Professional Documents
Culture Documents
UCM-CLD Set Up L80 - SB - 050 - E PDF
UCM-CLD Set Up L80 - SB - 050 - E PDF
Bulletin Page 1 OF 9
AIM :
This Service Bulletin provides you the factory settings to check UCM-CLD
configuration.
Alarm
ADAPTIVE CONTROL TM
NOTE : The configuration in Service settings has already been set before the unit leaves the factory and its password protected in
order to maintain proper operation of the chiller.
Trane EMA N° L80 SB 050 E 1097
APPLICABLE SOFTWARE :
This Service Bulletin applies to screw liquid chiller UCM-CLD microprocessor panels
with the following module revision.
Later software revisions may include items not found in the menu to follow.
The UCM shall impose a minimum difference of 2.8°C between "LVG WTR temp. Cutout setpoint" and "Chilled WTR temp.
Setpoint". Also 8.3°C between "Low RFGT temp. cutout setpoint" and "Chilled WTR temp. Setpoint".
Trane EMA N° L80 SB 050 E 1097
MR = Manuel reset
AR = Auto reset
IFW = Informational warnings
§2 LIMIT HP
"HPC" R 22 = 2793 kPA
"HPC" R 134a = 2200 kPA
"HPC" R 404a = 3000 kPA
"
AIR COOLED UNITS + RTXA clg
LVG WTR - 12 - 7.9 - 5.9 - 2.9 - 0.9 1.1 3.1 5.1
to - 8 to - 6 à-3 to - 1 to 1 to 3 to 5 to 10
TEMP
R22 83 84 85 86 87 88 89 90
% HPC R404a 78 79 81 82 83 84 85 87
R134a 83 84 85 86 87 88 89 90
§3 COMPRESSOR TONS
UNIT
108 109 110 207 209 210
Compressor CKT 1 CHHB 70 CHHB 85 CHHB 100 CHHN 35 CHHN 40 CHHN 50
(IS 70) (IS 85) (IS 100) (GP 35) (GP 40) (GP 50)
Config. 50 Hz 60 70 85 30 35 40
CKT 1 60 Hz 70 85 100 35 40 50
Compressor CKT 2 - - - CHHN 35 CHHN 40 CHHN
(GP 35) (GP 40) (GP 40)
Config. 50 Hz - - - 30 35 35
CKT 2 60 Hz - - - 35 40 40
UNIT
211 212 213 214 215 216 217
Compressor CKT 1 CHHN 50 CHHN 60 CHHB 70 CHHB 85 CHHB 85 CHHB CHHB
(GP 50) (GP 60) (IS 70) (IS 85) (IS 85) 100 100
(IS 100) (IS 100)
Config. 50 Hz 40 50 60 70 70 85 85
CKT 1 60 Hz 50 60 70 85 85 100 100
Compressor CKT 2 CHHN 50 CHHN 60 CHHB 70 CHHB 70 CHHB 85 CHHB 85 CHHB
(GP 50) (GP 60) (IS 70) (IS 70) (IS 85) (IS 85) 100
(IS 100)
Config. 50 Hz 40 50 60 60 70 70 85
CKT 2 60 Hz 50 60 70 70 85 85 100
UNIT
322 324 328 430 432 434
Compressor CKT 1 CHHB 70 CHHB 85 CHHB 100 CHHB 85 CHHB 100 CHHB 100
(IS 70) (IS 85) (IS 100 (IS 85) (IS 100) (IS 100)
Config. 50 Hz 60 70 85 70 85 85
CKT 1 60 Hz 70 85 100 85 100 100
Compressor CKT 2 CHHB 70 CHHB 85 CHHB 100 CHHB 85 CHHB 100 CHHB 100
(IS 70) (IS 85) (IS 100) (IS 85) (IS 100) (IS 100)
Config. 50 Hz 60 70 85 70 85 85
CKT 2 60 Hz 70 85 100 85 100 100
Compressor CKT 3 CHHB 85 CHHB 100 CHHB 100 CHHB 85 CHHB 85 CHHB 100
(IS 85) (IS 100) (IS 100) (IS 85) (IS 85) (IS 100)
Config. 50 Hz 70 85 85 70 70 85
CKT 3 60 Hz 85 100 100 85 85 100
Compressor CKT 4 - - - CHHB 85 CHHB 85 CHHB 100
(IS 85) (IS 85) (IS 100)
Config. 50 Hz - - - 70 70 85
CKT 4 60 Hz - - - 85 85 100
Trane EMA N° L80 SB 050 E 1097
§4 NUMBER OF FANS
EUROPE EXPORT
Std Low amb Hi eff Hi amb Hi eff
Nb conf Nb conf Nb conf Nb conf Nb conf
fans ucm fans ucm fans ucm fans ucm fans ucm
RTAB 108 ckt 1 4 4 4 4 6 6/5 / / / /
ckt 2 / / / / / / / / / /
RTAB 109 ck 1 5 5 5 5 6 6/5 / / / /
ck2 / / / / / / / / / /
RTAB 110 ckt 1 6 6 6 5 6 6/5 / / / /
ckt 2 / / / / / / / / / /
RTAB 207 ckt 1 2 4 2 4 2 4 3 5 / /
ckt 2 2 4 2 4 2 4 3 5 / /
RTAB 209 ckt 1 2 4 2 4 3 5 3 5 / /
ckt 2 2 4 2 4 3 5 3 5 / /
RTAB 210 ckt 1 3 5 3 5 3 5 3 5 / /
ckt 2 2 4 2 4 3 5 3 5 / /
RTAB 211 ckt 1 3 5 3 5 3 5 4 4 / /
ckt 2 3 5 3 5 3 5 4 4 / /
RTAB 212 ckt 1 3 5 3 5 4 4 4 4 / /
ckt 2 3 5 3 5 4 4 4 4 / /
RTAA 213 ckt 1 4 4 4 4 4 4 4 4 / /
ckt 2 4 4 4 4 4 4 4 4 / /
RTAA 214 ckt 1 4 4 4 4 5 5 4 4 / /
ckt 2 4 4 4 4 4 4 4 4 / /
RTAA 215 ckt 1 4 4 4 4 5 5 4 4 / /
ckt 2 4 4 4 4 5 5 4 4 / /
RTAA 216 ckt 1 5 5 5 5 5 5 5 5 / /
ckt 2 4 4 4 4 5 5 5 5 / /
RTAA 217 ckt 1 5 5 5 5 5 5 5 5 / /
ckt 2 5 5 5 5 5 5 5 5 / /
RTAA 322 ckt 1 8 4 8 4 8 4 8 4 8 4
ckt 2 4 4 4 4 6 5 4 4 6 5
RTAA 324 ckt 1 8 4 8 4 10 5 8 4 10 5
ckt 2 6 5 6 5 6 5 6 5 6 5
RTAA 328 ckt 1 10 5 10 5 / / 10 5 / /
ckt 2 6 5 6 5 / / 6 5 / /
RTAA 430 ckt 1 8 4 8 4 10 5 8 4 10 5
ckt 2 8 4 8 4 8 4 8 4 8 4
RTAA 432 ckt 1 10 5 10 5 10 5 10 5 10 5
ckt 2 8 4 8 4 10 5 8 4 10 5
RTAA 434 ckt 1 10 5 10 5 / / 10 5 / /
ckt 2 10 5 10 5 / / 10 5 / /
RTCA 108 111 208 211 213 213 216 113 116
109 209 215 115
RTUA 108 110 207 211 212 213 216 108 110
109 209 215 217 109
Ckt 1 Nb fan 4 6 2 3 4 4 6 8 12
Config 4 6 4 5 4 4 4 4 6
Ckt 2 Nb fan - - 2 3 4 4 6 - -
Config - - 4 5 4 4 4 - -
§5 CURRENT OVERLOAD
REFRIGERANT R134a
COMPRESSOR
CHHN 35 CHHN 40 CHHN 50 CHHN 60 CHHB 70 CHHB 85 CHHB 100
RLA (A) 44 50 59 71 86 99 115
380/50/3 CT ext. 09 09 10 10 01 01 02
Dip switch 10110 11111 01110 11100 10101 11100 01010
UCM confi 22 31 14 28 21 28 11
RLA (A) 42 48 56 68 82 94 110
400/50/3 CT ext. 09 09 10 10 01 01 02
Dip switch 10011 11100 01010 11001 10001 11000 00111
UCM confi 19 28 10 25 17 24 07
RLA (A) 41 46 54 65 79 90 106
415/50/3 CT ext. 09 09 10 10 01 01 02
Dip switch 10001 11001 00111 10110 01111 10110 00100
UCM confi 17 25 07 22 14 22 04
RLA (A) 76 87 102 123 149 171 200
220/50/3 CT ext. 01 01 02 02 02 03 03
Dip switch 01011 10110 00010 10001 11111 10001 11110
UCM confi 11 22 02 17 31 17 30
RLA (A) 53 60 71 86 104 118 139
380/60/3 CT ext. 10 10 10 01 02 02 02
Dip switch 00110 01111 11100 10101 00100 01011 11001
UCM confi 06 15 28 21 04 11 25
RLA (A) 44 50 58 71 85 98 115
460/60/3 CT ext. 09 09 10 10 01 01 02
Dip switch 10110 11111 01101 11100 10101 11011 01011
UCM confi 22 31 13 28 21 27 11
RLA (A) 92 104 122 148 179 204 240
220/60/3 CT ext. 01 02 02 02 03 03 04
Dip switch 11001 00100 10001 11110 11000 11110 10100
UCM confi 25 04 17 30 24 30 20
SW1-1 SW1-2
MCSP module Compressor A(A20-1) 0 0
(all unit) Compressor B (A20-2) 0 1
Compressor C (A20-3) 1 0
Compressor D (A20-4) 1 1
EXV module EXV master (A52-1) - Clg 0 0
(only RTXA) EXV slave (A52-2) - Htg 0 1