You are on page 1of 1

Rack Installation Considerations [NOT Supplied]

All equipment must be gro unded

M4 screw

Grounding lug

AWG#10-12 Copper Wire

Power Supply Cables

All Equipment (Except HOU &


EPSU) Fitted with IEC 320/C14
Receptacle.
IEC320/C13 > BS1363A P ower
Lead Requ ired. Various Length s.

For HOU & EPSU Fitted with IEC


320/C20 Receptacle.

GENESIS™ (Sub3) Rear View GENESIS™ (Sub3) Front View IEC320/C19 > BS1363A P ower
Lead Requ ired. Various Length s.

24
23
GENESIS™ UPOI SUBRACK (3U) P/N: UPOI_SUBRACK [636201]
22 Additiona l (Spare) Modules: UPI U [636202]: UPOI High Powered 3 Port Attenu ator (Inc QMA cables)
UPI U_BLK [636203]: Genesis UPOI Blank Unit
21
CBL_QMA to QMA_300 [636915]: RF Cable ss402 QMA – QMA, 300mm
20 DFAN [TBD]: Genesis Replacement Fa n Unit

19
18
GENESIS™ DAU SUBRACK (3U) P/N: DAU_SUBRACK_AC_E [636101] or
DAU_SUBRACK_DC_E [636102]
17 Additiona l (Spare) Modules: DRFU_XXX [636301-7]: RF Unit
DRFU_BLK [636306]: Blanking plate
16 DPSU_AC [TBC] or DPSU_DC [TBC]: DAU P ower Su pply Unit
15 DDTU_E [TBC]: DAU Digital Tran sceiver Unit

14 GENESIS™ DCU SUBRACK (1U) P/N: DCU_AC_E [636909]


13 Additiona l Modules: T-Sync_SPL_Kit [636910]: Supporting up to 8 DAU I nc. QMA Cables.

12 GENESIS™ HCU SUBRACK (1U) P/N: HCU_AC [636401] or HCU_DC [636402]


11 Additiona l (Spare) Modules: N/A

10
09 GENESIS™ HOU SUBRACK (1U) P/N: HOU_AC_E [636403]
08 Additiona l (Spare) Modules: HOPSU_AC [617412]: PSU module for HOU, EPSU, and eHUB, AC Input

07 GENESIS™ DMS300Lite (1U) P/N: DMS3000Lite [636002]


Additiona l (Spare) Modules: DMS_License_Extend [636011]: Extended Maintenan ce & Upgrade Package
06
05 GENESIS™ DMS300Pro (2U) P/N: DMS3000Pro [636001]
04 Additiona l (Spare) Modules: DMS_License_Extend [636011]: Extended Maintenan ce & Upgrade Package

03
02
01

Rack Installation Considerations


Ventilatio n Spacin g Between Chassis

All Equipment (Except EPSU)


Does Not Require Ven tilation
Gaps. Only Cabling Ingres s/
Egress Need Be Co nsidered.

For EPSU 1U Gap Above Chas sis


Required.

GENESIS™ (n78) Rear View GENESIS™ (n78) Front View

24
23
22 GENESIS™ UPOI SUBRACK (3U) P/N: UPOI_SUBRACK [636201]
Additiona l (Spare) Modules: UPI U [636202]: UPOI High Powered 3 Port Attenu ator (Inc QMA cables)
21 UPI U_BLK [636203]: Genesis UPOI Blank Unit
CBL_QMA to QMA_300 [636915]: RF Cable ss402 QMA – QMA, 300mm
20
DFAN [TBD]: Genesis Replacement Fa n Unit
19
18 GENESIS™ gRFU SUBRACK (1U) P/N: gRFU_AC_E [TBD] or gRFU_DC_E [TBD]
17 Additiona l (Spare) Modules: gMPSU [TBD]: PSU Module for g MU & gHOU

16 GENESIS™ gMU SUBRACK (1U) P/N: gMU_AC_E [TBD] or gMU_DC_E [TBD]


Additiona l (Spare) Modules: gMPSU [TBD]: PSU Module for g MU & gHOU
15
gFTU [TBD]: Rear mounted Fan tray module
14 GENESIS™ gHOU SUBRACK (1U) P/N: gHOU_AC_E [TBD] or gHOU_DC_E [TBD]
13 Additiona l (Spare) Modules: gMPSU [TBD]: PSU Module for g MU & gHOU
gFTU [TBD]: Rear mounted Fan tray module
12 GENESIS™ EPSU SUBRACK (1U) P/N: EPSU_SUBRACK [617411]
11 Additiona l (Spare) Modules: HOPSU_AC [617412]: PSU module for HOU, EPSU, and eHUB, AC Input
EPSU_BLK [ 617413]: Blanking plate for ESPU slot
10 GENESIS™ gHCU SUBRACK (1U) P/N: gHCU_AC_E [TBD] or gHCU_DC_E [TBD]
Additiona l (Spare) Modules: gFTU [TBD]: Rear mounted Fan tray module
09
08
07 GENESIS™ DMS300Lite (1U) P/N: DMS3000Lite [636002]
Additiona l (Spare) Modules: DMS_License_Extend [636011]: Extended Maintenan ce & Upgrade Package
06
05 GENESIS™ DMS300Pro (2U) P/N: DMS3000Pro [636001]
04 Additiona l (Spare) Modules: DMS_License_Extend [636011]: Extended Maintenan ce & Upgrade Package

03
02
01

Date: 20-10-2021

© SOLiD 2021
SOLiD GENESIS - Generic Rack Deployment Layout - Sub3 & n78
2021-SLD-00001

Drawn By: SCL