GENERATOR LOAD TEST REPORT

JOB NAME GENERATOR LOAD TEST DATE 10.6.2020


CUSTOMER GENERATOR LOCATION ATTARAT
GENERATOR SET CURSOR13TE2A.S551 S/N. 0262398 LOAD 80%
KVA 350 KW 280 VOLTS 400/230 AMPS 476
PHASE 3 Hz 50 RPM 1500 P.F. 0.8

 FUNCTIONAL CHECKS
 VISUAL INSPECTION
 Oil level
 Water level
 Fuel level
 Water line
 Fuel line
 Oil line
 FUNCTIONAL TEST
 Refueling system (Automatic, Manual)
 Automatic battery charger
 Manual start
 Manual stop
 Emergency Stop push button
 Stop for Failure
 Low oil pressure
 High engine temperature
 LOAD TEST
AMPS VOLTS OIL ENGINE
HERTZ
L1 L2 L3 L1 L2 L3 PRESSURE TEMP
50 0 0 0 230 230 230 5.9 bar 40 C°
50 37 37 37 230 230 230 5.9 bar 55 C°
50 77 77 77 230 230 230 5.8 bar 63 C°
50 105 105 105 230 230 230 5.7 bar 75 C°
50 150 150 150 230 230 230 5.6 bar 82 C°
50 200 200 200 230 230 230 5.6 bar 84 C°
50 225 225 225 230 230 230 5.6 bar 82 C°
50 275 275 275 230 230 230 5.6 bar 82 C°
50 335 335 335 230 230 230 5.6 bar 82 C°
50 365 365 365 230 230 230 5.6 bar 82 C°

 Notes:
 Engine oil needs to be increased
 Needs to replace the Boost Pressure Sensor