10 S Y N C H R O TA C T D ATA S H E E T S Y N C H R O N I Z I N G D E V I C E S A N D S Y S T E M S


SYNCHROTACT 6
Principle of operation
The synchronizing and paralleling process can be divided into the following blocks

Measuring Command generation


The main values, required for paralleling, are voltage diffe- The command generation calculates the necessary lead angle
rence ΔU (amplitude), slip s (frequency difference), and αv, by which the paralleling command must be advanced due
phase-angle difference α. These values are formed from the to closing time delay. The action ensures that the main contacts
two measurement signals u1 and u2 (see illustration below). close at precisely the right time. If α reaches αv at the same
time as paralleling release (CHK REL), the command is issued.
Matching With networks or dead bus conditions, the related signal
Voltage and frequency matching functions reduce the voltage from the monitoring CHK REL, SYNREL or DBREL will start
difference ΔU, and slip s by sending adjusting pulses to the its assigned supervision time t supC, t supS, or t supD. After
voltage or turbine regulators. the corresponding supervision time runs out, the command
is issued. Every single one of these branches can be used in
Monitoring of paralleling conditions parallel with the others, or switched off.
This function compares the actual values with their set
maximum values and releases paralleling (CHK REL) if all Synchrocheck mode (paralleling monitoring)
conditions are fulfilled simultaneously. Alternatively, for In synchrocheck mode, only the measuring and monitoring
almost synchronous sources (very small slip between two function blocks are active. The output relay is closed during
lines), the SYN REL-function may be used. If it comes to paralleling release.
voltage-free lines (dead bus), the DB REL-function is used.

Seite 8

SYNCHROTACT 6
Measuring Matching
u1 U1 = U+
=
U = U-
Utarget
u2 U2 f+
=
=
s ds/dt
= f-
ds/dt
s starget
s
d /dt Monitoring
d /dt Umax

Umin
& CHK REL
Umax

smax
SYN REL
max
&
d max
Dead Bus
U1not
&

1*2not & OR
DB REL
U0max &
Release DB U2not &
Exclusive DB
Block:
& - CHK REL
Excl. DB = ON - SYN REL

Command ds/dt
tsupS

generation tsupD CMD


f1
OR tpon
tsupC
s + v
+ &
ton S17002