Prior to START the ISOLATING OERATION, ENSURE that MGE’s for designated HM are in LOCAL MODE.

EPS FC for designated HM to be OFF (by Emergency Push Button). Also, the heavy consumer to be STOPPED.

Example PROCEDURE to ISOLATE HM2, HC2, LC2 & LM2 (LIVE to DEAD)

STEP 1: CLOSE LM2LM1 & LM1LM2 to ensure POWER for the LM2 MAIN SWBD 440Vac from LM1 MAIN SWBD 440Vac;
STEP 2: OPEN LM2HM2 (Secondary Part of Transformer HMTR2);
STEP 3: OPEN HM2LM2 (Primary Part of Transformer HMTR2) => HMTR2 is ISOLATE from HM2 MAIN SWBD 6600Vac;
STEP 4: CLOSE LC2LC1 & LC1LC2 to ensure POWER for the LC2 CARGO SWBD 440Vac from LC1 CARGO SWBD 440Vac;
STEP 5: OPEN LC2HC2 (Secondary Part of Transformer HCTR2);
STEP 6: OPEN HC2LC2 (Primary Part of Transformer HCTR2) => HCTR2 is ISOLATE from HC2 CARGO SWBD 6600Vac;
STEP 7: OPEN HM2HC2 => AUTOMATICALY HC2HM2 will OPEN and the HC2 CARGO SWBD 6600V is ISOLATE from HM2
MAIN SWBD 6600Vac;
STEP 8: OPEN HM1HM2 => AUTOMATICALY HM2HM1 will OPEN and the HM2 MAIN SWBD 6600V is ISOLATE from HM1
MAIN SWBD 6600Vac.

Example PROCEDURE to RECONNECT HM2, HC2, LC2 & LM2 (DEAD to LIVE)

STEP 1: CLOSE HM1HM2 => AUTOMATICALY HM2HM1 will CLOSE and the HM2 MAIN SWBD 6600V is POWERED from HM1
MAIN SWBD 6600Vac;
STEP 2: CLOSE HM2HC2 => AUTOMATICALY HC2HM2 will CLOSE and the HC2 CARGO SWBD 6600V is POWERED from HM2
MAIN SWBD 6600Vac;
STEP 3: CLOSE HC2LC2 (Primary Part of Transformer HCTR2);
STEP 4: CLOSE LC2HC2 (Secondary Part of Transformer HCTR2) => HCTR2 is POWERED from HM2 CARGO SWBD 6600Vac;
STEP 5: IN MAXIM 8 Sec. after CLOSE LC2HC2, OPEN LC2LC1 & LC1LC2 to Isolate LC2 CARGO SWBD 440Vac from LC1 CARGO
SWBD 440Vac; * The 8 Sec. is the maxim time allowed by PMS/IAS for RING Connection. If pass more than 8 Sec. and
LC2LC1 & LC1LC2 is not OPEN, IAS automatically will OPEN LC2LC1 & LC1LC2 or even LC2HC2 will OPEN => BLACKOUT
Situation for LC2 CARGO SWBD 440Vac can occur;
STEP 6: CLOSE HM2LM2 (Primary Part of Transformer HMTR2);
STEP 7: CLOSE LM2LH2 (Secondary Part of Transformer HMTR2) => HMTR2 is POWERED from HM2 MAIN SWBD 6600Vac;
STEP 8: OPEN LM2LM1 & LM1LM2 to ISOLATE LM2 MAIN SWBD 440Vac from LM1 MAIN SWBD 440Vac;