Professional Documents
Culture Documents
Functional Description
CONTENT
Functional Description.................................................................................................. 2
6. Field suppression.................................................................................................. 46
According to the block diagram of an UNITROL 5000 Excitation System for approximately
3500 A, which is shown on Figure 1, the entire system can be divided into four major
function groups:
In static excitation systems (so-called shunt excitation or self-excitation), the excitation power
is taken from the machines terminals. The field current of the synchronous machine flows
through the excitation transformer -T02, the field circuit-breaker -Q02, and the power
converter G31 … G34 (thyristor converter). The excitation transformer reduces the generator
terminal voltage to the required input voltage for the thyristor converter, provides the galvanic
isolation between the machine terminals and the field winding and acts at the same time as
the commutating reactance for the thyristor converter. The power converter G31 … G34
converts the AC current into a controlled DC current If.
At the beginning of the starting sequence the field flashing energy is derived from the
residual machine terminal voltage. As soon as 10 to 20 V at the input of the thyristor
converter are reached, the thyristor converter and control electronics are ready for the
normal operation and a soft-start sequence takes place. The new start up facilities and
design of the field flashing equipment (-R03, -V03, -Q03), which have been developed for
UNITROL 5000, are more described in Item 7 of this document.
The purpose of the field suppression equipment is to disconnect the excitation system from
the excitation transformer and to discharge the field winding energy as fast as possible. The
field suppression circuit consists basically of the field circuit breaker -Q02, the field
suppression resistor -R02 and the CROWBAR thyristors -F02 with their associated triggering
electronics. The field suppression with field circuit breaker on the AC side of the thyristor
converter is described in greater detail in Item 6 of this document.
Based on the system requirements the control electronics is configured as a single AVR-
channel (-A10) or double AVR-channel (-A20). One channel comprises basically one
Excitation Module with a Control Board (COB) and a Measuring Unit Board (MUB), forming
an individual processing system. Each channel contains the Software for the machine
terminal voltage regulation, field current regulation, excitation monitoring/protection functions
and a programmable logic control. In a single AVR-channel configuration a separate
controller so called Extended Gate Controller (EGC) is employed as a back-up channel, that
is a MANUAL controller.
In addition to control electronics interface cards such as Fast Input / Output (FIO) and Power
Signal Interface (PSI) are employed to provide the galvanic separation of the measuring and
control signals. Further, each thyristor bridge is equipped with a set of the converter interface
cards including Converter Interface (CIN), Gate Driver Interface (GDI) and Converter Display
(CDP).
UNITROL 5000 has a facility, by extension, for connection to a serial communication link.
For example a Modbus type serial interface can be applied. Within the excitation system the
exchange of the control and status signals is performed serially over the ARCnet Fieldbus.
The field-breaker tripping circuits are additionally hard-wired.
EXCITATION
-T02 TRANSFORMER
-Q02
T EXTERNAL I/O
-G33
COB LEGEND: -R03
-G32
MUB
AC70 Advant Controller 70 -G31
AIO Analog Input Output -V03
Interface
CDP Converter Display
CIN Converter Interface
COB Control Board -Q03
SPA -R06
CUS Current Sensor
DII Digital Input Interface
3BHS110389 E
EGC Extended Gate Controller GDI -F02 -F04
MBA FBC Fieldbus Coupler CIN
FC Field Communication M
Interface
FIO Fast I/O
-A20 GDI Gate Driver Interface -R04
LBI Local Bus Interface -R05 -C71
OR LCP Local Control Panel -C04 -C72
MBA Modbus Adapter CDP -C05
MBP Modbus Plus Adapter -R02
COB MUB Measuring Unit Board
OR MUB OBI Optical Bus Interface
PBA Profibus Adapter
ARCNET
PSI Power Signal Interface
FIELD BUS
PTI PT100 Interface
Page 4/47
2. Mechanical Design
General:
Excitation system assembly of an UNITROL 5000 is a compact mechanical structure
based on the ABB’s Modular Low Voltage Switchgear System; known as OJALA. The
functional units are fully modularized and standardized with respect to the usual rates of the
field currents and the ceiling parameters. The design works for standardization were
facilitated by introduction of the dynamic current distribution function. The equipment is
arranged in their modules, which are prepared on the stock according to the forecast. A
typical layout assembly, which is shown on Figure 2, comprises of a control electronics
cubicle; ac inlet with AC Field Circuit Breaker; the series of thyristor converter units; field
flashing, field suppression and DC Outlet.
Dynamic Current Distribution: The Effect on Mechanical Design:
In the recent history, the current distribution among the thyristor bridges was always a
problem. None of the applied methods, such as positioning of the ac inlet, current coils at the
inlet of each thyristor bridge, were totally effective. In the best case an asymmetry of 10% of
rated current as acceptable amount was more a theoretical than practical. Thanks to the
dynamic current distribution, which is a software function, the near equal currents flow
through the various thyristor bridges. In most cases for the higher current ranges, one
thyristor bridge can be saved on the account of the dynamic current distribution since the
asymmetry doesn’t need to be calculated. Further, the positioning of the ac inlet can be on
the left or on the right side of the series of the thyristor bridges. This is because appropriate
magnetic paths from the secondary to the thyristor bridges do not need to be considered.
Accordingly, the internal interconnection of the ac bus bars is now uniform and standardized.
Therefore, the workmanship and costs for the internal interconnected bus bars are
considerably reduced. Based on the forecast, most of the power parts are prepared as
modules in advance. Therefore the procurement of the material and manufacturing time
becomes easier, faster and more cost effective.
Panel Structure:
The basic mechanical construction comprises the steel base frame, cubicle frames and
cladding. Separate steel rails on the upper length of the cubicle are provided for the transport.
The cubicle frames are constructed of C-shaped galvanized sheet-steel girders with 2-mm
thickness. This provides a rigid and self-supporting construction for all of the elements of an
excitation system assembly. The cubicle frames are clad by the steel sheets, 1.5 mm in
thickness, serving only for a touching and atmospheric protection (e.g. against dust) and are
not for equipment support.
The total coating thickness amounts 55 + 5µ (primer + 1st. and 2nd. coats), whereas the
outside coat is structured inside is smooth. A higher coating thickness is provided optionally.
Door Handles:
The door handles are of a double keyway type. As an option the T - handles with cylinder
lock and two keys may be provided.
Power Circuits:
The power circuits from ac-input to the field breaker, including all interconnections between
the thyristor bridges, up to the dc – power outlets are made of bus bars.
Wiring:
The stranded wires with the tinned copper conductors, according to IEC 228 Class 5
standard, are used. The isolation is flame resistant and PVC-free. This means, in the case of
combustion, it develops very little toxic fumes. The prefabricated system cables are used for
the standard electronics connections.
Wiring Gauge:
The standard wire gauges are as follows:
• Measuring circuits:
PT’s circuits: 2.5 mm2
CT’s circuits: 2.5 mm2
• Power circuits:
According to the international standards.
Wiring Colors:
Blue cable is used for the DC Control circuits and their distribution circuits as well as for the
neutral wire. Black cable is used for all the other circuits. The earth is yellow/green. Other
colors are optional.
Terminals:
Terminals for the measuring and supply circuits are of PHOENIX disconnecting type for a
maximum gauge of 2.5 mm2. The terminals for the control and signal circuits are of the
PHOENIX clamps type for 2.5 mm2.
Designations of Components:
The components’ designations comply with the IEC 750 and DIN 40719 Part II standards.
MUB
MUB
PSI
AC-Field Breaker
PSI
SPA
Converter Electronics
Converter Electronics
Converter Electronics
FIO
3BHS110389 E
LCP
CT
CT
CUS CUS CUS
M M M
FIO
AC-Inlet
ARCnet Fieldbus
Pulse Bus
DC-Outlet
24V Supplybus
Figure 2: Basic layout of UNITROL 5000 Excitation System for approx. 3500 A
DC/DC AC/DC
Page 8/47
3. UNITROL 5000 Control Electronics
3.1 General
UNITROL 5000 is the microprocessor based control system. The platform for the control
electronics is an enhanced version of DCS 500 System mainly intended for the control and
regulation of the large static drive systems. By development of the control electronics several
elegant solutions and facilities for of the excitation systems were introduced, for example
dynamic current distribution mechanism for parallel operation of thyristor bridges and start up
from the residual machine terminal voltage. Further, the communication and diagnostic
features were also improved. In its special versions UNITROL 5000 has facilities to be
supplied from the network frequency of 162/3 Hz or from the high frequencies exciter
machines up to 500 Hz.
Possible Configurations with UNITROL 5000 System are shown on the Figures 3 … 9. The
abbreviations to the figures are as follows:
BLOCK
EGC BLOCK In this configuration, so
IF
called Twin Configuration,
BFCR
two fully redundant
converters are employed.
Any of these can be chosen
as the “on-line” converter,
whereas the other is in “stand by”. This configuration is usually applied for the rated currents
up to 2000 A.
THYRISTOR CONVERTER
Figure 5: Type D5S – Single
COB
UG
1 Channel and Back up Control
IG AVR with Redundant n – 1
IF Converters.
FCR
BLOCK
COB 2
UG
IG AVR
IF
FCR
BLOCK BLOCK
COB 2
UG
IG AVR
IF
FCR
IF
FCR
BLOCK
COB 2 2
UG
IG AVR
IF
FCR
Local
Service Control
Panel Panel
CMT
SPA AC70 FIO FIO LCP ARCnet
/
ARCnet
Field
Bus
AVR - Channel II CONVERTER 4
CONVERTER 3
AVR - Channel I
CONVERTER 2
COB CONVERTER 1
(Control Board)
Converter
AVR Uc Electronics
3BHS110389 E
Monitoring CIN
(Converter Interface)
MUB
Protection
(Measuring Board)
G31
(Gate Driver
Interface)
Logic Control
Converter Display
FIELD FLASHING
Page 13/47
SM
FIELD SUPPRESSION
• Measuring Unit Board (MUB)
Measuring Unit Board (MUB) consists of a Digital Signal Processor (DSP) and the Intel DSP
56303. This provides fast processing of the actual measuring values, galvanic separation
and level matching.
The following functions are implemented in the Measuring Unit Board (MUB):
- Filtering and digitizing.
- Calculation of field current and voltage; input currents and voltages of the
thyristor converter; active and reactive power; Cos-phi and machine’s
frequency.
- Power System Stabilizer (PSS) with accelerating power and frequency
input signals, in which the control algorithm is based on IEEE Std. 421-
Type 2A.
- Adaptable Power System Stabilizer (an alternative to the PSS).
16 function keys with LED’s for status indication are available for local operation control of
the excitation system.
CMT-Tools are MS-WindowsTM based tools intended for the testing, commissioning and
maintenance of the UNITROL 5000 System. CMT-Tools can be purchased as a stand alone
software package or installed into a PC, which is preferably a Laptop. For connection to the
Control Board (COB) a PCMCIA card for PC and a fibre-optic cable are also integrated parts
of the package. CMT-Tools are based on the windows with menu items and provides the
functions described in the followings.
• An image of the Local Control Panel can be displayed on the PC screen with
modern user visual interface like push buttons, status signal, reference value setting
indication, etc. Their controls are performed by the mouse click or by the PC keyboard.
Please refer to the Figure 13.
• Trending function is provided for optimising the transient response of the regulation
closed loop during commissioning and therefore for verification and final tuning of the
AVR’s and other regulating parameters. In fact, it replaces the conventional testing
equipment such as testing terminals, external provision for the step signals (e.g. +/-
10% to the reference value) and other typical testing ancillaries. Six freely chosen
measuring signals (six channels) can be displayed. The provision for scaling of the
signals and their scanning rate is also included. All trending can be stored and
subsequently used for the Commissioning Report.
• Handling of the Fault Logger with storing capacity up to the 100 events and alarms
with the system’s real-time stamp. The same recorded alarms/events can be
displayed on LCD of the Local Service Panel (SPA) in clear English test.
• Displaying of the Software Diagrams in real time, which are functional blocks of the
various functions such as logic control, AVR, limiters, protection and monitoring. This
function possesses the facility for measuring the input and output signals of the
particular function blocks in real time and for modification the system parameters (like
AVR parameters).
• Programming facilities for modification of the application program. That is, some
function blocks can be implemented into the control sequence.
The CMT-Tools described in the previous section can be handled remotely via the public
telephone network (via satellite). For this purpose two personal computers should be
provided; a host PC and a remote PC, both equipped with the CMT-Tools, the
communication software and modems. For the practical reason, an operator making a
remote diagnostic does not have a direct access to the CPU, but coordinate the diagnostic
with the operator on the host side. ABB can propose the remote diagnostic package,
including the service agreement on request.
3.6.1 Conventional control interface (with opto-coupler inputs and relay outputs)
The digital and analogue command and status signals are interfaced via the Fast Input /
Output boards (FIO). Each fast Input / Output board (FIO) is equipped with:
- 16 Digital inputs with opto-couplers, rated for 24 VDC. The control inputs are activated
using a local 24 VDC from the internal power packs.
- 18 output relays with change over contacts for status indications and alarms.
- 4 multipurpose analogue inputs + 10 V or + 20 mA
- 4 multipurpose analogue outputs 4 … 20 mA
- 3 analogue inputs for excitation transformer temperature measuring PTC or PT100
A maximum number of two Fast Input / Output boards can be implemented per system,
which is sufficient for most system requirements. In case that more digital inputs and outputs
are requested, the system can be supplemented with Digital Input Interface (DII) and Relay
Output Interface (ROI). These are connected to the ARCnet Field Bus over a Field Bus
Coupler (FBC).
Standard interface signals are assigned according to Table 1.
One of the following serial interfaces can be applied to handle the serial link communication
with another intelligent system:
• AC70BAS, Advant
Depending on the control requirements, certain function blocks must be added to the
application program during the project engineering.
The calculations are fully digital. Analogue measurement signals such as terminal voltage
and current are converted into digital signals by analogue/digital converters, which are parts
of the Measuring Unit Board (MUB). The set points and limit values are already defined in
digital form.
Figure 15 shows the overall software’s functions of an AVR, which are implemented into a
®
standard UNITROL 5000 static excitation system. For a better understanding of those
software’s functions, they are split into functional blocks followed by the short functional
description. The numbers within the functional blocks correspond to those mentioned in the
descriptions.
Ug
Uf ALARM
Fault logger
Uc
EVENTS
(8) Icosphi
If If Limiter Max.
Gate
Ig IG Limiter
AVR-PID
User Limiter
(11)
(12) Gate
Control
Ug
Σ Σ
IEEE, Type ST2A
Measuring Board (MUB)
P P Σ f t
(6) Follow-up
T
delay
0 Run Σ
(3) Q-static
Ch. II
U
Q
Q
(7) Uc (Ch. II) Σ
(1) AVR-setpoint
generator Man
AVR Integrator
Set
ref.
∫
value
Fast I/O (FIO)
CONTROL
LOGIC (15) Q-Reg.
RAISE raise
Set
LOWER lower
ref.
COSPHI ON CosPhi/
Var value
VAR ON AUTO/ Σ
AUTO ON MANUAL
MAN ON CH I / CH II
CH I ON Field Braker (16) Cos- P, Q
CH II ON ON/OFF phi Reg. Cos
Excitation -phi
BREKER ON ON/OFF
BREAKER OFF Set
EXC ON ref.
value
EXC OFF Σ
SM
3
®
Fig. 15: Internal structure of UNITROL 5000 Automatic Voltage Regulator
V/Hz Limiter
(4) V/Hz limiter is provided in order to avoid over fluxing of the transformers. If the set point
of the AVR is too high for a certain frequency, the set point will reduce smoothly according to
a pre-adjusted V/Hz characteristic. The limiter becomes active after an adjustable delay time.
Soft-start
(5) Soft start facility prevents overshoots of the terminal voltage when building up the
excitation (field flashing). As soon as the excitation is switched on and after the initial field
flashing is complete (approx. 10% of generator voltage), the soft-start-signal increases the
machine terminal voltage with an adjustable gradient. This signal is given priority until its
value exceeds the signal from the set point generator.
In a double automatic channel configuration the change over is normally from AUTO mode of
the active channel to the AUTO Mode of the stand-by channel. Indeed, any of channels may
be active or stand-by. In case the change over to the AUTO Mode of stand-by channel is not
possible, a change over to the MANUAL mode will be initiated. Only in case that both of
channels are inoperable a trip command will be given. In this configuration the follow-up
signal to the inactive channel is derived from the difference of the control signals of the
active and inactive channels (Follow up block (7)).
In a Single Channel and Back up control configuration the Back up Field Current Regulator
(BFCR) automatically follows up the Control Board (COB). In case the Control Board (COB)
Limiter gates
The limiter gates (8) and (9) determine the priority of the over excitation or under excitation
limiters over the terminal voltage control. In order to avoid that two limiters are active at the
same time (e.g. in case of system fault), a priority flag can be set choosing which of the
limiter groups (over excitation or under excitation) acts first.
PID Controller
The input voltage of the PID controller (11) represents the voltage error that is the difference
between an actual value and a set point. The output of the PID controller, which is so called
control voltage Uc, is required as an input signal for the gate control unit (12).
The feedback parameters of the PID controller are automatically adjusted in a way to
achieve an optimum control performance of the synchronous machine. Depending on that,
which limiter becomes active, the Parameter Selector (10) activates the appropriate set of
PID parameters (SET1/SET2). This contributes to the transient stability of the synchronous
machine.
Figure 16 shows a typical power chart of a salient pole synchronous machine with the
corresponding operation limits in steady state condition for 1 p.u. terminal voltage.
Fig.
16: Power chart of a salient pole synchronous machine
®
UNITROL 5000 excitation system provides the following limiter functions:
All the limiters have an actual value, which represents the value to be limited, and a set point
at which the limiter should actuate. Each limiter generates an error signal ∆ resulting from
the difference between the actual value and the set point.
When the over-excitation limiter acts, it will reduce the excitation to a maximum permissible
level and when an under-excitation limiter acts, it will increase the excitation to a minimum
required level. During normal operation, the machine is operated inside the permissible
range of the power chart. The input of the PID controller is the main error signal ∆act-ref
(Uact-Uref). If for some operational reason the error signal ∆lim- of the over-excitation limiter
becomes lower than the main error signal, it gets priority over the main error signal. That is,
the PID controller will receive in this particular case the lowest error signal. The same
philosophy is applicable for the under excitation limiters but obviously in the other direction.
Maximum field current limiter is used to protect the rotor and excitation power circuits from
overheating.
It has basically two different set points, for the ceiling limitation (field forcing) and for the
thermal limitation (maximum continuous). The feature of the thermal limitation is determined
with two additional set points, which represent the equivalent time for overheating and
cooling-down of the rotor.
From the above mentioned the basic set values are listed are follows:
With these settings, the maximum field current limiter is able to reproduce the maximum
permissible thermal energy ∆Emax in the field winding. The parameters’ settings and
functional blocks of this limiter are shown on Figure 17.
Itherm 1/2
Surpluscurrent
Surplus power Overheat detector
integrator
Overcurrent
∫ ∆i dt
2
Detector
+
∫ ∆i dt
2
Σ max ∫ ∆i 2 dt
2
-
t
∆E max 0
Tequiv Tcooling
+ ∆ifield
Actual
Actual field field current
current Ifield Σ K
-
To Gate Logic
If an another fault in the system occurs which forces the excitation again to a current higher
then Itherm, before the cooling down time has elapsed, the permissible time for ceiling will
obviously be shorter than in the first fault since the value of ∆Emax will be reached earlier.
The limiter will only allow the field current to remain at ceiling level during Tceiling if the
cooling down time has elapsed (reset).
The thermal set point Itherm can be influenced by an external signal, e.g. representing the
machine cooling air temperature. This signal is added to the internal set point Itherm.
The transient behavior of the maximum field current limiter in operation for two different
cases is shown on Figure 18.
If [A]
prospective value of
field current
Ifmax
(1,6*Ifn) Case 1
Case 2
Iftherm
(1,05*Ifn)
Tequiv
(10 s)
t [s]
The time for the activation of thermal limiter is given by the following expression:
2
Im ax1 / 2−0,9
t = •Tequiv
If −0 ,9
The main task of the minimum current limiter is to prevent the interruption of the field current.
This function is usually applied for the hydro generators, which may operate deeply in under-
excitation range of the power chart, i.e. close to zero current. In this range the minimum field
current limiter keeps on the field current to a minimum value, which is necessary for the
current commutation purposes. In addition, it may be employed to protect the rotor pole caps
from excessive overheating.
The minimum field current limiter has only one set point corresponding to the permissible
minimum field current and it acts immediately. The main parameter setting and functional
blocks of this limiter are shown on Figure 17.
This limiter prevents excessive heating of the generator’s stator windings, in both the over-
excited and under-excited operating ranges.
It is based on the similar operation principle as the maximum field current limiter. The main
difference in operation is related to the set value of the ceiling limitation (maximum stator
current), which has no a definite value. Theoretically, the limiter curve may reach an infinite
value (Imax = ∞) for the operation time close to zero. With appropriate setting of the
parameters an inverse time limiting characteristic can be achieved, which approaches to the
maximum permissible thermal energy ∆Emax of the stator winding.
To Gate Logic
- Lead
Itherm 1/2 ∆ig
+
Σ K
- Lag
Actual stator current
Overcurrent
∫ ∆i dt
2
detector
+
∫ ∆i dt
2
Σ max ∫ ∆i 2 dt
-
t
∆E max 0
Tequiv. Tcooling
Fig. 19: Stator current limiter for over and under excited mode of operation
Obviously, the stator current limiter can not influence the active current. If the value of the
active current reaches a level higher than the set point of the stator current limiter, the
reactive power is regulated close to zero in order to avoid incorrect operation of the limiter.
The P/Q limiter is basically an under excitation limiter which is intended to avoid the machine
being operated beyond the stability limit. The limiting curve can be set by 5 reactive power
values for five levels of active power (P=0%, P=25%, P=50%, P=75% and P=100%). These
values are defined for the rated machine voltage. The limiting characteristic is shifted
proportionally to the deviation from the actual to the rated machine voltage as the stability
limit is shifted.
85
60
I fmax = f(ϑ)
40
20
ϑ ROTO
20 40 60 80 100 (%)
75 90 120 150 ( °C)
Fig. 21: Temperature dependent field current limiter
Q-Regulation Function
P lower rise
raise
lower
ϕ
Qreg
pre-
set
reset
Q1 Q2 Q
The operation points within the power chart of the chosen superimposed control mode can
be adjusted:
• Locally from the Local Control Panel (LCP) or Service Panel (SPA).
• Remotely by Raise and Lower commands.
• Remotely by a mA signal.
• Remotely through a serial communication link.
P rise
raise lower
lower ϕ
pre- cosϕ1 cos ϕ 2
set
reset
Qcosphi reg. Q
KS3
∆ω-Washout ∆P-Integrator
GOVERNOR
P
SY. MACHINE Ug
THYRISTOR CONVERTER
Σ AVR
IDENTIFIER
Σ CONTROLLER
A 3rd. order, linear model algorithm of the power system is applied. This provides a good
approach and a compromise between the quality of results and the computation time. The
model parameters are estimated during operation and used by the controller.
The regulation algorithm calculates the characteristic equation of the closed loop. It also
adjusts the parameters of its own function in a way that the desired pole excursion achieves
a better damping position.
Additionally, a White-noise program is implemented. This is a random sequence with zero
average value and a relatively small magnitude. This signal is needed when the system is
stable. Namely, if the power system reaches an appropriate stability, the parameters can not
be identified from the almost constant power system output signal.
The set-point function (17) for the manual control mode has the same facilities of the set-
point function as the AVR control mode. The minimum and maximum set points as well as
the different running times can be adjusted. When operating in manual mode, the set point
for field current may be controlled by raise or lower commands.
An immediate reset input is provided in order to avoid over voltages caused by reactive load
rejections when operating in manual mode. In case the machine breaker trips, a pulse
command is applied to the reset input, which sets the field current immediately back to a pre-
set value which normally corresponds to 90..100% of the no-load field current of the
synchronous machine.
In case a so-called Manual Restrict (19) is desired, the minimum and maximum set-points
of the manual control are calculated as function of the present active and reactive power
levels as well as a function of the machine actual voltage. For the manual restrict function,
measured values from the machine PT's and CT's are required.
The resulting error signal at the output of the summing point is applied to a filter circuit with
PI characteristic.
The output of the PI-Filter is applied to a signal selector (20) which transmits either the Uc
signal from the AVR (automatic mode) or Uc from the field current controller (manual mode)
to the gate control unit depending on which control mode has been selected in the logic
control.
The actual value monitor is based on the comparison of two different measuring voltages.
That is, the machine terminal voltage measured by PT's is continuously compared with the
voltage at the secondary side of the excitation transformer. If the difference between these
two voltages exceeds a pre-adjusted threshold value, the control logic will initiate a change
over. If only one set of the PT’s is available, a change over will be from automatic to manual
mode of operation. In case two sets of PT’s are available, one set per channel, a change
over will be from automatic mode of the incorrect channel, if it was in operation, to the
automatic mode of the stand by channel. If, however, both sets of PT’s fail the change over
will be to a manual channel. A change over takes place when the mean value between both
compared signals exceeds a pre-set threshold value of 15% of the rated machine terminal
voltage.
The principle of the rotor temperature measuring is based on the calculation of the field
winding resistance according to the following expressions:
Uf
− U B − if ⋅ ( RB + RL )
pT 1
Rf =
if
Td 0'
T1 =
Tdl
Where:
Uf = Field voltage
If = Field current
Lf = Field inductance
UB = Voltage drop on brushes
RB = Resistance of brushes
RL = Resistance of the power conductors between measuring point for
field voltage and brushes
Td1 = Equivalent time constant
Td0’ = Field time constant
Tdl = Load time constant (between Td’ and Td0’)
p = Laplace’s operator
Based on the calculation result for the field winding resistance, the temperature is calculated
from the following expression:
The result for Tf may be displayed locally and / or remotely and can be used for alarm
indication.
Overcurrent protection
The overcurrent protection basically includes two protection functions:
• Inverse time characteristic overcurrent protection.
• Instantaneous overcurrent protection.
The overcurrent protection operates in conjunction with the Maximum Field Current Limiter
Function described in Item 4.3. Both operating characteristics are similar, whereas the
overcurrent protection characteristic is adjusted to operate above the limiter characteristic.
The operation is also time delayed with respect to the limiter characteristic.
The loss of field protection is intended to trip the synchronous machine in case of operation
beyond its stability limit.
The desired operating characteristic is set by the five operation points within the power chart,
according to Figure 26, Loss of Field Protection Block Diagram. The operation characteristic
is similar to the P/Q Limiter operation characteristic. Both characteristics are coordinated in a
way that the P/Q Protection characteristic is shifted for five to ten percent left from the P/Q
Limiter characteristic. Since the stability limit of a synchronous machine depends on the
machine terminal voltage, the operating characteristic are also corrected proportionally to the
machine terminal voltage.
Iq correction
Los of Excitation Protection =f(Ug)
P
Ug actual
T 0
Iq actual
act
This protection is intended to avoid the over-fluxing of the synchronous machine and block
transformer in case their maximum V/Hz characteristic is exceeded. The protection function
is based on the comparison of the reference voltage, which depends on the machine
frequency with the actual value of the machine voltage. If the reference value is exceeded, a
timer is activated. If the voltage does not return to the permissible value, before the adjusted
time delay has elapsed, a trip signal is initiated.
V/Hz-Protection
V/Hz-function
f UV/Hz
Detection Delay
f TRIP
Ug
T 0
Ug
The measurement of the excitation transformer winding temperature is performed within the
®
UNITROL 5000 software. The measurement of the temperature is derived either from the
PTC or PT100 Sensors. These are built into the hot-spot place of each phase of the
secondary winding. If the solution with PTC Sensors is chosen, two sensors per phase are
employed. Each set is serially connected and led to their assigned analog inputs of the Fast
Input / Output Boards (FIO). Two analog inputs are used. The temperature condition is
detected for two predefined temperature’s thresholds for Stage one and Stage two. The first
stage initiates an alarm and the second stage causes the trip of the excitation system.
In case the PT100 Sensors are chosen, one sensor per phase is employed and connected to
its assigned analog input of the Fast Input / Output Boards (FIO). In this solution three
analog inputs are used. The temperature of the excitation transformer is continuously
measured. The measuring signal of the real temperature can be displayed on the Local
Control Panel (LCP), Local Service Panel (LSP) or can be transmitted to the Control Room.
Similar to the former solution the temperature condition is detected in software for two
predefined temperature’s thresholds, for alarm and trip purposes.
Self-test functions of the electronics cards include program sequence monitoring ("watch
dog"). The particular faults are displayed on the seven-segment display of the Control Board
(COB). Further, the input voltages to the power packs and their stabilized values are
supervised.
Thyristor converter
The following functions for monitoring of the thyristor converter operation are available:
AC over-voltage protection
The CROWBAR circuit employs break-over diodes to detect positive and negative over-
voltages in the field circuit. Whenever they respond, the associated thyristor is fired,
connecting immediately the field suppression resistor in parallel to the field. Simultaneously,
an excitation trip is initiated, causing an immediate opening of the field circuit breaker.
The purpose of the earth fault protection is to monitor the isolation level of the field winding
with respect to the earth. If this function is requested to be included within the excitation
system equipment, ABB provides an Earth Fault Relay Type UNS 3020. The measuring
principle is based on the Whetstone’s Bridge, in which the balance of the measuring bridge
is established by two capacitors; one connected between the positive lead and the earth and
another one connected between the negative lead and the earth. With this relay, not only the
isolation level of the field winding is detected but also the isolation level of all power
equipment including secondary winding of the excitation transformer. It comprises two
stages or two different levels, both individually adjustable regarding the fault resistance and
time delay. Whenever an alarm for earth fault is given, it is stored in the relay and can be
acknowledged using the RESET button on the front of the module. This relay may be tested
while the excitation is switched on. More information can be taken from a separate brochure.
- The thyristor converter should continuously provide 10% more field current than
required by the synchronous machine under rated working conditions.
- The thyristor converter should supply a so-called field ceiling, e.g. 1.6 times of rated
field voltage, for a short period of time (usually 10 sec.). In case of disturbances in the
power network the field ceiling capability contributes to a shorter settling time of the
main machine terminal voltage, reactive and active power, load angle and network
parameters.
- The thyristor converter should withstand the induced field current due to a 3 phase
short circuit on the machine terminals or on the high voltage side of the block
transformer.
- The repetitive peak reverse voltage as well as the repetitive peak off-state voltage of
the applied thyristors should satisfy the voltage security factor of at least 2.7.This is
referred to the maximum value of the excitation transformer secondary voltage.
Each thyristor converter is a self-standing unit with its modularized parts, that are particularly
described in item 5.1. No part is commonly used between the thyristor converters connected
in parallel. Thus a fault in one thyristor converter does not influence the operation of other
thyristor converters working in parallel.
Each thyristor converter consists of one full wave thyristor bridge module, equipped with 6
double side-cooled thyristors. An ultra speed fuse is connected in series to each thyristor. Its
main purpose is to isolate a branch with faulty thyristor, thus protecting other thyristors and
their fuses from damage. On melting, a microswitch, forming part of the fuse, is actuated by
a spring for control and annunciation purpose.
The thyristor heatsinks are forced cooled by AC-motor driven centrifugal fan(s). The fan’s
fault is indirectly monitored by the measuring of the thyristor converter temperature, which is
a function within the Converter Interface (CIN). A redundant forced cooling is provided as an
option. The AC-motor driven centrifugal fan with other associated components are installed
in a fan box, which is easy removable.
Natural cooling, if required, is mainly applicable for the Mechanical Protection Class IP20.
However, if a higher Mechanical Protection Class is specified, requiring also the filter mats at
air inlets and outlets, the door fan is needed. Its main role is to establish an airflow through
the cubicle.
The equal current division between the thyristor converters working in parallel is assured by
the dynamic current distribution mechanism, which is a software function within the
Converter Interface (CIN). For this purpose and for the purpose of the conduction monitoring
the Hall-Sensors are employed for the current measuring.
Optionally, a 5 - pole isolator may be integrated per each thyristor converter. This is used for
repairing a faulty thyristor converter, while the others are under load. However, ABB
standard solution is with an additional thyristor converter (n-2 design) instead of 5 – pole
isolator.
Two level adjustable thermal-sensor is employed for monitoring of the thyristor converter
temperature.
5.3 N - 1 Configuration
N -1 configuration is designed by three or more thyristor converters working in parallel
simultaneously. With one thyristor bridge out of operation, all required working conditions are
possible without restrictions.
The conduction monitoring function within the Converter Interface (CIN) monitors the
operation of the thyristor converter and takes care of the fault evaluation. E.g. if two
thyristors in separate thyristor converters but if different branches fail, the excitation system
will still remain in operation. Only in the case when two or more thyristors in the same
branches fail, the trip will be initiated. With this function a higher availability of the excitation
system is achieved.
A field suppression starts upon receiving a trip command, either from the generator
protection system or from the internal excitation system protection. The sequential control
sends the simultaneous commands for: AC-Field breaker OFF, pulse blocking and for the
triggering of the CROWBAR thyristor. The later command enables the commutation of the
field current to the field suppression resistor. Since the pulse blocking is also applied, the
available negative wave of the ac-supply voltage is added to the arcing voltage of the field
breaker and the field suppression time is reduced.
The field suppression with the field circuit breaker on dc side of the thyristor converter is
applied if requested. The sequential control is similar to the above described but the inverter
operation of the thyristor converter is introduced instead of the is pulse blocking.
The rate of the field discharge resistor is sized and coordinated with the field breaker arching
voltage and the maximum admissible voltage across the field winding. It is also sized to
absorb the suppressing energy, accumulated in the field winding, due to an induced field
current from a three-phase short circuit on generator terminals and / or from the ceiling field
current in no-load operation.
Since only a small current is supplied from the back-up field flashing circuit, a battery can
always be used for large excitation systems. This means that with a relatively high ohmic
resistor in the field flashing circuit the field time constant (L/R) is also considerably reduced.