Professional Documents
Culture Documents
FACULTY OF ENGINEERING
ECNG 1006
ELab #4:
Three-Phase Circuits
Philippe Francois
810006519
Group E1
Table of Contents
Results from 4.1.1........................................................................................................................................3
5.1.1 – Delta Connected Load and Transformer..........................................................................................4
5.1.1 (a)...................................................................................................................................................4
5.1.1 (b)...................................................................................................................................................5
5.1.1 (c) Phasor Diagram....................................................................................................................5
5.1.1 (d)...................................................................................................................................................7
Results for 4.1.2...........................................................................................................................................9
5.1.2 – Star Connected Load and Tranformer..............................................................................................9
5.1.2 (a)...................................................................................................................................................9
5.1.2 (b).................................................................................................................................................10
5.1.2 (c)..................................................................................................................................................10
5.1.2.(d) Phasor diagram.......................................................................................................................12
5.1.2 (e).................................................................................................................................................13
Results from 4.1.3......................................................................................................................................14
5.1.3 – Unbalanced Loads..........................................................................................................................14
5.1.3 (a).................................................................................................................................................14
5.1.3 (b).................................................................................................................................................15
5.1.4 Power Factor....................................................................................................................................18
Results from 4.1.4......................................................................................................................................18
5.1.4 (a).................................................................................................................................................18
5.1.4 (b) Neutral Current..................................................................................................................19
5.1.4 (c)..................................................................................................................................................20
5.1.4 (d).................................................................................................................................................22
5.1.4 (e).................................................................................................................................................24
Notes:
I L =√ 3 x I P= √3 x 4.35=7.53 A
25% of IL:
25 % I L =7.53 X .25=1.88 A
Reading RY YB BR
The relationship between the phase and line currents in a delta connected load is:
I L =√ 3 x I P
A relationship between the phase angles of the line current and phase current also exists.
From Kirchoff’s Current Law (KCL):
I L =⃗
⃗ I 1− ⃗
I3
sin (120 ) x ⃗
I1
I L=
⃗
sin( 30)
I L =2 x I P x cos 30
5.1.1 (b)
The relationship between the phase voltage V P and line voltage VL in a delta connected load
is:
V P=V L
From Trigonometry:
a b
=
sin a sin b
Red Phase:
1.7 1.04
=
sin 120 sin θ
1.8 1.06
=
sin 120 sin θ
1.85 1.06
=
sin 120 sin θ
θ=sin−1 ( 1.061.85
x sin 120
)=29.75°
Phase Powers
P=V P I P cos φ
R
φ=tan−1 =0
X
P=230 x 1.04=239.2W
W1C = 239.2W
P=230 x 1.06=243.8 W
W2C = 243.8W
P=230 x 1.06=243.8 W
W3C = 243.8W
W T =W 1 C +W 2 C +W 3C
W T =239.2+243.8+243.8=726.8 Watts
5.1.1 (d)
1. If the wattmeter was connected as illustrated in the lab manual (figure 1), then the
wattmeter is measuring line current and line voltage not the phase current. Therefore,
using the formula:
IL
=I
√3 P
Then the actual phase power that should be measured by the wattmeter
Red Phase
1.7
phase power=230 x =225.7 watts
√3
Yellow Phase
1.8
phase power=230 x =239.0 watts
√3
Blue Phase
1.85
phase p ower=230 x =245.7 watts
√3
Corrected Wattmeter
225.7 239.0 245 709.7
(W1 /W2 /W3/WTOTAL)
Calculated
239.2 243.8 243.8 726.8
(W1C/W2C/W3C/WCTOTAL)
1. Energy losses in the circuit due to resistance of the connections and the wires used to
connect the circuit.
2. Differences in internal resistances of the wattmeter and ammeter and voltmeter.
Reading RY YB BR
5.1.2 (a)
The relationship between the phase and line currents at a star connected load is:
I L =I P
5.1.2 (b)
The relationship between the phase and line voltages in a star connected load is
V L= √ 3 x V P
V RY =⃗
⃗ V RN −⃗
V YN
sin ( 120 ) x ⃗
V RN
V RY =
⃗
sin(30)
V RY =2 x ⃗
⃗ V RN x cos (30)
The line voltages are therefore 30º from the phase voltages.
5.1.2 (c)
The neutral current is the current flowing in the neutral line (‘N’ in Figure 3) in a star connected
load.
The neutral current is therefore the vector sum of the currents at the center of the star
network. The currents in a three phase circuit are 120º apart and therefore in the circuit are:
1. IR = IM Sin(wt)
2. IY = IM Sin(wt +120)
3. IB = IM Sin(wt -120)
I N =I M ¿
I N =I M ¿
I N =I M sin ( wt ) ( 0 )=0
Therefore for balanced loads i.e. current magnitudes and phase angles are the same. IN = 0.
P=V P I P cos ∅
i. Red Phase:
5.1.2 (e)
A difference of 114 watts can be observed between the calculated and wattmeter phase powers.
In the star network circuit, negative terminal of the voltage coil of the wattmeter was connected
to neutral and therefore it would be measuring phase voltage. For a star network the phase
current and line current is the same and therefore would not have the error associated with the
first circuit.
114 watts is a significantly large difference that cannot be accounted for by simple factors such
as meter internal resistances and energy losses in wires. It is more likely that the readings taken
may have been slightly incorrect.
The neutral current is the vector sum of the IR IY and IB line/phase currents. i.e.
5.1.3 (a)
I N =⃗
⃗ I R +⃗
IY+⃗
IB
(a) Horizontally will cancel and equate to 0, since the magnitudes and angles of the currents
are the same:
I H =0.64 cos 30−0.64 cos 30=0
5.1.3 (b)
For star connected loads
V L=V RN +V YN
V L=V RN Sinθ +¿ ¿
When θ is 0:
For a purely resistive load, the phase voltages and phase currents are in phase. For the
unbalanced loads the magnitudes of the Y and B phase currents are less than that of the R phase
as shown by the phasor diagram. As such the Y and B phase powers are less than the R phase
power.
The phase powers can be calculated from the phasor diagram using the formula:
P=V P I P cos ∅
Where Ø is the phase angle between the current and voltage phasors. Since, the two are in phase
then Ø is 0. Power for each phase can therefore be calculated as:
Phase Power (W) for Line Current (IP)/A Phase Voltage (VP)/V Line Voltage (VL)/V
Wattmeter
Symbol Name Symbol Measured Symbo Measured Symbol Measured Symbol Measured
l
R Red WR 94 Ir 1.1 VRN 130 VRY 226
5.1.4 (a)
Real Power
Power Factor=
Apparent Power
Apparent Power is given as the sum of the products of the phase voltage and phase currents
recorded by the voltmeter and ammeter respectively.
Real Power
W R=94+94 +94=282 W
W A =3 V P I P =3 x 130 x 1.1=429 VA
282
Load Power Factor= =0.657
429
W A =W R cos ∅
282
∅=cos−1 =48.9
429
The inductive loads in each phase are assumed to be all equal. Therefore, if there is a
phase shift between the phase voltage and current in a single phase, that phase shift will
be prevalent and of equal magnitude in each phase. Hence, the phase currents will still be
120º from each other. From Equation:
I N =I R + I Y + I B
1. IR = IM Sin(wt)
2. IY = IM Sin(wt +120)
3. IB = IM Sin(wt -120)
I N =I M ¿
I N =I M ¿
I N =I M sin ( wt ) ( 0 )=0
5.1.4 (c)
The inductive loads would have caused the phase currents to shift from the phase voltages. It
is therefore necessary to calculate the phase shifts of each phase. From the results in 4.1.4,
the phase voltages and line currents are equal for each phase. It is therefore only required to
calculate the shift for one phase:
94
∅=cos−1 ( 143 )=48.9
5.1.4 (d)
The power triangle can be used to calculate reactive power (R), from the real power.
From trigonometry,
Reactive Power
tanθ=
Real Power
Where θ,
P 94
θ=cos−1 =cos−1 =48.9
S 143
- Red-phase
i. Real Power:
Real Power=V P I P cos ∅
- Yellow-phase
- Blue-phase
5.1.4 (e)