SIPROTEC 5

Configuration
Aug 20, 2019 6:25 AM

Device: 7UM85 Generator Protection

Product code
Short: P1L115320
Long: 7UM85-DAAA-AA0-0AAAA0-A10121-13611B-BBB000-000AC0-CB2BA1-CK2CD0

Firmware: Current version


Housing width: 2/3 x 19''
Housing type: Surface mounting
Binary inputs: 21
Binary outputs: 22 Relays (10 Standard, 10 Fast, 0 High-Speed, 2 Power)
Current transformers: 6 for protection, 2 for measurement and sensitive ground-current detection
Voltage transformers: 7
Measuring-transducer inputs: 4 (20 mA or 10 V, fast)
0 (20 mA, standard)
CPU: CP300
Modules in 19" row 1: IO202 , PS201 , IO210 , IO204
Modules in 19" row 2:
LEDs/Push-buttons: 16 LEDs
Operation Panel: Detach, width=1/3 + 5.0m cable
Key switch: Without
Display type: Large display
Front Design: Standard
SIPROTEC 5
Configuration
Aug 20, 2019 6:25 AM

Power Supply: DC 60 V-250 V, AC 100 V-230 V

Communication/Plug-in modules:
Communications encryption: Normal
Integrated Ethernet port J: for DIGSI 5
Plug-in module position E: ETH-BB-2FO: 2x optical Ethernet 100 Mbit/s, 1300 nm, duplex LC connector,
2 km over 50/125 um or 62.5/125 um multimode optical fiber Communication
Protocols: applicable for DIGSI 5, IEC 61850-8-1 MMS and GOOSE, IEC
60870-5-104, DNP3 TCP, Modbus TCP, Synchrophasor (IEEE C37.118 - IP),
Profinet IO, SUP, DHCP, SNTP, SNMP, etc. Redundancy protocols: Line Mode,
RSTP, HSR, PRP
Plug-in module position F: ETH-BB-2FO: 2x optical Ethernet 100 Mbit/s, 1300 nm, duplex LC connector,
2 km over 50/125 um or 62.5/125 um multimode optical fiber Communication
Protocols: applicable for DIGSI 5, IEC 61850-8-1 MMS and GOOSE, IEC
60870-5-104, DNP3 TCP, Modbus TCP, Synchrophasor (IEEE C37.118 - IP),
Profinet IO, SUP, DHCP, SNTP, SNMP, etc. Redundancy protocols: Line Mode,
RSTP, HSR, PRP

Functions:
Function points class: Base + 600 function points

Note on function-points class


The function-points class results from the sum of the function points of the selected functions. You can apply these
functions as selected. The device allows also each other selection of functions as long as the sum of the required
function points is within the selected function-points class. With the maximum function-points class of 1400 it is
possible to activate all the functions in the device. The function-points exceeding 1400 are free of charge. In the
engineering phase DIGSI 5 checks that the selected configuration is suitable (capable of running in the device) before
loading it to the device.

Miscellaneous:
Warranty: 5 years
Special approvement: Without
Firmware: Current version
SIPROTEC 5
Configuration
Aug 20, 2019 6:25 AM

Functional scope 7UM85 Generator Protection:


Always Add selected Result
ANSI Function Abbr. included Qty. x Value = Points Qty.
Hardware quantity structure expandable I/O

Process Bus Client Protocol (Note: This PB client 1 x 100 = 100 1x


function requires at least one dedicated
ETH-BD-2FO plug-in module, with
V8.0)
IEC61850-9-2 Merging Unit stream MU x 200 =
(Note: This function requires a
dedicated ETH-BD-2FO per stream,
with V8.0)
21T Impedance protection for transformers Z< x 25 =
24 Overexcitation protection V/f 2x x 25 = 2x
25 Synchrocheck, synchronization function Sync x 50 =
25 Synchronization function with balancing Sync 1 x 80 = 80 1x
commands
32, 37 Power protection active/reactive power P<>, 1 x 15 = 15 1x
Q<>
27 Undervoltage protection: "3-phase" V< 2x x 5 = 2x
or "positive-sequence system V1" or
"universal Vx"
27 Undervoltage protection: "3-phase" or V< 2x x 5 = 2x
"universal Vx"
Undervoltage-controlled reactive power Q>/V< x 15 =
protection
32R Reverse-power protection - P< 2x x 5 = 2x
37 Undercurrent I<

37 Power-plant disconnection protection -dP 1 x 50 = 50 1x


38 Temperature supervision >

40 Underexcitation protection 1/xd 2 x 45 = 90 2x


46 Negative-sequence overcurrent I2> 2x x 5 = 2x
protection
46 Unbalanced-load protection (thermal) I2² t> 1x x 10 = 1x
46 Negative-sequence overcurrent I2>, x 5 =
protection with direction (V2,I2)
47 Overvoltage protection, negative- V2> 2x x 5 = 2x
sequence system
SIPROTEC 5
Configuration
Aug 20, 2019 6:25 AM

Functional scope 7UM85 Generator Protection:


Always Add selected Result
ANSI Function Abbr. included Qty. x Value = Points Qty.
47 Overvoltage protection, negative- V2/V1> 2x x 5 = 2x
sequence/positive-sequence system
48 Starting-time supervision for motors I²start x 10 =
49 Thermal overload protection , I²t 2x x 10 = 2x
49 Thermal overload protection, user- , I²t 1x x 5 = 1x
defined characteristic
49H Hot spot calculation h, I²t x 20 =
49R Thermal overload rotor protection R
(motor)
49F Field-winding overload protection IF² t x 10 =
49S CG Stator overload protection with cold-gas , I²t x 15 =
consideration
49R CG Rotor overload protection with cold-gas , IR²t x 15 =
consideration
50N/ Overcurrent protection, ground IN>
51N TD
50/51 Overcurrent protection, phases I> 2x x 30 = 2x
TD
Instantaneous tripping at switch onto SOTF 1 x 10 = 10 1x
fault
50HS Instantaneous high-current tripping I>>>

50/51 Overcurrent protection with positive- I1>


TD sequence current I1 (from V7.9)
50N/ Overcurrent protection, 1-phase IN>
51N TD
50Ns/ Sensitive ground-current detection INs> 1 x 5 = 5 1x
51Ns for systems with resonant or isolated
neutral systems incl. a) 3I0>, b)
admittance Y0>, c) 3I0-harm> (from
V7.8)
50Ns/ Sensitive ground-current protection INs> 1 x 5 = 5 1x
51Ns for systems with resonant or isolated
neutral systems
Intermittent ground-fault protection Iie> x 20 =
50GN Shaft-current protection INs> x 10 =
SIPROTEC 5
Configuration
Aug 20, 2019 6:25 AM

Functional scope 7UM85 Generator Protection:


Always Add selected Result
ANSI Function Abbr. included Qty. x Value = Points Qty.
50/27 Inadvertent energization protection I>, 1 x 15 = 15 1x
V<reset
50N Direct-current/ direct-voltage protection IDC<>, x 10 =
DC, VDC <>
27,59F
DC
50 Startup overcurrent protection I-Start > x 20 =
50BF Circuit-breaker failure protection, 3-pole CBFP x 10 =
50RS Circuit-breaker restrike protection CBRS x 20 =
50L Load-jam protection I>L x 5 =
51V Overcurrent protection, voltage t=f(I,V) 2x x 10 = 2x
dependent
59, 59N Overvoltage protection: "3-phase" V> 2x x 5 = 2x
or "zero-sequence system V0" or
"universal Vx"
59N, Stator ground-fault protection (non- V0>,
67Ns directional, directional) (V0,I0)
27TH, Stator ground-fault protection with 3rd V03.H<, 1 x 20 = 20 1x
59TH, harmonic V03.H>;
59THD V03.H
59N IT Turn-to-turn fault protection V0> x 15 =
60 Voltage-comparison supervision U> x 5 =
64S Stator ground-fault protection 100 % RSG< x 55 =
(20Hz)
64F, Rotor ground-fault protection (IRgnd>, IRG> 2x x 5 = 2x
frated fn)
64F, Rotor ground-fault protection (Rgnd<, RRG< x 10 =
frated fn)
64F Rotor ground-fault protection (1 - 3 Hz) RRG< x 25 =
(1-3Hz)
66 Restart inhibit for motors I²t x 15 =
67 Directional overcurrent protection, I>, (V,I) x 5 =
phases
67N Directional overcurrent protection for IN>, (V,I) x 30 =
ground faults in grounded systems
SIPROTEC 5
Configuration
Aug 20, 2019 6:25 AM

Functional scope 7UM85 Generator Protection:


Always Add selected Result
ANSI Function Abbr. included Qty. x Value = Points Qty.
67N Directional overcurrent protection, IN>, (V,I) x 15 =
ground
67Ns Dir. sensitive ground-fault detection 1 x 30 = 30 1x
for systems with resonant or isolated
neutral incl. a) 3I0>, b) V0>, c) Cos-/
SinPhi, d) Transient ground-fault fct., e)
Phi(V,I), f) admittance
Directional stage with a harmonic; (V0h,I0h) x 10 =
Note: this stage additionally requires
the function "67Ns Dir. sensitive
ground-fault detection for systems with
resonant or isolated neutral"
Directional intermittent ground-fault Iie dir> x 20 =
protection
68 Power-swing blocking Z/t x 25 =
74TC Trip-circuit supervision TCS

74CC Closed-circuit supervision (from V7.9) CCS

78 Out-of-step protection Z/t x 55 =


81 Frequency protection: "f>" or "f<" or "df/ f<>; df/ 1x x 5 = 1x
dt" dt<>
81U Underfrequency load-shedding f<(UFLS) x 15 =
81 AF Abnormal frequency protection fBand x 15 =
Vector-jump protection > x 20 =
86 Lockout

87T Transformer differential protection I x 40 =


87N T Restricted ground-fault protection IN x 15 =
87M Motor differential protection I x 40 =
87G Generator differential protection I 2 x 40 = 80 2x
PMU Synchrophasor measurement PMU x 40 =
AFD Arc-protection (only with plug-in module
ARC-CD-3FO)
Measured values, standard

Measured values, extended: Min, Max, x 3 =


Avg
SIPROTEC 5
Configuration
Aug 20, 2019 6:25 AM

Functional scope 7UM85 Generator Protection:


Always Add selected Result
ANSI Function Abbr. included Qty. x Value = Points Qty.
Switching statistic counters

Circuit-breaker wear monitoring Ix, I²t, 2P x 10 =


CFC (Standard, control)

CFC arithmetic 1 x 40 = 40 1x
Switching sequences function x 5 =
Inrush current detection

External trip initiation

Control

PoW Point-on-Wave Switching (from V7.9) PoW x 425 =


Fault recording of analog and binary
signals
Monitoring and supervision

Protection interface, serial

Circuit-breaker 4x x 3 = 4x
Disconnector/Grounding switch 4x x 3 = 4x
Transformer side 7UM85 2x x 30 = 2x
Frequency-tracking groups (from V7.8)

Temperature acquisition via


communication protocol
Cyber Security: Role-Based Access x 25 =
Control (from V7.8)
Sum: 540