Professional Documents
Culture Documents
Sulfur Dew Point PDF
Sulfur Dew Point PDF
INTRODUCTION
In a letter (Ref No. 2500/0852 dated 23.3.1426) addressed to the Manager, R&D
Center, the Manager, SWCC Shuqaiq Plant informed about the failure of Boiler # 1
Economizer tubes. The Manager, Shuqaiq Plant requested RDC to carry out failure
analysis and sought advice on any further operation and maintenance strategy. Two
damaged tubes (tube #2 from row #13 and tube #2 from row # 14) were sent for
investigations by the plant. The RDC decided to take up the task.
BACKGROUND
The T & I Department, Shuqaiq Plant provided the following first-hand information
about the failure incidence took place related to economizer tube:
During the normal boiler operation, on 24 January 2005, a heavy water leakage was
observed at the flue gas outlet duct (upstream of economizer). Subsequently, the boiler
was brought to shut down and the manhole was opened for economizer inspection.
Heavy water leakage was observed from the bottom of the economizer coils at the 13th
and 14th rows – 2nd tubes from the top rows of the tube bank, approximately 300 mm
away from the water wall tube.
The washing of the external boiler tubes was carried out by the contractor followed by a
detailed visual testing by the T & I department. The important observations made were
as follows:
PHYSICAL EXAMINATION
The two samples of economizer tubes provided by the Shuqaiq Plant were visually
examined in as received condition. The external surface of the tubes appeared to be
cleaned without any deposits. Figure 4 shows two feed water inlet economizer tube # 2
samples from rows # 13 and 14, respectively. The magnified views of tube # 2, row 13
shows a large fish mouth rupture near the feed water inlet, a pin hole is also present
slightly away from the rupture (Fig. 5). The cross section of tube # 2, row 13 shows
wall thinning at the side of the rupture (Fig. 6). The shape of fish mouth rupture
indicates that rupture occurred from inside of the tube. Fig. 7 shows a closer view of
tube # 2, row 14. The tube appears to be without any pin hole, pit or rupture.
METALLOGRAPHIC STUDIES
The microstructures of the cross sections of economizer tube provide information about
the matrix structure and scaling. The fire side of the tube # 2, row 14 (inside furnace)
shows matrix structure which is pearlitic – ferritic without scaling but the side appears
to be fissured (Fig. 8). The outer side of the tube # 2, row 14 (outside furnace) shows a
coarsened peartlitic–ferritic with no scaling but some decarburization (Fig. 9).
The EDX studies have been carried out to determine the elemental compositions of the
matrix and the deposits/scales on the boiler tubes.
The EDX profile (Fig. 10) of the fire side of inlet tube # 2, row 14 (inside furnace)
shows iron in very high concentrations (81.3%) with low vanadium (4.7%). The EDX
(Fig. 11) of the inner most layer has some vanadium (2.9%) with very low sulfur
(0.22%). The results of EDX studies indicate that there is substantial incorporation of
vanadium compounds in the economizer tube during boiler operation. The source of the
vanadium compounds is flue gas.
Due to cleaning of economizer tubes after failure, the boiler samples received by the
RDC had no deposits on the external surface. This information is very important in
point of view of failure investigation. However, Shuqaiq Plant authorities sent fly ash
sample from boiler # 1, economizer area, which was collected during third economizer
tubes failure on 26/6/2005. This ash sample reflects the nature of ash deposited on
economizer tube during first failure on 24/1/2005. The composition of the ash sample is
given in table 2. EDX profile (Fig. 12) indicates significant concentration of sulfur
(12.8%), low concentration of vanadium (1.5%) and high concentration of iron
(34.0%). The high iron contents indicate that the ash is rich in iron sulfide / sulfate
containing corrosion products.
The average reduction in the outer and inner diameter of economizer tubes measured on
the same tube at two different locations, namely, inside the furnace and outside the
furnace is listed in Table 3. A reduction in the outer dia of the tube indicates the
thinning (loss in wall thickness) from outside (fireside) whereas a reduction in inner dia
is indicative of the inside (steam side) scaling. The portion of both the tubes located
inside the furnace show appreciable reduction (4 -5%) in outer dia indicating the
initiation of wall thinning from fire side. The inner dia of the tube are almost unaffected
at both the locations; this indicates negligible attack from steam side.
DISCUSSION
When the temperature of a metallic component drops below the H2SO4 dew point of the
flue gas, the H2SO4 is condensed on the metal surface and corrodes the metal. This type
of corrosion, known as cold end corrosion, is mainly encountered in relatively low
temperature boiler components such as economizer, air preheater, stack, etc. The
critical factors governing the cold end corrosion include the presence of sufficient
concentration of SO3 and moisture in the flue gas and a metal surface whose
temperature is below the H2SO4 dew point. It should be noted that in this type of
corrosion it is the temperature of metal which is critical and not the temperature of flue
gas. Even if the temperature of flue gas is above the dew point, the corrosion is very
likely to occur wherever the metal temperature is less than dew point.
Considering the present failure the economizer feed inlet temperature appears to be on
lower side keeping in view the high sulfur content in the flue gas. As the H2SO4 dew
point is directly dependent upon the sulfur content of the flue gas, a higher dew point
than the feed inlet temperature is most probable. This in turn, favored the condensation
of H2SO4 on the economizer tubes outer surfaces causing severe corrosion. This, in
consequence, resulted in the thinning of metal to a stage when it could not bear the
inside pressure of the feed water and ultimately got ruptured. Further, the external
deposits on the tubes helped in lowering down the tube metal temperature and thus
favoring acid condensation over the deposit. A reduction in the wall thickness of the
tubes, located inside the furnace support the initiation of corrosion from fire side as a
result of acid condensation.
CONCLUSIONS
1. The thinning and perforation in the economizer tubes are due to H2SO4 dew point
corrosion.
2. The relatively low temperature of feed water caused the lowering of the tube metal
temperature and promoted the condensation of H2SO4.
3. The external deposits on the tubes, as a result of bunker oil firing, further helped in
lowering down the tube metal temperature, thus promoting H2SO4 condensation
over the deposit.
RECOMMENDATIONS
1. An increase in the economizer feed inlet temperature will help in reducing the
severity of cold end corrosion.
2. An exact feed inlet temperature can be determined by knowing the acid dew point
temperature of the flue gas.
3. The possibility of carrying out condition/remnant life assessment of economizer
tube banks and header should be explored.
4. Sulfur content should be reduced to minimum which can help in preventing the
acid dew point corrosion.
5. An efficient fuel chemical additive program will help in reducing the possibility of
acid dew point corrosion.
6. The efficiency of soot blowing process should be improved.
Table 1. Details of Boiler # 1, Shuqaiq Plant
Economizer Type :
C 11.72 21.84
O 38.04 53.22
Mg 1.61 1.48
Si 0.26 0.20
S 12.84 8.96
V 1.52 0.67
Fe 34.00 13.62
Total 100.00 100.00
Table 3. % reduction in Economizer tubes # 2, Outer and Inner diameter .
Figure 5. Closer view of economizer inlet tube # 2, row 13 showing fish mouth open
rupture and a hole
Figure 6. Thinning of the economizer inlet tube # 2 row 13
Fe
60
40
20
O
V Fe
Ca
0
0 5 10 15 20
Energy (keV)
60 Fe
40
20
O
Fe
C V
S Ca Mn Ni
0
0 5 10 15 20
Energy (keV)
Figure 11. EDX profile of a cross section of economizer tube # 2, row 14 (fire side)
located inside furnace
cps
50
S
40 O
Fe
30
20
10
C Fe
Mg
V
Si
0
0 5 10 15 20
Energy (keV)
Figure 12. EDX profile of the ash deposits collected from economizer outer
surface