EPS FC for designated HM to be OFF (by Emergency Push Button). Also, the heavy consumer to be STOPPED.
Example PROCEDURE to ISOLATE HM2, HC2, LC2 & LM2 (LIVE to DEAD)
STEP 1: CLOSE LM2LM1 & LM1LM2 to ensure POWER for the LM2 MAIN SWBD 440Vac from LM1 MAIN SWBD 440Vac;
STEP 2: OPEN LM2HM2 (Secondary Part of Transformer HMTR2);
STEP 3: OPEN HM2LM2 (Primary Part of Transformer HMTR2) => HMTR2 is ISOLATE from HM2 MAIN SWBD 6600Vac;
STEP 4: CLOSE LC2LC1 & LC1LC2 to ensure POWER for the LC2 CARGO SWBD 440Vac from LC1 CARGO SWBD 440Vac;
STEP 5: OPEN LC2HC2 (Secondary Part of Transformer HCTR2);
STEP 6: OPEN HC2LC2 (Primary Part of Transformer HCTR2) => HCTR2 is ISOLATE from HC2 CARGO SWBD 6600Vac;
STEP 7: OPEN HM2HC2 => AUTOMATICALY HC2HM2 will OPEN and the HC2 CARGO SWBD 6600V is ISOLATE from HM2
MAIN SWBD 6600Vac;
STEP 8: OPEN HM1HM2 => AUTOMATICALY HM2HM1 will OPEN and the HM2 MAIN SWBD 6600V is ISOLATE from HM1
MAIN SWBD 6600Vac.
Example PROCEDURE to RECONNECT HM2, HC2, LC2 & LM2 (DEAD to LIVE)
STEP 1: CLOSE HM1HM2 => AUTOMATICALY HM2HM1 will CLOSE and the HM2 MAIN SWBD 6600V is POWERED from HM1
MAIN SWBD 6600Vac;
STEP 2: CLOSE HM2HC2 => AUTOMATICALY HC2HM2 will CLOSE and the HC2 CARGO SWBD 6600V is POWERED from HM2
MAIN SWBD 6600Vac;
STEP 3: CLOSE HC2LC2 (Primary Part of Transformer HCTR2);
STEP 4: CLOSE LC2HC2 (Secondary Part of Transformer HCTR2) => HCTR2 is POWERED from HM2 CARGO SWBD 6600Vac;
STEP 5: IN MAXIM 8 Sec. after CLOSE LC2HC2, OPEN LC2LC1 & LC1LC2 to Isolate LC2 CARGO SWBD 440Vac from LC1 CARGO
SWBD 440Vac; * The 8 Sec. is the maxim time allowed by PMS/IAS for RING Connection. If pass more than 8 Sec. and
LC2LC1 & LC1LC2 is not OPEN, IAS automatically will OPEN LC2LC1 & LC1LC2 or even LC2HC2 will OPEN => BLACKOUT
Situation for LC2 CARGO SWBD 440Vac can occur;
STEP 6: CLOSE HM2LM2 (Primary Part of Transformer HMTR2);
STEP 7: CLOSE LM2LH2 (Secondary Part of Transformer HMTR2) => HMTR2 is POWERED from HM2 MAIN SWBD 6600Vac;
STEP 8: OPEN LM2LM1 & LM1LM2 to ISOLATE LM2 MAIN SWBD 440Vac from LM1 MAIN SWBD 440Vac;