TRANE EMA N° L80 SB 050 E 1097

General Date October, 1997

Service Product RTA-RTW-RTU-RTR-RTX

Bulletin Page 1 OF 9

Prepared by Vincent LOUVIOT

Supersedes L80 SB 050 E 0497

SUBJECT : SERVICE SETTINGS UCM-CLD

AIM :
This Service Bulletin provides you the factory settings to check UCM-CLD
configuration.

ACCESS TO SERVICE SETTINGS :

Service settings, enables and units

Alarm

Service set-up menu


Select Report Group

Select Setting Group Machine configuration menu

ADAPTIVE CONTROL TM

NOTE : The configuration in Service settings has already been set before the unit leaves the factory and its password protected in
order to maintain proper operation of the chiller.
Trane EMA N° L80 SB 050 E 1097

General Service Bulletin Page 2 OF 9

APPLICABLE SOFTWARE :
This Service Bulletin applies to screw liquid chiller UCM-CLD microprocessor panels
with the following module revision.
Later software revisions may include items not found in the menu to follow.

RTA-RTW-RTU-RTR • CPM (A1) X 1365 0476-05 rev.G


• MCSP (A20) X 1365 0477-05 rev.E
• EXV (A52) X 1365 0475-06 rev.G
• CLD (A53) X 1365 0477-08 rev.J

RTX • CPM (A1) X 1365 0585-01 rev.A


• MCSP (A20) X 1365 0477-05 rev.E
• EXV (A52) X 1365 0586-01 rev.A
• CLD (A53) X 1365 0477-08 rev.J

SERVICE SETTINGS, ENABLES & UNITS :

DISPLAY COMMENTS SETTING


"Under/over voltage protection" With the option E
Without the option D
"Unit line voltage" refer order
"Restart inhibit time" 30 to 120 s 120
"Balanced CPRS starts & hours" E
"Display units" SI / English SI
"Language" 7 languages [Language]
"Programmable relay setup" Select 1 to 12 Refer to §1
Default 7
"External circuit lockout" Default D
Press simultaneously "previous" and "enter" to unlock the keypad.
D = Desable E = Enable
Trane EMA N° L80 SB 050 E 1097

General Service Bulletin Page 3 OF 9

SERVICE SETUP MENU :

Password : "+ + - - + +" "Enter"


DISPLAY COMMENTS SETTING
"Keypad display lock feature" D
"ICS Adress" Fixed to 55 55
"LVG WTR temp. cutout setpoint" from -23.3°C to 1.6°C
Default (0% glycol) 1.5°C
"Low RFGT temp.cutout setpoint" from -39.4°C to 1.6°C
Default (0% glycol) -5.4°C
"Low WTR temp EXV gain comp" - LVG WTR 5°C D
- LVG WTR < 5°C E
"Condenser limit setpoint" % HPC Refer to §2
"Cooling condenser limit setpoint" RTXA only % HPC Refer to §2
"Heating condenser limit setpoint" RTXA only % HPC Refer to §2
"Phase unbalance protection" E
"Phase reversal protection" E
"Superheat setpoint" 3.5 °C
"Cooling superheat setpoint" RTXA only 3.5°C
"Heating superheat setpoint" RTXA only 3.5°C
"EXV control response CKT 1" from 2 to 200 20
"EXV control response CKT 2" Increase the setting if EXV
response appear sluggish.
Decrease it if it appears to
be too responsive.
"Clg EXV control response CKT 1" RTXA only 20
"Clg EXV control response CKT 2"
"Htg EXV control response CKT 1" RTXA only 20
"Htg EXV control response CKT 2"
"LVG WTR temp control response setpt" from 2 to 200 40
"Fan control deadband bias CKT 1" from -50 to 50 (PSI)
"Fan control deadband bias CKT 2" Available with CHHB comp.
- a/c unit R22 and R134a 0
- a/c unit R404a -40
"Defrost delta temp setpt" RTXA only 11.9
Offset to initiate defrost cycle

The UCM shall impose a minimum difference of 2.8°C between "LVG WTR temp. Cutout setpoint" and "Chilled WTR temp.
Setpoint". Also 8.3°C between "Low RFGT temp. cutout setpoint" and "Chilled WTR temp. Setpoint".
Trane EMA N° L80 SB 050 E 1097

General Service Bulletin Page 4 OF 9

MACHINE CONFIGURATION MENU :


Password : "+-+-+-" "Enter"
DISPLAY COMMENTS SETTING
"Compressor model n° prefix" - 108-109-110-213 to 217-322 to 434 CHHB
- 107-207-209-211-212 CHHN
"Oil loss differential setpoint" Only with CHHN compressor
- R404a -10
- R22 and R134a -8
"Number of compressors" - Unit 100 1
- Unit 200 2
- Unit 300 3
- Unit 400 4
"Compressor A tons"
"Compressor B tons" Refer to §3
"Compressor C tons"
"Compressor D tons"
"Unit model" RTA (RTR)-RTU-RTW-RTX refer order
"Variable speed fan CKT 1" - RTAB/UA 207 to 212(R134a) E
"Variable speed fan CKT 2" - RTAB/UA 207 to 212 LA (R22- E
404a)
- Other units D
"Number of fan circuit 1" Refer to §4
"Number of fan circuit 2"
"Reduced inrush starting" E
"Starter type" Possible values are : refer order
Wye-delta or Part winding
"Current ovrld setting CPRSR A" from 0 to 31
"Current ovrld setting CPRSR B" Refer to §5
"Current ovrld setting CPRSR C"
"Current ovrld setting CPRSR D"
"Low amb uni, half airflow fan" Not available D
"Low amb unit, two speed motor" - RTAA LA E
- RTAB/UA LA 108 to110 E
- RTUA LA 207 to 212 with E
RTCA LA 213 to 216
- RTAB LA 212 HE E
- RTUA LA 213 to 217 E
- NNS option E
- Other units D
"Night noise set-back" Refer to the order, option NNS. E/D
"Number of EXV valves CKT 1" - Unit 100-200 1
- Unit 300-400-RTXA dual 2
"Number of EXV valves CKT 2" - Unit 100-200-300 1
- Unit 400-RTXA dual 2
"Refrigerant type" R22-R134a-R404a refer order
HE = High efficency
LA = Low Ambient unit
Trane EMA N° L80 SB 050 E 1097

General Service Bulletin Page 5 OF 9

§1 OUTPUT RELAY (A1; TB4)


confi RELAY 1 (1;2) RELAY 2 (4;5) RELAY 3 (6;7)
(
1 Alarm MR Unit is running Maximum capacity
2 Alarm MR+AR Unit is running Maximum capacity
3 Alarm MR+AR+IFW Unit is running Maximum capacity
4 Alarm MR+IFW Unit is running Maximum capacity
5 Circuit 1 alarm MR Circuit 2 alarm MR Maximum capacity
6 Circuit 1 alarm MR+AR Circuit 2 alarm MR+AR Maximum capacity
7 Circuit 1 alarmMR+AR+IFW Circuit 2 alarm MR+AR+IFW Maximum capacity
8 Circuit 1 alarm MR+IFW Circuit 2 alarm MR+IFW Maximum capacity
9 Alarm MR Circuit 1 running Circuit 2 running
10 Alarm MR+AR Circuit 1 running Circuit 2 running
11 Alarm MR+AR+IFW Circuit 1 running Circuit 2 running
12 Alarm MR+IFW Circuit 1 running Circuit 2 running

MR = Manuel reset
AR = Auto reset
IFW = Informational warnings

§2 LIMIT HP
"HPC" R 22 = 2793 kPA
"HPC" R 134a = 2200 kPA
"HPC" R 404a = 3000 kPA
"
AIR COOLED UNITS + RTXA clg
LVG WTR - 12 - 7.9 - 5.9 - 2.9 - 0.9 1.1 3.1 5.1
to - 8 to - 6 à-3 to - 1 to 1 to 3 to 5 to 10
TEMP
R22 83 84 85 86 87 88 89 90
% HPC R404a 78 79 81 82 83 84 85 87
R134a 83 84 85 86 87 88 89 90

Note : Add 3 % for the high ambient unit.

WATER COOLED UNITS + RTA HR


MINES TUV ISPESL
R22 85 80 80
% HPC R404a 81 74 74
R22 (RTXA htg) 90 - 88
R134a 80 80 80
Trane EMA N° L80 SB 050 E 1097

General Service Bulletin Page 6 OF 9

§3 COMPRESSOR TONS

UNIT
108 109 110 207 209 210
Compressor CKT 1 CHHB 70 CHHB 85 CHHB 100 CHHN 35 CHHN 40 CHHN 50
(IS 70) (IS 85) (IS 100) (GP 35) (GP 40) (GP 50)
Config. 50 Hz 60 70 85 30 35 40
CKT 1 60 Hz 70 85 100 35 40 50
Compressor CKT 2 - - - CHHN 35 CHHN 40 CHHN
(GP 35) (GP 40) (GP 40)
Config. 50 Hz - - - 30 35 35
CKT 2 60 Hz - - - 35 40 40

UNIT
211 212 213 214 215 216 217
Compressor CKT 1 CHHN 50 CHHN 60 CHHB 70 CHHB 85 CHHB 85 CHHB CHHB
(GP 50) (GP 60) (IS 70) (IS 85) (IS 85) 100 100
(IS 100) (IS 100)
Config. 50 Hz 40 50 60 70 70 85 85
CKT 1 60 Hz 50 60 70 85 85 100 100
Compressor CKT 2 CHHN 50 CHHN 60 CHHB 70 CHHB 70 CHHB 85 CHHB 85 CHHB
(GP 50) (GP 60) (IS 70) (IS 70) (IS 85) (IS 85) 100
(IS 100)
Config. 50 Hz 40 50 60 60 70 70 85
CKT 2 60 Hz 50 60 70 70 85 85 100

UNIT
322 324 328 430 432 434
Compressor CKT 1 CHHB 70 CHHB 85 CHHB 100 CHHB 85 CHHB 100 CHHB 100
(IS 70) (IS 85) (IS 100 (IS 85) (IS 100) (IS 100)
Config. 50 Hz 60 70 85 70 85 85
CKT 1 60 Hz 70 85 100 85 100 100
Compressor CKT 2 CHHB 70 CHHB 85 CHHB 100 CHHB 85 CHHB 100 CHHB 100
(IS 70) (IS 85) (IS 100) (IS 85) (IS 100) (IS 100)
Config. 50 Hz 60 70 85 70 85 85
CKT 2 60 Hz 70 85 100 85 100 100
Compressor CKT 3 CHHB 85 CHHB 100 CHHB 100 CHHB 85 CHHB 85 CHHB 100
(IS 85) (IS 100) (IS 100) (IS 85) (IS 85) (IS 100)
Config. 50 Hz 70 85 85 70 70 85
CKT 3 60 Hz 85 100 100 85 85 100
Compressor CKT 4 - - - CHHB 85 CHHB 85 CHHB 100
(IS 85) (IS 85) (IS 100)
Config. 50 Hz - - - 70 70 85
CKT 4 60 Hz - - - 85 85 100
Trane EMA N° L80 SB 050 E 1097

General Service Bulletin Page 7 OF 9

§4 NUMBER OF FANS

EUROPE EXPORT
Std Low amb Hi eff Hi amb Hi eff
Nb conf Nb conf Nb conf Nb conf Nb conf
fans ucm fans ucm fans ucm fans ucm fans ucm
RTAB 108 ckt 1 4 4 4 4 6 6/5 / / / /
ckt 2 / / / / / / / / / /
RTAB 109 ck 1 5 5 5 5 6 6/5 / / / /
ck2 / / / / / / / / / /
RTAB 110 ckt 1 6 6 6 5 6 6/5 / / / /
ckt 2 / / / / / / / / / /
RTAB 207 ckt 1 2 4 2 4 2 4 3 5 / /
ckt 2 2 4 2 4 2 4 3 5 / /
RTAB 209 ckt 1 2 4 2 4 3 5 3 5 / /
ckt 2 2 4 2 4 3 5 3 5 / /
RTAB 210 ckt 1 3 5 3 5 3 5 3 5 / /
ckt 2 2 4 2 4 3 5 3 5 / /
RTAB 211 ckt 1 3 5 3 5 3 5 4 4 / /
ckt 2 3 5 3 5 3 5 4 4 / /
RTAB 212 ckt 1 3 5 3 5 4 4 4 4 / /
ckt 2 3 5 3 5 4 4 4 4 / /
RTAA 213 ckt 1 4 4 4 4 4 4 4 4 / /
ckt 2 4 4 4 4 4 4 4 4 / /
RTAA 214 ckt 1 4 4 4 4 5 5 4 4 / /
ckt 2 4 4 4 4 4 4 4 4 / /
RTAA 215 ckt 1 4 4 4 4 5 5 4 4 / /
ckt 2 4 4 4 4 5 5 4 4 / /
RTAA 216 ckt 1 5 5 5 5 5 5 5 5 / /
ckt 2 4 4 4 4 5 5 5 5 / /
RTAA 217 ckt 1 5 5 5 5 5 5 5 5 / /
ckt 2 5 5 5 5 5 5 5 5 / /
RTAA 322 ckt 1 8 4 8 4 8 4 8 4 8 4
ckt 2 4 4 4 4 6 5 4 4 6 5
RTAA 324 ckt 1 8 4 8 4 10 5 8 4 10 5
ckt 2 6 5 6 5 6 5 6 5 6 5
RTAA 328 ckt 1 10 5 10 5 / / 10 5 / /
ckt 2 6 5 6 5 / / 6 5 / /
RTAA 430 ckt 1 8 4 8 4 10 5 8 4 10 5
ckt 2 8 4 8 4 8 4 8 4 8 4
RTAA 432 ckt 1 10 5 10 5 10 5 10 5 10 5
ckt 2 8 4 8 4 10 5 8 4 10 5
RTAA 434 ckt 1 10 5 10 5 / / 10 5 / /
ckt 2 10 5 10 5 / / 10 5 / /

For the RTAB 108 109 110 HI eff. , the configuration is :


Ambient STD =6
Low Ambient =5
Trane EMA N° L80 SB 050 E 1097

General Service Bulletin Page 8 OF 9

RTCA 108 111 208 211 213 213 216 113 116
109 209 215 115
RTUA 108 110 207 211 212 213 216 108 110
109 209 215 217 109
Ckt 1 Nb fan 4 6 2 3 4 4 6 8 12
Config 4 6 4 5 4 4 4 4 6
Ckt 2 Nb fan - - 2 3 4 4 6 - -
Config - - 4 5 4 4 4 - -

RTRA 107 107 LA 108 to 110


Ckt 1 Nb fan 2 2 2
Config 4 5 4

§5 CURRENT OVERLOAD

REFRIGERANT R22 - R404a


COMPRESSOR
CHHN 35 CHHN 40 CHHN 50 CHHN 60 ICHHB70 CHHB 85 CHHB 100
RLA (A) 63 71 84 102 123 141 165
380/50/3 CT ext. 10 10 01 01 02 02 03
Dip switch 10011 11100 10011 11111 10001 11011 10010
UCM confi 19 28 19 31 17 27 18
RLA (A) 60 68 80 97 117 134 157
400/50/3 CT ext. 10 10 01 01 02 02 03
Dip switch 01111 11001 01111 11101 01101 11000 01110
UCM confi 15 25 15 29 13 24 14
RLA (A) 58 66 77 93 113 129 151
415/50/3 CT ext. 10 10 01 01 02 02 03
Dip switch 01101 10110 01100 11010 01011 10101 01011
UCM confi 13 22 12 26 11 21 11
RLA (A) 109 124 145 176 213 244 285
220/50/3 CT ext. 02 02 02 03 04 04 05
Dip switch 01000 10010 11101 10110 01101 11110 00111
UCM confi 08 18 29 22 13 30 07
RLA (A) 76 86 101 123 148 169 198
380/60/3 CT ext. 01 01 02 02 02 03 03
Dip switch 01011 10101 00010 10001 11110 10100 11110
UCM confi 11 21 02 17 30 20 30
RLA (A) 63 71 83 101 122 140 164
460/60/3 CT ext. 10 10 01 01 02 02 03
Dip switch 10011 11100 10010 11111 10000 11011 10001
UCM confi 19 28 18 31 16 27 17
RLA (A) 131 148 175 212 255 292 343
220/60/3 CT ext. 02 02 03 04 04 05 05
Dip switch 00010 11110 10110 01100 11010 01000 10101
UCM confi 02 30 22 12 26 08 21
Trane EMA N° L80 SB 050 E 1097

General Service Bulletin Page 9 OF 9

REFRIGERANT R134a
COMPRESSOR
CHHN 35 CHHN 40 CHHN 50 CHHN 60 CHHB 70 CHHB 85 CHHB 100
RLA (A) 44 50 59 71 86 99 115
380/50/3 CT ext. 09 09 10 10 01 01 02
Dip switch 10110 11111 01110 11100 10101 11100 01010
UCM confi 22 31 14 28 21 28 11
RLA (A) 42 48 56 68 82 94 110
400/50/3 CT ext. 09 09 10 10 01 01 02
Dip switch 10011 11100 01010 11001 10001 11000 00111
UCM confi 19 28 10 25 17 24 07
RLA (A) 41 46 54 65 79 90 106
415/50/3 CT ext. 09 09 10 10 01 01 02
Dip switch 10001 11001 00111 10110 01111 10110 00100
UCM confi 17 25 07 22 14 22 04
RLA (A) 76 87 102 123 149 171 200
220/50/3 CT ext. 01 01 02 02 02 03 03
Dip switch 01011 10110 00010 10001 11111 10001 11110
UCM confi 11 22 02 17 31 17 30
RLA (A) 53 60 71 86 104 118 139
380/60/3 CT ext. 10 10 10 01 02 02 02
Dip switch 00110 01111 11100 10101 00100 01011 11001
UCM confi 06 15 28 21 04 11 25
RLA (A) 44 50 58 71 85 98 115
460/60/3 CT ext. 09 09 10 10 01 01 02
Dip switch 10110 11111 01101 11100 10101 11011 01011
UCM confi 22 31 13 28 21 27 11
RLA (A) 92 104 122 148 179 204 240
220/60/3 CT ext. 01 02 02 02 03 03 04
Dip switch 11001 00100 10001 11110 11000 11110 10100
UCM confi 25 04 17 30 24 30 20

IPC ADDRESS DIP SWITCH SETTINGS :

SW1-1 SW1-2
MCSP module Compressor A(A20-1) 0 0
(all unit) Compressor B (A20-2) 0 1
Compressor C (A20-3) 1 0
Compressor D (A20-4) 1 1
EXV module EXV master (A52-1) - Clg 0 0
(only RTXA) EXV slave (A52-2) - Htg 0 1