PL 70

Current relays (IT, IS, IA, ID, IP, NT, IM, RT, FI and IV)
Data Sheet
DSE_PL70current_eng_AU

No part of this publication may be reproduced


by whatever means without the prior written
permission of Ingeteam T&D.

One of the main aims of Ingeteam T&D lies in


the continuous improvement of the company’s
equipment and, therefore, the information
contained in this catalogue may be modified
without prior notification.

For further information, consult the


corresponding manual or contact us directly.
INDEX 

MODE CODE SELECTION ............................................................................................................. 4


FUNCTIONS TABLE ..................................................................................................................... 5
FUNCTIONAL DESCRIPTION AND CONFIGURATION ...................................................................... 5
General settings ........................................................................................................................................ 5
Protection settings .................................................................................................................................... 5
AUTOMATISM FUNCTIONS ........................................................................................................ 14
DATA ACQUISITION FUNCTIONS ................................................................................................ 15
MEASUREMENTS...................................................................................................................... 15
COMMUNICATION PROTOCOLS.................................................................................................. 16
LOCAL KEYPAD/DISPLAY ........................................................................................................... 17
TESTS ...................................................................................................................................... 18
TECHNICAL SPECIFICATIONS .................................................................................................... 19
ENVIRONMENTAL CONDITIONS ................................................................................................. 22
CONSTRUCTIVE CHARACTERISTICS........................................................................................... 22
CONNECTION DIAGRAMS .......................................................................................................... 23

Ingeteam Transmission & Distribution S.A.


DSC_PL70_Current III
CURRENT RELAYS (IT, IS, IA, ID, IP, NT, IM, RT, FI AND IV) 

MODE CODE SELECTION

Ingeteam Transmission & Distribution S.A.


DSC_PL70_Current 4
CURRENT RELAYS (IT, IS, IA, ID, IP, NT, IM, RT, FI AND IV) 

FUNCTIONS TABLE
Protection
The following table reflects the protection functions incorporated into each unit.

Functions IT IS IA ID IP NT IM RT FI IV
Undercurrent (37) X X
Phase overcurrent (50/51) X X X X** X
Thermal image (49) X X X X X X
Current unbalance (46), Broken conductor (46FA) X X X X
Neutral overcurrent (50/51N) X X X X**
Sensitive neutral overcurrent (50/51NS) X
Residual neutral overcurrent (50/51NR) X X X X
Neutral overcurrent 2 (50/51N2 or G1)) X X
Neutral overcurrent 3 (50/51N3 or G2) X
Voltage controlled overcurrent (51V) X
Breaker failure protection (50BF) X X X X X X X X X
Restricted earth fault protection (87N) X X
Directional neutral overcurrent (67N) X
Insulated neutral directional overcurrent (67NA) X
Overexcitation X
Flashover X
End fault X
Cold load pickup (CLP) O O
Recloser O O
Trip and close circuit surveillance (74TC/CC)* X X X X X X X X X X
Note:
X: Available function O: Optional function *Only with I/O extension module **Single-phase 50/51 or 50/51N depending on the connection

FUNCTIONAL DESCRIPTION AND CONFIGURATION


GENERAL SETTINGS
Setting Minimum Maximum Step Remarks
CT phase ratio 1 3.000 1
CT neutral ratio 1 3.000 1
CT ratio sensitive neutral 1 3.000 1
CT ratio 1 9.999 1
23,0 115,5 0,1 Family IV
Simple rated voltage (V)
40,0 200,0 0,1 Other families
Language English/Spanish

PROTECTION SETTINGS
Undercurrent protection (37) - IT, IS Models
Protects motors and pumps against drops in supply current.

Setting Minimum Maximum Step Remarks


Enabled YES/NO
Pick up (A) 0,10 10,00 0,01
Additional delay (s) 0,00 600 0,01

Ingeteam Transmission & Distribution S.A.


DSC_PL70_Current 5
CURRENT RELAYS (IT, IS, IA, ID, IP, NT, IM, RT, FI AND IV) 

Phase overcurrent protection (50/51) - IT, IS, IP, IM, IV Models


Protects the installation against shortcircuits between phases, with instantaneous and time trips.

Time characteristic setting (1 or 4 optional groups) Minimum Maximum Step Remarks


Enabled YES/NO
Pick up (A) 0,1 100,0 0,01
Definite time
User’s curve.
Curve type
IEC I,MI,EI,IC,IL,MIEs
ANSI I,MI,EI,MODI
0,05 1,09 0,01 For IEC curves
Dial
0,5 30,0 0,1 For ANSI curves
Definite time (s) 0,00 600,00 0,01
Instantaneous characteristic setting – low level ( 4 gorups) Minimum Maximum Step Remarks
Enabled YES/NO
Pick up (A) 0,1 100,0 0,01
Additional delay (s) 0,00 60,00 0,01
Instantaneous characteristic setting – high level ( 4 gorups) Minimum Maximum Step Remarks
Enabled YES/NO
Pick up (A) 0,1 100,0 0,01
Additional delay (s) 0,00 60,00 0,01

Neutral overcurrent protection (50N/51N) - IT, IP, NT, IS Models


In those installations with earthed ground, neutral overcurrent protection.

Time characteristic setting (4 groups) Minimum Maximum Step Remarks


Enabled YES/NO
0,02 20,0 0,01 IT/IS families (C and D models)
Pick up (A) 0,005 5,000 0,001 IS family (A and B models )
0,1 100,0 0,01 IT family (A and B models) ,IP and NT
Definite time
User’s curve.
Curve type
IEC I,MI,EI,IC,IL,MIEs
ANSI I,MI,EI,MODI
0,05 1,09 0,01 For IEC curves
Dial
0,5 30,0 0,1 For ANSI curves
Definite time (s) 0,0 600,0 0,1
Instantaneous characteristic setting – low level ( 4 groups) Minimum Maximum Step Remarks
Enabled YES/NO
0,02 20,0 0,01 IT/IS families (C and D models)
Pick up (A) 0,005 5,000 0,001 IS family (A and B models )
0,1 100,0 0,01 IT family (A and B models) ,IP and NT
Additional delay (s) 0,00 60,00 0,01
Instantaneous characteristic setting – high level ( 4 groups) Minimum Maximum Step Remarks
Enabled YES/NO
0,02 20,0 0,01 IT family D model
Pick up (A)
0,1 100,0 0,01 IT family B model
Additional delay (s) 0,00 60,00 0,01

Ingeteam Transmission & Distribution S.A.


DSC_PL70_Current 6
CURRENT RELAYS (IT, IS, IA, ID, IP, NT, IM, RT, FI AND IV) 

G1 overcurrent protection (50/51G1) - NT, RT Models


Neutral overcurrent protection 2, with the same characteristics as those described for phases (with the exception that it is
solely instantaneous), and independent settings.

Time characteristic setting (4 groups) Minimum Maximum Step Remarks


Enabled YES/NO
0,02 20,0 0,01 RT family (C model)
Pick up (A)
0,1 100,0 0,01 Other families
Definite time
User’s curve.
Curve type
IEC I,MI,EI,IC,IL,MIEs
ANSI I,MI,EI,MODI
0,05 1,09 0,01 For IEC curves
Dial
0,5 30,0 0,1 For ANSI curves
Definite time (s) 0,0 600,0 0,1
Instantaneous charact. setting ( 4 groups) Minimum Maximum Step Remarks
Enabled YES/NO
0,02 20,0 0,01 RT family (C model)
Pick up (A)
0,1 100,0 0,01 Other families
Additional delay (s) 0,00 60,00 0,01

G2 overcurrent protection (50/51G2) - NT model


Neutral overcurrent protection 3, with the same characteristics as those described for phases (with the exception that it is
solely instantaneous), and independent settings.

Time characteristic setting (4 groups) Minimum Maximum Step Remarks


Enbled YES/NO
Pick up (A) 0,1 100,0 0,01
Definite time
User’s curve.
Curve type
IEC I,MI,EI,IC,IL,MIEs
ANSI I,MI,EI,MODI
0,05 1,09 0,01 For IEC curves
Dial
0,5 30,0 0,1 For ANSI curves
Definite time (s) 0,0 600,0 0,1
Instantaneous charact. setting ( 4 groups) Minimum Maximum Step Remarks
Enabled YES/NO
Pick up (A) 0,1 100,0 0,01
Additional delay (s) 0,00 60,00 0,01

Ingeteam Transmission & Distribution S.A.


DSC_PL70_Current 7
CURRENT RELAYS (IT, IS, IA, ID, IP, NT, IM, RT, FI AND IV) 

Directional ground overcurrent protection (67N) - ID Model


Enables the detection of earth faults, with detection of the direction in isolated, compensated or solidly earthed systems.

Time characteristic setting (4 groups) Minimum Maximum Step Remarks


Enabled YES/NO
Pick up (A) 0,1 100,0 0,01
Definite time
User’s curve.
Curve type
IEC I,MI,EI,IC,IL,MIEs
ANSI I,MI,EI,MODI
0,05 1,09 0,01 For IEC curves
Dial
0,5 30,0 0,1 For ANSI curves
Definite time (s) 0,0 600,0 0,1
Instantaneous characteristic setting – low level ( 4 groups) Minimum Maximum Step Remarks
Enabled YES/NO
Pick up (A) 0,1 100,0 0,01
Additional delay (s) 0,00 60,00 0,01
Instantaneous characteristic setting – high level ( 4 groups) Minimum Maximum Step Remarks
Enbaled YES/NO
Pick up (A) 0,1 100,0 0,01
Additional delay (s) 0,00 60,00 0,01
Directional settings (4 groups) Minimum Maximum Step Remarks
Neutral lead/lag 0 359 1
Polarization voltage 1 15 0,1
Trip permission without Vpolariz. YES/NO
Angle extent 0 170 1

Ingeteam Transmission & Distribution S.A.


DSC_PL70_Current 8
CURRENT RELAYS (IT, IS, IA, ID, IP, NT, IM, RT, FI AND IV) 

Sensitive neutral overcurrent protection (50SN/51SN) – IS,IT Model


Enables the detection of highly resistive earth faults. A toroid transformer is required for the measurement of the sensitive
neutral.

Time characteristic setting (4 groups) Minimum Maximum Step Remarks


Enabled YES/NO
0,02 20,0 0,01 IT/ IS families (C and D models)
Pick-up (A)
0,005 5,000 0,001 IT/ IS families (A and B models)
Definite time
User’s curve.
Curve type
IEC I,MI,EI,IC,IL,MIEs
ANSI I,MI,EI,MODI
0,05 1,09 0,01 For IEC curves
Dial
0,5 30,0 0,1 For ANSI curves
Definite time (s) 0,0 600,0 0,1
Instantaneous characteristic setting – low level ( 4 groups) Minimum Maximum Step Remarks
Enabled YES/NO
0,02 20,0 0,01 IT/ IS families (C and D models)
Pick up (A)
0,005 5,000 0,001 IT/ IS families (A and B models)
Additional delay (s) 0,00 600,00 0,01
Instantaneous characteristic setting – high level ( 4 groups) Minimum Maximum Step Remarks
Enabled YES/NO
0,02 20,00 0,01 IS family D model
Pick up (A)
0,005 5,000 0,001 IS family B model
Additional delay (s) 0,00 600,00 0,01

Residual current overcurrent protection (50R/51R) - IT, IS, IP, IV models


This overcurrent protection function operates with residual current, which is the sum of the phase currents calculated
internally by the unit.

This function may be used in those situations in which a neutral transformer is not available.

Time characteristic setting (4 groups) Minimum Maximum Step Remarks


Enabled YES/NO
Pick up (A) 0,1 100,0 0,01
Definite time
User’s curve.
Curve type
IEC I,MI,EI,IC,IL,MIEs
ANSI I,MI,EI,MODI
0,05 1,09 0,01 For IEC curves
Dial
0,5 30,0 0,1 For ANSI curves
Definite time (s) 0,0 600,0 0,1
Instantaneous characteristic setting – single level ( 4 groups) Minimum Maximum Step Remarks
Enabled YES/NO
Pick up (A) 0,1 100,0 0,01
Additional delay (s) 0,00 60,00 0,01

Ingeteam Transmission & Distribution S.A.


DSC_PL70_Current 9
CURRENT RELAYS (IT, IS, IA, ID, IP, NT, IM, RT, FI AND IV) 

Current unbalance protection (46) – IT, IS, IP, IV models


Protects the installation against current unbalances, produced as a result of anomalies in the power system, or due to
unbalanced loads.

Time characteristic setting (4 groups) Minimum Maximum Step Remarks


Enabled YES/NO
Pick up (A) 0,1 100,0 0,01
Definite time
User’s curve.
Curve type
IEC I,MI,EI,IC,IL,MIEs
ANSI I,MI,EI,MODI
0,05 1,09 0,01 For IEC curves
Dial
0,5 30,0 0,1 For ANSI curves
Definite time (s) 0,1 600,0 0,1
Instantaneous characteristic setting ( 4 groups) Minimum Maximum Step Remarks
Enabled YES/NO
Pick up (A) 0,1 100,0 0,01
Additional delay (s) 0,10 60,00 0,01

Broken conductor protection (46FA) - IT, IS, IP, IV model


Detects one phase loss in the protected line, providing trip to the Circuit Breaker.It is a definite time protection unit.

Settings (4 groups) Minimum Maximum Step Remarks


Enabled YES/NO
I2
Pick up (A) 0,10 0,50 0,01 I1
Expressed as a decimal.
Definite time (s) 0,05 300,0 0,01

Phase overcurrent controlled by voltage supervision (51V) - IV model


Reduces the pick-up threshold of the overcurrent unit in accordance with the voltage level. Thus, the trip time is reduced
in the event of severe and close-up faults (with voltage drop).

Setting Minimum Maximum Step Remarks


Enabled YES/NO
V. control (V) 10,0 200,0 0,1
Pick up (A) 0,10 20,00 0,01
Definite time
User’s curve.
Curve type
IEC I,MI,EI,IC,IL,MIEs
ANSI I,MI,EI,MODI
Dial 0,05 30,00 0,01
Definite time (s) 0,00 600,0 0,01

Ingeteam Transmission & Distribution S.A.


DSC_PL70_Current 10
CURRENT RELAYS (IT, IS, IA, ID, IP, NT, IM, RT, FI AND IV) 

Restricted earth fault protection (87N) - IP, NT model


By comparing the neutral currents, this unit enables the detection of earth faults in the protected device. The function
compares the neutral current of one side of the breaker with the neutral current (or residual current) of the other side.

Setting Minimum Maximum Step Remarks


Enabled YES/NO
Pick up (A) 0,2 100,0 0,01
Additional delay (s) 0,00 10,00 0,01

Cold load pickup (Optional) - IT, IS models


Detects feeder connection conditions, avoiding non-desired trips due to possible in-rush. The function detects such
conditions and changes the trip settings during a programmed time.

Setting Remarks
Enabled YES/NO
Cold load time 0 to 10000 sec.
Operation time 0 to 3600 sec.

Insulated neutral protection (67 NA) – IA model


This unit provides protection against earth faults in insulated earth systems, by means of the detection of capacitive
currents.It is a directional unit.

Setting Minimum Maximum Step Remarks


Enabled YES/NO
Torque control (“external lock”)
Low current (A) 0,005 1 0,001
High current (A) 0,005 1 0,001
Low voltage (V) 0,5 60,0 0,1
High voltage (V) 0,5 60,0 0,1
1st trip time delay (s) 0,0 60,0 0,1
Inst. switchover time 0,0 10,0 0,1

Thermal image (49) - IT, IS, IP, IM, RT, IV models


Protects elements such as lines, transformers, etc., against thermal overloads by calculating the temperature in
accordance with the protected unit’s current and recent load conditions.

Setting Minimum Maximum Step Remarks


Enabled YES/NO
Heating time constant (min) 3 60 1
Cooling time constant (min) 3 180 1
Alarm threshold (%) 80 100 1
Reset threshold (%) 50 99 1
Rated current (A) 0,1 100,0 0,01

Ingeteam Transmission & Distribution S.A.


DSC_PL70_Current 11
CURRENT RELAYS (IT, IS, IA, ID, IP, NT, IM, RT, FI AND IV) 

Breaker failure protection (50BF) - IT, IS, ID, IP, IM, NT, RT, FI, IV models
Verifies the correct functioning of a breaker when clearing a fault. In the event of an incorrect functioning of a breaker
when clearing a fault, the protection trips the breakers necessary to isolate the fault.

Minimum Maximum Step Remarks


Setting (4 groups)

YES/NO
Enabled

Phase reset (A) 0,1 100,0 0,01


0,02 20,0 0,01 IS/IT families (C and D models) and RT (C model)
Neutral reset (A) 0,005 5,000 0,001 IS families (A and B models)
0,1 100,0 0,01 Other families
Definite time (sec) 0,0 60,00 0,01

The breaker failure protection unit of the FI model is special:

Breaker open failure

Detects breaker operation failure when receiving an open command. It can work in single-pole or three-pole mode.

Setting (4 groups) Minimum Maximum Step Remarks


Three-polar, general trip
Three-polar, general or monophase trip
Operation mode
Monopolar,monopolar trip*
Monopolar,general or monopolar trip*
Failure to trip on fault
Enabled Disabled/External trip enabled
Trip signal Impulse/Permanent
CB 52 status Independent/Both
Phase BF pickup current (A) 0,10 100 0,01
Earth BF pickup current (A) 0,10 100 0,01
Retrip time delay (sec) 0 60 0,001
Trip time delay (sec) 0 60 0,001
Failure to open on load
Enabled YES/NO
Load threshold (A) 0,10 10 0,1
Failure on load time delay 1 (sec) 0 1 0,001
Failure on load time delay 2 (sec) 0 1 0,001

*Only for units with extension board

Ingeteam Transmission & Distribution S.A.


DSC_PL70_Current 12
CURRENT RELAYS (IT, IS, IA, ID, IP, NT, IM, RT, FI AND IV) 

Open failure with low load or neutral current

Detects breaker operation failure when receiving a three-pole or two-pole trip command being some of the breakers closed
or having neutral current flow.

Setting (4 groups) Minimum Maximum Step Remarks


Enabled YES/NO
Two phase trip allowance YES/NO
Neutral detection enable YES/NO
Neutral current threshold (A) 0,10 100 0,01
Redundant trip time (sec) 0 60 0,001
Trip time (sec) 0 60 0,001
Trip signal Impulse/Permanent

Flashover – FI model
Protects against damage in the breaker due to internal arc between its contacts.

Minimum Maximum Step Remarks


Setting (4 groups)

Enabled NO/ Only current


Flashover pickup (A) 0,05 100 0,01
Flashover time delay (sec) 0,01 1 0,01

End fault – FI model


Protects against fault ocurred between the current transformer and the breaker, being this one opened. It gives open
command to those breakers associated to the end fault.

Minimum Maximum Step Remarks


Setting (4 groups)

Enabled YES/NO
End fault threshold (A) 0,1 100 0,1
End fault definite time (sec) 0 1 0,001

Overexcitation protection (24) - Modelo NT


Since the overexcitation of the protected unit can be assimilated to the voltage quotient (V) between the frequency (Hz),
the pick up is set as a decimal of the value of the quotient between the rated voltage and rated frequency.

Time characteristic (4 groups) Minimum Maximum Step Remarks


Enabled YES/NO
Minimum voltage (V) 40 120 1
Pick up (%Vn/Fn) 100 400 1
Definite time
User’s curve.
Timed response type
IEC I,MI,EI,IC,IL,MIEs
ANSI I,MI,EI,MODI
0,05 1,09 0,01 Para curvas IEC
Dial
0,5 30,0 0,1 Para curvas ANSI
Definite time(s) 0,00 100,0 0,1
Drop off time (s) 0,00 100,0 0,1

Ingeteam Transmission & Distribution S.A.


DSC_PL70_Current 13
CURRENT RELAYS (IT, IS, IA, ID, IP, NT, IM, RT, FI AND IV) 

Instantaneous charcateristic Minimum Maximum Step Remarks


Enabled YES/NO
Minimum voltage (V) 40 120 1
Pickup (%Vn/Fn) 100 400 1
Definite time (s) 0,00 10,0 0,01
Drop off time (s) 0,00 100,0 0,1

AUTOMATISM FUNCTIONS
Recloser (79) - Optional IT, IS models
Enables the automatic reconnection of the system following transient faults.

Setting (4 tables) Minimum Maximum Step Remarks


Recloser in operation YES/NO
Sequence coordination YES/NO
Number of reclosures 0 4 1
Dead time for the first reclosure of faults between phases (s) 0,05 600,0 0,01
Dead time for the second reclosure of faults between phases (s) 1 600 1
Dead time for the third reclosure of faults between phases (s) 1 600 1
Dead time for the fourth reclosure of faults between phases (s) 1 600 1
Dead time for the first reclosure of faults to earth (s) 0,05 600,0 0,01
Dead time for the second reclosure of faults to earth (s) 1 600 1
Dead time for the third reclosure of faults to earth (s) 1 600 1
Dead time for the fourth reclosure of faults to earth (s) 1 600 1
Reclaim time after automatic closure of faults between phases (s) 1 600 1
Reclaim time after automatic closure of faults to earth (s) 1 600 1
Reclaim time after manual closure (s) 1 600 1
Dead time for reference voltage (s) 1 600 1

Sequence coordination
This function supervises a reclosing sequence performed by the relay closer to the fault by following the whole cycle.

Operating logic
Ensures the correct functioning of the breaker and protects the relay. Also generates an alarm in the event of the non-completion
of an effected operation.

Setting (4 tables) Minimum Maximum Step Remarks


Trip sealing YES/NO
Breaker opening failure timing (s) 0,02 15,000 0,005
Breaker closure failure timing (s) 0,02 15,000 0,005

Ingeteam Transmission & Distribution S.A.


DSC_PL70_Current 14
CURRENT RELAYS (IT, IS, IA, ID, IP, NT, IM, RT, FI AND IV) 

DATA ACQUISITION FUNCTIONS


Type Description Non-volatile memory capacity
Date and time: Day/month/year hour/min/sec. m.sec.
Events Description of the event 400 events
Phase and neutral currents
Date and time: day/month/year hour/min/sec. m.sec
Description of the fault
Detail:
 Available units
 Units tripped during the fault
 Units picked-up during the fault
 Fault start date and -time (first unit picked up)
 Trip date and time (first unit tripped)
 Fault end date and time (when the trip signal disappears)
Faults  Current opened by breaker (maximum phase current detected between 20 faults
the moment the trip order is issued and the breaker opening)
 Setting table active during the fault
 Fault and trip type
 Pre-fault phase current in module and angle
 Fault phase current, module and angle
 Tripped phases
 Maximum currents of each phase and neutral during the fault
 Fault start and finish date and time
Measurement Date and time recording 200,500,1000,2000,3000,4000
historical report Each register contains the maximum and minimum average currents recordings
kl2 sum (kA opened by each breaker pole)
Statistical data Automatic reclosure meters
Breaker opening meter (trips or manual)
Date and time
Description Up to 600 cycles, distributed in a
Oscillograph data Up to 5 analogue channels (depending on model), the number of samples per number of pre-programmed registers
recorder channel cycle is 32 (depending on the number of
(optional) The number of cycles prior to the pickup and the length of each register are historical measurement recorded)
programmable
Digital channels: 60 selectable

MEASUREMENTS
Measurements IT IS IA ID IP IM NT RT FI IV
IA X X X X X X
IB X X X X X
IC X X X X X
Medium X X X X X
IN X X X X X X
INS X X
IN2 X
IN3 X
V comp X X
VN X X
Current maximeter X X X X X X

Ingeteam Transmission & Distribution S.A.


DSC_PL70_Current 15
CURRENT RELAYS (IT, IS, IA, ID, IP, NT, IM, RT, FI AND IV) 

COMMUNICATION PROTOCOLS
Communication via front port (Port 1_1):

 Serial (RS232C)
 PROCOME
Communication via rear port 2 (Port 1_2):

 Serial (RS232, RS485, G.F.O., P.F.O.)


 PROCOME
 Ethernet (RJ45)
 PROCOME TCP/IP
Communication via rear port 1 (Port 2):

 Serial (RS232, RS485, G.F.O., P.F.O.)


 PROCOME (this option is not available if the rear port 2 is Ethernet)
 DNP3.0
 MODBUS
 IEC 60870-5-103

Ingeteam Transmission & Distribution S.A.


DSC_PL70_Current 16
CURRENT RELAYS (IT, IS, IA, ID, IP, NT, IM, RT, FI AND IV) 

LOCAL KEYPAD/DISPLAY

6 RED LEDS AND 1 LIQUID CRYSTAL


GREEN/RED DISPLAY 2 LINES
WITH 8 CHARACT.

4-KEY KEYBOARD

RS232 CONNECTOR

Ingeteam Transmission & Distribution S.A.


DSC_PL70_Current 17
CURRENT RELAYS (IT, IS, IA, ID, IP, NT, IM, RT, FI AND IV) 

TESTS

Ingeteam Transmission & Distribution S.A.


DSC_PL70_Current 18
CURRENT RELAYS (IT, IS, IA, ID, IP, NT, IM, RT, FI AND IV) 

TECHNICAL SPECIFICATIONS
Auxiliary power supply
220 Vac
Range 176-264 Vac.
Ripple 20 % over the rated value
12 Vdc
Range 9-15 Vdc
Ripple 20 % over the rated value
24-48 Vdc
Range 19-58 Vdc
Ripple 20 % over the rated value
110-125-220 Vdc
Range 86-280Vdc
Ripple 20% over the rated value
Burden 7W min/ 12W max
Current circuits
Thermal capacity for phase I (unified rated current 5/1A)
Continuous 20 A
Short term (1 s.) 500 A
Very short term (½ cycles) 1250 A
Burden at In = 5 A <0.2 VA
Burden at In = 1A <0.02 VA
Thermal capacity for sensitive neutral I (Single rated current 0.25/0.025 A)
Continuous 20 A
Short term (1 s.) 100 A
Burden at In = 0.25 A <0.0010VA
Voltage circuits
Thermal capacity
Permanent 260 V
Burden at 63.5 V 0.015 VA
Burden at 100V <0.03 VA
Programmable phase shift: ABC or CBA

Closed terminals for voltage and current input (optional)


Terminal pitch 9.5 mm
Digital inputs and outputs without extension board
Number of inputs 2
Number of outputs 6

Digital inputs and outputs with extension board (without IRIG-B)


Number of inputs 8
Number of outputs 11
Digital inputs and outputs with extension board (with IRIG-B)
Number of inputs 7
Number of outputs 11

Ingeteam Transmission & Distribution S.A.


DSC_PL70_Current 19
CURRENT RELAYS (IT, IS, IA, ID, IP, NT, IM, RT, FI AND IV) 

Optoisolated digital inputs


Voltage range 9,6-50 Vdc
Inactive below 7,2 Vdc
Voltage range 19-160 Vdc
Inactive below 13 Vdc
Voltage range 86-280 Vdc
Inactive below 60 Vdc
Burden < 3mA
Output contacts
Trip relays (relays 1 to 5)
Carry (permanent) 5 A at 25 ºC
Make and carry for 0.5 s 30 A
Breaking capacity (L/R=40 ms)
220 Vdc 0.2 A
125 Vdc 0.5 A
48 Vdc 0.5 A
Breaking capacity (resistive)
220 Vdc 0.4 A
125 Vdc 1A
48 Vdc 3A
Performance time 8 ms.
Auxiliary relay (Relay 6 to 11)
Carry (permanent) 5 A at 25 ºC
Make and carry for 0.5 s 30 A
Breaking capacity (L/R=40 ms)
220 Vdc 0.15 A
125 Vdc 0.3 A
48 Vdc 0.5 A
Breaking capacity (resistive)
220 Vdc 0.15 A
125 Vdc 0.4 A
48 Vdc 2A
Performance time 8 ms.
Frequency
Programmable system frequency 50/60 Hz
Operational range Fn ± 5 Hz
Communications ports
Front communication port
RS232C connector DTE 9 pin D type female
Cable length 2 m maximum
Baud rate 600-38400 bps
Insulation No
Types of rear communication ports
RS232
RS232C connector DTE pin D type female
Cable type Shielded
Cable length 15 m max.
Insulation 500V

Ingeteam Transmission & Distribution S.A.


DSC_PL70_Current 20
CURRENT RELAYS (IT, IS, IA, ID, IP, NT, IM, RT, FI AND IV) 

RS485
RS485 connector DTE pin D type female
Cable type Shielded twisted pair
Cable length 1000 m max.
Insulation 500V
G.F.O.
G.F.O. Connector ST
Wavelength 820 nm
Permitted attenuation 8 db with 62.5 /125 µm glass fibre
Multimode glass fibre optic 62.5 /125 µm
P.F.O.
P.F.O. connector HP standard
Wavelength 660 nm
24.7 db with 1mm plastic cable
Permitted attenuation
22 db with 200 µm silica cable
115 m with 1mm low frequency plastic
Maximum distance cable
1.9 Km with 200 µm silica cable
Ethernet RJ45
RJ45 connector RJ45 Female
Cable type Shielded
Cable length 100 m max.
Insulation 500V
Baud rate 10/100 Mbps
IRIG-B port (optional)
Input Demodulated
Input level TTL
Cable type 2-wire, shielded
Insulation 500V
Accuracy
For unified rated current 5/1A Class 1 for V, I and P (up to120% nominal)
Accuracy in the protected range 3%
Curve operation accuracy ±5% or 30ms (the highest of the two values)
Bank voltage monitoring (optional)
24-48 Vdc
Range 19 to 58 Vdc
110-125-220 Vdc
Range 86 to 280 Vdc
12 Vdc
Range 9 to 15 Vdc
220 Vac
Range 176 to 264 Vac

Ingeteam Transmission & Distribution S.A.


DSC_PL70_Current 21
CURRENT RELAYS (IT, IS, IA, ID, IP, NT, IM, RT, FI AND IV) 

Mechanical characteristics
Weight 1.6 Kg
Approx. weight With packaging and documentation 2.6 Kg
Front IP IP40
Optional front IP IP54

ENVIRONMENTAL CONDITIONS
Operating temperature
24-48 Vdc -20ºC to 65 ºC
110-125-220 Vdc -20ºC to 60 ºC
12 Vdc -20ºC to 70 ºC
220 Vac -20ºC to 70 ºC
Storage temperature -40ºC to 85ºC
Up to 95% without
Relative humidity
condensation

The LCD contrast is not operative for temperatures below -20º and above 70ºC.

CONSTRUCTIVE CHARACTERISTICS

PL70IT, IS, IA, ID, IP, NT, IM, RT, FI and IV dimensions

Ingeteam Transmission & Distribution S.A.


DSC_PL70_Current 22
CURRENT RELAYS (IT, IS, IA, ID, IP, NT, IM, RT, FI AND IV) 

CONNECTION DIAGRAMS
The following figures reflect only one of the possible digital input and output programming options (very simple).

IT family

Ingeteam Transmission & Distribution S.A.


DSC_PL70_Current 23
CURRENT RELAYS (IT, IS, IA, ID, IP, NT, IM, RT, FI AND IV) 

IS family

Ingeteam Transmission & Distribution S.A.


DSC_PL70_Current 24
CURRENT RELAYS (IT, IS, IA, ID, IP, NT, IM, RT, FI AND IV) 

ID, IA families

Ingeteam Transmission & Distribution S.A.


DSC_PL70_Current 25
CURRENT RELAYS (IT, IS, IA, ID, IP, NT, IM, RT, FI AND IV) 

IP family

Ingeteam Transmission & Distribution S.A.


DSC_PL70_Current 26
CURRENT RELAYS (IT, IS, IA, ID, IP, NT, IM, RT, FI AND IV) 

NT family

Ingeteam Transmission & Distribution S.A.


DSC_PL70_Current 27
CURRENT RELAYS (IT, IS, IA, ID, IP, NT, IM, RT, FI AND IV) 

IM family

Ingeteam Transmission & Distribution S.A.


DSC_PL70_Current 28
CURRENT RELAYS (IT, IS, IA, ID, IP, NT, IM, RT, FI AND IV) 

RT family

Ingeteam Transmission & Distribution S.A.


DSC_PL70_Current 29
CURRENT RELAYS (IT, IS, IA, ID, IP, NT, IM, RT, FI AND IV) 

FI family

Ingeteam Transmission & Distribution S.A.


DSC_PL70_Current 30
CURRENT RELAYS (IT, IS, IA, ID, IP, NT, IM, RT, FI AND IV) 

IV family

Ingeteam Transmission & Distribution S.A.


DSC_PL70_Current 31
CURRENT RELAYSParque
(IT, IS,Tecnológico
IA, ID, IP, NT, IM, RT,• FIEdificio
de Bizkaia AND IV) 
108
48170 Zamudio, Bizkaia, Spain
Tel +34 94 601 8900
Fax +34 94 601 8901
ingeteamtd@ingeteam.com

Ingeteam Transmission & Distribution S.A.


Ingeteam Transmission & Distribution, S.A.
DSC_PL70_Current www.ingeteam.com 32

You might also like