Site Installation Standard Album (TS & Colo. & FTK) V1.1 PDF
Site Installation Standard Album (TS & Colo. & FTK) V1.1 PDF
V1.1
July. 2015
Document name: Site Installation Standard Album (TS & Colo. & FTK)
Prepared by: Xie Jinjun
Good Grid
Transformer
P
Power Grid
G id
3+1 25# AC cable
220Vac 35meter
Bad grid only
+
ATS+OVP+ACDB
Rectifier & Battery(North Star) Battery(North Star) & Equipment
Cabinet Cabinet
Genset
Solar Panel
+ Solar + CDC
+
Battery Battery
ATS + OVP + ACDB ZXDT22 Cabinet Cabinet
G
Genset
t S 01
SF01
+ + CDC
ATS + OVP +
Genset ACDB Battery Battery
ZXDT22 SF01
ZXDT22 SF01 Cabinet Cabinet
ACPDB &
Cabinets
MW & Antenna & RRU
Generator
BTS
Main input
Generator
Generator
input
Loading
Generator grounding
Power cable to
Power cable to
ACDB
Generator output
terminal
Generator
Generator
Grounding
Power Cabinet
Equipment
Cabinet
On grid site
On grid site
2X battery Cabinet
1000AH Off grid Scenario
Equipment
Cabinet CDC & CDC with solar
BBU
Cable tray
Cable tray
LPU
IDU/PTN
BBU grounding
BBU grounding 3G 2100M
3G 2100M 2G 900M
2G 900M
BBU is fixed to rack with 4x screws
To BBU
To IDU
IDU shall be fixed to rack with 4x screws
Bank 1#
Bank 3#
Bank 2#
Battery temperature sensor
Battery temperature sensor connect to
X13, X14, X15 port at PSU
Negative
Positive
Battery temperature sensor
Battery temperature sensor connect to
X13 X14 & X15 port at PSU
X13, X14 & X15 port at PSU
AC input
(from ACDB)
@ Power cabinet
Battery Bank
LLVD2 @ Equipment cabinet
LLVD1
LLVD1 (Left to right)
1#: RRU 2100 32A
2#: RRU 900 32A
2#: RRU 900 32A
LLVD2 (Left to right)
1#: PTN/MW 16A
1#: PTN/MW 16A
2#: PTN/MW 16A
3#: BBU 10A
RRU 900
RRU 900 TX BBU
RRU 2100
AC input
RRU 2100 RRU 900
LLVD1 (Left to right) LLVD2 (Left to right)
1#: RRU 2100 32A
1#: RRU 2100 32A 1#: PTN/MW 16A
/
2#: RRU 900 32A 2#: PTN/MW 16A
3#: A/C 1# 16A 3#: BBU 10A
3#: A/C 2# 16A Power cable termination shall be
protected with heat shrink tube
protected with heat shrink tube
without copper exposure.
1 2 3
Not‐used cable entry shall
N t d bl t h ll
be sealed with rubber
5 4
© ZTE Corporation. All rights reserved. 24
RRU installation – Connector waterproof
1 2 3 4 5
1 (t ) 1 ( tt )
1 (tape) +1 (putty)
Unused port shall be
Unused port shall be
protected with cap.
1 2 Unused port shall be 3
protected with cap.
protected with cap.
To RRU From DCPD7
Shielding layer of power cable shall be
grounded with RRU & ODCPD1
1. Bolts are fasten as per specification with spring & flat washer.
1 B lt f t ifi ti ith i & fl t h
2. Dual bolts is required to fix antenna on tower top
© ZTE Corporation. All rights reserved. 28
Antenna installation ‐ Waterproof
1 (tape) +1 (putty) +3 (tape)
waterproof treatment
Black tape: 2G 900M
Red tape: 3G 2100M
To RRU AISG port
To Antenna AISG port
S1 2G
S1 2G S1 3G
S1 3G S2 2G
S2 2G S2 3G
S2 3G S3 2G
S3 2G
To RRU AISG port
• Tighten torque of 22N.M +/‐10% for M10
• Tighten torque of 4.0N.M +/‐
g q / 10% for IDU
• Be careful not to damage O‐ring
• Reserve IF cable of proper length (2
Reserve IF cable of proper length (2‐5m5m
recommended) at the ODU end.
• Loop the IF cable & fix it at the top
platform with black cable tie.
Cable on ladder shall be clamped at cable
l dd
ladder.
Excessive cable shall be well managed.
Power cable on ground
bl d
or slab shall be
protected with conduit
Cable on ladder shall be clamped at 2.0m
max. interval each.
White cable shall NOT be used outside.
Cable running on tower top shall be
fixed with black cable tie.
Minimum 300mm
Color: yellow/Green
C l ll /G
Dia.: Min. 10mm2
BBU, LPU & IDU grounded to main
BBU, LPU & IDU grounded to main
bus bar in the cabinet
1 (tape) +1 (putty) +3 (tape)
Tower Bottom waterproof treatment
Color: Black
Dia.: 10mm2
Grounding bus bar
© ZTE Corporation. All rights reserved. 41
Grounding
ODU grounding
1 (tape) +1 (putty) +3 (tape)
waterproof treatment
Color: yellow/green
Dia.: 10mm2 min.
Color: Green/Yellow
Dia.: 16mm2 min.
Indoor Outdoor
• Indoor label: Customized paper material.
• Outdoor label: Material should be UV‐rated and waterporoof, along with any cable ties used.
• Label shall attach at which is less than 20mm from end point and facing to the same direction.
• Letter on the label shall be printed & eligible with the same format.
Letter on the label shall be printed & eligible with the same format.