900 SERIES WALL PANELS

CI-DS-01-900 C & I DISCLAIMER


CI-PP-01-900 900 SERIES PANEL PROFILE
CI-PJ-01-900 900 EXPANDED PANEL JOINT
CI-PJ-02-900 900 ENGAGED PANEL JOINT
CI-PJ-03-900 INTERMEDIATE SUPPORT
CI-BS-01-900 BASE DETAIL - FLUSH
CI-BS-02-900 BASE DETAIL - NOTCHED CONCRETE
CI-BS-03-900 BASE DETAIL - OVERHANG W/ SUPPORT
CI-BS-04-900 BASE DETAIL - OVERHANG W/ ANGLE
CI-BS-05-900 BASE DETAIL - OVERHANG W/ DRIP
CI-OC-01-900 OUTSIDE CORNER WITH FLAT TRIM
CI-OC-02-900 OUTSIDE CORNER WITH MITER CUT
CI-IC-01-900 INSIDE CORNER WITH FLAT TRIM
CI-FO-01-900 F.O. HEAD WITH DRIP EDGE
CI-FO-02-900 F.O. TWO PIECE JAMB
CI-FO-03-900 F.O. ONE PIECE JAMB
CI-FO-04-900 F.O. ONE PIECE SILL
CI-FO-05-900 O.H. DOOR HEAD WITH DRIP EDGE
CI-FO-06-900 O.H. DOOR TWO PIECE JAMB
CI-SJ-01-900 STACK JOINT WITH FLUSH TRIM
CI-SJ-02-900 STACK JOINT WITH PROFILED TRIM
CI-PR-01-900 PARAPET WITH FLUSH TRIM
CI-PR-02-900 PARAPET WITH PROFILED TRIM
CI-LE-01-900 LOW EAVE W/ GUTTER
CI-RK-01-900 RAKE
CI-HE-01-900 HIGH EAVE
CI-TL-01-900 TRIM END LAP
CI-TL-02-900 TRIM END LAP WITH HEM
CI-TL-03-900 TRIM END LAP WITH LAP STRIP
CI-TL-04-900 TRIM LAP AT F.O.

INDEX SHEET
900 SERIES WALL PANELS

DISCLAIMER:

THESE DETAILS ARE PROVIDED AS A GUIDELINE FOR PROPER PANEL AND ASSOCIATED
COMPONENT INSTALLATION, AND ARE BASED ON INDUSTRY ACCEPTED PRACTICES.

LOCATION OF VAPOR BARRIERS AND ASSOCIATED SEALANTS IN THESE DETAILS ARE BASED
ON TYPICAL DESIGN PRACTICES FOR MOST U.S. CLIMACTIC ZONES. (THE PRIMARY VAPOR
BARRIER IS PLACED ON THE "WARM" SIDE IN WINTER).

PROJECTS LOCATED IN AREAS SUBJECT TO EXTREME COLD AND/OR HIGH SNOW LOADS MAY
REQUIRE MODIFICATIONS TO THESE DETAILS - CONTACT KINGSPAN TECHNICAL SERVICES
FOR SPECIFIC PROJECT RECOMMENDATIONS.

COMMERCIAL/INDUSTRIAL
DISCLAIMER
900 SERIES WALL PANELS
CORE DEPTHS: MODULE WIDTH: EMBOSSING:
1.5", 2", 2.5", 3", 4", 5", 6" 39.375" (39 3 8") EXTERIOR: STUCCO / SMOOTH
INTERIOR: STUCCO / SMOOTH
STEEL GAUGES: PANEL ORIENTATION: LENGTHS:
EXTERIOR: 22, 24 VERTICAL APPLICATION ONLY MINIMUM: 8'-0"
INTERIOR: 26, 24, 22 MAXIMUM: 53'-0"

39 3 8" (1000mm)

HIGH RIB PROFILE

1 12"
EXTERIOR

1 12" - 6"
INTERIOR
V-GROOVE PROFILE

900 SERIES PANEL


PROFILE
900 SERIES WALL PANELS

1
4" - 14 STITCH TEK (HEX HEAD OR LOW PROFILE @ 24" O.C.
ALONG OVERLAP (MAX. 4" FROM PANEL ENDS)
1
4" - 14 THROUGH FASTENERS
W/ WASHER (AS REQUIRED
FOR WIND LOAD)

1
4" - 14 STITCH TEK SCREW (HEX HEAD OR
LOW PROFILE) @ 24" O.C. ALONG
OVERLAP (MAX. 4" FROM PANEL ENDS)

FIELD APPLIED BUTYL TAPE


ENTIRE LENGTH OF OVERLAP

1 FIELD APPLIED CONTINUOUS


4" - 14 THROUGH FASTENERS
W/ WASHER (AS REQUIRED BUTYL SEALANT
FOR WIND LOAD)

WALL PANEL INSTALLATION DIRECTION

900 EXPANDED
PANEL JOINT
900 SERIES WALL PANELS

1
4" - 14 STITCH TEK (HEX HEAD OR LOW PROFILE @ 24" O.C.
ALONG OVERLAP (MAX. 4" FROM PANEL ENDS)
1
4" - 14 THROUGH FASTENERS
W/ WASHER (AS REQUIRED
FOR WIND LOAD)

1
4" - 14 THROUGH FASTENERS
W/ WASHER (AS REQUIRED
FOR WIND LOAD)
1
4" - 14 STITCH TEK SCREW (HEX HEAD OR
LOW PROFILE) @ 24" O.C. ALONG
OVERLAP (MAX. 4" FROM PANEL ENDS)

FIELD APPLIED BUTYL TAPE


ENTIRE LENGTH OF OVERLAP

FIELD APPLIED CONTINUOUS


BUTYL SEALANT

WALL PANEL INSTALLATION DIRECTION

900 ENGAGED
PANEL JOINT
900 SERIES WALL PANELS

CONTINUOUS BUTYL
SEALANT AT PANEL JOINT

1
4" - 14 THROUGH FASTENERS
W/ WASHER (AS REQUIRED
FOR WIND LOAD)

HORZONTAL SUPPORT
(NOT BY KINGSPAN)

INTERMEDIATE
SUPPORT
900 SERIES WALL PANELS

1
4" - 14 STITCH TEK
(HEX HEAD OR LOW CONTINUOUS BUTYL
PROFILE @ 24" O.C. SEALANT AT PANEL JOINT
ALONG OVERLAP
(MAX. 4" FROM PANEL ENDS) 1
4" - 14 THROUGH FASTENER
RIB CLOSURE TRIM W/ WASHER (AS REQUIRED
FOR WIND LOAD)
POP RIVETS
@ 8" O.C. CONTINUOUS BUTYL SEALANT

BASE TRIM
BASE ANGLE W/ MIN. 3" VERT.
LEG FOR PANEL ATTACHMENT
BASE FLASHING (NOT BY KINGSPAN)

CONTINUOUS BUTYL
SEALANT BELOW BASE
FASTENER TO CONCRETE
FLASHING
(NOT BY KINGSPAN)

SEALANT MARRIAGE BEAD TO


VERTICAL PANEL JOINT

NOTE: SEE DETAIL CI-TL-01-900 AND CI-TL-02-900 FOR TYPICAL


TRIM LAP INSTRUCTIONS

BASE DETAIL - FLUSH


900 SERIES WALL PANELS

CONTINUOUS BUTYL
SEALANT AT PANEL JOINT
1
4" - 14 STITCH TEK
1
(HEX HEAD OR LOW 4" - 14 THROUGH FASTENERS
PROFILE @ 24" O.C. W/ WASHER (AS REQUIRED
ALONG OVERLAP FOR WIND LOAD)
(MAX. 4" FROM PANEL ENDS) CONTINUOUS BUTYL SEALANT W/
RIB CLOSURE TRIM MARRIAGE BEAD TO VERTICAL
PANEL JOINT
POP RIVETS BASE ANGLE W/ MIN. 3" VERT.
@ 8" O.C. LEG FOR PANEL ATTACHMENT
(NOT BY KINGSPAN)
BASE TRIM

(TYP.)
112"
BASE FLASHING

FASTENER TO CONCRETE
(NOT BY KINGSPAN)
CONTINUOUS BUTYL
SEALANT BELOW BASE
FLASHING

NOTE: SEE DETAIL CI-TL-01-900 AND CI-TL-02-900 FOR TYPICAL


TRIM LAP INSTRUCTIONS

BASE DETAIL - NOTCHED


CONCRETE
900 SERIES WALL PANELS

CONTINUOUS BUTYL
1 SEALANT AT PANEL JOINT
4" - 14 STITCH TEK
(HEX HEAD OR LOW 1
4" - 14 "LOW PROFILE" THROUGH
PROFILE @ 24" O.C. FASTENER (AS REQUIRED
ALONG OVERLAP FOR WIND LOAD)
(MAX. 4" FROM PANEL ENDS)
CONTINUOUS BUTYL SEALANT W/
RIB CLOSURE TRIM MARRIAGE BEAD TO VERTICAL
PANEL JOINT
POP RIVETS BASE ANGLE W/ MIN. 3" VERT.
@ 8" O.C. LEG FOR PANEL ATTACHMENT
(NOT BY KINGSPAN)
BASE TRIM

(TYP.)
112"
CONTINUOUS BUTYL SEALANT

FASTENER TO CONCRETE
(NOT BY KINGSPAN)

NOTE: SEE DETAIL CI-TL-01-900 AND CI-TL-02-900 FOR TYPICAL


TRIM LAP INSTRUCTIONS

BASE DETAIL -
OVERHANG W/
SUPPORT
900 SERIES WALL PANELS

CONTINUOUS BUTYL
1 SEALANT AT PANEL JOINT
4" - 14 STITCH TEK
(HEX HEAD OR LOW 1
4" - 14 "LOW PROFILE" THROUGH
PROFILE @ 24" O.C. FASTENER (AS REQUIRED
ALONG OVERLAP FOR WIND LOAD)
(MAX. 4" FROM PANEL ENDS)
CONTINUOUS BUTYL SEALANT W/
RIB CLOSURE TRIM MARRIAGE BEAD TO VERTICAL
PANEL JOINT
POP RIVETS BASE ANGLE W/ MIN. 3" VERT.
LEG FOR PANEL ATTACHMENT
(NOT BY KINGSPAN)
BASE TRIM

(TYP.)
112"
CONTINUOUS BUTYL SEALANT

FASTENER TO CONCRETE
(NOT BY KINGSPAN)

NOTE: SEE DETAIL CI-TL-01-900 AND CI-TL-02-900 FOR TYPICAL


TRIM LAP INSTRUCTIONS

BASE DETAIL -
OVERHANG W/ ANGLE
900 SERIES WALL PANELS

CONTINUOUS BUTYL
1 SEALANT AT PANEL JOINT
4" - 14 STITCH TEK
(HEX HEAD OR LOW 1
4" - 14 "LOW PROFILE" THROUGH
PROFILE @ 24" O.C. FASTENER (AS REQUIRED
ALONG OVERLAP FOR WIND LOAD)
(MAX. 4" FROM PANEL ENDS)
CONTINUOUS BUTYL SEALANT W/
RIB CLOSURE TRIM MARRIAGE BEAD TO VERTICAL
PANEL JOINT
POP RIVETS BASE ANGLE W/ MIN. 3" VERT.
@ 8" O.C. LEG FOR PANEL ATTACHMENT
(NOT BY KINGSPAN)
BASE TRIM

(TYP.)
112"
CONTINUOUS BUTYL SEALANT

FASTENER TO CONCRETE
(NOT BY KINGSPAN)
BASE TRIM
CONTINUOUS BUTYL SEALANT

NOTE: SEE DETAIL CI-TL-01-900 AND CI-TL-02-900 FOR TYPICAL


TRIM LAP INSTRUCTIONS

BASE DETAIL -
OVERHANG W/ DRIP
900 SERIES WALL PANELS
WILL VARY WITH
FIELD CONDITION

FIELD CONDITION
WILL VARY WITH

FIELD CUT

OUTSIDE CORNER
TRIM

F.I.P. INSULATION
AS REQUIRED
(BY OTHERS)

POP RIVETS
3
4" PHIL. PAN HEAD

CONTINUOUS
BUTYL SEALANT

RIB CLOSURE TRIM ATTACHMENT CLIP


(BY OTHERS)
1
4" - 14 THROUGH
FASTENERS W/ 1 18" CONTINUOUS
WASHER (AS REQUIRED BUTYL SEALANT
FOR WIND LOAD)
HORIZONTAL SUPPORT
(NOT BY KINGSPAN)

OUTSIDE CORNER
WITH PROFILED TRIM
900 SERIES WALL PANELS
WILL VARY WITH
FIELD CONDITION

FIELD CONDITION
WILL VARY WITH

FIELD CUT

OUTSIDE CORNER
TRIM

F.I.P. INSULATION
AS REQUIRED
(BY OTHERS)

POP RIVETS
@ 8" O.C. 3
4" PHIL. PAN HEAD

CONTINUOUS
BUTYL SEALANT
1
4" - 14 "LOW PROFILE"
THROUGH FASTENERS ATTACHMENT CLIP
W/ 1 18" WASHER (AS (BY OTHERS)
REQUIRED FOR WIND
CONTINUOUS
LOAD)
BUTYL SEALANT
HORIZONTAL SUPPORT
(NOT BY KINGSPAN)

OUTSIDE CORNER
WITH FLAT TRIM
900 SERIES WALL PANELS
WILL VARY WITH
FIELD CONDITION

FIELD CONDITION
WILL VARY WITH

FIELD CUT

CONTINUOUS BUTYL CONTINUOUS SEALANT APPLIED


SEALANT AT FASTENER LOCATIONS

OUTSIDE CORNER
TRIM

F.I.P. INSULATION
AS REQUIRED
(BY OTHERS)

HORIZONTAL SUPPORT
(NOT BY KINGSPAN)

POP RIVETS 8" O.C.


CONTINUOUS BUTYL
INSIDE CORNER TRIM
SEALANT
1
3 4" - 14 THROUGH FASTENERS
4" PHIL. PAN HEAD
W/ 118" BONDED WASHER
(AS REQUIRED FOR WIND LOAD)

RIB CLOSURE TRIM

INSIDE CORNER
WITH PROFILED TRIM
900 SERIES WALL PANELS

CONTINUOUS BUTYL
SEALANT AT PANEL JOINT

CONTINUOUS BUTYL
1 SEALANT BOTH SIDES OF
4" - 14 THROUGH FASTENER
TRIM W/ MARRIAGE BEAD
W/ WASHER
TO VERTICAL PANEL JOINT
RIB CLOSURE TRIM

POP RIVETS CONTINUOUS


@ 8" O.C. BUTYL SEALANT

FRAMED OPENING
EXTERIOR CAP TRIM
(NOT BY KINGSPAN)

DOOR/WINDOW FRAME,
DRIP FLASHING
COMPONENTS AND
ACCESSORIES
(NOT BY KINGSPAN)
EXPOSED SEALANT
(NOT BY KINGSPAN)

NOTE: SEE DETAIL CI-TL-01-900 AND CI-TL-02-900 FOR TYPICAL


TRIM LAP INSTRUCTIONS

FRAMED OPENING
HEAD W/ "DRIP EDGE"
900 SERIES WALL PANELS

FRAMED OPENING
(NOT BY KINGSPAN)

DOOR/WINDOW FRAME,
COMPONENTS AND
ACCESSORIES
1
(NOT BY KINGSPAN) 4" - 14 THROUGH FASTENER

CONTINUOUS BUTYL SEALANT


BOTH SIDES OF TRIM

INTERIOR CAP TRIM

EXPOSED SEALANT
(NOT BY KINGSPAN)

POP RIVETS
@ 8" O.C.

EXTERIOR CAP TRIM RIB CLOSURE TRIM

POP RIVETS @ 8" O.C.

NOTE: SEE DETAIL CI-TL-01-900 AND CI-TL-02-900 FOR TYPICAL


TRIM LAP INSTRUCTIONS

FRAMED OPENING
TWO PIECE JAMB
900 SERIES WALL PANELS

FRAMED OPENING FIELD BEND


(NOT BY KINGSPAN) (AS REQUIRED)

1
4" - 14 "LOW PROFILE"
DOOR/WINDOW FRAME, FASTENER (AS REQUIRED)
ACCESSORIES AND
WEATHER TIGHTNESS
1
(NOT BY KINGSPAN). 4" - 14 THROUGH FASTENER
FOLLOW COMPONENT
MANUFACTURER
INSTALLATION
CONTINUOUS BUTYL SEALANT
INSTRUCTIONS FOR
PROPER INSTALLATION.

CONTINUOUS BUTYL SEALANT

EXPOSED SEALANT
(NOT BY KINGSPAN)

EXTERIOR CAP TRIM

RIB CLOSURE TRIM

POP RIVETS @ 8" O.C.

NOTE: SEE DETAIL CI-TL-01-900 AND CI-TL-02-900 FOR TYPICAL


TRIM LAP INSTRUCTIONS

FRAMED OPENING
ONE PIECE JAMB
900 SERIES WALL PANELS

DOOR/WINDOW FRAME
EXPOSED SEALANT (NOT BY KINGSPAN)
(NOT BY KINGSPAN)
CONTINUOUS BUTYL FIELD BEND
SEALANT (AS REQUIRED)

CONTINUOUS BUTYL SEALANT W/


MARRIAGE BEAD AT JOINT
LOCATIONS

EXTERIOR CAP TRIM

1
POP RIVETS @ 8" O.C. 4" - 14 "LOW PROFILE"
FASTENER (AS REQUIRED)

RIB CLOSURE TRIM


FRAMED OPENING
1
4" - 14 THROUGH FASTENER (NOT BY KINGSPAN)

CONTINUOUS BUTYL
SEALANT AT PANEL JOINT

NOTE: SEE DETAIL CI-TL-01-900 AND CI-TL-02-900 FOR TYPICAL


TRIM LAP INSTRUCTIONS

FRAMED OPENING
ONE PIECE SILL
900 SERIES WALL PANELS

CONTINUOUS BUTYL
SEALANT AT PANEL JOINT

RIB CLOSURE TRIM CONTINUOUS BUTYL


SEALANT BOTH SIDES OF
TRIM W/ MARRIAGE BEAD TO
POP RIVETS VERTICAL PANEL JOINT
@ 8" O.C.
1
4" - 14 THROUGH FASTENER

3
EXTERIOR CAP TRIM

FRAMED OPENING
(NOT BY KINGSPAN)

2 FASTENER
DRIP FLASHING
(NOT BY KINGSPAN)
1
HEADER TRIM
EXPOSED SEALANT (OPTIONAL)
(NOT BY KINGSPAN)

TRIM INSTALLATION SEQUENCE:


1 INSTALL HEADER TRIM (OPTIONAL) & ALL APPLICABLE SEALANTS
2 INSTALL DRIP FLASHING & ALL APPLICABLE SEALANTS PRIOR TO
INSTALLING THE PANEL AND THROUGH FASTENERS
3 INSTALL EXTERIOR CAP TRIM

NOTE: SEE DETAIL CI-TL-01-900 AND CI-TL-02-900 FOR TYPICAL


TRIM LAP INSTRUCTIONS

OVERHEAD DOOR
HEAD W/ DRIP EDGE
900 SERIES WALL PANELS

FASTENER
(NOT BY KINGSPAN)

FRAMED OPENING
(NOT BY KINGSPAN)

1
4" - 14 THROUGH FASTENER

1
JAMB TRIM CONTINUOUS BUTYL SEALANT
(OPTIONAL)

2
INTERIOR CAP TRIM

EXPOSED SEALANT
(NOT BY KINGSPAN)

POP RIVETS
@ 8" O.C.
3
EXTERIOR CAP TRIM

RIB CLOSURE TRIM

POP RIVETS @ 8" O.C.

TRIM INSTALLATION SEQUENCE:


1 INSTALL JAMB TRIM (OPTIONAL) & ALL APPLICABLE SEALANTS
2 INSTALL INTERIOR CAP TRIM & ALL APPLICABLE SEALANTS PRIOR TO
INSTALLING THE PANEL AND THROUGH FASTENERS
3 INSTALL EXTERIOR CAP TRIM

NOTE: SEE DETAIL CI-TL-01-900 AND CI-TL-02-900 FOR TYPICAL


TRIM LAP INSTRUCTIONS

OVERHEAD DOOR
TWO-PIECE JAMB
900 SERIES WALL PANELS

RIB CLOSURE
TRIM
1
4" - 14 THROUGH FASTENER
(AS REQUIRED FOR WIND LOAD)
POP RIVETS
@ 8" O.C.
CONTINUOUS BUTYL
SEALANT W/ MARRIAGE
BEAD TO VERTICAL
STACK TRIM PANEL JOINT

HORIZONTAL SUPPORT
FIELD DRILL
OPTIONAL 3 8"
WEEP HOLES
AS REQUIRED

FASTEN AS REQUIRED
(NOT BY KINGSPAN)
STACK
FLASHING
CONTINUOUS BUTYL
SEALANT W/ MARRIAGE
BEAD AT PANEL JOINT LOCATIONS

CONTINUOUS 3" X 3" ANGLE


POP RIVETS
(GAUGE TO MATCH GIRT)
@ 8" O.C.
(NOT BY KINGSPAN)
RIB CLOSURE
1
TRIM 4" - 14 THROUGH FASTENER
(AS REQUIRED FOR WIND LOAD)

CONTINUOUS BUTYL
SEALANT AT PANEL JOINT

STACK JOINT
W/ FLUSH TRIM
900 SERIES WALL PANELS

RIB CLOSURE
TRIM
1
4" - 14 THROUGH FASTENER
(AS REQUIRED FOR WIND LOAD)
POP RIVETS
@ 8" O.C.
CONTINUOUS BUTYL
SEALANT W/ MARRIAGE
BEAD TO VERTICAL
STACK TRIM PANEL JOINT

HORIZONTAL SUPPORT

FASTEN AS REQUIRED
(NOT BY KINGSPAN)

CONTINUOUS BUTYL
STACK SEALANT W/ MARRIAGE
FLASHING BEAD AT PANEL JOINT LOCATIONS

CONTINUOUS 3" X 3" ANGLE


POP RIVETS
(GAUGE TO MATCH GIRT)
@ 8" O.C.
(NOT BY KINGSPAN)
RIB CLOSURE
1
TRIM 4" - 14 THROUGH FASTENER
(AS REQUIRED FOR WIND LOAD)

CONTINUOUS BUTYL
SEALANT AT PANEL JOINT

STACK JOINT
W/ PROFILED TRIM
900 SERIES WALL PANELS

PARAPET BLOCKING
CONTINUOUS BUTYL SEALANT W/ (NOT BY KINGSPAN)
MARRIAGE BEAD AT JOINT
LOCATIONS

PARAPET CAP

WRAP MEMBRANE
ADHERE TO EXTERIOR
PANEL FACE
FASTENER TO PARAPET
(NOT BY KINGSPAN)
BACKER (NOT BY KINGSPAN)

POP RIVETS 1
4" - 14 THROUGH FASTENER
@ 8" O.C. (AS REQUIRED FOR WIND LOAD)

CONTINUOUS BUTYL
SEALANT AT PANEL JOINT
900 SERIES FOAM
CLOSURE W/ BUTYL
TAPE TOP AND MEMBRANE ROOF &
BOTTOM PARAPET BACKER
(NOT BY KINGSPAN)
RIB CLOSURE TRIM

PARAPET
WITH FLUSH TRIM
900 SERIES WALL PANELS

CONTINUOUS BUTYL SEALANT W/ PARAPET BLOCKING


MARRIAGE BEAD AT JOINT (NOT BY KINGSPAN)
LOCATIONS

PARAPET CAP

WRAP MEMBRANE
ADHERE TO EXTERIOR
PANEL FACE
FASTENER TO PARAPET
(NOT BY KINGSPAN)
BACKER (NOT BY KINGSPAN)

POP RIVETS 1
4" - 14 THROUGH FASTENER
@ 8" O.C. (AS REQUIRED FOR WIND LOAD)

CONTINUOUS BUTYL
SEALANT AT PANEL JOINT
900 SERIES FOAM
CLOSURE W/ BUTYL
TAPE TOP AND MEMBRANE ROOF &
BOTTOM PARAPET BACKER
(NOT BY KINGSPAN)
RIB CLOSURE TRIM

PARAPET
WITH PROFILED TRIM
900 SERIES WALL PANELS

REFER TO 900/1000 SERIES


ROOF PANEL DETAILS FOR
ADDITIONAL INFORMATION

EAVE STRUT
(NOT BY KINGSPAN)

CONTINUOUS BUTYL
SEALANT W/ MARRIAGE
BEAD AT JOINT LOCATIONS

1
4" - 14 THROUGH
FASTENERS W/ WASHER
(AS REQUIRED FOR
WIND LOAD)
FASTENER (NOT BY KINGSPAN)
CONTINUOUS BUTYL
SEALANT AT PANEL 900 FOAM CLOSURE SET IN
JOINT BUTYL TAPE TOP AND BOTTOM

POP RIVETS RIB CLOSURE TRIM


@ 8" O.C.

LOW EAVE W/ GUTTER


900 SERIES WALL PANELS

REFER TO 900/1000 SERIES


ROOF PANEL DETAILS FOR
ADDITIONAL INFORMATION

SHEETING OR RAKE ANGLE


REQUIRED (NOT BY KINGSPAN)

CONTINUOUS BUTYL
SEALANT W/ MARRIAGE
BEAD TO AT PANEL JOINT
LOCATIONS
1
4" - 14 THROUGH
FASTENERS W/ WASHER
(AS REQUIRED FOR
FASTENER
WIND LOAD)
(NOT BY KINGSPAN)
POP RIVETS @ 8" O.C.
900 FOAM CLOSURE
SET IN BUTYL TAPE
TOP AND BOTTOM

RIB CLOSURE TRIM

CONTINUOUS BUTYL
SEALANT AT PANEL
JOINT

RAKE
900 SERIES WALL PANELS

REFER TO 900/1000 SERIES


ROOF PANEL DETAILS FOR
ADDITIONAL INFORMATION

EAVE STRUT
(NOT BY KINGSPAN)

CONTINUOUS BUTYL
SEALANT W/ MARRIAGE
BEAD AT PANEL JOINT
LOCATIONS
1
FASTENER 4" - 14 THROUGH
(NOT BY KINGSPAN) FASTENERS W/ WASHER
(AS REQUIRED FOR
900 FOAM CLOSURE WIND LOAD)
SET IN BUTYL TAPE
TOP AND BOTTOM POP RIVETS @ 8" O.C.

RIB CLOSURE TRIM

CONTINUOUS BUTYL
SEALANT AT PANEL
JOINT

RAKE
900 SERIES WALL PANELS

3"
N. P
MI LA
I M
TR
(2) BEADS
BUTYL SEALANT

3"
I N. AP
M L
IM
TR

TRIM END LAP


900 SERIES WALL PANELS

FIELD NOTCH HEM(S)


AS REQUIRED
(NOT BY KINGSPAN)

3"
I N. AP
M L
IM
TR
(2) BEADS
BUTYL SEALANT

3"
I N. AP
M L
IM
TR

TRIM LAP WITH HEM


900 SERIES WALL PANELS

(2) BEADS
BUTYL SEALANT

8" LONG LAP STRIP

1 "
M . 4
NO AP
G

TRIM END LAP WITH


LAP STRIP
900 SERIES WALL PANELS

FIELD NOTCH AND OVERLAP


TRIMS, POP RIVET AND SEAL AS
NECESSARY (NOT BY KINGSPAN)

SEALANT END DAM FIELD MITER AND OVERLAP


TRIMS, POP RIVET AS
NECESSARY (NOT BY KINGSPAN)
2
INTERIOR HEAD TRIM
WITH TABS BENT DOWN

E AD
ATH
M
RI
PT
CA
R D
RI
O
HEA
TE AT
IN IM
R
PT
CA FIELD CUT/NOTCH CAP
OR

EXTERIOR CAP TRIM AT JAMB


RI TRIM AT CORNERS TO
TE ALLOW FOR LAP
EX
(NOT BY KINGSPAN)

5
EXTERIOR HEAD TRIM W/
FIELD DRILL 3 8 4
EXTERIOR JAMB TRIM
(NOT BY KINGSPAN)
1
INTERIOR JAMB TRIM
6
EXPOSED SEALANT
(NOT BY KINGSPAN) FIELD CUT/NOTCH CAP
3 TRIM AT CORNERS TO
SILL TRIM WITH TABS ALLOW FOR LAP
BENT UP (NOT BY KINGSPAN)

FIELD MITER AND OVERLAP


TRIMS, POP RIVET AND SEAL AS
S ILL NECESSARY (NOT BY KINGSPAN)
AT
IM
P TR
A
RC TRIM INSTALLATION SEQUENCE:
RIO 1 INTERIOR JAMB TRIM
TE
EX 2 INTERIOR HEAD TRIM WITH TABS DOWN
3 SILL TRIM WITH TABS UP
4 EXTERIOR JAMB TRIM
5 EXTERIOR HEAD TRIM
6 EXTERIOR SEALANTS AS REQUIRED

TRIM LAP AT
FRAMED OPENING