Section 5.10.2.1 of
Per Section 5.10.2.2 of ANSYIEEE C37.04, the asymmet- ANSVIEEE C37.04.
rical current at the moment of contact part may consist of Two things need to be said about the K factor. First, the
any combination of symmetrical and dc components, provided concept agrees with the physical reality of oil-blast and air-
the symmetrical component does not exceed the required magnetic circuit breakers. Breakers using these technologies
symmetrical interrupting capability, the degree of asymmetry really do have higher interrupting ability at lower voltages,
does not exceed loo%, and the total short-circuit current does and assigning a K factor other than one allows a wider ap-
not exceed the required asymmetrical interrupting capability. plication of a given circuit breaker. However, circuit breakers
Since the IEC test procedure involves separate specification using vacuum or SFG puffer interrupters are essentially con-
of the ac and dc components, (1) may be rewritten as follows, stant current interrupters up to a limiting maximum voltage;
using the definition of percentage dc given in Fig. 1 of this therefore, a K factor other than one does not match the
paper: physical attributes of circuit breakers using these technolo-
gies.
Second, for a known system voltage, the K factor is
I = J(5$2+
("";;:c)2 (2) unimportant. On any given system, if the voltage decreases,
the available short circuit current will also decrease and
not increase. If a circuit breaker is properly applied at the
maximum system voltage, it will have the necessary short
circuit capability for any lower voltage on that system.

Standard Operating Duty


The ability of a circuit breaker to interrupt its rated short-
(4) circuit current is a function of how often it is required
to make this interruption. The time between operations is
If the value of the ac component is stated in rms terms, this important in that it gives the circuit breaker time to cool
equation becomes between interruptions. Both sets of standards specify stan-
dard operating duties to fix this variable. The values given
below are for circuit breakers not intended for reclosing
duty.
Section 5.6 of ANSYIEEE C37.04 specifies the standard
This is a convenient form for calculating the rated short- operating duty as two close-open operations with a 15-s
circuit breaking current for a given rated short-circuit current. interval between them or CO-15 s-CO.
BRIDGER: ALL AMPERES ARE NOT CREATED EQUAL 199

Section 4.104 of IEC 56 gives two alternative rated oper- Substituting in (3,we get
ating sequences. The first is 0-3 min-CO-3 min-CO.
The second is CO-15 s-CO, which the same as the ANSI I =I T m s / T q $
requirement. The 0-3 min-CO-3 min-CO duty cycle is
more commonly used in Europe.

Test Duties
27.5 kA = I,,,/l +2* (g)'
Both sets of standards list several test duties that must be 27.5 kA = I T m S d 1 +2 * (.5)'
performed to demonstrate the ability of a circuit breaker to
meet its short-circuit ratings. The ANSI requirements are listed 27.5 kA = I,,,d-
in Table 1 of ANSVIEEE C37.09. The IEC requirements are 27.5 kA
IT,, =
shown in IEC 56. Section 6.106 covers basic short circuit du- VCiT
ties, whereas Sections 6.107 and 6.108 cover more specialized I,,, = 22.45 kA.
test duties. From this, it can be seen that the ANSI asymmetrical
Both test series require testing at the rated short-circuit test requirements for this circuit breaker rated 25 kA can
current that is both symmetrical and asymmetrical. Both be satisfied with a test current of 22.45 kA rms plus a dc
series require tests at currents ranging from about 10 to component of 50% or 15.87 kA.Other currents could be used,
about 60% of the rated short-circuit current, and both tests provided the combination of ac and dc components meet the
require single-phase tests as well as three-phase tests. Beyond overall specification for total rms current.
the basic requirements, however, there are many differences. Using IEC test procedures, the circuit breaker would be
Duty cycles may vary, as does the degree of asymmetry called on to interrupt its rated I,,, plus a dc component.
required for tests at less than full short-circuit rating. Variations Since the opening time of the circuit breaker is 50 ms, and
in transient recovery voltage requirements and in require- the one-half-cycle relaying time is 8.33 ms, T is 58.33 ms.
ments for the condition of the circuit breaker after test- Referring to Fig. 3, we see that the required dc component is
ing make it very difficult to make an exact comparison approximately 25%. From (3,we get
of the severity of tests made under the two different sys-
tems. I = I ? - m s / l + 2 * ( 1 0%dc
0) '
Example
To compare the two sets of interrupting requirements, let us
consider a circuit breaker with a rated short-circuit current of
I = 25 kA/I +2 * (g)'
25 kA, a rated voltage range factor K of 1, a rated interrupting I = 25 k A \ / l + 2 * (.as)'
time of 5 cycles (83 ms), and an actual opening time of 50 ms. I = 25 k A d G T f %
Both ANSI and IEC standards require symmetrical inter-
rupting tests at rated short-circuit current. See test duty 4 in I = 26.52 kA.
Table 1 of ANSVIEEE C37.09 and test duty 4 of Section From this, it is seen that an IEC test using an ac component
6.106.4 of IEC 56. of 25 kA and the required percentage dc of 25% calls on
In accordance with Section 5.10.2.2 of ANSI/IEEE C37.04, the circuit breaker to interrupt a total current of only 96.4%
a breaker with a rated interrupting time of 5 cycles is assumed of the current required by the ANSI test. To meet the ANSI
to have a contact parting time of 3.0 cycles. From Fig. 2, requirements for total asymmetrical current would require a
this breaker is assigned an S factor of 1.1. The highest minimum dc component of 32.4%. Referring to Fig. 3, we
asymmetrical currents required by Table 1 of ANSMEEE find that this value corresponds to a contact parting time of 50
C37.09 are S I in test duty 6 and K S I in test duty 7. ( I ms, which is exactly the contact parting time assigned to our
is the rated short-circuit current, which is equivalent to I,,, breaker under the ANSI standards.
in (3.)Asymmetry of 50 to 100% is also specified for these
two tests. Summary of Short Circuit Current Considerations
Since our example has a rated K of 1, S I = K S I . To
meet the ANSI test requirements, this circuit breaker would Both ANSI and IEC standards define rated short circuit
be required to interrupt a maximum short-circuit current of current in terms of the rms symmetrical value of an ac current.
S I , or 1 . 1 ITmS,with a minimum asymmetry of 50%. This The definitions are the same, and the ratings are directly
gives us the following: comparable.
Both ANSI and IEC standards require asymmetrical
interrupting capability. The requirements differ. In general,
I = s * I,,, the ANSI standards require higher total current than the IEC
I = 1.1 * 25 kA standards, at least partly because the ANSI standards require
assignment of an artificially short opening time to most circuit
I = 27.5 kA. breakers.
200 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 29, NO. 1, JANUARYFEBRUARY 1993

The standard operating duty differs between the two stan- The two values are equivalent, and the actual performance of
dards. ANSIflEEE C37.04 defines the standard operating duty the circuit breaker was not required to change.
as CO-15 s-CO. This is one of two standards listed in IEC Section 4.103 of IEC 56 defines the rated short-circuit-
56, but breakers tested to IEC standards more commonly use making current as the peak current of the first major loop
the other cycle 0-3 min-CO-3 min-CO. of the short-circuit current and requires it to be 2.5 times
The exact requirements of individual test duties differ the rms value of the ac component of the rated short-circuit
between the two standards in such areas as the percentage breaking current. The ability to close against this current is
asymmetry for a particular test current level, transient recovery tested by Test Duty No. 4, as described in Section 6.106.4 of
voltage, etc. IEC 56. This test duty also includes full short-circuit current
Because of these factors, it is extremely difficult to make a interruption. There is no requirement similar to the ANSI
direct comparison of the severity of the tests required by the requirement for latching and carrying a current for 2 s before
two sets of standards. interrupting.

SHORTTIME CURRENT CONCLUSIONS


Section 5.10.2.5 of ANSUIEEE C37.04 defines the short- Rating and testing of high-voltage circuit breakers are
time current as any short-circuit current whose maximum crest very complex procedures, and this paper merely scratches
value does not exceed 2.7K times the rated short circuit the surface by looking at some of the basic current ratings
current and whose rms value over the required test period and the tests required to demonstrate these ratings. Similar
does not exceed K times rated short-circuit current. The circuit analysis could be done on voltage ratings, specialized current
breaker is required to carry this current for a period of 3 s. ratings such as capacitor switching, and other required ratings
Section 4.5 of IEC 694 defines the rated short-time with- of circuit breakers.
stand current as the rms value of the current a mechanical In the areas examined, we find that similar terms do not
switching device can carry in the closed position during a necessarily mean the same thing in ANSI and IEC standards.
specified short time. Section 4.6 requires this current to have a In many cases, it is difficult to relate the two standards to
peak value of 2.5 times the rated short-time withstand current. each other because the differences are not easily compared
Section 4.7 gives the standard rated duration of the short-time or quantified. As a general statement, however, it seems that
current as 1 s but also says that if a time greater than 1 s the ANSI standards require more stringent performance of a
is necessary, a value of 3 s is recommended. Section 4.5 of circuit breaker for equivalent ratings. Some examples include
IEC 56 requires the rated short-time withstand current to be the following:
equal to the rated short-circuit breaking current, which is the
1. Continuous Current: Several of the allowable tempera-
asymmetrical short-circuit current. This would seem to imply ture rise limits in the ANSI standard are lower by 5 or
that the current over the time period should have an integrated 10" C than the comparable limits in the IEC standard. If
value equal to the asymmetrical value of the breaking current, the circuit breaker is applied in an enclosure, its enclosed
but a careful reading of Section 6.5.2 of IEC 694, which rating should be verified. In addition, if the continuous
specifies the test current, shows that the required current is current test is run at 50 Hz rather than 60 Hz, the
the same as that required by the ANSI standard. resulting temperature rise may be lower.
Ignoring the K factor, the two differences between the 2. Short Circuit Current: For asymmetrical interrupting
standards are the difference in the peak current required and tests, the degree of asymmetry and the total short-circuit
the duration of the current flow. The peak current is required breaking current may be lower under the IEC standards
by ANSI to be 2.7 times the rated short-circuit current, but IEC than under the ANSI standards. In addition, it appears
only requires 2.5 times this current. The duration of current that the ANSI standard operating duty of CO-15 s-CO
flow is specified as 3 s by ANSI but only 1 s by IEC. is more severe than the commonly-used IEC standard
operating duty of 0-3 min-CO-3 min-CO.
CLOSINGCURRENT 3. Short Time Current: The ANSI requirement of a test
Section 5.10.2.4 of ANSI/IEEE C37.04 requires that a duration of 3 s is much more severe than the standard
circuit breaker close and, immediately thereafter, latch against IEC test duration of 1 s, and the ANSI requirement for a
a current whose peak value does not exceed 2.7K times the peak current of 2.7 times the rated short-circuit current is
rated short-circuit current. It must then carry a current equal more severe than the IEC requirement for a peak current
to K times the rated short-circuit current for a time delay of 2 of 2.5 times the rated short-circuit current.
s and then interrupt this current. This capability is proved by 4. Closing Current: The ANSI requirement for latching
Test Duty 11 of Table 1 of ANSUIEEE C37.09. against the rated closing current, carrying rated short-
As a matter of interest, it should be noted that the value circuit current for 2 s, and then interrupting that current
of this closing and latching current, as given in Tables 1-3 is not present in the IEC standards. In addition, the same
of ANSI C37.06-1987 [2], is stated in peak kiloamps and is difference exists in the ratio of peak current to rated
equal to 2.7K times the rated short-circuit current. In earlier short-circuit current as in the short-time current rating.
editions of ANSI C37.06, this value was stated in rms terms Any engineer who is responsible for applying a high-voltage
and was equal to 1.6K times the rated short-circuit current. circuit breaker rated and tested in accordance with unfamiliar
BRIDGER. ALL AMPERES ARE NOT CREATED EQUAL 201

standards should study those standards to understand exactly High-Voltage Alternating-Current Circuit-Breakers, IEC Std. 56, Int.
what the ratings mean in terms of actual performance of the Electrotech. Comm., Geneva, 4th ed., 1987.
Common Clauses for High-Voltage Switchgear and Control Gear Stan-
circuit breaker. Since most breaker applications are not made dards, IEC Std. 694, Int. Electrotech. Comm., Geneva, 1st ed., 1980.
at the limit of the breaker’s ratings, it should be possible to IEEE Application Guide for AC High-Voltage Circuit Breakers Rated
on a Symmetrical Current Basis, ANSVIEEE Std. C37.010-1979, IEEE
find a circuit breaker that will fit the application regardless Product No. SH06569.
of the set of standards with which it complies. A little care IEEE Application Guide for Transient Recovery Voltage for AC High-
exercised at the start of a project will pay dividends at the end. Voltage Circuit Breakers Rated on a Symmetrical Current Basis,
ANSVIEEE Std. C37.011-1979, IEEE Product NO. SH07005.
IEEE Application Guide for Capacitance Current Switching for AC
REFERENCES High- Voltage Circuit Breakers Rated on a Symmetrical Current Busis,
ANSVIEEE Std. C37.012-1979, IEEE Product No. SH06957.
111 IEEE Standard Rating Structure for ac High-Voltage Circuit Breakers
Rated on a Symmetrical Current Basis, ANSI/IEEE Std. C37.04- 1979,
IEEE Product no. SH06288.
[2] American National Standard for Switchgear-uc High-Voltage Circuit
Breakers Rated on a Symmetrical Current Basis-Preferred Ratings and
Related Required Capabilities, ANSI Std. C37.06-1987, Amer. Nat.
Stds. Inst. Inc, New York.
[3] IEEE Standard Test Procedure for ac High-Voltage Circuit Breakers Baldwin Bridger, Jr. (M’50-SM’59-F’88), For photgraph and biography
Rated on a Symmetrical Current Basis, ANSIflEEE Std. C37.09-1979, please see the Officers in the Industry Applications Society section of this
IEEE Product No. SH06312. issue on page 2.

You might also like