You are on page 1of 1

39 M Deck Type Truss Bridge -Design

LARSEN & TOUBRO LIMITED


ECC DIVISION
400/220/66kV GIS Substation Project Wangtoo, Himachal Pradesh 110/100 MVA
PROJECT:
Transformer Transportation across River Sutlej
STRUCTURE: 39 M Deck Type Truss Bridge -Typical Welded Connection

Typical Connection

14 MT 49 MT

50 MT
35 MT

Free Body Diagram 520


50

MC 200 Front to Front

330 300 400


130
520 340 50

140 140 210

F1

F2
Weld Capacity of Diagonal Member
Thickness of Weld = 10
Area of Weld = 3304 mm2
Axial Load on Gusset = 25 MT
Direct Shear Stresses on Weld = 75.7 N/mm2
< 100 N/mm2
Capacity available

Weld Capacity of Vertical Member


Thickness of Weld = 10
Area of Weld = 6160 mm2
Axial Load on Gusset = 17.5 MT
Direct Shear Stresses on Weld = 28.4 N/mm2
< 100 N/mm2
Capacity available

Weld Capacity of Main Member


Thickness of Weld = 10
Area of Weld = 6440 mm2
Moment of Inertia = 271301333 mm2
Horizontal Load on Gusset (Component on Diagonal Member) = 17.7 MT
Shear Stresses on Weld = 27.4 N/mm2
Vertical Load on Gusset (Component on Diagonal Member) Tension = 17.7 MT
Vertical Load on Gusset (Vertical Member)Compression = 17.7 MT
Moment = 0.9 MT-m
Max Shear Stress due to Moment = 9.8 N/mm2
Resultant Shear Stress on weld Group = 29.1 N/mm2
< 100 N/mm2
Capacity available